Honeywell VISTA 21iP Programming Guide - Dated 6/09
Related Products
Related Categories
Document Transcript
K14488PRV2 6/09 Rev. A
ADEMCO VISTA SERIES
VISTA-21iP / VISTA-21iPSIA
Security Systems
Programming Guide
K14488PRV2 6/09 Rev. A
TO ENTER PROGRAMMING MODE
(using an alpha keypad connected to the control)
:
A.
POWER UP, then press [
!
] and [#] at the same time, within 50 seconds of powering up (this method must be used if
!
98
was used to exit program mode).
OR
B.
Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0.
PROGRAMMING MODE COMMANDS
Task
Command/Explanation
Go to a Data Field
Press [
∗
∗
∗
∗
] + [Field Number], followed by the required entry.
Entering Data
When the desired field number appears, simply make the required entry. When the last entry
for a field is entered, the keypad beeps three times and automatically displays the next data
field in sequence. If the number of digits that you need to enter in a data field is less than the
maximum digits available (for example, the phone number fields *41, *42), enter the desired
data, then press [
∗
] to end the entry. The next data field number is displayed.
Review a Data Field
Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Deleting an Entry
Press [
∗
∗
∗
∗
] + [Field Number] + [
∗
∗
∗
∗
].
(Applies only to fields
∗
40 thru *46, *94, and pager fields)
Initialize Download ID
Press
∗
∗
∗
∗
96.
Initializes download ID and subscriber account number.
Reset Factory Defaults
Press
∗
∗
∗
∗
97.
Sets all data fields to original factory default values.
Zone Programming
Press
∗
∗
∗
∗
56.
Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
RF transmitters.
Function Key Programming
Press
∗
∗
∗
∗
57.
Unlabeled keypad keys (known as ABCD keys) for special functions
Zone Programming
(Expert Mode)
Press
∗
∗
∗
∗
58.
Same options as *56 mode, but with fewer prompts. Intended for those familiar
with this type of programming, otherwise *56 mode is recommended.
Output Device Mapping
Press
∗
∗
∗
∗
79.
Assign module addresses and map individual relays/powerline carrier devices
Output Programming
Press
∗
∗
∗
∗
80.
4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
Zone List Programming
Press
∗
∗
∗
∗
81.
Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Alpha Programming
Press
∗
∗
∗
∗
82.
Zone alpha descriptors
IP/GSM Programming
Press
∗
∗
∗
∗
29.
For programming the IP/GSM options.
Exit Program Mode with
installer code lockout
Press
∗
∗
∗
∗
98.
Exits programming mode and
prevents
re-entry by: Installer Code + 8 + 0 + 0.
To reenter programming mode, the system must be powered down, then powered up. Then
use method A above. See field *88 for other *98 Program mode lockout options.
Exit Program Mode
Press
∗
∗
∗
∗
99.
Exits programming mode and
allows
re-entry by: Installer Code + 8 + 0 + 0 or
method A above.
Scheduling Mode
Enter code + [#] + 64.
Create schedules to automate various system functions.
Site-Initiated Download
Installer code + [#] + 1
(perform while system is disarmed and in normal mode)
SPECIAL MESSAGES
OC
= OPEN CIRCUIT (no communication between Keypad and Control).
EE
or
ENTRY ERROR
= ERROR (invalid field number entered; re-enter valid field number).
After powering up,
AC, dI
(disabled) or
Busy Standby
and
NOT READY
will be displayed after approximately 4 seconds.
This will revert to a “
Ready
” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
delay by pressing [#] + [0].
If
E4
or
E8
appears, more zones than the expansion units can handle have been programmed. The display will clear after
you correct the programming.
AVS QUICK PROGRAMMING COMMANDS (for AAV sessions using the AVS system)
For controls with the following firmware revision levels, these commands automatically configure the control for AVS
operation. VISTA-15P = version 6.0 or higher; VISTA-20P = version 7.0 or higher
•
installer code + [#] + 03
: enable AVS operation
•
installer code + [#] + 04
: enable AVS operation and enable panel sounds on the AVST speaker
•
installer code + [#] + 05
: remove all programming options set by [#] + 03 quick command
•
installer code + [#] + 06
: remove all programming options set by [#] + 04 quick command
Refer to the AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS section for details on the specific options
that are set with each command, depending on the control used.
To select the AAV session communication path (phone line/communication device), see field
∗
55 Dynamic Signaling Priority.
To enable AAV operation, use
∗
91 Options field (option 4).
IMPORTANT:
The Real-Time Clock must be set before the end of the installation. See procedure in the Setting
the Real-Time Clock section of this manual.
