Honeywell Lyric Programming Guide



Related Products

Honeywell Lyric Controller - Encrypted Wireless Security System
Honeywell Lyric Alarm System
Encrypted, HomeKit, Wireless Security System

Related Categories


Document Transcript


Lyric
TM TM TM TM
Controller



Programming Guide














Ref: LCP500-L
800-18077 4/15 Rev. B DRAFT (6/25/15)

Lyric Controller Programming Guide

- 2 -
RECOMMENDATIONS FOR PROPER PROTECTION RECOMMENDATIONS FOR PROPER PROTECTION RECOMMENDATIONS FOR PROPER PROTECTION RECOMMENDATIONS FOR PROPER PROTECTION

The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper
Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors Recommendations for Smoke and Heat Detectors Recommendations for Smoke and Heat Detectors Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be installed outside of
each separate sleeping area, and on each additional floor of a multi-floor family living unit, including
basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.
• For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.

In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up
the sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room
could prevent the control from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION APPLIANCES. SOUNDING OF FIRE NOTIFICATION APPLIANCES. SOUNDING OF FIRE NOTIFICATION APPLIANCES. SOUNDING OF FIRE NOTIFICATION APPLIANCES.

DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
BEDROOM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
BEDROOM BEDROOM
TO
BR
LVNG RM
BASEMENT
KTCHN
.
CLOSED
DOOR
GARAGE
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BDRM
floor_plan-001-V1


Recommendations For Proper Intrusion Protection Recommendations For Proper Intrusion Protection Recommendations For Proper Intrusion Protection Recommendations For Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multi-level
building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals
can be sent to the alarm monitoring station in the event that the communications (alarm signals are normally
sent over the phone lines, if connected to an alarm monitoring station).
Lyric Controller Programming Guide
- 3 -
Table of Contents Table of Contents Table of Contents Table of Contents
Mechanics of Programming .......................................................................................................................................................................... 4
Navigation Keys ............................................................................................................................................................................................. 4
Home Screen .................................................................................................................................................................................................... 5
Security Screen ............................................................................................................................................................................................... 5
Master User Tools Screen ........................................................................................................................................................................... 5
Accessing the Master User Tools Screen.................................................................................................................................................. 5
General Programming Information ............................................................................................................................................................ 6
Entering Programming Mode ....................................................................................................................................................................... 6
Programming the Data Fields ...................................................................................................................................................................... 6
Exiting Programming Mode ........................................................................................................................................................................... 7
Loading a Default Set ....................................................................................................................................................................................... 7
Reset Master User Code .................................................................................................................................................................................. 7
Security Code Notes ......................................................................................................................................................................................... 7
Data Fields ............................................................................................................................................................................................................. 7
Change Installer Code ..................................................................................................................................................................................8
Change Language ..........................................................................................................................................................................................8
Program System Type ..................................................................................................................................................................................8
Program Date Time ..................................................................................................................................................................................... 9
Program Communicator ............................................................................................................................................................................ 10
Program Zones .............................................................................................................................................................................................. 12
Batch Learning Enrollment................................................................................................................................................................... 15
Program Keys ................................................................................................................................................................................................. 16
Program Reporter ........................................................................................................................................................................................ 17
Program Sounder ......................................................................................................................................................................................... 19
Program System Settings ......................................................................................................................................................................... 19
Program Z-Wave ......................................................................................................................................................................................... 22
Program RF Keypad ................................................................................................................................................................................... 23
Communication Diagnostics ................................................................................................................................................................... 24
Registering the Lyric Control ............................................................................................................................................................. 27
Testing the System ......................................................................................................................................................................................... 28
Armed System Test .................................................................................................................................................................................... 28
Additional Tests ........................................................................................................................................................................................... 28
Rebooting the System ............................................................................................................................................................................... 29
Zone Programming Worksheet ................................................................................................................................................................. 30
Explanation of Zone Assignment Table Headings ........................................................................................................................ 34
5800 Series Transmitter Loop Numbers Diagram ............................................................................................................................ 35
Programming Default Values ..................................................................................................................................................................... 36
Lyric Summary of Connections Diagram .............................................................................................................................................. 39


Refer to the Refer to the Refer to the Refer to the Lyric Lyric Lyric Lyric Controller Controller Controller Controller Installation and Installation and Installation and Installation and Reference Reference Reference Reference Guide Guide Guide Guide p/n p/n p/n p/n 800 800 800 800- -- -1 11 18076 8076 8076 8076 or later or later or later or later for detailed for detailed for detailed for detailed
information information information information on on on on programming the system. programming the system. programming the system. programming the system.


Lyric Controller Programming Guide

- 4 -
Mechanics of Programming

Navigation Keys Navigation Keys Navigation Keys Navigation Keys
Navigating through the screens is accomplished by lightly touching the icons or menu items on the touch-
screen. Once activated, the control advances to the next screen. Selecting the “Home” (cancel) key or the “”
key will return you to the previous screen at any time unless Program mode is active. By Touching (selecting)
an icon or key the system, depending on the function, advances to another screen, toggles between options or
scrolls through multiple options that can be selected. The system provides a prompt when a specific input is
required.
lyric-009-V1
Ready To Arm - Chime
Notices
Automation
Settings
Video
Smart Scenes
66F
Mostly Sunny
5-Day Forecast
December 31, 2014
Security
12:00PM

LYRIC LYRIC LYRIC LYRIC
TM TM TM TM
Controller Controller Controller Controller Home Screen (Page 1) Home Screen (Page 1) Home Screen (Page 1) Home Screen (Page 1)

Key Key Key Key Description Description Description Description

Panic key Panic key Panic key Panic key - -- - Initiates panic alarm options when selected for 4
seconds.

Home key Home key Home key Home key - -- - Used to exit from a screen or return to the home screen
NOTE: NOTE: NOTE: NOTE: You may find it convenient to adjust the volume setting before entering the Program mode. This will allow you to
clearly hear the feedback announcements or system beeps from the system’s built-in speaker. To adjust the volume,
select “Settings” on the Home screen. Adjust the volume using the slide displayed on the Settings screen and then
select “Save” to accept. Upon exiting the Program Mode, the system resets the volume to the default value (mid level).

Home Screen Home Screen Home Screen Home Screen
System Status is displayed at the top of screen. In addition to the system status, two Home Screen pages
display the current date and time and Security, Automation, Video, Smart Scenes, Notices and Settings icons.
When Total Connect Services are connected and web content is enabled, Weather, News, Traffic and Notices
icons are displayed along with the current local weather forecast and a 5-Day Forecast button. Select the “〉” to
advance to the second page of the Home Screen and the “〈” to return to the first page.

Icon or Button Icon or Button Icon or Button Icon or Button Functio Functio Functio Function nn n
Security Provides access to Security Screen
Automation Provides access to Automation Screen
Video Provides access to Video Screen
Smart Scenes Provides access to Smart Scenes Programming Screen
Notices Provides access to Dealer Notification Message Screen
Settings Provides access to System Settings Screen
Help Videos Provides access to Instructional Help Videos
News Provides access to News Screen
Traffic Provides access to Traffic Screen
5-Day Forecast Provides access to local 5-Day Weather Forecast Screen
Current Local Weather Provides local forecast and severe weather alerts
Lyric Controller Programming Guide
- 5 -
Mechanics of Programming (Continued)
Security Screen Security Screen Security Screen Security Screen
System Status is displayed at the top of
each screen and the time and date are
displayed at the bottom of the Security
Screen. The Security Screen displays the
system status and selection “icons” and
“tabs”. The displayed pages and options
may vary slightly depending upon the
devices and services that are installed in or
connected to the system.

Ready To Arm - Chime
lyric-019-V1
ARM CUSTOM ARM STAY ARM AWAY ZONES
TOOLS
MESSAGE
SYSTEM
Ready To Arm
9:11 AM December 17, 2014 Delay

Security Screen Security Screen Security Screen Security Screen

Selection Selection Selection Selection Function Function Function Function
Arm Away Used to Arm the system in Away mode (displayed on both Security Screen pages).
Arm Stay Used to Arm the system in Stay mode (displayed on both Security Screen pages).
Arm Custom Used to Arm the system in Custom mode that arms specific selected zones (displayed on
both Security Screen pages).
System Provides information about system status
Tools Provides access to Installer and User Programming Menus (Master User Code required for
access).
Message Provides access to Message Center.
Zones Provides access to Zone information and options.
Message Provides access to Message Center.
Settings Provides access to various keypad functions (i.e.; Brightness, Volume, Voice & Chime).
Delay/Instant Used to toggle between exit delay and instant arming options (displayed on both Security
Screen pages).

Master Master Master Master User User User User Tools Tools Tools Tools Screen Screen Screen Screen
The Master User Tools screen provides access to
the User configurable features and displays eight
options. Entering the Master User Code is
required to access the User Menu. Select the “〉”
to advance to the second page of the User Tools
Menu Screen and the “〈” to return to the first
page.


Ready To Arm - Chime
lyric-018-V1
Voice Command
Advanced
WiFi Config
Back
Keypad
Date Time
Users
Reminders
Events

Master Master Master Master User User User User Tools Tools Tools Tools Menu Menu Menu Menu Screen Screen Screen Screen (Page 1) (Page 1) (Page 1) (Page 1)
Accessing the Master User Tools Screen

You may find it convenient to adjust the volume setting before entering the Programming Mode. You may find it convenient to adjust the volume setting before entering the Programming Mode. You may find it convenient to adjust the volume setting before entering the Programming Mode. You may find it convenient to adjust the volume setting before entering the Programming Mode.
This will allow you to clearly hear feedback announcements or system beeps This will allow you to clearly hear feedback announcements or system beeps This will allow you to clearly hear feedback announcements or system beeps This will allow you to clearly hear feedback announcements or system beeps. .. .
1. At the Security Screen select the “Tools” icon then enter the Master User Code (1 + 2 + 3 + 4).
Lyric Controller Programming Guide

- 6 -
General Programming Information

When power cycling the control, remove AC power first and wait approximately 1 minute before When power cycling the control, remove AC power first and wait approximately 1 minute before When power cycling the control, remove AC power first and wait approximately 1 minute before When power cycling the control, remove AC power first and wait approximately 1 minute before
disconnecting battery. disconnecting battery. disconnecting battery. disconnecting battery. If the system is Armed or in Alarm, the Tools If the system is Armed or in Alarm, the Tools If the system is Armed or in Alarm, the Tools If the system is Armed or in Alarm, the Tools icon will not be functional. icon will not be functional. icon will not be functional. icon will not be functional.
The system must first be disarmed The system must first be disarmed The system must first be disarmed The system must first be disarmed. .. .
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The
system can be programmed at any time, even at the installer's premises prior to the actual installation. Simply
apply power temporarily to the Control and then program the unit as desired.
Entering Installer Programming Mode

You may find it convenient to adjust the volume setting before entering the Programming Mode. You may find it convenient to adjust the volume setting before entering the Programming Mode. You may find it convenient to adjust the volume setting before entering the Programming Mode. You may find it convenient to adjust the volume setting before entering the Programming Mode.
This will allow you to This will allow you to This will allow you to This will allow you to clearly hear feedback announcements or system beeps clearly hear feedback announcements or system beeps clearly hear feedback announcements or system beeps clearly hear feedback announcements or system beeps. .. .
1. Power-up the control and allow it to “boot-up”. “System Standby” is displayed on the touchscreen. When
the “boot-up” is complete (approximately 1-2 minutes) “Ready to Arm” is displayed.
2. Select the “Security” icon.
3. Select “Tools” icon.
4. Enter the Installer Code (4 + 1 + 1 + 2) on the displayed keypad.
5. The Installer Tools menu screen appears. Select the “Program” button. “System Programming…” is displayed
in an orange band at the top of the screen. Additionally, the “Panic” button is lit and the “Home” button
alternately flashes red and green.
NOTE: NOTE: NOTE: NOTE: Step 6 is only required if the Controller has not already been associated with an AlarmNet 360
TM

