Honeywell Lyric Installation Guide - Dated 11/15 Rev B



Related Products

Honeywell Lyric Controller - Encrypted Wireless Security System
Honeywell Lyric Alarm System
Encrypted, HomeKit, Wireless Security System

Related Categories


Document Transcript

Lyric

TM

Controller

Installation and Reference Guide

Ref: LCP500-L
800-18076

4/15 Rev. B – DRAFT (6/25/15)

Lyric Controller Installation and Reference Guide

RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices
Help Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted
below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all
rooms and areas of the household as follows: For minimum protection a smoke detector should be
installed outside of each separate sleeping area, and on each additional floor of a multi-floor family
living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or
unfinished), or in garages is not normally recommended.
• For additional protection the NFPA recommends that you install heat or smoke detectors in the living
room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms,
basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or
completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside
may not wake up the sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm
control connections to an AC source or phone lines are made. If detectors are not so located, a fire
within the room could prevent the control from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
DINING

BEDROOM BEDROOM

TV ROOM

KITCHEN

DINING

BDRM

LIVING ROOM
BDRM
BEDROOM

BEDROOM

LIVING ROOM

Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors

BEDROOM

BEDROOM

TO
BR

BEDROOM
KTCHN

LVNG RM

.

CLOSED
DOOR

GARAGE

BASEMENT
floor_plan-001-V1

Recommendations for Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multilevel building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm
signals can be sent to the alarm monitoring station in the event that the communications are out of
order (if connected to an alarm monitoring station).

-2-

Lyric Controller Installation and Reference Guide

Table of Contents
System Features ..................................................................................................................................................................................................5
Installing the Control ........................................................................................................................................................................................ 7
Battery Installation ............................................................................................................................................................................................... 7
Battery Selection .......................................................................................................................................................................................... 7
Installing the Rechargeable Backup Battery .................................................................................................................................... 7
Replacing the Rechargeable Backup Battery .................................................................................................................................. 7
Wall Mounting ........................................................................................................................................................................................................8
Desktop Mounting ............................................................................................................................................................................................... 9
Place the Back Plate ................................................................................................................................................................................... 9
Install the Desk Stand ................................................................................................................................................................................ 9
AC Power ............................................................................................................................................................................................................... 10
Wiring Overview ................................................................................................................................................................................................. 10
Make Electrical Connections.................................................................................................................................................................. 10
Communications Modules ................................................................................................................................................................................ 11
Communications Module 24-Hour Standby power ...................................................................................................................... 11
Install and Configure Communications Module ...................................................................................................................................... 11
Installing the Cellular Module ................................................................................................................................................................. 11
Checking Signal Strength ....................................................................................................................................................................... 12
Wireless Zones ................................................................................................................................................................................................... 13
General Information ........................................................................................................................................................................................... 13
Zones ............................................................................................................................................................................................................... 13
Range ............................................................................................................................................................................................................... 13
Transmitters .................................................................................................................................................................................................. 13
House Identification .................................................................................................................................................................................. 13
Transmitter Supervision .......................................................................................................................................................................... 13
Transmitter Input Types .......................................................................................................................................................................... 13
Transmitter Battery Life .......................................................................................................................................................................... 13
5800 Series Transmitter Loop Numbers .......................................................................................................................................... 14
Mechanics of Programming ......................................................................................................................................................................... 15
Navigating Menus ............................................................................................................................................................................................... 15
Touch-screen Display ............................................................................................................................................................................... 15
Navigation Keys .......................................................................................................................................................................................... 16
Home Screen ................................................................................................................................................................................................ 16
Security Screen ........................................................................................................................................................................................... 17
Master User Tools Screen ....................................................................................................................................................................... 17
Programming ........................................................................................................................................................................................................ 18
Enter Installer Programming Mode ..................................................................................................................................................... 18
Loading Factory Defaults ................................................................................................................................................................................ 19
Select a Default Configuration.............................................................................................................................................................. 19
Exit Programming Mode .................................................................................................................................................................................. 19
Zone Response Type Definitions
Definiti ons ............................................................................................................................................................. 20
General Information .......................................................................................................................................................................................... 20
System Operation ............................................................................................................................................................................................ 22
Key/Touchscreen Operation ........................................................................................................................................................................ 22
Panic Key/Icons .................................................................................................................................................................................................. 22
Security Codes .................................................................................................................................................................................................... 22
Installer Code .............................................................................................................................................................................................. 22
Master Code ................................................................................................................................................................................................. 22
Enter/Change the Master Code by Installer .................................................................................................................................. 22
Secondary User Codes ............................................................................................................................................................................ 22
Reset Master Code .................................................................................................................................................................................... 23
Security Code Notes ................................................................................................................................................................................ 23
System Displays ................................................................................................................................................................................................. 24
Zone Status Displays ........................................................................................................................................................................................ 24
Audio Alarm Verification (Two-Way Voice Feature) ......................................................................................................................... 25
Activation...................................................................................................................................................................................................... 25
Operator Commands ............................................................................................................................................................................... 25
Event Log .............................................................................................................................................................................................................. 26
Contact ID Event Log Codes ................................................................................................................................................................ 26
Central Station Messages ............................................................................................................................................................................... 27
Testing the System ......................................................................................................................................................................................... 28
-3-

