Honeywell 4229 - Install Guide - Dated 03/14 Rev. D
Related Products
Related Categories
- Wired Security System Zone Expanders
- Wired Zone Expansion Modules
- Wired Zone Expanders
- Wired Security System Zone Expanders
Document Transcript
n
4229
Wired Zone Expander/Relay Module
Installation and Setup Guide
GENERAL INFORMATION
The ADEMCO 4229 Wired Zone Expander/Relay Module
adds up to eight normally closed or eight end-of-li
ne resistor
supervised zones and two dry form C (SPDT) relay ou
tputs
to compatible control communicators via the control
’s
keypad wiring.
The module may be mounted within the control’s cabi
net (if
room permits), or remotely. If mounted remotely, t
here are
provisions to tamper-protect the unit. Communicati
on to the
module is supervised so that it cannot be disconnec
ted from
the keypad wiring without detection by the control.
If the
wiring is cut, a tamper or alarm signal will result
, to indicate
that this device (and possibly other similarly conn
ected
devices) has become inoperative.
IMPORTANT
: Some carbon monoxide detectors may not be
compatible with the ADEMCO 4229 hardwire zone
expanders. When using carbon monoxide detectors in
systems that support the 4229 zone expanders, insta
ll the
detectors only on the basic hardwire zones of the s
ystem
control panel, and NOT on the zone expanders.
INSTALLATION
When the module is to be mounted inside the control
’s
cabinet
, it should be mounted horizontally. Insert self-
tapping screws (provided) in two adjacent raised ta
bs at the
back of the cabinet. Leave the heads projecting 1/
8”. Hang
the module on the screw heads via two of the slotte
d holes
on the back of its housing. In this case, the modu
le’s cover
need not be tamper protected. See the control’s in
structions
for additional information.
When the module is to be mounted remotely, holes on
its
back permit it to be mounted horizontally or vertic
ally.
Wires
can exit from the side or the breakout on the back
of its
housing. Place DIP switch #8 in the OFF position a
nd,
when the installation is completed, the module’s co
ver put
on. A magnet in the cover, positioned near a reed
switch in
the unit, will cause a tamper signal to be sent to
the control if
the cover is removed.
NOTE:
For EN50131-3 compliance a tie-wrap must be
secured around the case of a remotely mounted 4229.
Apply tie-wrap around the case to the right of the
large zone
wire opening (4-inch case width). This is in opposi
tion of the
tamper switch and magnet.
Affix the connections label that accompanies the un
it to the
inside of the module’s cover (if the cover is to be
used)) or to
the inside of the control’s cover
CONNECTIONS AND SETTINGS
See the table and the diagram on the reverse side.
Zone Connections
Make protection zone connections to 12-position ter
minal
block TB1. Set DIP switch 7 for the desired zone o
peration
(NC or EOLR):
OFF = End of line resistor operation. Each zone tha
t is
used must have a
2K-ohm end-of-line resistor
connected across the end of its loop, as shown in
Figure 2.
UL: Set to OFF (EOLR)
ON = Normally closed operation
The method of programming each zone for type of ala
rm
and reporting code to the central monitoring statio
n varies
with the control to which the module is connected.
Refer to
the installation instructions for that control unit
.
Module Address
Set the module address using DIP switches 2-6.
Select one of 31 addresses, as shown in the table o
n the
reverse side, so the control can identify the modul
e and
communicate with it properly. The address to be se
t is
determined by the particular control to be used, an
d the
control’s installation instructions must be consult
ed.
Normal/Fast Response Time for Zone A
Use DIP switch 1 to select normal or fast response
time for
all zones:
OFF = fast response time of 10ms to an open circuit
ON = normal response time of 300ms. All other modul
e
protection zones have a nominal response time of
300ms.
Relay Connections
Connect the module’s two relays to the appropriate
devices
via the 7-conductor cord provided.
Refer to the control’s
installation instructions for specific information
on how to
program the control’s various activation options fo
r the
relays.
Connection to the Control Panel
Connect the module to the control panel’s keypad (E
CP)
terminals via4-terminal block TB2 or the 4-pin plug
(wire
color connections are the same).
SPECIFICATIONS
Physical
............................... 6-7/16”W x 4-1/4”H
x 1-1/4”D
163mm x 108mm x 32mm)
Electrical
Input Voltage: ......... 12VDC (from control’s rem
ote keypad
connection points)
Input Current: ....................................
....... 30mA (relays off)
..................................................
............. 100mA (relays on)
Relay Contact Rating: ...................... 2A max
. at 28VDC/AC
SW #
0
1
2
3
4
5
6
7
8
9
10
11 12 13
14
15
2
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
3
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON ON
—
—
4
ON
ON
ON
ON
—
—
—
—
ON
ON
ON ON
—
—
—
—
5
ON ON
ON
ON ON
ON ON
ON
—
—
—
—
—
— —
—
DIP SWITCH:
(WHITE AREAS DENOTE SWITCH HANDLES)
POSITIONS 2-6:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS
FOR ADDRESS USE.
SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES RESPONSE TIME FOR ALL ZONES:
6
ON
ON
ON
ON
ON
ON
ON
ON
16 17 18 19 20 21 22
23
24
25 26
27
28
29
30
31
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON ON
—
—
ON
ON
ON
ON
—
—
—
—
ON
ON
ON ON
—
—
—
—
ON ON
ON
ON
ON
ON ON
ON
—
—
—
—
—
— —
—
—
—
—
—
—
— —
—
—
—
—
—
—
—
—
—
ON
ON
ON
ON
ON
ON
ON
ON
POSITION 7:
POSITION 8:
DIP SWITCH POSITION #7: SELECTS USE OF NC OR EOLR ZONES.