account. If the Controller has been enrolled proceed to step 7.
6. If programming the Lyric locally, program the following fields by selecting the field and entering the
required information on the keyboard. The User Name and Customer Account Number are required in order
for the Lyric Controller to communicate with AlarmNet 360
TM
.
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
User Name Enter the associated Dealer Identification Number assigned to the
Dealer/Installer.
Password Enter the Dealer’s AlarmNet 360 Password
Alarm Reporting Number Enter the AlarmNet 360 Account Number (City/CS/Sub ID information)
Supervision Time Enter the Supervision Time (None, 24-Hour or 30 Day)
7. Select “Save” when complete.
8. Select one of the following options to advance to that Programming screen:
Installer Code
Date Time
Zones
Keys
Sounder
System Type
Communicator
Comm. Diagnostics
Reporter
System Settings
Use the down “˅” arrow to scroll to the second page of options.
Default Config.
Reset Master Code
RF Keypad
Z-Wave
Language
9. The system advances to the Programming screen of the selected option.
Programming the Data Fields
1. Select each desired programming option, and then select the required entry. The system beeps each time
a selection is made.
2. The system will toggle or scroll through the options or display a new screen as applicable.
3. To delete or change an entry, select the desired option, and then select the required entry.
Lyric Controller Programming Guide
- 7 -
Exiting Programming Mode
1. Select the “” key to exit the current screen. The system returns to the previous screen.
2. Select the “” key as required until the system returns to the Security Screen
3. Select the “” key OR depress the Home button to return to the Home Screen.
Loading a Default Set
Refer to the Programming Default Values section of this manual to view the default values.
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Default Config. Default Config. Default Config. Default Config.
Select ‘Default Config’ and select the appropriate Default Configuration from the
following options:
Default Config 1
Default Config 2
Default Config 3
Default Config 4
Reset Master User Code
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Reset Master Code Reset Master Code Reset Master Code Reset Master Code 1. The system displays a confirmation screen. Select the “Yes” key to reset the
Master User Code to “1234”.
2. If confirmed, the Master Code will be reset back to “1-2-3-4”. This will be logged
in the System Event Log as “Reset Master Code User 2 E655”. The system
returns to the second page of the Installer Programming Tools menu. OR
If the reset failed, the system will display: “Command Failed. Unable to Reset
Master Code”.
Security Code Notes
• The Master and Secondary security codes permit access to the system for arming, disarming, etc.
• The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code cannot disarm
the system if it was armed by pressing and holding a Quick-Arm button.
• The Guest Code can disarm the system only if it was used to arm it. In addition, the Guest Code cannot disarm the
system if it was armed by pressing and holding a Quick-Arm button.
• Duress code sends a special code to the monitoring station when used to perform any system operation. Instruct
users to be careful not to use this code for normal usage.
• Opening/closing reports are sent for the Installer Code, with the appropriate subscriber number. Master Code and
set of secondary user codes are sent as No. 2 and 3-48 respectively, in Contact ID® format (with the appropriate
user number).
Lyric Controller Programming Guide

- 8 -
DATA FIELDS
Change Installer Code
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Installer Code Installer Code Installer Code Installer Code
1. The current four-digit Installer Code is displayed on the left side
of the screen. Select “Clear”.
2. Enter a new four-digit Installer Code on the displayed keypad.
The system will display the new code on the left side of the
screen.
3. Select “Done” when you are finished.
4. The system returns to the “System Programming” Screen.
4112
Change Language
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Language Language Language Language
1. If applicable, select “Language” to display the following options:
Installer Language User Language
2. Select “Installer Language” OR User Language. The system toggles between the
following options:
English
French
Spanish
Portuguese
3. Select the desired language.
4. Select “Save” when you are finished.
5. A confirmation screen appears. If “Yes” is selected, the System returns to the
second page of the Programming screen, which will be displayed in the selected
language.
Program System Type
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
RF Jam RF Jam RF Jam RF Jam

Enable or disable RF Jam Detection, Log & Reporting Options.
Options: Options: Options: Options:
Disabled
RF Jam Log
RF Jam Log & Report
RF Jam Log
RF House Code RF House Code RF House Code RF House Code Enter a two-digit code (00-31) and select “Done”. 0
Two Way Voice Two Way Voice Two Way Voice Two Way Voice

Enable or disable Two Way Voice communication with the Central
Station.
The system toggles between “Disabled” and “Enabled”.
Disabled
Events Events Events Events - -- - Log All Log All Log All Log All

Enable or disable multiple options for event logging (i.e.; alarms,
troubles, open/close & bypass).
The system toggles between “Log All Set” and “Press To Log All”
NOT NOT NOT NOTE: E: E: E: Selecting “Press” to Log All” will set all of the remaining options
to “Enabled”.
Press to Log All
Events Events Events Events - -- - Log Alarm Log Alarm Log Alarm Log Alarm
Enable or disable Alarm Event Logging
The system toggles between “Disabled” and “Enabled”.
Enabled

Lyric Controller Programming Guide


- 9 -
Program System Type (Continued)
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Events Events Events Events - -- - Log Bypass Log Bypass Log Bypass Log Bypass
Enable or disable Zone Bypass Event Logging
The system toggles between “Disabled” and “Enabled”.
Enabled
Events Events Events Events - -- - Log Open Log Open Log Open Log Open
Close Close Close Close
Enable or disable Open/Close Event Logging
The system toggles between “Disabled” and “Enabled”
Enabled
Events Events Events Events - -- - Log Log Log Log
Trouble Trouble Trouble Trouble
Enable or disable Trouble Event Logging
The system toggles between “Disabled” and “Enabled”
Enabled
Non Security Non Security Non Security Non Security
Enable or disable Non Security Event Logging
The system toggles between “Disabled” and “Enabled”
Enabled
Remote Access Remote Access Remote Access Remote Access
Serial Serial Serial Serial
Enable or disable end user to access their system via a website
The system toggles between “Disabled” and “Enabled”
Disabled
Multi Mode Serial Multi Mode Serial Multi Mode Serial Multi Mode Serial

Enable or disable transmission of panel status events via email
(Active only when Remote Access Serial is enabled)
The system toggles between “Disabled” and “Enhanced Reports”.
Disabled
Program Date Time
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Date Time Date Time Date Time Date Time 1. Using the left “ “arrows select the Month and
Year then select the date. Select the “˅” arrow to advance to
the next screen.
2. To set the correct time, touch the “Clear” button.
3. Enter the correct time and then select AM or PM. Select the “˅”
arrow to advance to the next screen or select “Save” to return
to the System Programming Screen.
None
Time Zone Time Zone Time Zone Time Zone

Select the correct Time Zone.
Options: Options: Options: Options:
Eastern (EST) Pacific (PST) Atlantic (AST)
Central (CST) Alaska (AKST) Newfoundland (NT)
Hawaii (HAST) Brasilia (BRT)
Mountain (MST) Mid-Atlantic (MAT)

Eastern (EST)
Dayl Dayl Dayl Daylight Savings ight Savings ight Savings ight Savings
Time Time Time Time

Enable or disable Daylight Savings Time adjustment. If “Yes” is
selected the Start Month, Start Week, End Month and End Week
options will be active.
The System toggles between “Yes” and “No”.
Yes
Start Month Start Month Start Month Start Month Select a Daylight Savings Time Start Month.
Options: Options: Options: Options:
January September June
March November August
May February October
July April December

March
Start Week Start Week Start Week Start Week Select a Daylight Savings Time Start Week
The System toggles between “First”, “Second”, “Third”, “Last”,
“Next to Last” and “3rd from Last”.
Second
End Month End Month End Month End Month Select a Daylight Savings Time End Month.
Options: Options: Options: Options:
January September June
March November August
May February October
July April December

November
End Week End Week End Week End Week Select a Daylight Savings Time End Week
The System toggles between “First”, “Second”, “Third”, “Last”,
“Next to Last” and “3rd from Last”.
First

Lyric Controller Programming Guide

- 10 -
Program Communicator

A router is required if you are utilizing WiFi for communications. The router must be powered on A router is required if you are utilizing WiFi for communications. The router must be powered on A router is required if you are utilizing WiFi for communications. The router must be powered on A router is required if you are utilizing WiFi for communications. The router must be powered on
and connected for WiFi operation (a and connected for WiFi operation (a and connected for WiFi operation (a and connected for WiFi operation (alarm reporting) to occur. larm reporting) to occur. larm reporting) to occur. larm reporting) to occur. The panel must be connected to the The panel must be connected to the The panel must be connected to the The panel must be connected to the
WiFi network in order to communicate with WiFi network in order to communicate with WiFi network in order to communicate with WiFi network in order to communicate with AlarmNet 360 AlarmNet 360 AlarmNet 360 AlarmNet 360 . .. .
Remote Access (Total Connect) and Multi Mode (PSD) over WiFi or Cellular cannot be enabled in the
panel alone. Availability of this service is controlled via the web-based programming tool on the
AlarmNet 360 website. These features must be enabled through the AlarmNet 360 website first and
transferred to the device.
Where applicable, use the down “˅” arrow to scroll to the subsequent pages of options. Use the “˄” arrow to
return to the previous page. If the account associated with the Lyric Controller has been set up using AlarmNet
360, the APL, City ID, CS ID, Supervision, Old Alarm Time, Remote Acc. Comm., Multi Mode Comm., WiFi Fault
Time, Cellular Fault Time, Cellular Rollover, Cellular 24 Hour Test fields can be viewed but are not programmable
locally. Only the Communications Path, DHCP and IP Address fields can be programmed locally at the panel.
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Communications Communications Communications Communications
Path Path Path Path
Select the type of Communications Module.
NOTE: NOTE: NOTE: NOTE: The available options are dependent upon which
communications module(s) has been installed. If
Communication Path is set to Cellular, the control will
report to AlarmNet 360 over the Cellular network not
WiFi.
Options: Options: Options: Options:
None
WiFi
Cellular
WiFi & Cellular
WiFi
APL APL APL APL Enable or disable Advanced Protection Logic “Enabled” and
“Disabled”.
Options: Options: Options: Options:
Disabled
Enabled
Disabled
City ID City ID City ID City ID

Enter 2-digit Central Station Primary City ID (Decimal).
Options Options Options Options: :: :
01-99
Blank
CS ID CS ID CS ID CS ID Enter 2-digit Primary Central Station ID (Hex).
Options: Options: Options: Options:
01-FE
Blank
Sub ID Sub ID Sub ID Sub ID

Enter the 4-digit Subscriber Account Number (Decimal).
Options Options Options Options: :: :
0001-9999
Blank
Supervision Supervision Supervision Supervision

Select how often the Communications Module sends supervisory
messages to the Central Station.
O OO Options: ptions: ptions: ptions:
None
24 Hours
30 Days
24 Hours
Old Alarm Time Old Alarm Time Old Alarm Time Old Alarm Time Select how long the system will attempt to redeliver an
undeliverable alarm message to the Central Station.
Options: Options: Options: Options:
10 Minutes 15 Minutes
30 Minutes 1 Hour
2 Hours 4 Hours
8 Hours 12 Hours
24 Hours
10 Minutes

Lyric Controller Programming Guide


- 11 -
Program Communicator (Continued)
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Remote Acc. Comm. Remote Acc. Comm. Remote Acc. Comm. Remote Acc. Comm.

Enables or disables user remote access via internet and/or Cellular.
NOTE: NOTE: NOTE: NOTE: This field will not be programmable unless it is enabled when
creating the Communications Module account in AlarmNet
360.
Options: Options: Options: Options:
Disabled
Enabled
Disabled
Multi Mode Comm. Multi Mode Comm. Multi Mode Comm. Multi Mode Comm.

Enables or disables Multi Mode feature.
NOTE: NOTE: NOTE: NOTE: This field will only be available if Remote Acc. Comm. Is
enabled.
Options: Options: Options: Options:
Disabled
Enhanced Reports
Disabled
WiFi WiFi WiFi WiFi Fault Time Fault Time Fault Time Fault Time
(min) (min) (min) (min)

Selects time delay before the Communications Module notifies the
control panel of a loss of contact with the internet. Appears only if
WiFi is enabled in Communications Path field. Enter the 2-digit time
delay (in minutes).
Options Options Options Options: :: :
00-99
60
Use DHCP Use DHCP Use DHCP Use DHCP

Allows the panel to dynamically select the IP addresses.
NOTE: NOTE: NOTE: NOTE: If “No” is selected, four additional programming fields are
displayed.
Options: Options: Options: Options:
Yes
No
Yes
NIC IP Address NIC IP Address NIC IP Address NIC IP Address

This field only appears if “No’ is selected in the Use DHCP field. Enter
the 4-part Network Interface Card (NIC) IP address (up to 12 digits).

