4208U - Installation and Setup Guide Dated 2/11



Related Products

Honeywell 4208U - 8 Zone Universal Zone Expansion Module
Honeywell 4208U
8 Zone Universal Zone Expansion Module
List Price: $216.00
Our Price: $151.99

Document Transcript




ADEMCO 4208U

Universal

V
-
P
lex
®

Eight Zone Expander



Installation and Setup Guide
GENERAL INFORMATION
The ADEMCO 4208U is a V-Plex
®
eight-zone expander for use
with ADEMCO controls that support V-Plex

(polling loop) devices.
Characteristics of this device include:


Can be optionally powered from the control panel a
ux. power
supply to reduce the amount of current draw from th
e polling
loop.
NOTE:
The 4208U cannot be used with an external
power supply for commercial fire applications.


Uniquely identifies 8 EOLR supervised zones (all z
ones use
10k resistors, supplied).


DIP Switches can be used to set zone numbers or se
rial
numbers.


When used in the serial number mode, each serial n
umber in
the selected group can be assigned to any zone numb
er.


Loops A & B can be programmed for fast (10msec) re
sponse.


Tamper protected.
MOUNTING
!

1. Power should be disconnected before proceeding.

2.
Be sure to mount the 4208U before making any wiring

connections.

When mounted remotely, tamper protection is require
d. Holes on
the back of the module’s housing permit it to be mo
unted
horizontally or vertically. Wires can exit from th
e side or the
breakout on the back of the housing. To enable tam
per protection,
set DIP Switch 8 to OFF and attach the tamper magne
t (provided)
(Figure 1) to the module inside cover. Be sure to
enable the
expansion zone tamper option at the control (progra
m field
\
24 =
0). If the module’s cover is removed, the magnet a
ttached to the
cover (positioned near the reed switch) will cause
a tamper signal
to be sent to the control for every active zone on
the 4208U
module. When the installation is complete, install
the cover and
affix the Serial Number and Zone Assignment Tables
to the inside
cover of the control.
When mounted inside the cabinet with the control, t
he 4208U
should be mounted horizontally and does not need ta
mper
protection, provided the cabinet is supervised. In
sert two screws
into the raised metal tabs leaving the heads app. 1
/8” exposed,
and then hang the 4208U using the two slots on the
back.
WIRING
C
E

For CE installations ADEMCO N6361 EMI suppression
bead is required. Refer to the N6361 Installation
Instructions for wire routing instructions.

Polling loop and protection loop wires can be broug
ht in either
through the back or front of the unit by removing t
he knockouts.
Use 22 gauge twisted pair wire for polling loop con
nections. All
protection loops use 10k EOL resistors (included).
A maximum
resistance of 300 ohms is allowed on protection loo
ps (excluding
EOLR). See Figure 2 for all connections.
Keep in mind that connections to the polling loop a
re always
required, while power supply connections are option
al.


1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.
4219-002-V0

Figure 1. Tamper Magnet Installation
DIP SWITCH SETTINGS
Serial Number Mode:
In the serial number mode, the DIP Switches on the
4208U are used
to assign the unit to a group of 8 serial numbers.
You can assign any
serial number to any zone number (except hardwire z
one numbers of
the control) and you do not lose zone numbers if yo
u don’t use all
eight loops on the 4208U. Follow steps below using
Table 2 for DIP
Switch settings.

Zone Assignment Mode:
In the zone assignment mode, the DIP Switches on th
e 4208U are
used to assign the unit to a group of 8 consecutive
zones. These
zone numbers, once designated for the 4208U, cannot
be used for
anything else, even if you don’t use all 8. Follow
the steps below
using Table 1 for DIP Switch settings.
Note:
Zone Assignment Mode should only be used on panels
that
DO NOT support Serial Mode.
4208U-SOC-V0
1 2 3 4 5
(EACH LOOP’S MAX
RESISTANCE:
300 ohms + 10k EOLR)
7
8
ON
1
DIP Switches
4208U
TB1
REED (TAMPER) SWITCH
1
9
8
7
6
5
4
3
2
10k 10k
10k 10k
10k 10k
10k 10k
LOOPS: A
B
C
D
E
F
G
H
12
11
10
( )
(+)
1
2
3
4
TB2
TO POLLING LOOP
(USE TWISTED PAIR)
( ) GND
(+) 12V
OPTIONAL AUX.
POWER INPUT.
SEE NOTE 1.
NOTES:
IF USING AUXILIARY POWER ON COMMECRICAL
FIRE/BURG COMBINATION SYSTEMS
(e.g. VISTA-128FBP), DO NOT CONNECT THE
POLLING LOOP GROUND ON TERMINAL 2.
AUXILIARY POWER CAN ONLY BE USED IN
BURGLARY APPLICATIONS.

