Honeywell VISTA 128BPT Connections Summary


Yes, you can use Compass to connect directly to a VISTA-128BPT.
The 128bpt?
Can compass be used to program by connecting directly to the panel?

Related Products

Honeywell Tuxedo Touch - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch
Talking Color Graphic Wired Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI
Talking Color Graphic Touchscreen Alarm Keypad
Honeywell VISTA-128BPT PCB - Commercial Alarm Control Panel
Honeywell VISTA-128BPT
Commercial Alarm Control Panel
List Price: $746.00
Our Price: $461.99

Related Categories


Document Transcript

11-3/4"
* RESIDENTIAL FIRE AND COMMERCIAL AND RESIDENTIAL BURGLARY, LOCAL AND POLICE STATION, MERCANTILE SAFE AND VAULT, CENTRAL STATION CONTROL UNIT WITH DACT ** RESIDENTIAL FIRE AND RESIDENTIAL BURGLARY CONTROL UNIT WITH DACT
FOR DRY, INDOOR USE ONLY
NOTES:

WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM.
* With Model COM-UL Commercial Enclosure. ** With Model RES-UL Residential Enclosure. 4. Cut blue jumper to disable supervision of alarm sounder output. Leave jumper intact to supervise output. (See Installation and Setup Guide for Programming and Wiring Instructions). 5. Canadian installation must comply with CAN/ULC-S302, CAN/ULC-S301 and CSA C22.1. 6. The use of Recognized limited-energy cable for connections to the initiating devices, indicating devices, and supplementary devices for those units having their energy limited to a maximum of 100 volt-amperes is required. (Refer to Installation and Setup Guide for information concerning Direct Wire Downloading and printer connections.)
MAKE CONNECTIONS FROM J9 USING NO. VT-SERCBL CABLE. CONNECT TO A PC, USING A STANDARD STRAIGHT THROUGH SERIAL CABLE WITH A 9-PIN CONNECTOR ON THE PANEL END AND THE APPROPRIATE CONNECTOR FOR THE PC ON THE OTHER END.

Blue Jumper (Note 4)

1. Zone 1 may be selected for EOLR supervised or normally closed (no EOLR) operation via cut jumper. (Cut red jumper for normally closed operation. Do not cut for Fire Usage). Zones 2-8 may be selected for either operation via program field *41.

J9 CONNECTOR NOT EVALUATED BY UL

TXD RXD RTS/DTR CTS/DSR GND J9

TB4

J7 Header 1. Not Used 2. Ground3. Out 1 4. Ground5. Out 2 6. Ground7. Out 3 8. Ground 9. Out 4

J8 Header 1. 2. 3. 4. 5. 6. 7. 8. 9.

BLK (-) RED (+) BLK (-)

Connect to 12VDC, 4AH or 12VDC, 7AH GEL CELL BATTERY CHARGING VOLTAGE 13.65VDC See Installation and Set up Guide for required capacity NOTE In UL Installations battery capacity for emergency stand by is at least 24 hours Replace every 3 years

BATTERY TABS

2. Zone 1 supports 2-wire smoke detectors. See Installation and Setup Guide for recommended type and maximum number of detectors supported. 3. Zone 7 may be used for remote keyswitch arming/disarming. See Installation and Setup Guide for wiring instructions.

Red Jumper (note 1)
ZONE 2 ZONE 3

In 2 Ground In 3 (1361X10 sync) Not Used Ground Out 5 (1361X10 data) Out 6 Ground Ground

Optional programming: Out 1: Smoke Detector Reset Out 2: Armed LED Out 4: Ready LED Ratings for Out 1: Active: 10VDC-13.8VDC through 4k OHMS Not Active: 100 OHMS to ground Ratings for out 2-4: Active: 10VDC-13.8VDC through 5k OHMS Not Active: 1k OHMS to ground

MAKE CONNECTIONS USING No. 4142TR CABLE

J8
1 2 3 4 5 6 7 8 9

J7
1 2 3 4 5 6 7 8 9

ZONE 4 ZONE 5

ZONE 6 ZONE 7

ZONE 8 ZONE 9

1

2

3

4

5

6

7

8

9

10

11
ZONE 1

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26
(B TIP RO WN

27

28

29

30

2-WIRE SMOKE DETECTOR LOOP (Also supports NO/NC Burg contacts)

Data out

Data in

+
N.C.

-

+
N.C.

+
N.C.

-

+
POLLING LOOP

) R (G ING RA Y) (G TIP RE EN ) RI (R NG ED )

+
N.C.