255.255.255.255
Subnet Mask Subnet Mask Subnet Mask Subnet Mask

This field only appears if “No’ is selected in the Use DHCP field. Enter
the 4-part Subnet Address (up to 12 digits).
255.255.255.255
Gateway IP Address Gateway IP Address Gateway IP Address Gateway IP Address

This field only appears if “No’ is selected in the Use DHCP field. Enter
the 4-part Gateway IP Address (up to 12 digits).
255.255.255.255
DNS Server IP DNS Server IP DNS Server IP DNS Server IP
Addre Addre Addre Address ss ss ss

This field only appears if “No’ is selected in the Use DHCP field. Enter
the 4-part Domain Name Server IP Address (up to 12 digits).
Select “Save” and then select “OK” when the “Programming Done”
screen appears.
255.255.255.255
Cellular Cellular Cellular Cellular Fault Time Fault Time Fault Time Fault Time
(m (m (m (min) in) in) in)

Selects time delay before the Communications Module notifies the
control panel of a loss of contact with the network. Appears only if
Cellular is enabled in Communications Path field. Enter the 2-digit
time delay (in minutes).
Options: Options: Options: Options:
00-99
60
Cell Cell Cell Cellular ular ular ular Rollover Rollover Rollover Rollover

Allows Supervision messages to be sent over Cellular in the event
that contact with the internet is lost. Appears only if “WiFi &
Cellular” is enabled in the Communications Path field.
Options: Options: Options: Options:
No
Yes
No
Cellular Cellular Cellular Cellular 24 Hour Test 24 Hour Test 24 Hour Test 24 Hour Test

Enables daily test of Cellular module operation. Appears only if “WiFi
& Cellular” is enabled in the Communications Path field.
Options: Options: Options: Options:
No
Yes
Select “Save” and then select “OK” when the “Programming Done”
screen appears.
No
Lyric Controller Programming Guide

- 12 -
Program Zones
The Lyric supports both Honeywell 5800 Series and SiX™ Series Bi-Directional sensors. The steps required to
enroll these sensors differ. It should be noted that once a SiX™ Series sensor has been enrolled in the panel it
must be deleted before it can be enrolled in a different panel. Multiple SiX™ Series sensors can be enrolled using
the Batch Learning Mode.
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Zones Zones Zones Zones

Use the down “˅” arrow to scroll to the next page of options or the “˄” arrow to
return to the previous page.
1. New
3. Front Door
5. Window
7. New
2. New
4. Back Door
6. Motion Sensor
8. New
9. – 126. New
127. – 130. New (Main) (reserved for Garage Door Zones)
131. – 162. (Button Zones)
280. – 291. Temperature (Z-Wave Thermostat zones)
840. – 843. WiFi Tablets
850. – 857. SiX™ Keypads
995. Fire
996. Medical
997. No alarm Zone
999. Police
Select a zone and then select “Edit” or “Add New” to program the next available zone.
The following fields are displayed (dependent upon selected Zone).
Serial Number Serial Number Serial Number Serial Number

NOTE: NOTE: NOTE: NOTE: This field does not apply to Hardwire Zone 1 and 2 or Temperature Zones 280-291)
When “Serial Number” has been selected “Enter Serial Number or Activate” is
displayed. Follow the applicable steps below to enroll the SiX™ or 5800 Series sensors.

Enroll Enroll Enroll Enroll SiX™ SiX™ SiX™ SiX™ Series Series Series Series Devices Devices Devices Devices (Refer to the documentation provided with the specific
SiX™ device being enrolled for additional information.)
1. Insert the battery in the sensor or pull the battery tab as applicable. The sensor’s
green LED will flash rapidly. Allow up to 10 minutes for pairing to complete. If the
sensor has been successfully paired with the control, the sensor’s green LED will
light steady for three seconds and the control will beep once to confirm. If the
pairing is not successful, remove the battery and repeat this step.
2. Two transmissions (open/close) of the device will be required. The device serial
number is displayed on the screen following the first transmission and the panel
beeps two times. Following the second transmission the system beeps three times
and returns to the Zone Programming Screen.
3. The device’s battery level and signal strength is displayed on the Lyric control.

Enroll 5800 Series Devices Enroll 5800 Series Devices Enroll 5800 Series Devices Enroll 5800 Series Devices
The transmitter serial number and loop number can be enrolled via RF transmission OR
manually.
Enroll via RF Learning - To enroll the 5800 device using RF Learning mode, three
transmissions (open/close) of the device will be required. The initial transmission
activates the RF Learning mode and the system will emit a single beep. A second
transmission enrolls the serial number (which is displayed on the screen) and the
system beeps two times and displays “Activate Sensor Again To Confirm”. A third
transmission will confirm the serial number. The system beeps two times and returns to
the Zone programming screen. Select “Save”. The system returns to the Zone
programming screen.
Enroll 5800 Devices Manually - Enter the 7-digit serial number printed on the
transmitter using the displayed keypad and select “Done”. The system beeps one time
and returns to the Zone Programming Screen. Select “Save”. The system returns to the
Zone Programming Screen.
NOTE: NOTE: NOTE: NOTE: If a duplicate serial number is entered, the system will emit a single long beep and a
confirmation screen will be displayed. Select “OK”. The system returns to the
previous screen.


Lyric Controller Programming Guide


- 13 -
Program Zones (Continued)

Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Loop Number Loop Number Loop Number Loop Number

NOTE: NOTE: NOTE: NOTE: This field does not apply to Hardwire Zone 1 and 2 or Temperature Zones (280-291)
or if SiX™ Series devices are being programmed.
Select “Loop Number” to toggle between 1, 2, 3 and 4 as applicable. Select Save.
Service Service Service Service NOTE: NOTE: NOTE: NOTE: This field applies if SiX™ Series devices are being programmed.
Select “Service” to change the option, which is dependent upon the type of SiX™
device that is being installed.
Zone Description1/ Zone Description1/ Zone Description1/ Zone Description1/
Zone Description 2 Zone Description 2 Zone Description 2 Zone Description 2
Select “Zone Description 1 or Zone Description 2”. Using the displayed keypad enter
Zone Description 1 or Zone Description 2. The system announces the Zone Description.
Enter “Done”, when you are finished. The system returns to the Zone Programming
page.
NOTE: NOTE: NOTE: NOTE: When programming the Zone Description, after entering the first letter of the
description on the keypad, use the up “˄” and down “˅” arrows to scroll through
the available preprogrammed zone descriptions. For a list of the pre-programmed
Zone Descriptors, please visit:
http://www.security.honeywell.com/hsc/resources/MyWebTech
Devi Devi Devi Device Type ce Type ce Type ce Type

Use the down “˅” arrow to scroll to the next page of options. Use the “˄” arrow to
return to the previous page.
Select “Device Type” from the displayed list, the system returns to the Zone screen.
Select “Save” if programming is complete.
Options: Options: Options: Options:
New Door
Window Motion Sensor
Glass Break Smoke Detector
Heat Sensor Carbon Mono. Det.
Temperature Flood
Environmental Medical
Fire Police
Local Alarm Bell
Garage Door Other
Response Type Response Type Response Type Response Type

The system displays the specific options, which are dependent upon the Device Type
that was selected for the zone. Use the down “˅” arrow to scroll to the next page of
options. Use the “˄” arrow to return to the previous page.
Select “Response Type” from the displayed list, the system returns to the Zone screen.
Select “Save” if programming is complete.
Options: Options: Options: Options:
Not Used Entry Exit 1
Entry Exit 2 Perimeter
Interior Follower Trouble
24 Hour Silent 24 Hour Audible
24 Hour Auxiliary Fire No Verification
Interior With Delay Monitor
Carbon Monoxide Garage
Arm Stay Arm Away
Disarm No Response
Silent Burglary Resident Monitor
Resident Response General Monitor
General Response Fire With Verification
Day/Night Garage Monitor
Local Alarm
Select “Save” if programming is complete. The system returns to the Zone
Programming screen.

Lyric Controller Programming Guide

- 14 -
Program Zones (Continued)
Programming Field Programming Field Programming Field Programming Field F FF Function and Action unction and Action unction and Action unction and Action
Alarm Report Alarm Report Alarm Report Alarm Report

Activates reporting option for the device being enrolled.
NOTE: NOTE: NOTE: NOTE: This field is for Alarms. If Response Type “Trouble” is set up and Alarm Report is
set to “No” the system will still report if Report Alarms was enabled in the Reporter
programming.
Select “Alarm Report” to toggle between “No” or “Yes”. Select “Save” if programming
is complete. The system returns to the Zone Programming screen.
Options: Options: Options: Options:
No
Yes
Chime Chime Chime Chime

Enable or disable chime mode for specific device being enrolled (applies to Entry/
Exit, Perimeter, and Interior Response types only)
Select “Chime” to scroll through the available chime sounds. Select “Save” if
programming is complete. The system returns to the Zone Programming screen.
Options: Options: Options: Options:
Disabled
Standard
Melody
Melody Long
Ascend
Ascend Long
Alert 1
Alert 2
Doorbell 1
Doorbell 2
Evolve
Select “Save” if programming is complete. The system returns to the Zone
Programming screen.
Supervision Supervision Supervision Supervision

Select supervision for device being enrolled. The system displays the applicable
options based upon the Device Type that was selected. Select “Supervision” to scroll
between the following options:
Options: Options: Options: Options:
Hardwire Zone
Normal Open
Normal Closed
End of Line
RF Zone
Supervised
Unsupervised
Temperature
High Temp (Default selection for Zones 280, 282, 284 and 286, 288, 290)
Low Temp (Default selection for Zones 281, 283, 285 and 287, 289, 291)
Select “Save” if programming is complete. The system returns to the Zone
Programming screen.
Arm Night Arm Night Arm Night Arm Night Allows specific programmed motion sensors to be active when Arm Night Stay mode
is enabled and the system is Armed in Stay mode by the User. If “Motion Sensor” is
selected in the Response Type Field, the Arm Night option will be available.
Options: Options: Options: Options:
Yes
No
Select “Save” if programming is complete. The system returns to the Zone
Programming screen.

Lyric Controller Programming Guide


- 15 -

Program Zones (Continued)
Batch Learning Enrollment (SiX™ Series Devices only)
The Lyric Controller is capable of learning multiple SiX Series devices via the Batch (RF) Learning
Mode.
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Zones Zones Zones Zones After entering the Zone Programming mode, fault and restore each of the sensors
being enrolled. (Refer to the documentation provided with the specific SiX™ device
being enrolled for additional information.)
The controller will assign the device to the next available Zone. The device’s battery
level and signal strength is displayed on the Lyric control.
N NN NOTE OTE OTE OTE: :: : The default “Service” for the SiXCT Contacts is set to “Reed” whether learned
locally at the Controller or via TotalConnect 360.
To change the Service to “Contact” perform the following for each applicable Zone:
1. Select the appropriate Zone and then select ‘Edit”
2. Select “Service”. The system toggles between “Reed” and “Contact”.
3. Select “Save”
4. Select the “” key to exit the current screen. The system returns to the previous
screen.

Lyric Controller Programming Guide

- 16 -
Program Keys
The Lyric Controller features 32 RF Keyfob Zones that allow it to support a combination of one, two, four, six
and eight button devices. It should be noted that once a SiX™ Series keyfob has been enrolled in the panel it
must be deleted before it can be enrolled in a different panel.
Prog Prog Prog Programming Field ramming Field ramming Field ramming Field Function and Action Function and Action Function and Action Function and Action
Keys Keys Keys Keys

Select the “Add new” button to enroll a new keyfob.
Key Type Key Type Key Type Key Type Select the specific type of key being entered or enrolled. The system scrolls through
the available options.
NOTE NOTE NOTE NOTE: :: : Before enrolling a SiXFOB keyfob select “4 Button”, if you are enrolling four buttons or
“8 Button” if you are enrolling all 8 buttons.
Options: Options: Options: Options:
1 Button 6 Button
2 Button 8 Button
4 Button
User User User User Select a User from the displayed list.
Options: Options: Options: Options:
Master
Guest
Duress
User 3 – User 46
N NN NOTE OTE OTE OTE: :: : The keyfob must be associated with a specific User/User Code in order for it to operate.
Refer to the Lyric User Guide for additional Information regarding User Codes.
Serial Number Serial Number Serial Number Serial Number

When “Serial Number” has been selected “Enter Serial Number or Activate” is displayed.
Follow the applicable steps below to enroll the SiX™ or 5800 Series Key Fobs.
Enroll Enroll Enroll Enroll SiXFOB k SiXFOB k SiXFOB k SiXFOB key ey ey eyf ff fobs obs obs obs (Refer to the documentation provided with the SiXFOB
keyfob being enrolled for additional information.)
1. Press the top two buttons on the SiXFOB. The keyfob’s left and right LEDs will
alternately flash green for 3-8 seconds. Allow up to 20 seconds for pairing to
complete. If the sensor has been successfully paired with the control the keyfob’s
green LED will light steady for three seconds and the control will beep once to
confirm. The device serial number is displayed on the screen following the first
transmission and the panel beeps two times. If the pairing is not successful, press
the top two buttons again to restart the enrollment and repeat this step.
2. Two transmissions of the device will be required. Depress and hold the top two
buttons on the keyfob for 3-8 seconds. Following the second transmission the
system beeps three times and returns to the Zone Programming Screen.
3. Assign a User and select “Save”
4. The keyfob’s battery level and signal strength is displayed on the Lyric control
Zone programming screen.