Lyric Controller Installation and Reference Guide

Table of Contents (Continued)
Test Modes ........................................................................................................................................................................................................... 28
Testing the System ........................................................................................................................................................................................... 28
Armed System Test .......................................................................................................................................................................................... 28
Zone Discovery Mode ...................................................................................................................................................................................... 29
Rebooting the System..................................................................................................................................................................................... 29
Lynx Programming Default Values.........................................................................................................................................................
30
Values
Zone Assignment/Alarm Response Type for Configuration 1 ....................................................................................................... 32
Zone Assignment/Alarm Response Type for Configuration 2 ...................................................................................................... 33
Zone Assignment/Alarm Response Type for Configuration 3 and 4 ......................................................................................... 34
Zone Response Type Matrix ...................................................................................................................................................................... 35
Regulatory Agency Statements ............................................................................................................................................................... 36
Limitations of this System Statement .................................................................................................................................................. 37
Agency
Agenc y Notices ................................................................................................................................................................................................ 38
SIA Quick Reference Guide ........................................................................................................................................................................ 39
Specifications .................................................................................................................................................................................................... 39
Glossary ................................................................................................................................................................................................................ 40
Contacting Technical Support ................................................................................................................................................................... 41
Index ....................................................................................................................................................................................................................... 42
Summary of Connections Diagram ........................................................................................................................................................ 43
Warranty Information ................................................................................................................................................................ Rear Cover

-4-

Lyric Controller Installation and Reference Guide

System Features
The Lyric Controller is a self-contained, rechargeable wireless control/communicator that features easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice
descriptors of each zone. An internal module allows the controller to communicate with the Central Station via
the Internet or (if installed) Cellular Wireless.

ETL

Lyric Controller is not intended for UL985 Household Fire applications u
unless
nless a 2424- hour backup
battery ( p/n 300300 - 03866)
03866) is installed.

System Features












7.0-inch color graphic touch screen
Message center (for user recorded messages)
Voice announcement of system and zone status
Ten user-selectable voice chimes sounds
Reminders
Automatic stay arming
Night stay arming
48 User Codes (Installer, Master, Guest, Duress)
Panic Functions (Police, Fire, Medical)
Programmable Reminders
Video Camera Control (requires WiFi connection)
Supports Mobile Devices (Tablet, iPAD, etc.) that duplicate functions of the Lyric Controller (i.e.;
Security, Web Content Home Automation and Video Control)
Built-in Camera

Home Automation




Integrated Z-Wave Support
Control up to 232 Z-Wave Home Automation devices including:
- Thermostats (up to 6)
- Door locks (up to 6)
- Devices (outlets, switches, lamps/appliances)
Supports Z-Wave Network Wide Inclusion (NWI) Mode
100 programmable Smart Actions
Up to 150 scheduled events
Supports Garage Door Feature (5877 Relay Receiver)

Zones and Devices







Two Hardwire Zone (EOLR, N/C, N/O)
128 Wireless Zones (5800 and SiX™ Series transmitters)
Four Garage Door Zones
32 Wireless Button (Keyfob) Zones (5800 and SiX™ Series transmitters)
Eight (SiX™ Series) Wireless Keypad Zones
12 Temperature Zones
Resident Monitor Zone Types
Built-in Case Tamper

