INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The
VISTAHTKVR
-V Gateway module
allows compatibility for
Resideo
V-Plex
devices to operate on compatible
First Alert Pro
VISTA
Hybrid
Control Panels. I
t connects to the control’s iBus bus wiring terminals
and is mounted remotely.
The
VISTAH3
Control panel support 4
VISTAHTKVR
-V modules, one for each partition.
Maximum Number of Devices
•
96 total devices supported.
•
172 number of input zones
•
52 relay modules (4101SNs)
IMPORTANT NOTE:
PROHVPLEX module only supports
serial mode
! Modules that support
zone assignment and serial must be
set for serial mode. Refer to the
module's installation instructions
for more information.
V-P
lex
Sensor Compatibility
Sensor
Description
Sensor
Description
269SN
Hold up Switch
4939SN
Surface Mount Contact
4101SN
1 Zone + 1 Relay
4959SN
OHD
Contact
4190SN
2
-
zone Expander
5193SD
Smoke Detector
4191SN
Recessed Contact
5193SDT
Smoke Detector
4193SN
1 zone Expander
DT8050A
-
SN
Dual Tec PIR
, w/Anti
-
Mask
4193SNP
1 zone Expander
DT7500SN
Dual
-
Tec PIR
4208SN
8 Zone Expander
FG1625SN
Glass
Break Detector
4208SNF
8 Zn Exp. w/Class A
IS2500SN
V
-
Plex/Sim Dual Tech
4208U
*
8 Zone Expander
IS3050A
-
SN
Motion Detector
4209U
*
4
,
2
-
Wire Smoke
Zn
VPLEX
-
VSI
V
-
Plex
Short Isolator
* Must be set to serial mode
INSTALLATION
•
The module has two
built
-in tampers (front and rear), allowing it to
detect and report the removal of its cover and/or the removal from
the wall to the control panel.
•
Communication with the module is supervised. If the wiring is cut,
a supervision
or alarm signal will result, indicating that this module
(and possibly other devices connected to the iBus wiring) has
become inoperative.
MOUNTING
1. Push the button on top of the
module to open the cover.
2a. For surface installations, using the 5 provided screws [2a], mount
the back case to the wall using the designated mounting holes and
back case tamper [2b].
2b. For gang box installations, carefully remove PCB and using the 5
provided screws [2a], mount the back case to the wall using the
designated mounting holes and back case tamper [2b].
3. Using best practices, choose the appropriate knockout [3a] to feed
the wires through (or use the hole provided in the back of the box
[3b]).
IMPORTANT:
Damage to product can occur if incorrectly wired. See summary
of connections for proper wiring.
4.
Rotate the cover and snap it into place [4
a], secure it with provided
lock screw [4
b].
VIS
TAHTKVR-
V-001-V0
VIS
TATKVR-B-004-V0
VIS
TAHTKVR-
V-002-V0
VIS
TAHEXPH
W-005-V0
SUMMARY OF CONNECTIONS
iBus Input
V
-
P
lex
Connections
1
Red: Positive (+)
5
12V Positive (+)
*
2
Black: Negative (
-
)
6
12V Negative (
-
)
*
3
Yellow: iBus B
7
V
-
P
lex
Positive (+)
4
Green: iBus A
8
V
-
P
lex
Negative (
-
)
iBus Output
9
Green: iBus A
13
LED
10
Yellow: iBus B
14
Tamper
11
Red:
Positive (+)
12
Black: Negative (
-
)
*
This AUX power can be used to connect to V
-
P
lex
devices that have 4 terminals on board (Power+, Power
-,
Loop+, Loop
-) when current drawn from V
-P lex
Loop
exceed 128mA.
iBUS
WIRING LIMITATIONS
CONNECTIONS AND SETTINGS
1.
Power should be disconnected before
proceeding.
2.
Be sure to mount the module before making any wire
connections.
Using the summary of connections above
; using best practices,
connect to the control’s iBus terminals via a 4
-position terminal block
(input)
.
After powering up, enroll the module through the panel's iBus
programming.
Refer to the
module
’s installation instructions for
specific information on enabling and configuring each V
-Plex
device
.
After enrollment, the module is configurable via the control panel
programming or the app.
ENROLLMENT
1.
The unique identifier defined on the attached label is required.
2.
The control panel
automatically
assigns each
V-Plex
device
to the
next available zone
or
relay.
3.