Enroll 5800 Series Keyf Enroll 5800 Series Keyf Enroll 5800 Series Keyf Enroll 5800 Series Keyfobs obs obs obs
The transmitter serial number and loop number can be enrolled via RF transmission OR
manually.
Enroll via RF Learning - To enroll the 5800 device using RF Learning mode, three
transmissions (open/close) of the device will be required. The initial transmission
activates the RF Learning mode and the system will emit a single beep. A second
transmission enrolls the serial number and the system beeps two times and displays
“Activate Sensor Again To Confirm”. A third transmission will confirm the serial
number. The system beeps two times and returns to the programming Screen.
Enroll 5800 Devices Manually - Enter the 7-digit serial number printed on the
transmitter using the displayed keypad and select “Done”. The system beeps one time
and returns to the programming Screen.
Zone Zone Zone Zone

The system displays the next available Key Zone Number. Select “Zone” to manually
enter a specific 3-digit Zone Number on the displayed keypad.
NOTE NOTE NOTE NOTE: :: : If the desired Zone Number is not available, the system returns to the previous screen.
Options: Options: Options: Options:
131-162
Select ”Done”. The system returns to the previous screen. Repeat the previous step to
enter another Zone Number.

Lyric Controller Programming Guide


- 17 -
Program Keys (Continued)
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Button Key * Button Key * Button Key * Button Key * - -- - Zn * Zn * Zn * Zn *
* The Key number and
Zn number are
dependent upon the
Key Type selected.


Assign a function to a specific Button Key. The system scrolls through the available
options.
Options: Options: Options: Options:
Disarm Arm Away * Options are the same for each
Button/Zone combination.
Arm Stay No Response
24 Hour Silent 24 Hour Audible
24 Hour Auxiliary Silent Burglary
Fire No Verification
Program Reporter
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Repor Repor Repor Report Selection t Selection t Selection t Selection

Enable or disable Reporting of Specific Events. Use the down “˅”
arrow to scroll to the next page of options. Use the “˄” arrow to
return to the previous page.
Not Applicable
Arm Away Arm Away Arm Away Arm Away Enable or disable reports to the Central Station when the system
is Armed Away.
The system toggles between “Disabled” and “Enabled”.
Enabled
Arm Stay Arm Stay Arm Stay Arm Stay Enable or disable reports to the Central Station when the system
is Armed Stay.
The system toggles between “Disabled” and “Enabled”.
Enabled
Disarm Disarm Disarm Disarm Enable or disable reports to the Central Station when the system
is Disarmed.
The system toggles between “Disabled” and “Enabled”.
Enabled
Exit Error Exit Error Exit Error Exit Error Enable or disable reports to the Central Station when an Exit Error
is detected.
The system toggles between “Disabled” and “Enabled”.
Enabled
Recent Closing Recent Closing Recent Closing Recent Closing Enable or disable reports to the Central Station when the system
is Armed Away and any burglary zone is faulted (within two
minutes after the initial exit delay expires).
The system toggles between “Disabled” and “Enabled”.
Enabled
Event Log Full Event Log Full Event Log Full Event Log Full Enable or disable reports to the Central Station when system
detects that the Event Log is full.
The system toggles between “Disabled” and “Enabled”.
Enabled
Trouble Trouble Trouble Trouble Enable or disable reports to the Central Station when the system
detects that a Zone has a Trouble condition.
The system toggles between “Disabled” and “Enabled”.
Enabled
Trouble Restore Trouble Restore Trouble Restore Trouble Restore Enable or disable reports to the Central Station when the system
detects that a zone that had been in Trouble has been restored.
The system toggles between “Disabled” and “Enabled”.
Enabled
Alarm Restore Alarm Restore Alarm Restore Alarm Restore Enable or disable reports to the Central Station when the system
detects that a zone that had been in Alarm has been restored.
The system toggles between “Disabled” and “Enabled”.
Enabled
Alarm Cancel Alarm Cancel Alarm Cancel Alarm Cancel Enable or disable reports to the Central Station when Alarm has
been cancelled
The system toggles between “Disabled” and “Enabled”.
Enabled
Test Test Test Test Enable or disable reports to the Central Station when a Test has
been initiated.
The system toggles between “Disabled” and “Enabled”.
Enabled
Test Restore Test Restore Test Restore Test Restore Enable or disable reports to the Central Station when a Test has
been completed.
The system toggles between “Disabled” and “Enabled”.
Enabled
Bypass Bypass Bypass Bypass Enable or disable reports to the Central Station when a Zone has
been manually bypassed.
The system toggles between “Disabled” and “Enabled”.
Enabled
Lyric Controller Programming Guide

- 18 -
Program Reporter (Continued)
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Bypass Restore Bypass Restore Bypass Restore Bypass Restore Enable or disable reports to the Central Station when a bypassed
zone has been restored.
The system toggles between “Disabled” and “Enabled”.
Enabled
AC Loss AC Loss AC Loss AC Loss Enable or disable reports to the Central Station when the system
detects the loss of AC power.
The system toggles between “Disabled” and “Enabled”.
Enabled
AC Loss Restore AC Loss Restore AC Loss Restore AC Loss Restore Enable or disable reports to the Central Station when the system
detects that AC power has been restored.
The system toggles between “Disabled” and “Enabled”.
Enabled
Low Battery Low Battery Low Battery Low Battery Enable or disable reports to the Central Station when the system
detects a Low Battery condition.
The system toggles between “Disabled” and “Enabled”.
Enabled
Low Battery Restore Low Battery Restore Low Battery Restore Low Battery Restore Enable or disable reports to the Central Station when the system
detects that a Low Battery condition has been corrected.
The system toggles between “Disabled” and “Enabled”.
Enabled
RF Low Battery RF Low Battery RF Low Battery RF Low Battery Enable or disable reports to the Central Station when the system
detects a Low Battery condition in an RF transmitter.
The system toggles between “Disabled” and “Enabled”.
Enabled
RF Low Battery RF Low Battery RF Low Battery RF Low Battery
Restore Restore Restore Restore
Enable or disable reports to the Central Station when the system
detects that a Low Battery condition in an RF transmitter has
been corrected.
The system toggles between “Disabled” and “Enabled”.
Enabled
Options Options Options Options Select Reporter Options Reporting of Specific Events. Not applicable
Number of Reports Number of Reports Number of Reports Number of Reports
Limits the number of messages sent to the Central Station during
an armed period. The system scrolls between the available options.
Options: Options: Options: Options:
1 Report
2 Reports
3 Reports
4 Reports
5 Reports
6 Reports
2 Reports
Alarm Report Delay Alarm Report Delay Alarm Report Delay Alarm Report Delay Select the time delay for alarm reporting. The system scrolls
between the available options.
Options: Options: Options: Options:
No delay
15 Sec.
30 Sec.
45 Sec.
30 Sec.
First Offset Report First Offset Report First Offset Report First Offset Report Select the time for the first Test Report following power-
up/programming or downloading. The system scrolls between the
available options.
O OO Options: ptions: ptions: ptions:
6 Hrs
12 Hrs
18 Hrs
24 Hrs
6 Hrs
Report Frequency Report Frequency Report Frequency Report Frequency Select the Test Report frequency. The system scrolls between the
available options.
O OO Options: ptions: ptions: ptions:
Never
Every Day
Every 7 Days
Every 30 Days
Never

Lyric Controller Programming Guide


- 19 -
Program Sounder
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Burglary Alarm Burglary Alarm Burglary Alarm Burglary Alarm
Sound Sound Sound Sound
Enables or disables alarm sound for burglary. The system toggles
between the available options.
Options: Options: Options: Options:
Yes
No
Yes
Burglary Bell Timeout Burglary Bell Timeout Burglary Bell Timeout Burglary Bell Timeout Disable or select the time for timeout of the Burglary Alarm
Sounder. The system scrolls between the available options.
Options: Options: Options: Options:
No
4 Minutes
8 Minutes
12 Minutes
16 Minutes
4 Minutes
F FF Fire Bell Timeout ire Bell Timeout ire Bell Timeout ire Bell Timeout Disable or select the time for timeout of the Fire Alarm Sounder.
The system scrolls between the available options.
Options: Options: Options: Options:
No
4 Minutes
8 Minutes
12 Minutes
16 Minutes
4 Minutes
Arm Confirm Arm Confirm Arm Confirm Arm Confirm Disable or enable sounder “ding” when system is armed locally or
via an RF Keypad or Keyfob. The system scrolls between the
available options.
NOTE: NOTE: NOTE: NOTE: This feature must be enabled for Commercial Burglary
installations.
Options: Options: Options: Options:
None
All RF
RF Key Fob
RF Keypad
RF Keyfob
Program System Settings
Progra Progra Progra Programming Field mming Field mming Field mming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Entry Delay 1 Entry Delay 1 Entry Delay 1 Entry Delay 1 Select an Entry Delay time in seconds. The system will wait the
selected time before sounding alarm upon entering, if system has
not been disarmed.
ETL ETL ETL ETL: :: : The Entry Delay must be set for a maximum of 45 seconds.
SIA SIA SIA SIA: :: : The Entry Delay must be set to a minimum of 30 seconds. The
sum of Entry Delay 1 and the Alarm Report Delay (burglary
abort window) should not exceed 1 minute. “None” is only
allowed allowed allowed allowed for use in Commercial High-Security applications.
Options: Options: Options: Options:
None 90 Seconds
15 Seconds 2 Minutes
30 Seconds 3 Minutes
45 Seconds 4 Minutes
60 Seconds
30 Seconds

Lyric Controller Programming Guide

- 20 -
Program System Settings (Continued)
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Entry Delay 2 Entry Delay 2 Entry Delay 2 Entry Delay 2 Select an Entry Delay time in seconds. The system will wait the
selected time before sounding alarm upon entering, if system has
not been disarmed.
ETL ETL ETL ETL: :: : The Entry Delay must be set for a maximum of 45 seconds.
SIA SIA SIA SIA: :: : The Entry Delay must be set to a minimum of 30 seconds. The
sum of Entry Delay 1 and the Alarm Report Delay (burglary
abort window) should not exceed 1 minute. “None” is only
allowed allowed allowed allowed for use in Commercial High-Security applications.
Options: Options: Options: Options:
None 90 Seconds
15 Seconds 2 Minutes
30 Seconds 3 Minutes
45 Seconds 4 Minutes
60 Seconds

30 Seconds
Exit Delay Exit Delay Exit Delay Exit Delay Select an Exit Delay time in seconds for both Entry Delay 1 and 2
Zone Types. The system will wait the selected time before
sounding an alarm if the exit door is left open after the system has
been armed.
Options: Options: Options: Options:
45 Seconds
60 Seconds
90 Seconds
2 Minutes
60 Seconds
Backlight Timeout Backlight Timeout Backlight Timeout Backlight Timeout Disable or enable backlight turnoff after 30 seconds. The system
toggles between the available options.
Options Options Options Options: :: :
No
30 Seconds
30 Seconds
Quick Arm Quick Arm Quick Arm Quick Arm Disable or enable Quick Arm Mode. If enabled, pressing the AWAY
button (ICON) and then selecting the “Quick Arm” button on the
displayed keypad will arm the system. The system toggles
between the available options.
Options: Options: Options: Options:
No
Yes
Yes
Quick Exit Quick Exit Quick Exit Quick Exit Disable or enable Quick Exit Mode. If enabled the Exit Delay can
be restarted to allow entry or exit when the system is armed. The
system toggles between the available options.
Options: Options: Options: Options:
No
Yes
Yes
R RR Restart Exit Time estart Exit Time estart Exit Time estart Exit Time Disable or enable Restart Exit Time Mode after the system has
been armed and the Exit Delay is counting down. If enabled, the
Exit Delay time can be restarted by selecting the “Restart” icon
and entering the User Code (if quick arming is disabled) or by
selecting the Restart icon (if quick arming is enabled). The system
toggles between the available options.
NOTE: NOTE: NOTE: NOTE: This option also enables automatic Exit Delay Reset, which
resets exit delay if the entry/exit door is re-opened and
closed before Exit Delay time expires after arming.
Options: Options: Options: Options:
No
Yes
Yes
Lyric Controller Programming Guide


- 21 -
Program System Settings (Continued)
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Auto Stay Arming Auto Stay Arming Auto Stay Arming Auto Stay Arming Disable or enable Auto Stay Arming Mode. The system toggles
between the available options. If enabled, when the control panel
has been armed “Armed Away” locally or via RF keypad, the
system will switch to the “Armed Stay” mode if the Exit Time has
expired and no exit has been made.
Options Options Options Options: :: :
No
Yes
Yes
Lack of Usage Notify Lack of Usage Notify Lack of Usage Notify Lack of Usage Notify Disable or enable Lack of Usage Notification feature. The system
scrolls between the available options. If enabled, notifies the
Central Station if an end user has not operated the security system
for a selected period of time by sending a System Inactivity report
(CID code 654).
Options: Options: Options: Options:
Disabled
1 Day
7 Days
27 Days
90 Days
180 Days
365 Days
Disabled
Power Power Power Power- -- -Up in Previous Up in Previous Up in Previous Up in Previous Disable or enable Power-Up in Previous Mode feature. The system
toggles between the available options. When the system powers
up armed, an alarm will occur 1 minute after arming if a zone is
faulted. Any bypassed zones will remain bypassed.
Options: Options: Options: Options:
No
Yes
Yes
Display Alarm Cancel Display Alarm Cancel Display Alarm Cancel Display Alarm Cancel Disable or enable display of Cancelled Alarm. The system toggles
between the available options.
Options: Options: Options: Options:
No
Yes
Yes
Display Exit Time Display Exit Time Display Exit Time Display Exit Time Disable or enable display of Exit Time. The system toggles
between the available options.
Options: Options: Options: Options:
No
Yes
Yes
(A) Cross Zone 1 (A) Cross Zone 1 (A) Cross Zone 1 (A) Cross Zone 1
(B) Cross Zone 1 (B) Cross Zone 1 (B) Cross Zone 1 (B) Cross Zone 1
(C) Cross Zone 1 (C) Cross Zone 1 (C) Cross Zone 1 (C) Cross Zone 1
(D) Cross Zone 1 (D) Cross Zone 1 (D) Cross Zone 1 (D) Cross Zone 1
Select the first zone that will be used for Cross Zoning for the
respective Cross Zone List [(A) – (D)]. The system displays the
available zones.