Communication





ADEMCO Contact ID
Integrated WiFi support
Internet Central Station communication
Cellular (GSM or CDMA) Central Station communication
WiFi Central Station communication
Two-way Voice communication

Supports AlarmNet 360

TM

Remote Services

-5-

Lyric Controller Installation and Reference Guide

System Features (Continued)
System Power

Primary Power: Plug-in Power Supply, 110VAC to 9VDC, 2.7A output p/n 300-07332US (TBD in Canada)
Backup battery: Rechargeable nickel-metal hydride battery pack rated at 7.2Vdc. (p/n 300-03864-3PIN
or 300-03866

Alarm Output




Built-in sounder
Steady output for burglary/panic
Temporal (3) pulse output for fire alarms
Temporal (4) pulse output for carbon monoxide alarms
Audio Alarm Verification (AAV)

Programming


Options stored in EEROM
TM
Can be uploaded, downloaded or controlled via AlarmNet 360
using capable Cellular or WiFi
Communications Module
Flash downloading

Other Features



Exit Error feature (detects difference between an actual alarm and exit alarm caused by leaving a door
open after the exit delay expires)
Event log storage (total 6,000 events)
RF jam detection
Advanced Protection Logic™ (APL) (Minimizes the likelihood of the system being disabled before
notification can be sent to the Central Station indicating that the premises have been compromised.)
Lyric™ Lock (Customer Retention Logic) Dealer selectable Lockout (anti-takeover) feature
Displays web content including Local News, Weather and Traffic (requires Total Connect Service)
Dealer/Central Station messages (requires Total Connect Service)

Built-in IR camera




-6-

Lyric Controller Installation and Reference Guide

Installing
Installing the Control
Battery Installation
The Lyric Controller is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc. In the
event of an AC power loss, the system is supported by the long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a
“low battery” message is displayed and a report is sent to the Central Station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping). Select
the appropriate battery pack, based on the installation’s requirement, and install the battery pack. Follow the
steps and refer to the figure below to install and connect the battery.

Battery Selection
Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack.
Battery Part Number
300-03864-3PIN
300-03866

Battery StandbyTime
4-hours (minimum)
24-hours (minimum)

Low Battery Notification
Approximately 1-hour before battery depletion
At least 1-hour before battery depletion

Installing the Rechargeable Backup Battery
1.
2.
3.
4.
5.
6.
7.

Insert the battery pack into controller’s rear case.
Install the battery retainer.
Secure the battery retainer with the provided screws (2).
Connect the battery pack connector to the receptacle on the back of the controller.
Align the slots on the back of the controller with the hooks on the wall mount as shown below.
Once attached, insert the screw to secure the controller to the wall mount.
Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the system will display
the “System Standby!” screen will be displayed.

RETAINER

RETAINER

STANDARD CAPACITY
BATTERY PACK
(p/n 300-0364-3PIN)
SCREWS (2)

HIGH CAPACITY
BATTERY PACK
(p/n 300-03866)

SCREWS (2)

OR

lyric-031-V0

Rechargeable batteries may take up to 4848- hours to fully charge. The “Low Battery” message
should clear within four hours or by entering Test Mode.

Replacing the Rechargeable Backup Battery
1.
2.

When battery replacement is required, at the Master User screen select the “Advanced” icon.
Select “Install Backup Battery” and follow the displayed steps to replace the battery or follow the steps
below.
Remove the battery
1. Unscrew the screw securing the controller to the wall mount (if used).
2. Release the catch that secures the controller to the wall mount.
3. Rotate the controller away from the wall and lift it from the wall mount, being careful not to damage the
wiring.
-7-

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
4.
5.
6.
7.

Disconnect the battery pack connector from the receptacle on the back of the controller.
Remove the screws (2) that secure the battery retainer and remove the battery retainer.
Remove the battery pack from the back case.
Install a replacement battery pack (p/n 300-03864-3PIN OR p/n 300-03866) into the back of the
controller.
8. Install the battery retainer.
Install the replacement battery
1. Secure the battery retainer with the provided screws (2).
2. Connect the battery pack connector to the receptacle on the back of the controller.
3. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
4. Once attached, insert the screw to secure the Lyric to the wall mount.
NOTE: If a Cellular Communication Module is being installed, verify the module’s signal strength before
selecting a final mounting location. Refer to Checking the Signal Strength in the Communications
Module section.