DIP SWITCH POSITION #8: CASE TAMPER ON = DISABLED OFF = ENABLED
NOTE:
ADDRESSES 16-31 MAY NOT BE AVAILABLE; CONSULT THE HOST CONTROL PANEL INSTALLATION INSTRUCTIONS.
ADDRESS "0" SETTING SHOWN.
ON = NORMAL (300MS)
OFF = FAST (10MS) RESPONSE TO AN OPEN 300MS ZONE A
SETTING SHOWN (AS SHIPPED).
ON = ALL ZONES NORMALLY CLOSED
OFF = ALL ZONES EOLR SUPERVISED UL: SET TO OFF (EOLR)
4 2 2 9 A D D R E S S S E T T I N G S
("—" means "OFF")
4229-003-V4
8 7 6 5 4
OFF
ON
3
2 1
EOLR value is 2K ohms.
U
L
For UL, use 14-22AWG wire, and no more than one wir
e may be connected per terminal. Use UL Listed EOL
resistors.
4229
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
ZONES
A
B
C
D
F
G
H
TB1
TB2
1
2
3
4
DATA OUT
TO CONTROL
DATA IN FROM
CONTROL
IF EOLR OPTION SELECTED, TERMINATE EACH PROGRAMMED
ZONE WITH 2K OHM END-OF-LINE RESISTOR (EACH ZONE'S
MAX.
LOOP RESISTANCE: 300 OHMS + EOL). IF NORMALLY CLOSED
OPTION SELECTED, CONNECT ALL ZONES AS NC LOOPS.
SEE DETAIL A
5
8
11
2
E
1
3
4
6
7
9
10
12
ZONES
A
B
TB1
2
1
3
DETAIL A
4
3
2
1
4-PIN CONSOLE
PLUG
EITHER
OR BOTH
CAN BE
USED
WIRED ZONE
EXPANDER/RELAY
MODULE
RELAY
2
RELAY
1
REED
(TAMPER)
SWITCH
RELAY
CONNECTOR
1
DIP SWITCH
BRN
WHT
GRY
VIO
BLK
YEL
ORG
NO
NC
C
GND
NO
NC
C
RLY
1
RLY
2
RELAYS
"OFF"
{
{
{
4229-004-V3
8 7 6 5 4
OFF
ON
3
2 1
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONT
ROL WITH WHICH THIS DEVICE IS USED, FOR DETAILS REG
ARDING LIMITATIONS
OF THE ENTIRE ALARM SYSTEM
.
Federal Communications Commission (FCC) Part 15
The user shall not make any changes or modification
s to the equipment unless authorized by the Install
ation Instructions or User's Manual.
Unauthorized changes or modifications could void th
e user's authority to operate the equipment.
FCC CLASS B STATEMENT:
This equipment has been tested to FCC requirements
and has been found acceptable for use. The FCC requ
ires the following statement for your
information:
This equipment generates and uses radio frequency e
nergy and if not installed and used properly, that
is, in strict accordance with the manufacturer's
instructions, may cause interference to radio and t
elevision reception. It has been type tested and fo
und to comply with the limits for a Class B
computing device in accordance with the specificati
ons in Part 15 of FCC Rules, which are designed to
provide reasonable protection against such
interference in a residential installation. However
, there is no guarantee that interference will not
occur in a particular installation. If this equipme
nt does
cause interference to radio or television reception
, which can be determined by turning the equipment
off and on, the user is encouraged to try to
correct the interference by one or more of the foll
owing measures:
• If using an indoor antenna, have a quality outdoo
r antenna installed.
• Reorient the receiving antenna until interference
is reduced or eliminated.
• Move the radio or television receiver away from t
he receiver/control.
• Move the antenna leads away from any wire runs to
the receiver/control.
• Plug the receiver/control into a different outlet
so that it and the radio or television receiver ar
e on different branch circuits.
• Consult the dealer or an experienced radio/TV tec
hnician for help.
FCC/IC STATEMENT
This Class B digital apparatus complies with Canadi
an ICES-003.
Cet appareil numérique de la classe B est conforme
à la norme NMB-003 du Canada.
This device complies with Part 15 of the FCC rules
and RSS 210 of Industry Canada. Operation is subjec
t to the following two conditions: (1) This
device may not cause harmful interference, and (2)
This device must accept any interference received,
including interference that may cause undesired
operation.
Cet appareil est conforme à la partie 15 des règles
de la FCC & de RSS 210 des Industries Canada. Son
fonctionnement est soumis aux conditions
suivantes: (1) Cet appareil ne doit pas causer d' i
nterférences nuisibles. (2) Cet appareil doit accep
ter toute interference reçue y compris les
interférences causant une réception indésirable.
Responsible Party / Issuer of Supplier’s Declaratio
n of Conformity: Ademco Inc., a subsidiary of Resid
eo Technologies, Inc., 2 Corporate
Center Drive., Melville, NY 11747, Ph: 516-577-2000
The product should not be disposed of with other ho
usehold waste. Check for the nearest authorized col
lection centers or authorized
recyclers. The correct disposal of end-of-life equi
pment will help prevent potential negative conseque
nces for the environment and human
health.
Any attempt to reverse-engineer this device by deco
ding proprietary protocols, de-compiling firmware,
or any similar actions is strictly
prohibited.
SUPPORT & WARRANTY INFORMATION
For the latest documentation and support, please go
to:
www.resideo.com
For the latest warranty information, please go to:
www.security.honeywellhome.com/warranty
The Honeywell Home Trademark is used under license
from Honeywell International Inc.
This product manufactured by Resideo Technologies,
Inc. and its affiliates
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
2020 Resideo Technologies, Inc.
www.resideo.com
ÊN8910V3DAŠ
N8910V3D 3/14 Rev. D
- Uploaded