Disabled
(A) Cross Zone 2 (A) Cross Zone 2 (A) Cross Zone 2 (A) Cross Zone 2
(B) Cross Zone 2 (B) Cross Zone 2 (B) Cross Zone 2 (B) Cross Zone 2
(C) Cross Zone 2 (C) Cross Zone 2 (C) Cross Zone 2 (C) Cross Zone 2
(D) Cross Zone 2 (D) Cross Zone 2 (D) Cross Zone 2 (D) Cross Zone 2
Select the second zone that will be used for Cross Zoning for the
respective Cross Zone List [(A) – (D)]. The system displays the
available zones.

Disabled


Lyric Controller Programming Guide

- 22 -
Program Z-Wave
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
Programmed Programmed Programmed Programmed
Default Default Default Default
Z ZZ Z- -- -Wave Wave Wave Wave Enable or Disable Z-Wave operation. The system toggles between
the available options.
Options: Options: Options: Options:
Enabled
Disabled
Enabled
Temperatu Temperatu Temperatu Temperature Display re Display re Display re Display Select the correct temperature display. The system toggles
between the available options.
Options: Options: Options: Options:
Fahrenheit
Celsius
Fahrenheit


Lyric Controller Programming Guide


- 23 -
Program RF Keypad
The Lyric supports the installation of up to eight SiX™ Series RF keypads. The Keypad should be setup in
accordance with the documentation provided with the keypad prior to beginning the enrollment process.
Programming Field Programming Field Programming Field Programming Field Function and Action Function and Action Function and Action Function and Action
RF Keypad RF Keypad RF Keypad RF Keypad

Select a keypad zone from the available options, then select “Add New” to program
the next available zone.
850. Keypad
852. Keypad
854. Keypad
856. Keypad
851. Keypad
853. Keypad
855. Keypad
857. Keypad
Select a zone and then select “Edit” or “Add New” to program the next available zone.
The following options are displayed:
Serial Number
Zone Description 1 Zone Description 2

Supervision
Time


Serial Number Serial Number Serial Number Serial Number

When “Serial Number” has been selected “Enter Serial Number or Activate” is
displayed. Follow the applicable steps below to enroll the SiX™ Keypad.

(Refer to the documentation provided with the SiX™ keypad for additional information.)

1. Apply power to the RF keypad. Allow up to 10 minutes for pairing to complete. If
the keypad has been successfully paired with the control, the “Pairing Complete”
will be displayed. If the pairing is not successful, remove electrical power and
disconnect the battery.
2. Reinstall the battery, reconnect electrical power and repeat step 1.
3. A single transmission (open/close) of the device will be required. The device serial
number is displayed on the Lyric screen and the system beeps three times and
returns to the Zone Programming Screen.
4. The device’s battery level and signal strength are displayed on the Lyric control.
Zone Description1/ Zone Description1/ Zone Description1/ Zone Description1/
Zone Descript Zone Descript Zone Descript Zone Description 2 ion 2 ion 2 ion 2
Select “Zone Description 1 or Zone Description 2”. Using the displayed keypad enter
Zone Description 1 or Zone Description 2. The system announces the Zone Description.
Enter “Done”, when you are finished. The system returns to the Zone Programming
page.
NOTE: NOTE: NOTE: NOTE: When programming the Zone Description, after entering the first letter of the
description on the keypad, use the up ˄ and down ˅, arrows to scroll through the
available preprogrammed zone descriptions. For a list of the pre-programmed Zone
Descriptors, please visit:
http://www.security.honeywell.com/hsc/resources/MyWebTech
Supervision Time Supervision Time Supervision Time Supervision Time
(minutes) (minutes) (minutes) (minutes)
The Supervision Time is not programmable locally and is set to 60 minutes


Lyric Controller Programming Guide

- 24 -
Communications Diagnostics
For additional information regarding these fields, refer to the Lyric Controller Installation and Setup Guide p/n
800-18076 or higher.

Communication Diagnostics Communication Diagnostics Communication Diagnostics Communication Diagnostics
Use the down “˅” arrow to scroll to the next page of options. Use the “˄” arrow to return to the previous
page. Choose from the following options (depending upon the Communication Module that is installed):
Configure WiFi Configure WiFi Configure WiFi Configure WiFi – Provides access to the options for connecting the Lyric Controller panel to a WiFi Network
WiFi WiFi WiFi WiFi Information Information Information Information – Displays IP information if the WiFi Communication Path is enabled.
Cellular Cellular Cellular Cellular Information Information Information Information - Displays Cellular information if the Communication Path is enabled and the device is
registered.
Commu Commu Commu Communication Status nication Status nication Status nication Status – Displays status of the WiFi or Cellular Communications Paths and performs a self-
test of the advanced encryption standard (AES) algorithm.
Test Communication Test Communication Test Communication Test Communication – Performs network diagnostics and sends test alarms to the network.
Setup Communication Setup Communication Setup Communication Setup Communication – Resets factory defaults.
Communication ID Numbers Communication ID Numbers Communication ID Numbers Communication ID Numbers – Displays programmed information for the installed communication module.



Configure WiFi Configure WiFi Configure WiFi Configure WiFi
1. Select “Comm. Diagnostics” from the Installer Programming screen to connect the Lyric Controller panel
to a WiFi Network.
2. Select “Configure WiFi”. The System displays the following options:
Scan Access Points
Manual Configure AP
WPS
Automatic Video Recovery
Enroll using Scan Access Points Enroll using Scan Access Points Enroll using Scan Access Points Enroll using Scan Access Points
NOTE: NOTE: NOTE: NOTE: If the preferred access point is not available after scanning, manually select the network via the
“Manually Configure Access Points” procedure. .. .
1. Select “Scan”. The available networks and signal strength are displayed. Use the down “∨” arrow to scroll
to the next page of options. Use the “∧” arrow to return to the previous page.
Ready To Arm - Chime
lyric-022-V0
SSID = Video_Link, RSSI = -43dtm
SSID = Video_Link, RSSI = -44dbm
Scan Edit
SSID = Video_Link, RSSI = -51dbm
SSID = Video_Link, RSSI = -46dbm

Bars Bars Bars Bars Meaning Meaning Meaning Meaning RSSI range (dBM) RSSI range (dBM) RSSI range (dBM) RSSI range (dBM)
4 White No connection -255 (used internally)
1 Yellow, 3 White Weak -81 or higher
2 Yellow, 2 White Fair -71 to -80
3 Yellow, 1 White Good -51 to -70
4 Yellow Excellent -50 or less

3. Select the desired Network and then press the “Edit” button. The network information is displayed. If the
network is not password protected, select the “Join” button. A confirmation screen will be displayed.
4. Select the ‘Key” button and enter the password for the WiFi Network, then select the “Save” button.
5. Select the “Join” button. A confirmation screen is displayed.
6. Select “OK.
7. Select the “” button. The WiFi information will be displayed. Signal strength is indicated by a series of
colored bars along with the RSSI level (in dBM).
Manual Configure AP (Access Point) Manual Configure AP (Access Point) Manual Configure AP (Access Point) Manual Configure AP (Access Point)
1. Select “Manual Configure AP”.
2. Select “SSID Name” and then enter a name (not to exceed 31 characters) on the displayed keyboard.
3. Select “Security”. The system scrolls between the following options:
Open
wpa/wpa2
WPA2
WEP
4. Select “Network Type”. The system scrolls between “Infrastructure” and “Ad-Hoc”.
5. If a password is required, select “Key” and enter the password.
6. Select the “Join” option.
7. “Device successfully added to the Network” is displayed. Select “OK to confirm the selection.
8. Select the “” option. The WiFi information will be displayed. Signal strength will be indicated by a series
of colored bars along with the RSSI level (in dBM). (Refer to the table above.)
Lyric Controller Programming Guide


- 25 -
Communications Diagnostics (Continued)
WiFi Protected Set WiFi Protected Set WiFi Protected Set WiFi Protected Set up (WPS) up (WPS) up (WPS) up (WPS)
NOTE: NOTE: NOTE: NOTE: For WPS operation, press the WPS button on the access point first. Then press the WPS button
within 2 minutes
1. Select “WPS”, the system displays “Please Stand-by for WPS Operation…”.
2. If the operation is successful the system displays “Device has been successfully added to the network.”
Select “OK” to confirm the selection.
3. If the operation is unsuccessful the system displays “Failed Operation. Device not added to the
network.” Select “OK”.


WiFi WiFi WiFi WiFi Information Information Information Information – The following information is displayed:
Message Message Message Message Function Function Function Function
WiFi Link: Confirms physical link connection and speed (*** Mbps or Bad)
DHCP: Displays status of server (OK, Bad or Off)
NIC IP Address: Displays the communication device’s assigned IP address
Subnet Mask:
Displays the 32-bit address mask used to indicate the portion
(bits) of the IP address that is being used for the subnet address
Gateway IP Address: Displays the IP address assigned to the Gateway
DNS Server IP Address: Displays the IP address assigned to the DNS server

Cellular Information Cellular Information Cellular Information Cellular Information – The following information is displayed:
LYRIC LYRIC LYRIC LYRIC- -- -3G Communications Module 3G Communications Module 3G Communications Module 3G Communications Module
Message Message Message Message Function Function Function Function
Cell Phone Type: UMTS
Model: Displays model number (i.e.; PHS8-USA)
IMEI: Displays device’s 15-digit serial number
ICC ID: Display SIM Card’s 20-digit serial number
Registration Status:
Displays registration status
(Home, Registration Failed - not registered, Registration Denied,
Registration Unknown, Roam, Searching)
Access Technology: UMTS/HSDPA/HSPA (3G) OR GSM (2G)
Channel: Displays 4-digit RF channel no.
Ec/No Power to Noise Ratio (in -dBm)
RSCP Displays signal code power (in -dBm)

LYRIC LYRIC LYRIC LYRIC- -- -CDMA Communications Module CDMA Communications Module CDMA Communications Module CDMA Communications Module
Message Message Message Message Function Function Function Function
Cell Phone Type: CDMA
Model: Displays model number (i.e.; SL3010T)
ESN/MEID: Displays Device’s 32-bit serial number
Registration Status: Displays registration status
Access Technology: CDMA 1X
Channel: Displays 3-digit RF channel no.
Ec/lo Power to Noise Ratio (in -dB)
RSSI Displays RSSI signal strength (in -dBm)
If the Cellular is not registered the following may be displayed:
Configuring radio module – Please wait…
Radio module powered up but not initialized yet – Please wait…
Radio module operation suspended – cannot retrieve information
Radio module failure – SIM error
Radio module failure – Cannot initialize radio module
Radio module in airplane mode – reconfiguring and rebooting – please wait…
Radio module powering up – please wait…


Lyric Controller Programming Guide

- 26 -
Communications Diagnostics (Continued)

Communication Status Communication Status Communication Status Communication Status - The following information is displayed:
Message Message Message Message Function Function Function Function
Cellular and/or IP:
Displays Network Connectivity status (OK, Fault Reported!, Not Connected,
Not Registered! Or No Physical Link)
Encryption: Displays result of encryption test (Pass or Fail)
AlarmNet Registration: Displays Account Registration status (Registered or Not Registered)

