Honeywell 4219 Install Guide - Newest Dated 3/14
Related Products
Related Categories
Document Transcript
Document ID N8924V4 Dated 3/14 Rev. C
4219 Wired Zone Expander Module – Installation I
nstructions
GENERAL INFORMATION
The 4219 expander module adds up to eight normally
closed or
eight end-of-line resistor supervised zones to comp
atible
control/communicators via the control’s keypad wiri
ng.
The module may be mounted within the control’s cabi
net (if room
permits), or remotely. If mounted remotely, there
are provisions to
tamper protect the unit. Communication to the modu
le is
supervised so that it cannot be disconnected from t
he keypad wiring
without detection by the control. If the wiring is
cut, a tamper
alarm or signal will result, to indicate that this
device (and possibly
other similarly connected devices) has become inope
rative.
IMPORTANT
: Some carbon monoxide detectors may not be
compatible with the Honeywell 4219 hardwire zone ex
panders.
When using carbon monoxide detectors in systems tha
t support the
4219 zone expanders, install the detectors only on
the basic
hardwire zones of the system control panel, and NOT
on the zone
expanders.
INSTALLATION
1. Disconnect power before proceeding.
2.
Mount the 4219 before making any wire connections.
When the module is mounted remotely, holes on the b
ack of the
module’s housing permit it to be mounted horizontal
ly or vertically.
Wires can exit from the side or the breakout on the
back of its
housing. For tamper protection, attach the tamper m
agnet
(provided) (Figure 1) to the module inside cover. P
lace DIP switch
position #8 in the OFF position. Affix the connecti
ons label that
accompanies the module to the inside of the module’
s cover. When
the installation is complete, put the modules cover
on. The magnet
attached to the cover, positioned near the reed swi
tch, will cause a
tamper signal to be sent to the control if the cove
r is removed.
When the module is to be mounted inside the control
’s cabinet,
mount it horizontally to the raised tabs at the bac
k of the cabinet.
Insert self-tapping screws (provided) in two adjace
nt raised tabs at
the back of the cabinet. Leave the heads projectin
g 1/8”. Hang the
module on the screw heads via two slotted holes on
the back of the
module’s housing. When the module is installed in
the control’s
cabinet, it need not be tamper protected.
NOTE:
For EN50131-3 compliance a tie-wrap must be secur
ed
around the case of a remotely mounted 4219.
Apply tie-wrap around the case to the right of the
large
zone wire opening (4-inch case width). This is in o
pposition
of the tamper switch and magnet.
Affix the connections label that accompanies the mo
dule to the
inside of the control’s cover.
See the control’s installation and setup guide for
additional
information.
CONNECTIONS AND SETTINGS
Zone Connections
Make protection zone connections to the module’s 12
-position
terminal block TB1.
Set DIP switch 7 for the desired zone operation (NC
or EOLR):
OFF = End of line resistor operation. Each zone tha
t is used must
have
a 2K-ohm end-of-line resistor
connected across the
end of its loop, as shown in Figure 2.
UL: Set to OFF (EOLR)
ON = Normally closed operation
The method of programming each zone for the type of
alarm and
reporting code to the central monitoring station va
ries with the
control to which the module is connected. Refer to
the Installation
and Setup Guide for that control unit.
1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.
4219-002-V0
Figure 1. Tamper Magnet Installation
Module Address
Set the module address using DIP switches 2-6.
Select one of 31 addresses, as shown in Figure 3, s
o the control can
identify the module and communicate with it properl
y. The address
to be set is determined by the particular control t
o be used, and the
control’s installation instructions must be consult
ed.
Normal/Fast Response Time for all zones
Use DIP switch 1 to select normal or fast response
time for all
zones:
OFF = fast response time of 10ms to an open circuit
ON = normal response time of 300ms. All other modul
e
protection zones have a nominal response time of 30
0ms.
Connection to the Control Panel
Connect the module to the control panel’s keypad (E
CP) terminals
via 4-terminal block TB2 or the 4-pin plug (wire co
lor connections
are the same).
SPECIFICATIONS
Physical
6-7/16”W x 4-1/4”H x 1-1/4” D (163mm x
108mm x 32mm)
Electrical
Input Voltage:
12VDC (from control’s remote keypad
connection points)
Current:
30mA
4219-SOC-V4
4219
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4
3
2
1
ZONES
A
B
C
D
F
G
H
TB1
TB2
1
2
3
4
DATA OUT TO CONTROL
DATA IN FROM CONTROL
IF EOLR OPTION SELECTED, TERMINATE EACH PROGRAMMED ZONE WITH 2K OHM END-OF-LINE RESISTOR
(EACH ZONE'S MAX. LOOP RESISTANCE: 300 OHMS + EOL). IF NORMALLY CLOSED OPTION SELECTED,
CONNECT ALL ZONES AS NC LOOPS.
SEE DETAIL A
5
8
11
2
E
1
3
4
6
7
9
10
12
NOTE:
ADDRESSES 16-31 MAY
NOT BE AVAILABLE; CONSULT
THE HOST CONTROL PANEL
INSTALLATION INSTRUCTIONS.