–
2
–
PROGRAMMING FORM
Entries apply to the ADEMCO VISTA-21iP/VISTA-21iPSIA controls, except where noted, certain fields have special settings when us
ed with the
VISTA-21iPSIA (indicated by
V21iPSIA
with heavy borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines:
Notes in certain fields give instructions for programming the VISTA-21iP for False Alarm Reduction.
IMPORTANT! Make sure the Real-Time Clock is set before the end of the installation (see page 16 for procedure)
.
∗
∗
∗
∗
20
Installer Code
[4112] | | |
4 digits, 0–9
∗
∗
∗
∗
21
Quick Arm Enable
[0,0]
0 = no; 1 = yes
Part. 1 Part.2
∗
∗
∗
∗
22
RF Jam Option
[0]
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
∗
∗
∗
∗
23
Quick (Forced) Bypass
[0,0]
0 = no quick bypass
UL: must be “0”
Part. 1 Part. 2
1 = allow quick bypass (code + [6] + [#] )
∗
∗
∗
∗
24
RF House ID Code
[00,00,00]
|
|
|
00 = disable all wireless keypad usage Part. 1 Part. 2
Common
01–31 = using 5827, 5827BD or 5804BD keypad
∗
∗
∗
∗
26
Chime By Zone
[0]
0 = no; 1 = yes (list chime zones on zone list 3 using *81 Menu mode)
∗
∗
∗
∗
27
Powerline Carrier Device (X–10)
[0]
House Code
0 = A; 1 = B; 2 = C; 3 = D; 4 = E; 5 = F; 6 = G; 7 = H; 8 = I; 9 = J;
#10 = K; #11 = L; #12 = M; #13 = N; #14 = O; #15 = P
UL: not for fire or UL installations
∗
∗
∗
∗
28
Access Code For Phone Module
[00]
|
00 = disable;
(Partition 1 only)
1st digit: enter 1–9; 2nd digit: enter # + 11 for "
!
", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
∗
∗
∗
∗
29
Menu Mode for IP/GSM Enable
This is a Menu Mode command, not a data field, for programming IP/GSM
options. See respective section later in this document.
∗
∗
∗
∗
31
Single Alarm Sounding Per Zone
[0]
0 = unlimited sounding (bell output); 1 = one alarm sounding per zone
V21iPSIA:
If “0” selected, “alarm sounding per zone” will be the same
as the “number of reports in armed period” set in field *93 (1 if one
report, 2 if 2 reports, unlimited for zones in zone list 7).
∗
∗
∗
∗
32
Fire Alarm Sounder Timeout
[0]
0 = sound stops at timeout; 1 = no timeout UL: must be “1” for fire install.
∗
∗
∗
∗
33
Alarm Sounder (Bell) Timeout
[1]
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
∗
∗
∗
∗
34
Exit Delay
[60,60]
|
|
00 - 96 = 0 - 96 secs; 97 = 120 secs
Part. 1
Part. 2
SIA Guidelines: minimum exit delay is 45 seconds
V21iPSIA:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
UL: see inst. instr. for requirements. Common zones use part. 1 delay.
∗
∗
∗
∗
35
Entry Delay #1
[30,30]
|
|
Common zones use same delay as partition 1.
Part. 1
Part. 2
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA Guidelines: minimum entry delay is 30 seconds
V21iPSIA:
30-96 = 30 - 96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installations, must be set for a
maximum of 30 seconds; entry delay plus dial delay should not
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.
∗
∗
∗
∗
36
Entry Delay #2
[30,30]
|
|
See *35 Entry Delay 1 for entries.
Part. 1
Part. 2
∗
∗
∗
∗
37
Audible Exit Warning
[1,1]
0 = no; 1 = yes (SIA Guidelines: must be enabled)
Part. 1 Part. 2
V21iPSIA:
Feature always enabled; field does not exist.
∗
∗
∗
∗
38
Confirmation Of Arming Ding
[0,0]
0 = no; 1 = yes (wired keypads and RF)
Part. 1 Part. 2
2 = yes, RF only (except 5827/5827BD)
UL: must be “1” for UL Commercial Burglar Alarm inst.
∗
∗
∗
∗
39
Power Up In Previous State
[1]
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL: must be “1” SIA Guidelines: must be “1”
V21iPSIA:
Feature must be enabled (enter 1).
DIALER PROGRAMMING (
!
40 –
!
42)
Do not fill unused spaces. Enter 0–9; #+11 for '
!