Test Communication Test Communication Test Communication Test Communication - Performs network diagnostics and sends test alarms to AlarmNet 360. The following
tests are available depending on the type of communications module installed:
Test Ethernet Test Ethernet Test Ethernet Test Ethernet
This test is available if WiFi communication path is enabled. The network diagnostic process tests the integrity
of the links between the Lyric Controller and the various connection points of AlarmNet Control that are
known as “Redirectors”. If a physical link is detected and is ready, the following diagnostics are performed.
Testing Gateway… Testing Gateway… Testing Gateway… Testing Gateway… Traces the connection to the Gateway and displays the following:
Testing Gateway –
Successful!
A successful trace to Gateway
Testing Gateway – Failed! Failed to reach Gateway
Testing Redirector * Testing Redirector * Testing Redirector * Testing Redirector * Sequentially traces the connection to Redirector 1, 2 and 3 at AlarmNet
Control. The following will be displayed:
Redirector * – Service OK Service at AlarmNet Control on Redirector 1, 2 or 3 is functioning.
Redirector * – Failed Error occurred on Redirector 1, 2 or 3.
SUMMARY SUMMARY SUMMARY SUMMARY
Redirector 1 – Service OK
Redirector 2 – Service OK
Redirector 3 – Service OK
A summary of the tests is displayed after Redirector 3 is tested. The
example shows that the tests of all three connection points, or
Redirectors, were successful. If an error occurred at any point, the
summary will display “Failed” next to the faulty Redirector
If no physical link is detected, the test is aborted and one of the following is displayed:
No Physical Link No physical link is detected.
Link Not Ready There is a link but it is not ready (address not resolved).
* = Number of the director being tested is displayed
Send Any Send Any Send Any Send Any
If both WiFi and Cellular communication paths are enabled and the Lyric Controller is registered, a Test alarm
is sent over WiFi path. If that is not successful, it sends the alarm over Cellular path.
Send Send Send Send Cellular Cellular Cellular Cellular Message Message Message Message
If Cellular communication path is enabled and the Lyric Controller is registered, a Test alarm to AlarmNet 360
over the Cellular path.
Send Ethernet Message Send Ethernet Message Send Ethernet Message Send Ethernet Message
If WiFi communication path is enabled and the Lyric Controller is registered, a test alarm to AlarmNet 360
over the WiFi path
The following messages are displayed in response to the Send Any, Send Cellular Message and Send Ethernet
Message selections:
Sending Message Sending Message Sending Message Sending Message
Test Message is being sent
Waiting For ACK Waiting For ACK Waiting For ACK Waiting For ACK
ACK Received ACK Received ACK Received ACK Received The device is registered
Test Message Failed Test Message Failed Test Message Failed Test Message Failed – –– – Not Registered Not Registered Not Registered Not Registered The device is not registered


Setup Communication Setup Communication Setup Communication Setup Communication – Reset factory defaults. Select the following option:
Factory Defaults – The communication device is reset to factory default values.
Communication ID Numbers Communication ID Numbers Communication ID Numbers Communication ID Numbers – The following information is displayed, as applicable to communications path
that has been programmed:
Message Message Message Message Function Function Function Function
MAC: Displays Panel MAC address
MAC CRC: Displays Panel MAC CRC number
WiFi Module Displays physical address of the WiFi module
WiFi Ver Displays WiFi Module software version


Lyric Controller Programming Guide


- 27 -
Communications Diagnostics (Continued)
Registering the Registering the Registering the Registering the Lyric Lyric Lyric Lyric Controller Controller Controller Controller
Register the communications module through the AlarmNet 360 website.
The following information available should be available when programming the device:
• Primary City ID (two-digit number)
• Primary Central Station ID (two-digit hexadecimal number)
• Primary Subscriber ID (four-digit number)
• MAC ID and MAC CRC number (located on the outside of the box and on label inside module).
Data must be transferred to the module, and it must be registered.

Step Step Step Step Action Action Action Action
1. Go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx
2.
Log in and follow the on-screen prompts. If you are not signed up for this service, click on “Dealer
Signup” from the login screen to gain access to the Honeywell web-based programming.
Dealer Sign Dealer Sign Dealer Sign Dealer Sign- -- -Up D Up D Up D Up Direct Link irect Link irect Link irect Link: https://services.alarmnet.com/AlarmNetDirectP_Sign-Up.
3.
You will be instructed how to proceed upon completing the sign-up form. Only one sign-up per
dealer is required. Once an initial user is established, additional logins may be created by that user.
4
Once the module has registered, log out of the AlarmNet 360 website.


Checking Signal Strength Checking Signal Strength Checking Signal Strength Checking Signal Strength
When choosing a suitable mounting location, check the communications module’s signal strength to ensure
proper operation. For most installations, using the module’s internal antenna, mounting the Lyric controller as
high as practical, and avoiding large metal components provides adequate signal strength for proper operation.
To check signal strength, perform the following test.

Check Signal Strength Check Signal Strength Check Signal Strength Check Signal Strength
1. With the System in the Installer Programming mode,
select the “Comm. Diagnostics” button and then select
the “Cellular Information” button. The Cellular
Information will be displayed. The signal strength is
displayed (in dBm) as RSCP if the Lyric-3G module is
operating on the 3G Network or RSSI if the module
Lyric-3G module is operating on the 2G Network and
for the Lyric-CDMA module.
2. Compare the displayed RSCP or RSSI number to the
correct Signal Strength Guide at right to ensure
adequate signal strength. If necessary, relocate the
Controller to obtain better signal strength (select
“Cellular Information” again to refresh the reading).
3. If adequate signal strength cannot be achieved, External
Antenna Kit model Cell-ANTST should be used.
Lyric Lyric Lyric Lyric - -- -3G Signal Strength 3G Signal Strength 3G Signal Strength 3G Signal Strength

RSCP (3G) RSCP (3G) RSCP (3G) RSCP (3G)
Good ................... -20 to -90 dBm
OK ........................ -91 to -100 dBm
Marginal ............. -101 to -106 dBm
Bad ...................... -107 to -120 dBm

RSSI (2G) RSSI (2G) RSSI (2G) RSSI (2G)
Good ..................... -20 to -89 dBm
OK .......................... -90 to -98 dBm
Marginal ............... -99 to -104 dBm
Bad ........................ -105 to -120 dBm

Lyric Lyric Lyric Lyric - -- -CDMA Signal Strength CDMA Signal Strength CDMA Signal Strength CDMA Signal Strength

RSSI
Good ..................... -20 to -90 dBm
OK .......................... -91 to -100 dBm
Marginal ............... -101 to -106 dBm
Bad ........................ -107 to -120 dBm
Lyric Controller Programming Guide

- 28 -
Testing the System
After installation is completed, the security system should be carefully tested, as follows:
Step Step Step Step Action Action Action Action
1. With the system in the disarmed state, check that all zones are intact. If the “Home” button is not lit,
select the Zones icon to display the faulted zone(s). If necessary, restore faulted zone(s) so that the
“Home” button lights. Fault and restore every sensor individually to assure that it is being monitored
by the system.
Armed System Test Armed System Test Armed System Test Armed System Test
Alarm messages will be sent to the Central Station during the following steps 1 and 2. Notify the Notify the Notify the Notify the Central Central Central Central
Station Station Station Station in advance that tests will be in progress. in advance that tests will be in progress. in advance that tests will be in progress. in advance that tests will be in progress.
Step Step Step Step Action Action Action Action
1. Arm the system and fault one or more zones. Silence alarm sounder(s) and disarm the system by
selecting the Home key and entering the Security Code. Check entry/exit delay zones.
2. Check the keypad-initiated alarms that are in the system by selecting the Panic key. If the system
has been programmed for audible emergency, the keypad will emit a steady alarm sound, and
“ALARM” and zone number will be displayed. Silence the alarm by pressing the Home key and
entering the Security Code. If the system has been programmed for silent emergency, there will be
no audible alarms or displays, but a report will be sent to the Central Station.
3. Notify the Central Station when all tests are finished, and verify results with them.
4. To test the wireless part of the system and the RF receiver, perform the RF Sniffer Mode and Go-
No-Go Tests.

Additional Tests Additional Tests Additional Tests Additional Tests
The Test button provides access to several test modes. The system displays the selected Test Mode in the status
bar and beeps every 30-40 seconds.
RF Sniffer Test Mode RF Sniffer Test Mode RF Sniffer Test Mode RF Sniffer Test Mode
This mode is used to verify that all transmitters have been properly programmed. Sniffer Mode does not
automatically expire. You must manually exit Sniffer Mode to return to normal operation.
Go Go Go Go- -- -No No No No- -- -Go Go Go Go Test Test Test Test Mode Mode Mode Mode

Conducting this test with your hand wrapped around the transmitter will cause inaccurate results. Conducting this test with your hand wrapped around the transmitter will cause inaccurate results. Conducting this test with your hand wrapped around the transmitter will cause inaccurate results. Conducting this test with your hand wrapped around the transmitter will cause inaccurate results.
If a button is pressed on a transmitter that has been progra If a button is pressed on a transmitter that has been progra If a button is pressed on a transmitter that has been progra If a button is pressed on a transmitter that has been programmed to set ARM AWAY, ARM STAY, or mmed to set ARM AWAY, ARM STAY, or mmed to set ARM AWAY, ARM STAY, or mmed to set ARM AWAY, ARM STAY, or
DISARM, the system will exit the Go/No Go Test mode and the programmed action will occur. DISARM, the system will exit the Go/No Go Test mode and the programmed action will occur. DISARM, the system will exit the Go/No Go Test mode and the programmed action will occur. DISARM, the system will exit the Go/No Go Test mode and the programmed action will occur.
The Go-No-Go tests is used to verify adequate RF signal strength from the proposed transmitter location, and
allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This
mode is similar to the RF Sniffer Mode, except that the wireless receiver gain is reduced. This will enable you to
make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system
is in the normal operating mode.
Walk Walk Walk Walk Test Mode Test Mode Test Mode Test Mode
The Walk Test mode allows each protection point to be checked for proper operation.
Zone Discov Zone Discov Zone Discov Zone Discovery ery ery ery Mode Mode Mode Mode

Zone Discovery Zone Discovery Zone Discovery Zone Discovery M MM Mode requires Installer supervision when in use. The system is not fully operational for fire ode requires Installer supervision when in use. The system is not fully operational for fire ode requires Installer supervision when in use. The system is not fully operational for fire ode requires Installer supervision when in use. The system is not fully operational for fire
or life safety while Zone Discovery Mode is active. or life safety while Zone Discovery Mode is active. or life safety while Zone Discovery Mode is active. or life safety while Zone Discovery Mode is active.
Zone discovery mode can be used to remotely view all zones that have been programmed in the system for
operation. The zones must have a response type programmed and in the case of RF zones, must also have a
serial number programmed. All programmed zones (except for duress) will be displayed.

Programming Field Programming Field Programming Field Programming Field Fun Fun Fun Function and Action ction and Action ction and Action ction and Action
Walk Test Walk Test Walk Test Walk Test

1. Open each protected door and window and all sensors and listen for three beeps
from the control, followed by the zone’s Voice Descriptor, if it is programmed.
Identification of each faulted protection point should appear on the display. The
display will clear when the zone is restored.
2. When all protection points have been checked and restored, there should be no zone
identification numbers displayed on the touchscreen.

Lyric Controller Programming Guide


- 29 -
Testing the System (Continued)
Programming Field Programming Field Programming Field Programming Field Functi Functi Functi Function and Action on and Action on and Action on and Action
RF Sniffer Test RF Sniffer Test RF Sniffer Test RF Sniffer Test NOTE: NOTE: NOTE: NOTE: If the communicator is in the process of sending a report to the Central
Station, the system will not enter the RF Sniffer Mode. If so, wait a few minutes and
try again.
1. The system displays all programmed zone numbers and zone descriptors which have
a non-zero Zone Type. Fault each transmitter in turn, causing each one to send a
signal. As the system receives a signal from each of the transmitters, the zone number
of that transmitter disappears from the display. The transmitters may be checked
upon installation, or in an installed system.
2. When all transmitters have been checked, Exit RF Sniffer Test mode by depressing
the Home key and entering the Installer Code or a User Code. .. .
Go Go Go Go- -- -No No No No- -- -Go Test Go Test Go Test Go Test
Once the transmitters have been enrolled and placed in their desired locations, and the
approximate length of wire to be run to sensors is connected to the transmitter screw
terminals (if used), fault each transmitter.
1. The keypad beeps three times indicating signal reception, displays the appropriate
zone number and announced the zone description.
2. If the keypad does not beep, reorient or move the transmitter to another location.
Usually a few inches in either direction is all that is required.
3. If each transmitter produces the proper keypad response when faulted, they can be
permanently mounted according to their respective instructions.
3. Exit Go-No-Go Test mode by depressing the Home key and entering the Installer
Code or a User Code.
Diagnostics Diagnostics Diagnostics Diagnostics
Provides access to the Reboot Feature. Refer to the paragraph in this section for
additional information regarding this feature.
Zone Discovery Zone Discovery Zone Discovery Zone Discovery
1. The “Zone Discovery” button is highlighted indicating that the mode is active.
2. Exit Zone Discovery Mode by depressing the Home key and entering the Installer or a
User Code. If you do not exit Zone Discovery Mode manually, the system will
automatically exit Zone Discovery Mode in approximately 1-4 minutes dependent
upon the number of zones that are programmed. The system beeps once and returns
to the home screen.
Install Cell Install Cell Install Cell Install Cell
User feature that allow the Master User to install or replace a Communications Module.
Refer to the User Guide (p/n 800-18078) for additional information.
System Information System Information System Information System Information System Information is displayed. Select OK to return to the previous screen.
Install Backup Install Backup Install Backup Install Backup
Battery Battery Battery Battery
User feature that allow the Master User to replace the backup battery. Refer to the User
Guide (p/n 800-18078) for additional information.