Confirm and document each device
and its assignments for multi
-
module installations to prevent confusion.
LED OPERATION
Color
Indication
Function
Green
Slow Blink
Module Firmware Updating
Solid
Normal Operation, iBus Online
Amber
Fast
Blink
iBus Offline
Solid
System Trouble"
1. Tamper Fault
2. Power Overload
3. Relay Output Supervision Trouble
4. Device Supervision Trouble
N/A
Off
1.
No power or communication
2. Panel is in AC Loss mode
SPECIFICATIONS
Physical
Dimensions
6.93
” W x
5.43
” H x 1.
99
D
(1
76
mm x 1
38
mm x
50.5
mm)
Electrical
Input Voltage
12VDC nominal (10
-
14VDC)
Input Current
5
6
mA
NOTE:
This does not include powered
devices using the AUX terminals
or current
of the V
-
P
lex
devices
.
Environmental
Operating
Temperature
32°
-
122°F (0°
-
50°C)
Operating Humidity
0
-
95% Relative Humidity
FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANADA (IC) STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by
the Installation Instructions or User's Manual. Unauthorized changes or modifications could
void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested and found to comply with the limits for a Class B digital
device, as defined by FCC Rules Part 15.105. The Class B Digital Device statement can be
viewed at:
https://customer.resideo.com/en
-US/support/residential/codes
-and
-
standards/FCC15105/Pages/default.aspx
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and Industry Canada’s license
-exempt
RSSs. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) This device must accept any interference receiv
ed, including
interference that may cause undesired operation.
Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary
of Resideo Technologies, Inc., 2 Corporate Center Drive., Melville, NY 11747, Ph: 516
-577
-2000
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS
DEVICE IS USED, FOR DETAILS ON LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
For the latest warranty information, please go to:
www.resideo.com
For technical support, call 1
-800
-645
-7492, M
-F 8:30am to 5pm EST.
For documentation, go to:
www.resideo.com
This equipment should be installed in accordance with National Electrical Code, NFPA 70, Standard for
the Installation of Residential Fire Warning Systems, CAN/ULC
-S540 and Chapter 2 of the National Fire
Alarm Code, ANSI/NFPA 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA
02269). Printed information describing proper installation, operation, testing, maintenance, evacuation
planning, and repair service is to be provided with this equipment.
Canadian Installations
For Installation in Canada, wiring shall be in accordance with CSA C22.1, Canadian Electrical Code, Part
I, Safety Standard for Electrical Installations; CAN/ULC S302,
Standard for the Installation, Inspection
and Testing of Intrusion Alarm Systems; and CAN/ULC S301, Standard for Signal Receiving Centre
Intrusion Alarm Systems and Operations.
Warning
: Owner’s instruction notice: ’Not to be removed by anyone except occupant’
This system must be checked by a qualified technician at least once every three (3) years.
Note:
The product should not be disposed of with other household waste. Check for the nearest
authorized collection centers or authorized recyclers. The correct disposal of end
-of-life equipment will
help prevent potential negative consequences for the environm
ent and human health.
Any attempt to reverse
-engineer this device by decoding proprietary protocols, de-
compiling
firmware, or any similar actions is strictly prohibited.
Resideo Technologies, Inc
2 Corporate Center Drive
P.O. Box 9040, Melville, NY 11747
© 2024 Resideo Technologies, Inc.All rights reserved
ÊR800-28650AÉŠ
R800
-28
650
A 5
/24 Rev A
INPU
T
OUTPU
T
VIS
T
AH
TKVR-V
TO V
-PLEX
13
14
1
2
3
4
12
11
10
9
5
6
7
8
Wire Gauge
(AWG)
Total Current of All Devices Connected to a Single Wire Run
50mA or less
100mA
300mA
500mA
600mA
#22
700ft (213m)
350ft (107m)
120ft (37m)
70ft (21m)
60ft (19m)
#20
1200ft (366m)
600ft (183m)
200ft (61m)
120ft (37m)
100ft (30m)
#18
1900ft
(579m)
950ft (290m)
320ft (98m)
190ft (58m)
160ft (49m)
#16
3000ft (914m)
1500ft (457m)
500ft (152m)
300ft (91m)
260ft (76m)
NOTE:
The length of all wire runs for all partitions combined must not exceed 3000 feet
(914m) when unshielded quad conductor cable is used or 1500 feet (457m) if shielded
cable is used.