-

EARTH GROUND Connect to good earth ground to maintain immunity to transients. See Instructions for proper grounding.
DOC LOAD NO.: 5

NO CONNECTION

Connect to 24hr. 120VAC, 60 Hz Outlet

+
Red

Blk

Handset

Incoming Phone Line

Grn

Yel

7"

TRANSFORMER 16.5VAC, 40VA ADEMCO No.1361 (IN CANADA USE No. 1361CN) or 1361X10 IF X-10 DEVICES WILL BE USED

REMOTE KEYPAD 6160 (Addressable keypad) only

N.O.

N.O.

N.O.

N.O.

Telephone connections using Ademco No. 620 RJ31X direct connect cord.

WARNING: TO PREVENT RISK OF ELECTRICAL SHOCK, DISCONNECT TELCO JACK BEFORE SERVICING THIS PANEL.

See Installation Instructions for max # of keypads and for max wire run length. BELL

2k EOLR (note 1)

2k EOLR (note 1)

2k EOLR (note 1)

2k EOLR (note 1,3)

+

-

+

-

Fire Usage

+
N.C.

-

+
N.C.

+

-

+

4208U

NOTE: THE AC TRANSFORMER SHOULD NOT BE PLUGGED INTO A SWITCHED OUTLET. WHEN POWERING UP THE PANEL, PLUG THE TRANSFORMER IN BEFORE CONNECTING THE BATTERY.

+

-

SIREN

AUXILIARY POWER OUTPUT 9.6VDC - 13.8VDC, 750mA maximum Note: Include current drawn by keypads and polling loop devices when making auxiliary power calculations.

5193SD SMOKE

SMOKE

N.O.

N.O.
2k EOLR (note 1)

N.C.
N.O.

N.C.
4190SN

N.C.
Burg. Usage N.O.

2k EOLR (note 1)

N.C.

THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72 (NATIONAL FIRE PROTECTION ASSOC., BATTERY MARCH PARK. QUINCY, MA. 02169). PRINTED INFORMATION DESCRIBING PROPER INSTALLATION, OPERATION, TESTING, MAINTENANCE, EVACUATION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT.
COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION NO. AC398U-68192-AL-E RINGER EQUIVALENCE: 0.7B
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

ASSEMBLED IN MEXICO

ALARM SOUNDER OUTPUT 10VDC - 13.8VDC

2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747
Copyright © 2010 Honeywell International Inc. www.honeywell.com/security

Notes For UL HouseholdFire Installations: 1. Use 12VDC, 14AH battery 2. Maximum auxiliary current, 2k EOLR including polling loop 300mA (note 1,2) 3. Combined alarm and auxiliary ZONE INPUT SPECIFICATIONS power output and polling loop ZONE 8 ZONES 2-7 EOLR CONFIG. current must be limited to Maximum Loop I: 9mA Maximum Loop Current (shorted loop): 7.4mA 750mA for UL985 Household Maximum Loop V: 13.3VDC Maximum Loop Voltage (open loop): 13.3VDC Fire Installations. Loop Short: 0V - 1.5V - 300 ohms total resistance) Loop Short: 0 - 2.2V - (0 - 300 ohms) Loop Normal: 5 - 9V (0.9k - 3.4k) Loop Normal: 4.2 - 6.8V, 1.2k - 2.6k Loop Open: 10V - 13.3V, 3.8k Loop Open: 7.2V - 13.3V, 3k -

Zone resistance (Excluding EOLR): ZONE 1,8: 100 OHMS MAXIMUM ALL OTHER ZONES: 300 OHMS MAXIMUM Zone response time: ZONES 1: 350mSec-500mSec

2k EOLR (note 1,4)

USE LIMITED-ENERGY CABLE FOR ALL CONNECTIONS

Polling loop rating: 128mA max. See Installation and Setup Guide for maximum number of devices supported and maximum wire run length CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE APPROVAL OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER.

ZONE 9 Maximum Loop I: 4mA Maximum Loop V: 13.3V Loop Short: NA Loop Normal: 0 - 1.5V (0 ohms - 400 ohms) Loop Open: 5.3V, 2.2k -

SEE INSTALLATION INSTRUCTIONS 800-06903 REV. C. DATED 6/10

ALL CIRCUITS ARE POWER LIMITED EXCEPT THE OUPUT OF THE BACKUP BATTERIES.

VISTA-128BPT SUMMARY OF CONNECTIONS

Ê800-06906NŠ
800-06906 7/10 Rev. C