N NN NOTES OTES OTES OTES: : : : (1) Button-type 5800 series devices do not automatically send check-in signals and must physically be
activated to clear the display.
(2) When one button of a button type, supervised or unsupervised RF transmitter is activated, all zones assigned to
other buttons on that transmitter are cleared. This also applies to transmitters that have multiple loops (zones).
(3) Any transmitter that is not “entered” will not turn off its zone number.
(4) For SIA installations, the following devices may be used as specified for panic (24-hour) alarm response:
• wireless keys which have two-button panic pairs available (e.g., 5804BDV), on which only the two-button
panic pairs may be programmed for any 24-hour alarm response
• wireless keypads keypads that have a two-second delay on the special function keys, or two-button panic
pairs
• built-in keypad panic key
(5) Go-No-Go Test will be automatically terminated after 3-1/2 to 4 hours if it is not manually terminated. This
ensures that fire and panic zones will not remain disabled. RF Sniffer Test Mode does not automatically expire
and must be exited manually to return to normal operation. During the final 5 minutes the system will emit
double beeps indicating that the end of Test mode is nearing.
Rebooting the System Rebooting the System Rebooting the System Rebooting the System
The Reboot function allows you to restart the system if required. To reboot the system perform the following:
Step Step Step Step Action Action Action Action
1. With the System in the Installer Programming mode, select the “Test” button and then select the
“Diagnostics” button.
2. The system advances to the next screen. Select the “Reboot” button.
3. A confirmation screen appears. Select “Yes”. The system will restart
N NN NOTE OTE OTE OTE: :: : After the reboot sequence is complete a “Walk Test” should be performed to verify that all transmitters are
operational in the system.
Lyric Controller Programming Guide

- 30 -
Zone Programming Worksheet
Fill in the required data on this worksheet, then follow the programming procedure. (The defaults for
Configuration 1 are shown)
See See See See E EE Explanation of xplanation of xplanation of xplanation of Zone Assignment Table H Zone Assignment Table H Zone Assignment Table H Zone Assignment Table Headings eadings eadings eadings
Zone Zone Zone Zone
No. No. No. No.
Loop Loop Loop Loop
No. No. No. No.
Device Device Device Device
Type Type Type Type
Response Type Response Type Response Type Response Type
Alarm Alarm Alarm Alarm
Report Report Report Report
Chime Chime Chime Chime Supervision Supervision Supervision Supervision
Arm Arm Arm Arm
Night Night Night Night
Transmitter Transmitter Transmitter Transmitter
Serial Number Serial Number Serial Number Serial Number
Zone Zone Zone Zone
Descriptor Descriptor Descriptor Descriptor
1 N/A New Not Used Yes Disabled End of Line N/A N/A (HW Zone)
2 N/A New Not Used Yes Disabled End of Line N/A N/A (HW Zone)
3 2 Door Entry Exit 1 Yes Standard Supervised N/A Front
4 2 Door Entry Exit 1 Yes Standard Supervised N/A Back
5 2 Window Perimeter Yes Standard Supervised N/A
6 1 Motion Sensor Interior with Delay Yes Disabled Supervised No
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43

Lyric Controller Programming Guide


- 31 -

Zone Programming Worksheet (Continued)
Zone Zone Zone Zone
No. No. No. No.
Loop Loop Loop Loop
No. No. No. No.
Device Device Device Device
Type Type Type Type
Response Type Response Type Response Type Response Type
Alarm Alarm Alarm Alarm
Report Report Report Report
Chime Chime Chime Chime Supervision Supervision Supervision Supervision
Arm Arm Arm Arm
Night Night Night Night
Transmitter Transmitter Transmitter Transmitter
Serial Number Serial Number Serial Number Serial Number
Zone Zone Zone Zone
Descriptor Descriptor Descriptor Descriptor
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
Lyric Controller Programming Guide

- 32 -

Zone Programming Worksheet (Continued)
Zone Zone Zone Zone
No. No. No. No.
Loop Loop Loop Loop
No. No. No. No.
Device Device Device Device
Type Type Type Type
Response Type Response Type Response Type Response Type
Alarm Alarm Alarm Alarm
Report Report Report Report
Chime Chime Chime Chime Supervision Supervision Supervision Supervision
Arm Arm Arm Arm
Night Night Night Night
Transmitter Transmitter Transmitter Transmitter
Serial Number Serial Number Serial Number Serial Number
Zone Zone Zone Zone
Descriptor Descriptor Descriptor Descriptor
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127 1 New Not Used No Standard Supervised N/A Main
128 1 New Not Used No Standard Supervised N/A Main
129 1 New Not Used No Standard Supervised N/A Main
130 1 New Not Used No Standard Supervised N/A Main
131 3 4 Button Arm Away Yes Disabled Button N/A
132 2 4 Button Disarm Yes Disabled Button N/A
133 4 4 Button Arm Stay Yes Disabled Button N/A
134 1 4 Button No Response No Disabled Button N/A
135 3 4 Button Arm Away Yes Disabled Button N/A
Lyric Controller Programming Guide


- 33 -

Zone Programming Worksheet (Continued)
Zone Zone Zone Zone
No. No. No. No.
Loop Loop Loop Loop
No. No. No. No.
Device Device Device Device
Type Type Type Type
Response Type Response Type Response Type Response Type
Alarm Alarm Alarm Alarm
Report Report Report Report
Chime Chime Chime Chime Supervision Supervision Supervision Supervision
Arm Arm Arm Arm
Night Night Night Night
Transmitter Transmitter Transmitter Transmitter
Serial Number Serial Number Serial Number Serial Number
Zone Zone Zone Zone
Descriptor Descriptor Descriptor Descriptor
136 2 4 Button Disarm Yes Disabled Button N/A
137 4 4 Button Arm Stay Yes Disabled Button N/A
138 1 4 Button No Response No Disabled Button N/A
139 1 New Not Used Yes Disabled Button N/A
140 1 New Not Used Yes Disabled Button N/A
141 1 New Not Used Yes Disabled Button N/A
142 1 New Not Used Yes Disabled Button N/A
143 1 New Not Used Yes Disabled Button N/A
144 1 New Not Used Yes Disabled Button N/A
145 1 New Not Used Yes Disabled Button N/A
146 1 New Not Used Yes Disabled Button N/A
147 1 New Not Used Yes Disabled Button N/A
148 1 New Not Used Yes Disabled Button N/A
149 1 New Not Used Yes Disabled Button N/A
150 1 New Not Used Yes Disabled Button N/A
151 1 New Not Used Yes Disabled Button N/A
152 1 New Not Used Yes Disabled Button N/A
153 1 New Not Used Yes Disabled Button N/A
154 1 New Not Used Yes Disabled Button N/A
155 1 New Not Used Yes Disabled Button N/A
156 1 New Not Used Yes Disabled Button N/A
157 1 New Not Used Yes Disabled Button N/A
158 1 New Not Used Yes Disabled Button N/A
159 1 New Not Used Yes Disabled Button N/A
160 1 New Not Used Yes Disabled Button N/A
161 1 New Not Used Yes Disabled Button N/A
162 1 New Not Used Yes Disabled Button N/A
280 N/A Temperature Monitor Yes Disabled High Temp N/A N/A
281 N/A Temperature Monitor Yes Disabled Low Temp N/A N/A
282 N/A Temperature Monitor Yes Disabled High Temp N/A N/A
283 N/A Temperature Monitor Yes Disabled Low Temp N/A N/A
284 N/A Temperature Monitor Yes Disabled High Temp N/A N/A
285 N/A Temperature Monitor Yes Disabled Low Temp N/A N/A
286 N/A Temperature Monitor Yes Disabled High Temp N/A N/A
287 N/A Temperature Monitor Yes Disabled Low Temp N/A N/A
288 N/A Temperature Monitor Yes Disabled High Temp N/A N/A
289 N/A Temperature Monitor Yes Disabled Low Temp N/A N/A
290 N/A Temperature Monitor Yes Disabled High Temp N/A N/A
291 N/A Temperature Monitor Yes Disabled Low Temp N/A
850 N/A Keypad N/A N/A N/A N/A N/A N/A
851 N/A Keypad N/A N/A N/A N/A N/A N/A
852 N/A Keypad N/A N/A N/A N/A N/A N/A
853 N/A Keypad N/A N/A N/A N/A N/A N/A
854 N/A Keypad N/A N/A N/A N/A N/A N/A
855 N/A Keypad N/A N/A N/A N/A N/A N/A
856 N/A Keypad N/A N/A N/A N/A N/A N/A
Lyric Controller Programming Guide

- 34 -

Zone Programming Worksheet (Continued)
Zone Zone Zone Zone
No. No. No. No.
Loop Loop Loop Loop
No. No. No. No.
Device Device Device Device
Type Type Type Type
Response Type Response Type Response Type Response Type
Alarm Alarm Alarm Alarm
Report Report Report Report
Chime Chime Chime Chime Supervision Supervision Supervision Supervision
Arm Arm Arm Arm
Night Night Night Night
Transmitter Transmitter Transmitter Transmitter
Serial Number Serial Number Serial Number Serial Number
Zone Zone Zone Zone
Descriptor Descriptor Descriptor Descriptor
857 N/A Keypad N/A N/A N/A N/A N/A N/A
995 N/A Fire Fire No Verification Yes Disabled Panic Trigger N/A N/A N/A
996 N/A Medical Not Used Yes Disabled Panic Trigger N/A N/A N/A
998 N/A Local Alarm Local Yes Disabled Panic Trigger N/A N/A N/A
999 N/A Police 24 Hour Silent Yes Disabled Panic Trigger N/A N/A N/A

Explanation of Zone Assignment Table Headings
Loop Number Loop Number Loop Number Loop Number - -- - Used with 5800 Devices. Record transmitter loop number. Entries are 1-4, depending on device
being used. Refer to the transmitter’s instructions or the figure provided for appropriate loop numbers.
Device Type Device Type Device Type Device Type- -- - Dependent upon the Zone Number being programmed.
Door Smoke Detector Flood Fire
Window Heat Sensor Environmental Garage Door
Motion Sensor Carbon Mono. Det. Medical Other
Glass Break Temperature Police Local Alarm

Response Type Response Type Response Type Response Type - -- - Dependent upon the Device Type that has been selected.
Entry Exit 1 24 Hour Audible Trouble Resident Monitor
Entry Exit 2 24 Hour Auxiliary Arm Stay Resident Response
Perimeter Fire No Verification Arm Away General Monitor
Interior Follower Interior with Delay Disarm General Response
Day/Night Monitor No Response Fire With Verification
24 Hour Silent Carbon Monoxide Silent Burglary Garage
Garage Monitor Local

Supervision Supervision Supervision Supervision - -- - Dependent upon the Zone Number being programmed.
Hardwire Zone Hardwire Zone Hardwire Zone Hardwire Zone
(Zone 1 & 2)
Wireless Zone Wireless Zone Wireless Zone Wireless Zone
(Zone 3-130)
Key Key Key Key
(Zone 131-162)
Temperature Temperature Temperature Temperature
(Zone 280-291)
End of Line (Resistor) Supervised Button High Temp
Normal-Closed Unsupervised Low Temp
Normal-Open
Lyric Controller Programming Guide