'; #+12 for '#'; #+13 for a 2-
second pause. If fewer than the maximum digits entered, exit the field by
pressing [
"
]. The next data field number is displayed.
∗
∗
∗
∗
40
PABX Access Code or
| | | | |
Call Waiting Disable
Enter up to 6 digits. To clear entries,
press
!
40
!
. If call waiting is used, enter call waiting disable digits “
∗
(#+11) 70” plus “# + 13” (pause).
NOTES:
1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will
prevent successful communication to the central station.
V21iPSIA:
If call waiting is used, enter call waiting disable digits as
described above, and also set Call Waiting Disable option in field *91.
∗
∗
∗
∗
41
Primary Phone No.
| | | | | | | | | | | | | | | | | | |
∗
∗
∗
∗
42
Secondary Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press
!
41
!
or
!
42
!
respectively
.
NOTE:
For fields *43 thru *46:
Enter 0–9; #+11 for B; #+12 for C; #+13 for D;
#+14 for E; #+15 for F. Enter
[
!
]
as the fourth digit if a 3-digit account number
(for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit
account number for Nos. 0000-0999. Exit field by pressing
!
if only 3 digits are
used. E.g., For Acct.
B234
, enter: #+11 + 2 + 3 + 4
∗
∗
∗
∗
43
Partition 1 Primary Acct. No.
| | | / | | | | |
[FFFFFFFFFF] Enter 4 or 10 digits, as
chosen in *48 Report Format. See box above. To clear entries, press
*
43
*.
∗
∗
∗
∗
44
Part. 1 Secondary Acct. No.
(see field *43 for entries)
| | | / | | | | |
[FFFFFFFFFF] To clear, press
*
44
*
.
∗
∗
∗
∗
45
Partition 2 Primary Acct. No.
(see field *43 for entries)
| | | / | | | | |
[FFFFFFFFFF] To clear, press
*
45
*
.
∗
∗
∗
∗
46
Partition 2 Secondary Acct. No.
(see field *43 for entries)
| | | / | | | | |
[FFFFFFFFFF] To clear, press
*
46
*
.
∗
∗
∗
∗
47
Phone System Select
[1]
If Cent. Sta.
is not
on a WATS line: 0=Pulse Dial; 1=Tone Dial;
if Cent. Sta.
is
on
a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
∗
∗
∗
∗
48
Report Format
[77]
0 = 3+1, 4+1 ADEMCO L/S STANDARD
primary secondary
1 = 3+1, 4+1 RADIONICS STANDARD; 2 = 4+2 ADEMCO L/S STAND.
3 = 4+2 RADIONICS STANDARD
5 = 10-digit ADEMCO CONTACT ID® REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4-digit ADEMCO CONTACT ID® REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXP.; 9 = 3+1, 4+1 RADIONICS EXP.
–
3
–
∗
∗
∗
∗
49
Split/Dual Reporting
[0]
0 = Standard/backup reporting only (all to primary)
Primary Phone No.
2nd Phone No.
1 = Alarms, Restore, Cancel
Others
2 = All except Open/Close, Test
Open/Close, Test
3 = Alarms, Restore, Cancel
All
4 = All except Open/Close, Test
All
5 = All
All
∗
∗
∗
∗
50
Burglary Dialer Delay
[2,0]
Delay Time:
Delay Time
V21iPSIA
0 = no delay UL: must be “0”
Delay Disable
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
SIA Guidelines: delay must be minimum of 15 seconds
V21iPSIA:
Delay Time:
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
Delay Disable:
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6 (use zone list 6
to enter those zones that require dial delay to be disabled;
these zones ignore the setting in entry 1)
UL: Dial delay plus entry delay must not exceed one minute; use zone
list 6 to disable dial delay from appropriate zones, if necessary.
∗
∗
∗
∗
53
SESCOA/Radionics Select
[0]
0 = Radionics (0-9, B-F); enter “0” for all non-SESCOA formats
1 = SESCOA (0-9 only reporting)
∗
∗
∗
∗
54
Dynamic Signaling Delay
[0]
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent); 1 = 15 secs; 2 = 30 secs, etc.
NOTE: If
∗
55 is set to “0,” use min. 30 sec to avoid redundant IP
report.
However, this value may need to be adjusted (ex. 45 secs)
depending on the reporting environment.
For UL Burglar Alarm installations with Line Security, must be “0”
∗
∗
∗
∗
55
Dynamic Signaling Priority /
[0]
AAV Enable
0 = Primary Dialer first/ using AAV via phone line
1 = IP/GSM module first / not using AAV
For UL Commercial Burglary installations that use a DACT and
IP/GSM, this field must be “0”.