FOR CE INSTALLATIONS A N6363 EMI
SUPPRESSION BEAD IS REQUIRED.
1.

2.

Figure 2. Summary of Connections
Note:
For Commercial and Residential Fire installations,
no more than
one (1) wire per terminal may be connected.

1 2 3 4 5
6
7
ON
ON
OFF
SIDE VIEW
POSITIONS 2-5: SELECT THE 8 SENSOR
DEVICE GROUP ADDRESS
(SHOWN ON, ON, ON,
OFF = 2nd GROUP SELECTION).
POSITION 6:
DEVICE TYPE (SHOWN
ON = “SERIAL NUMBER MODE”).
POSITION 7:
NORMALLY SET TO "OFF"
8
ON
1
POSITION 1:
SELECT RESPONSE TIME
FOR LOOPS A and B
(SHOWN ON = SLOW).
POSITION 8:
SELECT TAMPER PROTECTION
SETTING (SHOWN
“OFF” = TAMPER ENABLED).
}
4208U-001-V2

Figure 3. DIP Switch Settings
U
L

1. For all fire (NFPA) and UL Commercial Burglary
installations, the 4208U must be tamper protected o
r
mounted in a tamper-protected cabinet.
2. Refer to the control panel installation instruct
ions for
specific programming/installation requirements.
3. All circuits are supervised and power-limited.
4. Use only 14-22 AWG wire.
5. Close contact type initiating devices.
6. All zones are Class B, Style B.
7. Voltage rating all zo
nes: 11VDC max., 1.5mA max.

- 2 -

Table 1. 4208U Zone Assignments

For “Zone Assignment” mode, DIP Switch position 6 m
ust be off.
When using this mode, program each zone’s “Input Ty
pe” as “DIP Switch Polling Loop Device” (DP), where
applicable.
THIS SWITCH SETTING PRESETS THE LOOPS TO THESE ZONE
NUMBERS

Z o n e N u m b e r
DIP Switch Position
(“-” Means “off”)
Loop Designations

2
3
4
5
6
A
B
C
D
E
F
G
H
*
On On On On -
1
2
3
4
5
6
7
8
**
On On On
-
-
9
10
11
12
13
14
15
16

On On
-
On -
17
18
19
20
21
22
23
24

On On
-
-
-
25
26
27
28
29
30
31
32

On
-
On On -
33
34
35
36
37
38
39
40

On
-
On
-
-
41
42
43
44
45
46
47
48

On
-
-
On -
49
50
51
52
53
54
55
56

On
-
-
-
-
57
58
59
60
61
62
63
64

-
On On On -
65
66
67
68
69
70
71
72

-
On On
-
-
73
74
75
76
77
78
79
80

-
On
-
On -
81
82
83
84
85
86
87
88

-
On
-
-
-
89
90
91
92
93
94
95
96

-
-
On On -
97
98
99
100 101 102 103 104

-
-
On
-
-
105 106 107 108 109 110 111 112

-
-
-
On -
113 114 115 116 117 118 119 120 ***
-
-
-
-
-
121 122 123 124 125 126 127 N/A


*Do not select 1 – 8 for VISTA controls.

**If 9 – 16 is selected for controls that have 9 ha
rdwire zones. Loop A (Zone 9) will be inactive.
***Accommodates option “ONE 4208 IN USE” if referre
d to in control programming.
NOTE: Consult the Control Panel Instructions to de
termine the valid zone numbers for that control pan
el.
Table 2. 4208U Serial Number Assignments

THIS SWITCH SETTING PRESETS THE LOOP TO THESE SERIA
L NUMBERS
DIP Switch Position (“-” Means “off”)
Loop Designation
2
3
4
5
6
LOOP A
LOOP B
LOOP C
LOOP D
LOOP E
LOOP F