4-PIN CONSOLE
PLUG
CONNECTIONS
SAME
AS TB2
REED (TAMPER) SWITCH
DIP SWITCH
ZONES
A
B
TB1
2
1
3
DETAIL A
8 7 6 5 4
OFF
ON
3
2 1
Figure 2. Summary of Connections
EOLR value is 2K ohms.
U
L
For UL, use 14-22AWG wire, and no more than one wir
e may be connected per terminal. Use UL Listed
EOL resistors.
4219-001-V3
SW #
0
1
2
3
4
5
6
7
8
9
10
11 12 13
14
15
2
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
3
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON ON
—
—
4
ON
ON
ON
ON
—
—
—
—
ON
ON
ON ON
—
—
—
—
5
ON ON
ON
ON ON
ON ON
ON
—
—
—
—
—
— —
—
DIP SWITCH:
(WHITE AREAS DENOTE SWITCH HANDLES)
POSITIONS 2-6:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS
FOR ADDRESS USE.
SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES RESPONSE TIME FOR ALL ZONES:
6
ON
ON
ON
ON
ON
ON
ON
ON
16 17 18 19 20 21 22
23
24
25 26
27
28
29
30
31
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON ON
—
—
ON
ON
ON
ON
—
—
—
—
ON
ON
ON ON
—
—
—
—
ON ON
ON
ON
ON
ON ON
ON
—
—
—
—
—
— —
—
—
—
—
—
—
— —
—
—
—
—
—
—
—
—
—
ON
ON
ON
ON
ON
ON
ON
ON
POSITION 7:
POSITION 8:
DIP SWITCH POSITION #7: SELECTS USE OF NC OR EOLR ZONES.
DIP SWITCH POSITION #8: CASE TAMPER ON = DISABLED OFF = ENABLED
ON = NORMAL (300MS)
OFF = FAST (10MS) RESPONSE TO AN OPEN 300MS ZONE A
SETTING SHOWN (AS SHIPPED).
ON = ALL ZONES NORMALLY CLOSED
OFF = ALL ZONES EOLR SUPERVISED UL: SET TO OFF (EOLR)
NOTE:
ADDRESSES 16-31 MAY NOT BE AVAILABLE; CONSULT THE HOST CONTROL PANEL INSTALLATION INSTRUCTIONS.
4 2 1 9 A D D R E S S S E T T I N G S
("—" means "OFF")
8 7 6 5 4
OFF
ON
3
2 1
Figure 3. DIP Switch Settings
SEE THE CONTROL PANEL’S INSTALLATION AND SETUP GUID
E FOR COMPLETE INFORMATION
REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SY
STEM.
Federal Communications Commission (FCC) Part 15
The user shall not make any changes or modification
s to the equipment unless authorized by the Install
ation Instructions or User's Manual. Unauthorized
changes
or modifications could void the user's authority to
operate the equipment.
FCC CLASS B STATEMENT:
This equipment has been tested to FCC requirements
and has been found acceptable for use. The FCC requ
ires the following statement for your information:
This equipment generates and uses radio frequency e
nergy and if not installed and used properly, that
is, in strict accordance with the manufacturer's in
structions,
may cause interference to radio and television rece
ption. It has been type tested and found to comply
with the limits for a Class B computing device in a
ccordance
with the specifications in Part 15 of FCC Rules, wh
ich are designed to provide reasonable protection a
gainst such interference in a residential installat
ion.
However, there is no guarantee that interference wi
ll not occur in a particular installation. If this
equipment does cause interference to radio or telev
ision reception,
which can be determined by turning the equipment of
f and on, the user is encouraged to try to correct
the interference by one or more of the following me
asures:
• If using an indoor antenna, have a quality outdoo
r antenna installed.
• Reorient the receiving antenna until interference
is reduced or eliminated.
• Move the radio or television receiver away from t
he receiver/control.
• Move the antenna leads away from any wire runs to
the receiver/control.
• Plug the receiver/control into a different outlet
so that it and the radio or television receiver ar
e on different branch circuits.
• Consult the dealer or an experienced radio/TV tec
hnician for help.
FCC/IC STATEMENT
This Class B digital apparatus complies with Canadi
an ICES-003.
Cet appareil numérique de la classe B est conforme
à la norme NMB-003 du Canada.
This device complies with Part 15 of the FCC rules
and RSS 210 of Industry Canada. Operation is subjec
t to the following two conditions: (1) This device
may not
cause harmful interference, and (2) This device mus
t accept any interference received, including inter
ference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles
de la FCC & de RSS 210 des Industries Canada. Son
fonctionnement est soumis aux conditions suivantes:
(1)
Cet appareil ne doit pas causer d' interférences nu
isibles. (2) Cet appareil doit accepter toute inter
ference reçue y compris les interférences causant u
ne réception
indésirable.
ÊN8924V4uŠ
N8924V4 3/14 Rev. C
For the latest warranty information, please go to:
http://www.security.honeywell.com/hsc/resources/wa
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2008 Honeywell International Inc.
- Uploaded