Honeywell 4204 Install Guide - Dated 01/07 Rev. A
Related Products
Related Categories
Document Transcript
N8909V1 1/07 Rev.
A
ADEMCO 420
4
Relay Modul
e
For Use With Control/Communicators Supporting Relay Module Connection Via Keypad Lines
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 4204 Relay Module adds from one to
four dry, form C (SPDT) relay outputs to compatible
control/communicators. It interfaces to the control’s
keypad wiring.
The 4204 can be mounted inside the control’s cabinet
or mounted remotely.
If mounted remotely, the 4204 has a built-in tamper
switch that allows it to detect and report the removal
of its cover to the control. Second, communication to
the 4204 is supervised so that it cannot be
disconnected from the keypad wiring without
detection by the control. If the wiring is cut, a tamper
or alarm signal will result, to indicate that this
device (and possibly other devices connected to the
keypad wiring) has become inoperative.
INSTALLATION
For UL Installations:
When used with controls that do not support cover
tamper or supervise communications wiring to the
4204, mount the 4204 inside the control’s cabinet.
When used with controls that support cover tamper
and supervise communications wiring to the 4204,
mount the 4204 may either be mounted inside the
control’s cabinet or mounted remotely.
When mounted inside the control’s cabinet, some
controls allow the 4204 to be mounted horizontally as
follows: insert the self-tapping screws (provided) in two
adjacent raised tabs on the back of the cabinet. Leave
the heads projecting 1/8”. Hang the 4204 on the screw
heads via two of the slotted holes on the back of its
housing. The 4204’s cover need not, in this case, be
tamper-protected. If the DIP switch is set with its
position 1 “ON” (see the table below), the cover can be
left off.
See the control
’
s instructions for additional
information.
When the 4204 is mounted remotely, holes on its back
permit it to be mounted horizontally or vertically.
Wires
can exit from the side or via the breakout on the back of
its housing. The DIP switch must be set with its
position 1
“
OFF
”
and when the installation is completed,
the unit
’
s tamper-protected cover must be replaced.
Affix the connections label
that accompanies the 4204
to the inside of the 4204
’
s cover (if the cover is used) or
to the inside of the
control
’
s
cover.
CONNECTIONS AND SETTINGS
Select and set an address for the 4204
, using its DIP
switch as shown in the table below. Each 4204 used
with the control must be assigned a unique address so
the control can identify the 4204 and communicate with
it properly.
The address to the set is determined by the
particular control; to be used, and the control
’
s
installation instructions must be consulted.
As shipped,
the DIP switch is set for an address of
“
0
”
.
Connections to the 4204
’
s four relays are made via 12-
position terminal block TB2.
Refer to the control
’
s
installation instructions for specific information on how
to program the control
’
s various activation options for
the relays.
Connection to the control
’
s keypad wiring points can be
made via 4-position terminal block TB1, the 4-pin plug,
or both (wire color connections are the same). See the
diagram on the other side of this page.
SPECIFICATIONS
Physical:
6-7/16
”
W x 4-1/4
”
H x 1-1/4
”
D
(163mm x 108mm x 32mm)
Electrical:
Input Voltage: 12VDC nominal (10-14VDC, from
control
’
s remote keypad connection points)
Input Current: 15mA standby + 40mA per active relay
Contact Rating: 2A max. at 28VDC/AC (resistive loads)
4204 ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
3
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
4
ON
ON
ON
ON
—
—
—
—
ON
ON
ON
ON
—
—
—
—
5
ON
ON
ON
ON
ON
ON
ON
ON
—
—
—
—
—
—
—
—
12345
OFF
ON
4204-01-V0
{
DIP SWITCH SETTINGS
DIP SWITCH:
(WHITE AREAS DENOTE SWITCH HANDLES)
POSITION 1:
DETERMINES COVER TAMPER RESPONSE.
ON = DISABLED (SHOWN AS SHIPPED)
OFF = ENABABLED (COVER IS TAMPER-PROTECTED)
POSITIONS 2 - 5:
DETERMINE 4204's ADDRESS.
CONSULT CONTROL'S INSTRUCTIONS FRO ADDRESS TO USE.
SHOWN SET (AS SHIPPED) FOR ADDRESS = 0.
ÊN8909V1qŠ
N8909V1 1/07 Rev. A
TB2
12
11
10
9
8
7
6
5
4
3
2
1
(
–
) GROUND
(+) 12V
YEL
BLK
GRN
RED
13 14 15 16
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
COVER TAMPER
(REED)
SWITCH
TB1
4204
4-PIN TOUCHPAD PLUG
3
2
RELAY
1
4
RELAY CONTACTS ARE
NOT SUPERVISED
TYPICAL
(SHOWN "OFF")
C
NC
NO
C
NC
NO
C
NC
4204-02-V0
NC
NO
C
NC
NO
EITHER OR BOTH
CAN BE USED
DATA IN
FROM CONTROL
DATA OUT
TO CONTROL
RELAY
RELAY
RELAY
4204 CONNECTIONS
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH
THIS DEVICE IS USED FOR DETAILS REGARDING THE ENTIRE ALARM SYSTEM.
LIMITED WARRANTY
Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way,
Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to
be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp
control on the product(s) or, for product(s) not having a manufacturer’s date stamp, for 12 months from date of
original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter
period shall apply. Seller's obligation shall be limited to repairing or replacing, at its option, free of charge for
materials or labor, any product(s) which is proved not in compliance with Seller's specifications or proves defective
in materials or workmanship under normal use and service. Seller shall have no obligation under this Limited
Warranty or otherwise if the product(s) is altered or improperly repaired or serviced by anyone other than
Honeywell factory service. Connection of any device(s) to a communicating bus of a Honeywell security system (e.g.,
keypad bus, polling loop) other than those manufactured or approved by Honeywell shall void this warranty. For
warranty service, return product(s) transportation prepaid, to Honeywell Factory Service, 165 Eileen Way, Syosset,
New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR
PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO CASE
SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH
OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY
WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the product(s) it sells may not be compromised or circumvented; that the product(s)
will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product(s) will in
all cases provide adequate warning or protection. Customer understands that a properly installed and maintained
alarm system may only reduce the risk of a burglary, robbery, fire
,
or other events occurring without providing an
alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or
property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL
INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THAT THE PRODUCT(S) FAILED TO
GIVE WARNING. HOWEVER,
IF
SELLER
IS
HELD
LIABLE,
WHETHER
DIRECTLY
OR
INDIRECTLY,
FOR
ANY
LOSS
OR
DAMAGE
ARISING
UNDER
THIS
LIMITED
WARRANTY
OR
OTHERWISE,
REGARDLESS
OF
CAUSE
OR
ORIGIN,
SELLER'S
MAXIMUM
LIABILITY
SHALL
NOT
IN
ANY
CASE
EXCEED
THE
PURCHASE
PRICE
OF
THE
PRODUCT(S),
WHICH
SHALL
BE
THE
COMPLETE
AND
EXCLUSIVE
REMEDY
AGAINST
SELLER.
This warranty replaces any previous warranties and is the only warranty made by Seller on this product(s). No
increase or alteration, written or verbal, of the obligations of this Limited Warranty is authorized.
165 Eileen Way, Syosset, New York 11791
Copyright © 2007 Honeywell International Inc.
www.honeywell.com/security
- Uploaded