Honeywell 5809SS Heat Detector Installation Instructions



Related Products

Honeywell 5809SS - Wireless Fixed Temperature/ROR Heat Detector
Honeywell 5809SS
Wireless Fixed Temperature/ROR Heat Detector
List Price: $114.00
Our Price: $81.99

Document Transcript



5809SS
Wireless
Rate-
of -Rise
Heat Detector –
Installation
Instructions

General Information

The Honeywell 5809SS
Rate-
of-
Rise Heat Detector is a wireless
device used with alarm systems that support Honeywell’s 5800 series
devices.

The 5809SS
combines a rate-
of-rise sensor and a fixed temperature
sensor in one device. The rate-
of-rise sensor detects a rapid rise in
temperature and signals an alarm if the rise is 15

F (8

C) or more
per minute. Fires typically cause a rapid rise in temperature in the
surrounding area. The fixed temperature sensor will signal an alarm
when the ambient temperature rises above 135

F (57

C).

IMPORTANT:
The 5809SS
will be permanently damaged if stored,
shipped, or installed in environments where the temperature exceeds
100

F (38

C). If the metal disc is detached, the detector has
exceeded 135

F (57

C) and must be replaced.

Heat detectors should be used for property protection. Reliance
should not be placed solely on heat detectors for life safety. When
life safety is i
nvolved, smoke detectors MUST also be used.

Detectors MUST NOT be painted.

Notes:


It is not recommended to install at a site where the ambient
temperature exceeds 100

F (38

C).


UL:
Unit is for dry, indoor use only.


If the fixed temperature sensor activates
, the detector must be
replaced.

When the battery voltage drops below a threshold, a low battery signal is
sent to the control panel.


The 5809SS
includes a tamper switch. If removed from its mounting
base, a trouble signal is sent to the control panel.


Detectors should never be relocated without the advice or assistance of
the alarm service company.


Replace the battery when the system reports a low battery condition.

SPECIFICATIONS

Battery

3- volt lithium; Duracell DL123A, Panasonic
CR123A
, or HUIDERUI CR123A
.
Operating Temp.

40

F to 1
35

F (
4

C to 57

C)
Rate of Rise Temp.

15

F (8

C) increase per minute.

Note:
The rate
-of-rise sensor does not operate
above 100

F (38

C).

Fixed Temp.

135

F (57

C)
Maximum Spacing

50ft x 50ft

UL:
30ft x 30ft

Refer to NFPA 72 for application requirements.

Dimensions

4.5” diameter, 2.
5” deep

zzz




1

Install the Battery

1.
If the 5809SS
is already mounted, remove the detector assembly by
twisting counter
-clockwise and withdraw it from the mounting base.
DO N
OT touch the metal disc.
2.
Remove the old battery and wait 30 seconds.
3.
Install or replace battery with a Duracell DL123A, Panasonic CR123A
,
or HUIDERUI CR123A
.
Observe polarity!

NOTE
: Constant exposure to high or low temperature or high humidity
may reduce battery life.




2

Program the Detector

NOTE:
The detector’s serial number is located inside the detector.
This number must be enrolled in the control panel. Refer to the
control panel’s installation guide for details.
1.
Remove the detector assembly by twisting counter
-clockwise and
withdraw it from the mounting base. DO NOT touch the metal disc.
2.
Install the battery (if not already installed).
Observe polarity!

3.
Enter the control panel’s programming mode. When programming
this device, program the following:
Input Ty
pe = 3 (Supervised RF)

Loop number = 1

4.
To enable the control panel to capture the detector’s serial number,
when prompted force the detector to transmit by momentarily
depressing the RF TEST button. Alternately, you can manually enter
the detector’s serial number.

5.
Test the detector after enrolling into the system. Refer to the
Testing
the Detector
topic.





3

Select a Location and Mount the Detector

SELECT A LOCATION


Refer to the “Specifications” topic for maximum spacing requirements.

Avoid m
ounting the detector near heat generating devices (e.g.,
ovens, heat vents, furnaces, boilers).


Wall Mounting – Mount the detector 4” to 6” from the ceiling.


Ceiling Mounting – Mount the detector at least 4” from any wall.
Ensure the ceiling temperature w
ill not exceed 100

F.

Verify a good RF transmission path from the selected mounting
location before mounting. Test the detector first before mounting.

Testing The Detector
:
This test should be performed to verify a good RF transmission path
before mounting the detector at the intended location, and again after
the installation is complete.
CAUTION:
The rate-
of-
rise heat sensor is intended for a one time
use. If the metal disc on the detector detaches, the detector must
be replaced.

1.
Activate the control panel’s test mode.

2.
Press and release the RF TEST button on the sensor’s PC board.

3.
Verify the system’s keypads beep and the detector’s serial number is
displayed.

4.
Exit the control panel’s test mode.
MOUNT THE DETECTOR

The detector’s mounting base has a var
iety of holes to accommodate
securing it to; a wall, ceiling, 4” junction box, or a 3
–1/4” octagon box.

1.
Use at least two mounting holes.
2.
When securing to wallboard, in addition to the mounting holes, ensure
to also use a screw in the Anti
-Twist mounting hole. This will prevent
the base plate from coming loose when untwisting the sensor.




3.
Secure the sensor to the mounting base by aligning the sensor’s index
tabs to the index tab recesses on the mounting base. While pushing
in, turn the sensor clockwise until it locks. DO NOT touch the metal
disc.


TO THE INSTALLER

The rate-
of-rise sensor may be subject to reduced sensitivity over time. Annual testing of the rate-
of-rise operation is recommended. Regular
maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any
alarm system.

The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainti
ng the user
with the proper operation and limitations of the alarm system and its components parts. Recommendations must be included for
a specific program
of frequent testing (at least weekly) to ensure the system’s proper operation at all times.

FEDE
RAL COMMUNICATIONS COMMISSION & INDUSTRY CANADA
STATEMENT
S
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or
User's Manual. Unauthorized changes or modifications could void the user'
s authority to operate the equipment.


FCC / IC STATEMENT

This device complies with Part 15 of the FCC Rules, and RSS
-210 of IC. Operation is subject to the following two conditions:

(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.


Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS
-210 des Industries Canada. Son fonctionnement est
soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d' interférences
nuisibles. (2) Cet appareil doit accepter
toute interférence reçue y compris les interférences
causant une réception indésirable.




For Limitations of the entire alarm system, refer to the control panel’s installation guide.

SUPPORT & WARRANTY

For the latest documentation and online support information, please go to:

https://mywebtech.honeywell.com/

For the latest warr
anty information, please go to:

www.honeywell.com/security/hsc/resources/wa.


For patent information, see www.honeywell.com/patents



MyWebTech


Warranty


Patents


Ê800-20876eŠ

800
-
20876

6
/
15

Rev.
B



2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747

Copyright

201
5 Honeywell International Inc.
www.honeywell.com/security


Uploaded