Wall Mounting
For wall mounting follow the steps and refer to the figure below.
1. Feed the field wiring through the appropriate openings in the wall mount.
2. Attach the wall mount to a sturdy wall using the four provided screws.
3. If required, install an additional mounting screw in the case tamper.
4. Align the slots on the back of the controller with the hooks on the wall mount as shown below.
5. Once attached, insert the screw to secure the Lyric to the wall mount.

WALL
MOUNT

MOUNTING
SCREW (4)
TYP.
TAMPER
SCREW
(OPTIONAL)

WALL
SURFACE

INSERT SCREW
(IF APPLICABLE)

lyric-036-V1

-8-

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
Desktop Mounting
For desktop mounting the Lyric Desk Stand (LCP500-DK) is installed in place of the wall mount. The desk Stand
can be installed in two positions that provide a viewing angle of 30 degrees or 60 degrees. Follow the steps and
refer to the figures below.

Replace the Back Plate
1.
2.
3.

Remove the screw securing the rear cover to the controller.
Remove the rear cover.
Feed the field wiring through the appropriate openings in the rear cover included with the Lyric Desk Stand
(LCP500-DK).
4. Install the new rear cover.
5. Install the screw to secure the rear cover to the Lyric Controller.

INSTALL
SCREW
REMOVE

lyric-050-V0

Install Desk Stand
1. Align the slots on the back of the controller with the hooks on the desk stand as shown below.
2. Insert the stand into the slots on the rear case to provide the desired viewing angle and slide up to lock in
place.
STAND LOCATION 30

STAND LOCATION 60

lyric-052-V0

-9-

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
AC Power
The Lyric Controller is powered by a 9 Volt DC, 2.7 Amp Plug-in Power Supply, 300-07332US (TBD in Canada).
Refer to the wiring table below for wire gauge and length.
Use only the 300300 - 07332US (TBD Canada) Power Supply. Do not plug the power supply into the AC
outlet until after all wiring connections have been made.

Wiring Overview
The following summarizes the electrical connections associated with the Lyric Controller. Follow the steps and
refer to the figure below when making connections. Refer to the Summary of Connections diagram for
additional information.

Make Electrical Connections
Temporarily hang the controller from the hook on the wall mount.
If used, connect the hardwire sensors/contacts to the HWZ1/HWZ2 (+) and GND (-) terminals.
Connect the Power Supply (p/n 300-07332US) to the +9VDC and GND terminals on the controller.
Align the slots on the back of the controller with the hooks on the wall mount as shown below.
Once attached, insert the screw to secure the controller to the wall mount.
Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the system will display
the “System Standby!” screen will be displayed.

USB PORT

GND

+9VDC

GND

HWZ1

TERMINAL
BOARD
HWZ2

1.
2.
3.
4.
5.
6.

TAMPER

BATTERY
RECEPTACLE

DETAIL A

lyric-035-V1

- 10 -

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
Communication Modules
The Lyric Controller supports Central Station reporting using wireless/cellular and WiFi communications
devices. They also support upload/download programming capability via the Internet or a Private local area
network (Intranet). This allows site maintenance independent of Central Station monitoring, and modification to
sites globally via the Internet or through a private LAN. Refer to the Programming Guide (p/n 800-16077) for
information regarding programming and registration. Additionally, an internal Z-Wave module allows the Lyric
Controller to support Home Automation functions. (refer to the Lyric User Guide (p/n 800-16078 for additional
information.) The controllers are compatible with the following AlarmNet Communication Modules:
Model
LYRIC-3G
LYRIC-CDMA

Description
GSM Cellular Communications Module
CDMA Cellular Communications Module

Communications
Communications Module 2424- Hour Standby Power
If 24-hour standby is required, the Super High Capacity battery (p/n 300-03866) must be installed.

RF Exposure
E xposure

!

WARNING: The Lyric Controller must be installed to provide a separation distance of at least 7.8
in (20 cm) from all persons and not coco- located or operated in conjunction with any other
transmitter except in accordance with FCC multimulti - transmitter product
product procedures.

Install
Insta ll and Configure
Configur e C ommunication Module
Follow the steps and refer to the figure below to install the Communications Module.

Installing the Cellular Communications Module
1.