- 35 -

5800 Series Transmitter Loop Numbers
LOOP 1
5806/5806W3/5807
5808/5808LST/5808W3
ENROLL AS
SUPERVI SED
LOOP 1
LOOP 1
5809
ENROLL AS
SUPERVI SED
5818MNL
ENROLL AS
SUPERVI SED
LOOP 1
LOOP 1
LOOPS
1 - 3
LOOP 1
LOOP 1
5814
ENROLL AS
SUPERVI SED
l
y
r
i
c
-
0
5
3
-
V
1
5804E
ENROLL AS BUTTON
5822T
ENROLL AS
SUPERVI SED
5877
5816MN
ENROLL AS
SUPERVI SED
LOOP 1
(TERMINALS)
ALTERNATE
POSITION
FOR LOOP 2
LOOP 2
(REED)
LOOP 3
(TERMINALS)
5821
ENROLL AS
SUPERVI SED
5820L
ENROLL AS
SUPERVI SED
5819S ( WHS & BRS)
ENROLL AS
SUPERVI SED
LOOP 1
(INTERNAL
SHOCK
SENSOR
LOOP 2
(REED)
5819
ENROLL AS
SUPERVI SED
LOOP 2
(REED)
LOOP 3
(TERMINALS)
LOOP 1
(TERMINALS)
5800WAVE
PROGRAM
HOUSE I D
5800PI R- OD
ENROLL AS
SUPERVI SED
5800PI R/ 5800PI R- COM
ENROLL AS
SUPERVI SED
5811
ENROLL AS
SUPERVI SED
5800PI R- RES
ENROLL AS
SUPERVI SED
5800Mi cra
ENROLL AS
SUPERVI SED
5800CO
ENROLL AS
SUPERVI SED
5800SS1
ENROLL AS
SUPERVI SED
5800RL
SET HOUSE I D
LOOP 1
LOOP 1
(LOW
SENSITIVITY
LOOP 2
(HIGH
SENSITIVITY)
LOOP 3 (TEMP)
LOOP 4 (TAMPER)
LOOP 1
(HIGH
SECURITY)
LOOP 2
(STANDARD
SECURITY)
LOOP 3 (TILT MODE)
LOOP 4 (TAMPER)
LOOP 1
(LOW
SENSITIVITY
LOOP 2
(HIGH
SENSITIVITY)
LOOP 3 (TEMP)
LOOP 4 (TAMPER)
5834-2
ENROLL AS BUTTON
5834-4
ENROLL AS BUTTON
LOOP
1
LOOP
1 LOOP
1
LOOP
1
5878
ENROLL AS BUTTON
5870API
ENROLL AS
SUPERVI SED
5869
ENROLL AS
SUPERVI SED
5853
ENROLL AS
SUPERVI SED
LOOP 1
(LOW SENSITIVITY)
LOOP 2
(HIGH SENSITIVITY)
5898
ENROLL AS
SUPERVI SED
LOOP 4
LOOP 1
LOOP 2
LOOP 3
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
SERIAL #1
LOOP 2
SERIAL #1
LOOP 1
SERIAL #2
LOOP 2
3
AWAY
STAY
1
2
4
OFF
ON
SERIAL #1
LOOP 4
SERIAL #2
LOOP 1
SERIAL #2
LOOP 2
SERIAL #2
LOOP 3
SERIAL #1
LOOP 1
SERIAL #2
LOOP 4 LOOP 3
5816
ENROLL AS
SUPERVI SED
LOOP 1
(TERMINALS)
LOOP 2
(REED)
SERIAL #2
LOOP 1
SERIAL #1
LOOP 3
SERIAL #1
LOOP 2

NOTES NOTES NOTES NOTES: :: : (1) The 5806W3 smoke detector must be used in SIA applications.
(2) Button type devices send only fault and low battery signals; no restore or check-in signals.
Supervised RF devices send periodic check-in signals, faults, restore and low battery signals.
(3) If an external sounder is required, the 5800WAVE should be used.
(4) The 5804E and 5834-4 encrypted (High-Security) devices must be activated while the system is
in Go/No-Go Test Mode. Refer to the transmitter’s Installation Instruction for complete details. The
system will confirm the enrollment of the encrypted device by beeping two times
(5) The 5800PIR-OD, 5800RL, 5800SS1, 5804E, 5814, 5816TEMP, 5821, 5877, and 5878 wireless
transmitters have not been evaluated by ETL.
Lyric Controller Programming Guide

- 36 -

Programming Default Values
Program Function Program Function Program Function Program Function Configuration Configuration Configuration Configuration 1 11 1 Configurati Configurati Configurati Configuration on on on 2 22 2 Configuration Configuration Configuration Configuration 3 33 3 Configuration Configuration Configuration Configuration 4 44 4
Installer Code 4112 4112 4112 4112
System Type
RF Jam RF Jam Log RF Jam Log RF Jam Log RF Jam Log
RF House Code 0 0 0 0
Two Way Voice Disabled Disabled Disabled Disabled
Events - Log All Press to Log All Press to Log All Press to Log All Press to Log All
Events - Log Alarm Enabled Enabled Enabled Enabled
Events - Log Bypass Enabled Enabled Disabled Disabled
Events - Log Open/Close Enabled Enabled Disabled Disabled
Events - Log Trouble Enabled Enabled Enabled Enabled
Non Security Enabled Enabled Disabled Disabled
Remote Access Serial Disabled Disabled Disabled Disabled
Multi Mode Serial Disabled Disabled Disabled Disabled
Date Time
Calendar January 1, 2013 January 1, 2013 January 1, 2013 January 1, 2013
Enter Time 12:00 PM 12:00 PM 12:00 PM 12:00 PM
Time Zone Eastern (EST) Eastern (EST) Eastern (EST) Eastern (EST)
Day Light Savings time Yes Yes Yes Yes
Start Month March March March March
Start Week Second Second Second Second
End Month November November November November
End Week First First First First
Communicator
Communications Path WiFi WiFi WiFi WiFi
APL Disabled Disabled Disabled Disabled
City ID Blank Blank Blank Blank
CS ID Blank Blank Blank Blank
Sub ID Blank Blank Blank Blank
Supervision 24 Hours 24 Hours 24 Hours 24 Hours
Old Alarm Time 10 Minutes 10 Minutes 10 Minutes 10 Minutes
Remote Acc. Comm. Disabled Disabled Disabled Disabled
Multi Mode Comm. Disabled Disabled Disabled Disabled
WiFi Fault Time (min) 60 60 60 60
Use DHCP Yes Yes Yes Yes
GSM Fault Time 60 60 60 60
GSM Rollover No No No No
GSM 24 Hour Test No No No No
NIC IP Address 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255
Subnet Mask 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255
Gateway IP Address 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255
DNS Server IP Address 255.255.255.255 255.255.255.255 255.255.255.255 255.255.255.255
Zones See Zone Programming Default Configurations
Keys See Zone Programming Default Configurations
Reporter
Report Selection
Arm Away Enabled Enabled Enabled Enabled
Arm Stay Enabled Enabled Enabled Enabled
Disarm Enabled Enabled Enabled Enabled
Exit Error Enabled Enabled Enabled Enabled
Recent Closing Enabled Enabled Enabled Enabled
Event Log Full Enabled Enabled Enabled Enabled
Trouble Enabled Enabled Enabled Enabled
Trouble Restore Enabled Enabled Enabled Enabled
Alarm Restore Enabled Enabled Enabled Enabled
Alarm Cancel Enabled Enabled Enabled Enabled
Lyric Controller Programming Guide


- 37 -
Programming Default Values
Program Function Program Function Program Function Program Function Configuration Configuration Configuration Configuration 1 11 1 Configurati Configurati Configurati Configuration on on on 2 22 2 Configuration Configuration Configuration Configuration 3 33 3 Configuration Configuration Configuration Configuration 4 44 4
Test Enabled Enabled Enabled Enabled
Test Restore Enabled Enabled Enabled Enabled
Bypass Enabled Enabled Enabled Enabled
Bypass Restore Enabled Enabled Enabled Enabled
AC Loss Enabled Enabled Enabled Enabled
AC Loss Restore Enabled Enabled Enabled Enabled
Low Battery Enabled Enabled Enabled Enabled
Low Battery Restore Enabled Enabled Enabled Enabled
RF Low Battery Enabled Enabled Enabled Enabled
RF Low Battery Restore Enabled Enabled Enabled Enabled
Options
Number of Reports 2 Reports 2 Reports 2 Reports 2 Reports
Alarm Report Delay 30 Sec. 30 Sec. 30 Sec. 30 Sec.
First Report Offset 6 Hrs 12 Hrs 12 Hrs 12 Hrs
Report Frequency Never 30 Days Never Never
Sounder
Burglary Alarm Sound Yes Yes Yes Yes
Burglary Bell Timeout 4 Minutes 4 Minutes 4 Minutes 4 Minutes
Fire Bell Timeout 4 Minutes 4 Minutes 4 Minutes 4 Minutes
Arm Confirm RF Keyfob RF Keyfob RF Keyfob RF Keyfob
System Settings
Entry Delay 1 30 Seconds 30 Seconds 30 Seconds 30 Seconds
Entry Delay 2 30 Seconds 30 Seconds 30 Seconds 30 Seconds
Exit Delay 60 Seconds 60 Seconds 60 Seconds 60 Seconds
Backlight Timeout 30 Seconds 30 Seconds 30 Seconds 30 Seconds
Quick Arm Yes Yes Yes Yes
Quick Exit Yes Yes Yes Yes
Restart Exit Time Yes Yes Yes Yes
Force Bypass No No No No
Exit Warning Yes Yes Yes Yes
Auto Stay Arming Yes Yes Yes Yes
Lack Of Usage Notify Disabled Disabled Disabled Disabled
Power-Up In Previous Yes Yes Yes Yes
Display Alarm Cancel Yes Yes Yes Yes
Display Exit Time Yes Yes Yes Yes
(A) Cross Zone Delay None None None None
(A) Cross Zone 1 Disabled Disabled Disabled Disabled
(A) Cross Zone 2 Disabled Disabled Disabled Disabled
(B) Cross Zone Delay None None None None
(B) Cross Zone 1 Disabled Disabled Disabled Disabled
(B) Cross Zone 2 Disabled Disabled Disabled Disabled
(C) Cross Zone Delay None None None None
(C) Cross Zone 1 Disabled Disabled Disabled Disabled
(C) Cross Zone 2 Disabled Disabled Disabled Disabled
(D) Cross Zone Delay None None None None
(D) Cross Zone 1 Disabled Disabled Disabled Disabled
(D) Cross Zone 2 Disabled Disabled Disabled Disabled
Z-Wave
Z-Wave Enabled Enabled Enabled Enabled
Temperature Fahrenheit Fahrenheit Fahrenheit Fahrenheit
Language
Installer Language English English English English
User Language English English English English
RF Keypad See Zone Programming Default Configurations


- 38 -


– Notes –
Lyric Controller Programming Guide


- 39 -
lyric-SOC-V2
NOTE: THE HARD WIRE ZONES CANNOT BE USED AS FIRE ZONES.
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE
MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARDS ANSI/NFPA 70 NATONAL ELECTRIC CODE AND
NFPA 72 NATIONAL FIRE ALARM CODE, CHAPTER 2
(NATIONAL FIRE PROTECTION ASSOC., BATTERY MARCH
PARK, QUINCY, MA 02169). PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION, EVACUATION
PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
EXTERNAL CELLULAR RADIO ANTENNAS MAY ONLY BE INSTALLED OR REPLACED BY A PROFESSIONAL INSTALLER
REPLACE EVERY FOUR YEARS
THE LYRIC CONTROLLER IS COMPATIBLE WITH THE
FOLLOWING INTEGRAL RECHARGEABLE BATTERY PACKS:
P/N 300-03864-3PIN (STANDARD CAPACITY)
P/N 300-03866 (HIGH CAPACITY)
LYRIC ALSO COMPLIES WITH THE FOLLOWING:
CANADIAN STANDARDS ASSOCIATION (CSA)
C22.1, CANADIAN ELECTRICAL CODE, PART 1,
SAFETY STANDARD FOR ELECTRICAL
INSTALLATIONS AND CAN/ULC-S540
INSTALLATION OF RESIDENTIAL FIRE WARNING
SYSTEMS.
CIRCUIT
(ZONE)
CONTROL UNIT
DELAY-SEC
SMOKE DETECTOR
MODEL DELAY-SEC
THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM
VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING
DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
WARNING
5806W3 10 seconds 30 seconds 03 - 126
ZONE TYPE -
SUPERVISED
FIRE WITH
VERIFICATION
USB PORT
BATTERY
RECEPTACLE
TAMPER
TERMINAL
BOARD
2K OHM
EOLR
2K OHM
EOLR
HARD
WIRED
ZONE
POWER SUPPLY
(300-07332US)
HARD
WIRED
ZONE
H
W
Z
2
G
N
D
H
W
Z
1
+
9
V
D
C
G
N
D



Lyric Summary of Connections













































2 Corporate Center Drive, Suite 100 2 Corporate Center Drive, Suite 100 2 Corporate Center Drive, Suite 100 2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY P.O. Box 9040, Melville, NY P.O. Box 9040, Melville, NY P.O. Box 9040, Melville, NY 11747 11747 11747 11747
Copyright © 2015 Honeywell International Inc. Copyright © 2015 Honeywell International Inc. Copyright © 2015 Honeywell International Inc. Copyright © 2015 Honeywell International Inc.

www.honeywell.com/security www.honeywell.com/security www.honeywell.com/security www.honeywell.com/security


Ê800 Ê800 Ê800 Ê800- -- -18077aŠ 18077aŠ 18077aŠ 18077aŠ
800 800 800 800- -- -18077 4/15 Rev. A BETA 18077 4/15 Rev. A BETA 18077 4/15 Rev. A BETA 18077 4/15 Rev. A BETA


Uploaded