Honeywell 5817CB Wiring w/ Hardwire Heat Detector
Related Products
Document Transcript
Ê800
-14164V13Š
800-14164V1
2/1
5 Rev A
Wiring
Instructions
for BK-5601P
/ 5817
CBXT
Applications
1. Connect the BK
-5601P detector to the
5817CBXT
loop 1 terminals as shown
below
.
2. Enroll the 5817CBXT
in the control panel
(see control’s instructions)
.
3. After enrolling the 5817CBXT
, set DI
P switch 1 to ON (repeating).
IMPORTANT:
•
Wire length between 5817CBXT
transmitter and the
BK-
5601P
heat detector must be less than
20
feet.
•
Use fire rated wire for connections
(ex. FPL, FPLR, FPLP)
.
5817CBXT
DIP Switch Settings
PRIMARY LOOP OP
TIONS TABLE
SWITCH
SET TO
DIP SWITCH POSITION
ON
REPEATING TRANSMISSION
(every 4 sec.)
UPON PRIMARY LOOP FAULT
Use for high priority alarm, such as fire.
OFF
SINGLE TRANSMISSION
PER PRIMARY LOOP CHANGE-OF
-STATE