LOOP G
LOOP H
ON
ON
ON
ON
ON
000-4116
000-4117
000-4118
000-4119
000-4124
000-4125
000-4126
000-4127
ON
ON
ON
-
ON
006-9908
006-9909
006-9910
006-9911
0
06-9916
006-9917
006-9918
006-9919
ON
ON
-
ON
ON
013-9812
013-9813
013-9814
013-9815
0
13-9820
013-9821
013-9822
013-9823
ON
ON
-
-
ON
020-9716
020-9717
020-9718
020-9719
02
0-9724
020-9725
020-9726
020-9727
ON
-
ON
ON
ON
027-9620
027-9621
027-9622
027-9623
0
27-9628
027-9629
027-9630
027-9631
ON
-
ON
-
ON
034-9524
034-9525
034-9526
034-9527
03
4-9532
034-9533
034-9534
034-9535
ON
-
-
ON
ON
041-9428
041-9429
041-9430
041-9431
04
1-9436
041-9437
041-9438
041-9439
ON
-
-
-
ON
048-9332
048-9333
048-9334
048-9335
048
-9340
048-9341
048-9342
048-9343
-
ON
ON
ON
ON
055-9236
055-9237
055-9238
055-9239
0
55-9244
055-9245
055-9246
055-9247
-
ON
ON
-
ON
062-9140
062-9141
062-9142
062-9143
06
2-9148
062-9149
062-9150
062-9151
-
ON
-
ON
ON
069-9044
069-9045
069-9046
069-9047
06
9-9052
069-9053
069-9054
069-9055
-
ON
-
-
ON
076-8948
076-8949
076-8950
076-8951
076
-8956
076-8957
076-8958
076-8959
-
-
ON
ON
ON
083-8852
083-8853
083-8854
083-8855
08
3-8860
083-8861
083-8862
083-8863
-
-
ON
-
ON
090-8756
090-8757
090-8758
090-8759
090
-8764
090-8765
090-8766
090-8767
-
-
-
ON
ON
097-8660
097-8661
097-8662
097-8663
097
-8668
097-8669
097-8670
097-8671
-
-
-
-
ON
104-8564
104-8565
104-8566
104-8567
104-
8572
104-8573
104-8574
104-8575
- 3 -
Set the DIP switches on the 4208U as instructed bel
ow (see
Figure 3):
1. Select fast/slow response for loops A and B usin
g DIP Switch
1: Fast = OFF (10msec) Slow = ON (400msec).
2. Select mode of operation (serial number or zone
assignment
mode) using DIP Switch 6: Serial Number mode = ON;
Zone
Assignment mode = OFF.
3. Select the group setting using DIP Switches 2, 3
, 4, and 5.
See Table 1 for zone assignments or Table 2 for ser
ial
number assignments. If using more than one 4208U,
be sure
to set each one to a different group setting.
4. DIP Switch 7: Set DIP Switch 7 to “OFF”.
5. Select the 4208U Tamper Protection setting using
DIP Switch
8: Tamper Disabled = ON Tamper Enabled = OFF. Tam
per
will report for every active zone on the 4208U modu
le.
PROGRAMMING
When setting the 4208U to a group of zone numbers,
each zone
must be programmed as follows:


On ADEMCO 4140XMP and earlier controls, these zone
s
must be programmed as Left Loop Polling Loop Zones.



On ADEMCO VISTA-40 and later controls, these zones
must
be programmed in the #93 Menu Mode Zone Programming
as
INPUT TYPE “7” -- DIP Switch type polling dev
ice (DP).
When setting the 4208U to a group of serial numbers
, each zone
must be programmed as INPUT TYPE “6” --SL (Serial N
umber
Polling Loop Device). Loops can be learned in any
order and
assigned to any legitimate zone number.
When prompted to learn the serial number for a part
icular zone,
you may either enter it manually through the keypad
, through
COMPASS Downloader, or “learn” it by momentarily fa
ulting
(shorting) the terminals of that zone as required b
y the control. If
entering a serial number manually through the keypa
d, enter it and
press “
\
” to advance to the next prompt, which will ask you
for the
loop number. Entering a “1” for each serial number
entered.
If learning or entering a serial number, “Duplicate
of Zone XX”
Duplicate of Zone XX” is displayed; another device
with that same
serial number is already in the system. In that ca
se, use a
different serial number group setting on the 4208U.


!

If learning a serial number by faulting its
associated loop, make sure that other V-Plex
devices are no
t activated, as they may interfere
with the device being learned.

VERIFICATION OF PROGRAMMING
To verify proper programming, the following test sh
ould be
performed:
1. Be sure to enable expansion zone tamper protecti
on at the
control (program field
\
24 = 0).
2. Set DIP Switch 8 to OFF (tamper enabled).
3. Replace the 4208U cover and clear the keypad of
any faulted
zones.
4. Remove the 4208U’s cover and verify (on the keyp
ad) that
only the zones you designated for this 4208U are in
dicating a
check (or trouble) condition.
Table 3. Current Draw Calculations
Power Input Source
(Input Voltage: 8 – 11VDC)
Current Draw
(All zones shorted)

From Polling Loop
From Control Panel Aux. Power
Polling Loop Only
28.6mA

Polling Loop and Auxiliary Power
Input
0.6mA
28mA

SPECIFICATIONS
Physical:
Width: 6-7/16”(163mm)
Height: 4-1/4” (108mm)
Depth: 1-1/4” (32mm)
Electrical:
Polling loop input: 8 – 11 VDC
Current draw: 28.6mA max. Aux. Power and Polling l
oop (see
Table 3)
Power Input (optional): Burg. Applications Only
12VDC @ 28mA (from control panel’s auxiliary power)

Sensor Loop Response:
Slow: 400 msec (all loops)
Fast: 10 msec (option for loops A and B)
Sensor Loop Current:
(@ Polling loop input = 8 -11VDC, no external power
input):
0.52mA (normal)
1.3mA (shorted)
Sensor Loop Max. Resistance:
Up to 300 ohms of wire resistance + 10k EOLR.
Compliance:
NFPA-72
Compliant

NOTE:
Do not use a remote power supply.