Enter Installer Programming then select “Test”
or Enter Master User Programming, then select “Advanced”.
2. Select “Install Cellular Module” and follow the prompts displayed on the controller or follow the steps below.
3. Remove controller side cover (bezel).
4. Remove the screw securing the module to the controller (if installed,).
5. Remove the existing Cellular Communications Module (if installed).
6. Install the Cellular Communications Module into the controller.
7. Ensure that the Communications Module is properly seated into the controller and secure the module with
the provided screw (if required).
8. Insert the side cover (bezel) into the controller.
9. Slide the bezel down to lock it in place and secure the Communications Module.
10. Select OK to complete the installation.
11. Enable the Communications Module, configure alarm reporting and module supervision and register the
device. Refer to the “Program Communicator” and “Communications Diagnostics” sections in the
TM
Programming Guide (p/n 800-16077). OR Log on to the AlarmNet 360 website
(https://webdev2.alarmnet.com/AlarmNetDirect/Account/LogOn).
TM

The Communications Module must be registered with AlarmNet 360 TM before downloading or
alarm reporting can take place.

INSERT
PUSH
DOWN
COMMUNICATION
MODULE

SCREW

DETAIL A
lyric-034-V0

- 11 -

Lyric Controller Installation and Reference Guide

Installing the Control (Continued)
Communication Modules
Checking Signal Strength
When choosing a suitable mounting location, check the communications module’s signal strength to
ensure proper operation. For most installations, using the module’s internal antenna, mounting the
Lyric controller as high as practical, and avoiding large metal components provides adequate signal
strength for proper operation. To check signal strength, perform the following test.
Check Signal Strength
1.

With the System in the Installer Programming mode,
select the “Comm. Diagnostics” button and then select
the “Cellular Information” button. The Cellular
Information will be displayed. The signal strength is
displayed (in dBm) as RSCP if the Lyric-3G module is
operating on the 3G Network or RSSI if the module
Lyric-3G module is operating on the 2G Network and for
the Lyric-CDMA module.

2. Compare the displayed RSCP or RSSI number to the
correct Signal Strength Guide at right to ensure
adequate signal strength. If necessary, relocate the
Controller to obtain better signal strength (select
“Cellular Information” again to refresh the reading).
3. If adequate signal strength cannot be achieved, External
Antenna Kit model Cell-ANTST should be used.

Lyric - 3G Signal Strength
Strength
RSCP (3G)
Good............................................ -20 to -90 dBm
OK ................................................ -91 to -100 dBm
Marginal .................................... -101 to -106 dBm
Bad ............................................. -107 to -120 dBm
RSSI (2G)
Good............................................. -20 to -89 dBm
OK ................................................. -90 to -98 dBm
Marginal ................................... -99 to -104 dBm
Bad ............................................ -105 to -120 dBm
Lyric - CDMA Signal Strength
RSSI
Good............................................. -20 to -90 dBm
OK .................................................-91 to -100 dBm
Marginal .................................... -101 to -106 dBm
Bad .......................................... -107 to -120 dBm

- 12 -

Lyric Controller Installation and Reference Guide

Wireless Zones
General Information
Zones
The Lyric Smart Control supports up to 128 total wireless zones using 5800 and SiX™ Series transmitters, and
wireless keyfobs.

Range
The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.

Transmitters
5800 and SiX™ Series transmitters have built-in serial numbers that must be entered into the system using the
TM
“Zones” programming section, or input to the controller via AlarmNet 360 . 5800 Series transmitters (except
the 5800WAVE and 5800RL) do not have DIP switches. Each transmitter's zone number is also programmed
into the system in the “Zones” programming section. Some transmitters, such as the 5816 can support more
than one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection terminal block is
loop 1; the reed contact is loop 2. Each loop must be assigned a different zone number.
For button transmitters (RF "keyfobs") such as the 5804E and 5834-2/5834-4, you must assign a unique zone
number to each individual button used on the transmitter. Each button on the transmitter also has a predesignated loop or input number, which is automatically displayed.

ETL

The 5816 Transmitters do not
not have EOL supervision
sup ervision of their loop wiring,
wiring , which must not exceed 3
feet.
The 5800PIR5800PIR- OD, 5800RL, 5800SS1, 5804E, 5814, 5816TEMP,
5816TEMP, 5821, 5877 and 5878 wireless
transmitters have not been evaluated by ETL.
ETL.

House Identification
If a 5800WAVE or a 5800RL is being installed with the system, to establish proper communication a RF House
Code (House ID Code) (01–31) must be programmed in the Lyric, and the device must be set to the same code.
Refer to the “System Type” programming section in the Lyric Controller Programming Guide (p/n 800-16077).
An RF House ID is not necessary for other 5800 Series transmitters; the entry should be left at “0” (default) in
those cases.

Transmitter
Transmitter Supervision
With the exception of some transmitters/keypads that may be carried off-premises (5804E, 5834-2/5834-4
and SiXFOB), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the
"missing" transmitter zone number(s) and "Supervision" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises may be turned off by entering it as an
“Unsupervised” type. For additional information, refer to the “Zones” programming section in the Lyric
Controller Programming Guide (p/n 800-16077). 5800 and SiX™ Series transmitters have built-in tamper
protection and will annunciate as a fault condition if covers are removed. In Canada the RF supervision period
is 3-hours for Fire zones and 12 hours for all other zone types.

Transmitter Input Types
Each transmitter has one or more unique factory-assigned input (loop/5800 Series or service/SiX™ Series) ID
codes. Each of the inputs requires a programming zone (e.g., a 5804E's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitter’s instructions for appropriate
Supervision type):
Type
Supervised
Unsupervised
Button

Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals. The
transmitter must remain within the receiver's range.
Sends all the signals that the Supervised type does, but the controller does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
Sends only fault signals. Do not send low battery signals until being activated. The
transmitter is unsupervised and may be carried off-premises.

Transmitter Battery Life

Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and
the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large
swings in temperature may all reduce the actual battery life in a given installation. The wireless system can
identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change
of battery and maintain protection for that point within the system.
Button-type transmitters should be periodically tested for battery life. The 5804E, 5834-2/5834-4, 5878 and
SiXFOB button transmitters have replaceable batteries.
- 13 -

Lyric Controller Installation and Reference Guide

Wireless Zones (Continued)
5800 Series Transmitter Loop Numbers
(Refer to this information when programming 5800 Series transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop designations.

LOOP
1
LOOP 1
LOOP
1

LOOP 1
(LOW
SENSITIVITY

LOOP 1
(LOW
SENSITIVITY

LOOP 2
(HIGH
SENSITIVITY)

LOOP 2
(HIGH
SENSITIVITY)

LOOP 3 (TEMP)

LOOP 3 (TEMP)
LOOP 4 (TAMPER)

LOOP 4 (TAMPER)
5800Micra
ENROLL AS
SUPERVISED

5800CO
ENROLL AS
SUPERVISED

5800PIR-RES
ENROLL AS
SUPERVISED

5800PIR-OD
ENROLL AS
SUPERVISED

5800PIR/5800PIR-COM
ENROLL AS
SUPERVISED

5800RL
SET HOUSE ID

LOOP 3
LOOP 4
LOOP
1

LOOP 1

LOOP 2
LOOP 1

OF

F

LOOP 1

LOOP 1

5804E
ENROLL AS BUTTON

LOOP 2
(REED)

LOOP 2
(REED)

LOOP 3
(TERMINALS)

LOOP 1

ALTERNATE
POSITION
FOR LOOP 2
5816MN
ENROLL AS
SUPERVISED

LOOP 1
(TERMINALS)
5819
ENROLL AS
SUPERVISED

5818MNL
ENROLL AS
SUPERVISED

SERIAL #2
LOOP 1

SERIAL #1
LOOP 4

5834-2
ENROLL AS BUTTON

SERIAL #1
LOOP 3
SERIAL #1
LOOP 2

1
2
3
4

5819S (WHS & BRS)
ENROLL AS
SUPERVISED

5820L
ENROLL AS
SUPERVISED

5821
ENROLL AS
SUPERVISED

SERIAL #1
LOOP 1

LOOP 1
(HIGH
SECURITY)
LOOP 2
(STANDARD
SECURITY)