For UL Listed Commercial Fire Usage
:
Use N.O. contacts. Style B, supervise these loops
using Model # EOL 100 fire listed
10k EOLRs (purchased separately).
For UL Listed Commercial Burglary Usage:
Use N.O. or N.C. contacts. Supervise using EOLRs s
upplied.


N8215V8C 2/11 Rev. C
TO THE INSTALLER
Regular maintenance and inspection (at least annual
ly) by the installer and frequent testing by the us
er are vital to continuous satisfactory operation o
f
any alarm system. The installer should assume the
responsibility of developing and offering a regular
maintenance program to the user, as well as
acquainting the user with the proper operation and
limitations of the alarm system and its component p
arts. Recommendations must be included for a
specific program of frequent testing (at least week
ly) to insure the system’s operation at all times.

FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modification
s to the equipment unless authorized by the Install
ation Instructions or User's
Manual. Unauthorized changes or modifications could
void the user's authority to operate the equipment
.
FCC CLASS B STATEMENT
This equipment has been tested to FCC requirements
and has been found acceptable for use. The FCC requ
ires the following
statement for your information:
This equipment generates and uses radio frequency e
nergy and if not installed and used properly, that
is, in strict accordance with the
manufacturer's instructions, may cause interference
to radio and television reception. It has been typ
e tested and found to comply with
the limits for a Class B computing device in accord
ance with the specifications in Part 15 of FCC Rule
s, which are designed to provide
reasonable protection against such interference in
a residential installation. However, there is no gu
arantee that interference will not
occur in a particular installation. If this equipme
nt does cause interference to radio or television r
eception, which can be determined by
turning the equipment off and on, the user is encou
raged to try to correct the interference by one or
more of the following measures:
• If using an indoor antenna, have a quality outdoo
r antenna installed.
• Reorient the receiving antenna until interference
is reduced or eliminated.
• Move the radio or television receiver away from t
he receiver/control.
• Move the antenna leads away from any wire runs to
the receiver/control.
• Plug the receiver/control into a different outlet
so that it and the radio or television receiver ar
e on different branch circuits.
• Consult the dealer or an experienced radio/TV tec
hnician for help.
INDUSTRY CANADA CLASS B STATEMENT
This Class B digital apparatus complies with Canadi
an ICES-003.
Cet appareil numérique de la classe B est conforme
à la norme NMB-003 du Canada.

FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules,
and RSS-210 of IC. Operation is subject to the fol
lowing two conditions: (1) This
device may not cause harmful interference (2) This
device must accept any interference received, inclu
ding interference that may cause
undesired operation.

Cet appareil est conforme à la partie 15 des règles
de la FCC & de RSS-210 des Industries Canada. Son
fonctionnement est soumis
aux conditions suivantes: (1) Cet appareil ne doit
pas causer d’interférences nuisibles. (2) Cet appar
eil doit accepter toute interférence
reçue y compris les interférences causant une récep
tion indésirable.


REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONT
ROL WITH WHICH THIS DEVICE IS USED, FOR DETAILS REG
ARDING LIMITATIONS OF THE
ENTIRE ALARM SYSTEM
.

Responsible Party / Issuer of Supplier’s Declaratio
n of Conformity: Ademco Inc., a subsidiary of Resid
eo Technologies, Inc., 2 Corporate Center Drive.,
Melville, NY 11747, Ph: 516-577-2000


The product should not be disposed of with other ho
usehold waste. Check for the nearest authorized col
lection centers or authorized recyclers. The
correct disposal of end-of-life equipment will help
prevent potential negative consequences for the en
vironment and human health.
Any attempt to reverse-engineer this device by deco
ding proprietary protocols, de-compiling firmware,
or any similar actions is strictly prohibited.

SUPPORT & WARRANTY INFORMATION
For the latest documentation and support, please go
to:
www.resideo.com

For the latest warranty information, please go to:
www.security.honeywellhome.com/warranty



The Honeywell Home Trademark is used under license
from Honeywell International Inc.
This product manufactured by Resideo Technologies a
nd its affiliates





2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747

2020 Resideo Technologies, Inc.
www.resideo.com


Uploaded