SERIAL #1
LOOP 1

SERIAL #2
LOOP 2

SERIAL #2
LOOP 3

LOOP 1
(INTERNAL
SHOCK
SENSOR

SERIAL #2
LOOP 4

LOOP 3

ST
AY

LOOPS
1-3

LOOP 1
SERIAL #2
LOOP 3

AW
AY

LOOP 1

SERIAL #2
LOOP 1
SERIAL #1
LOOP 2

SERIAL #1
LOOP 4

5814
ENROLL AS
SUPERVISED

LOOP 3 (TILT MODE)
LOOP 4 (TAMPER)
5853
ENROLL AS
SUPERVISED

5834-4
ENROLL AS BUTTON

5869
ENROLL AS
SUPERVISED

5870API
ENROLL AS
SUPERVISED

LOOP 1
(LOW SENSITIVITY)
LOOP 2
(HIGH SENSITIVITY)

lyric-053-V1

SERIAL #1
LOOP 3

LOOP 2
(REED)

5811
ENROLL AS
SUPERVISED

LOOP 3
(TERMINALS)

LOOP 1
(TERMINALS)

5816
ENROLL AS
SUPERVISED

5809
ENROLL AS
SUPERVISED

5806/5806W3/5807
5808/5808LST/5808W3
ENROLL AS
SUPERVISED

LOOP 2
(REED)

LOOP 1
(TERMINALS)

5822T
ENROLL AS
SUPERVISED

LOOP 1

LOOP
1

5 8 0 0 WAV E
P RO G R A M
HOUSE ID

5800SS1
ENROLL AS
SUPERVISED

ON

SERIAL #2
LOOP 2
5877

5878
ENROLL AS BUTTON

5898
ENROLL AS
SUPERVISED

Notes: (1) The 5806W3 smoke detector must be used in SIA applications.
(2) Button type devices send only fault and low battery signals; no restore or check-in signals.
Supervised RF devices send periodic check-in signals, faults, restore and low battery signals.
(3) If an external sounder is required, the 5800WAVE should be used.
(4) The 5804E and 5834-4 encrypted (High-Security) devices must be activated while the system is in
Go/No-Go Test Mode. Refer to the transmitter’s Installation Instructions for complete details. The
system will confirm the enrollment of the encrypted device by beeping two times.
(5) The 5800PIR-OD, 5800RL, 5800SS1, 5804E, 5814, 5816TEMP, 5821, 5877, and 5878 wireless
transmitters have not been evaluated by ETL.

- 14 -

Lyric Controller Installation and Reference Guide

Mechanics of Programming
Navigating Menus
TouchTouch -screen Display
The LYRIC Controller’s Liquid Crystal Display (LCD) touch-screen displays variable icons and text on “screens”.
The screen displays status icons and associated text, the current time and date, system status information and
menu choices. The Menu area includes a list of commands, or choices that apply to the current selection. The
status area provides information about various system events and a colored bar also provides an indication of
system status. A “Home Screen” is displayed whenever power is applied to the system. In addition, the Home
Function key is lit Green when the system is ready or flashes when it is not. When the system is armed the Home
Function key is lit Red.

Ready To Arm - Chime

12:00PM
December 31, 2014

Security

Automation

Video

Smart Scenes

Notices

Settings

66F
Mostly Sunny

5-Day Forecast

lyric-009-V1

TM

LYRICTM Controller
Key

Description
Panic key - Initiates panic alarm options when selected for 4
seconds.
Home key - Used to exit from a screen or return to the home screen

- 15 -

Lyric Controller Installation and Reference Guide

Mechanics of Programming (Continued)
Navigation Keys
Navigating through the screens is accomplished by lightly touching the icons or menu items on the touchscreen. Once activated, the controller advances to the next screen. Selecting the “Home” (cancel) key or the “”
key will return you to the previous screen at any time unless System Programming mode is active. By touching
(selecting) an icon or key the system, depending on the function, advances to another screen, toggles between
options or scrolls through multiple options that can be selected. The system provides a prompt when a specific
input is required.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will
allow you to clearly hear the feedback announcements or system beeps from the system’s built-in
speaker. To adjust the volume, select “Settings” on the Home screen. Adjust the volume using the slide
displayed on the Settings screen and then select “Save” to accept. Upon exiting the Program Mode, the
system resets the volume to the default value (mid-level).

Home Screen
System Status is displayed at the top of screen. In addition to the system status, the Home Screen displays the
current date and time and Security, Automation, Video, Smart Scenes, Notices Settings and Help Videos icons
on two pages. When Total Connect Services are connected and web content is enabled, News and Traffic icons
are displayed along with the current weather forecast and a 5-Day Forecast button. Selectable options are
displayed on two pages. Select the “>” and “


Uploaded