∗
∗
∗
∗
56
,
∗
∗
∗
∗
57
,
∗
∗
∗
∗
58
Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming,
Function Key Programming, and Expert Mode Zone Programming respectively.
See page 2 and respective sections later in this document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (
∗
∗
∗
∗
59 thru
∗
∗
∗
∗
68, *70 thru
∗
∗
∗
∗
76, and
∗
∗
∗
∗
89):
For 3+1 or 4+1 Standard Format:
Enter a code in the
first
box: 1–9, #+10 for
0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 (
not
#+10) in the
first
box will disable a report. A 0 (
not
#+10) in the
second
box will result in automatic advance to the next field.
For Expanded or 4+2 Format:
Enter codes in
both
boxes (1st and 2nd digits)
for 1–9, 0, or B–F, as described above.
A 0 (
not
#+10) in the
second
box will eliminate the expanded message for
that report. A 0 (
not
#+10) in
both
boxes will disable the report.
For Ademco Contact ID® Reporting:
Enter any digit (other than 0) in the
first
box, to enable zone to report (entries in the
second
boxes are ignored).
A 0 (
not
#+10) in the
first
box disables the report.
UL: see installation instructions for requirements
SYSTEM STATUS REPORT CODES
(
!
59–
!
68)
∗
∗
∗
∗
59
Exit Error Alarm Report Code
[0]
See above for entries.
V21iPSIA:
[1] Always enabled.
∗
∗
∗
∗
60
Trouble Report Code
[10] |
∗
∗
∗
∗
61
Bypass Report Code
[00] |
∗
∗
∗
∗
62
AC Loss Report Code
[10] |
∗
∗
∗
∗
63
Low Bat Report Code
[10] |
∗
∗
∗
∗
64
Test Report Code
[00] |
Use Scheduling mode to set periodic test reports, or use the following
key commands:
installer code +[#] + [0] + 0 = test report sent every 24 hours
installer code +[#] + [0] + 1 = test report sent once per week
installer code +[#] + [0] + 2 = test report sent every 28 day
Each mode sets schedule 32 to the stated repeat option; first test report
sent 12 hours after command.
∗
∗
∗
∗
65
Open Report Code
[0,0,0]
Part. 1
Part. 2 Common
∗
∗
∗
∗
66
Arm Away/Stay Rpt Code
[0,0,0,0,0,0]
Away
Stay
Away
Stay
Away
Stay
Part. 1
Part. 2
Common
∗
∗
∗
∗
67
RF Trans. Low Bat Report Code
[00] |
UL: must be enabled if wireless devices are used
∗
∗
∗
∗
68
Cancel Report Code
[00] |
V21iPSIA:
[10] Report enabled.
∗
∗
∗
∗
69
Recent Closing Report Code
[11] |
V21iPSIA:
Always enabled.
Field does not apply to other controls.
RESTORE REPORT CODES (
!
70 –
!
76)
∗
∗
∗
∗
70
Alarm Restore Rpt Code
[0]
∗
∗
∗
∗
71
Trouble Restore Rpt Code
[00] |
∗
∗
∗
∗
72
Bypass Restore Rpt Code
[00] |
∗
∗
∗
∗
73
AC Restore Rpt Code
[00] |
∗
∗
∗
∗
74
Low Bat Restore Rpt Code
[00] |
∗
∗
∗
∗
75
RF Trans. Lo Bat Rst Rpt Code
[00] |
UL: must be enabled if wireless devices are used
∗
∗
∗
∗
76
Test Restore Rpt Code
[00] |
OUTPUT AND SYSTEM SETUP (
!
77 –
!
93)
∗
∗
∗
∗
77
Daylight Saving Time
[3][11]
|
Start/End Month
0 = Disabled
1-12 = January-September (1 = Jan, 2 = Feb, etc)
#+10 = October; #+11 = November; #+12 = December
∗
∗
∗
∗
78
Daylight Saving Time
[2][1]
|
Start/End Weekend
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth;
5 = last; 6 = next to last; 7 = third to last
∗
∗
∗
∗
79
,
*80
,
*81
,
*82
Menu Modes
These are Menu Mode commands, not data fields, for Output Device Mapping,
Output Programming, Zone List Programming, and Alpha Programming
respectively. See page 2 and their respective sections in the Installation and
Setup Guide for procedures.
∗
∗
∗
∗
84
Auto Stay Arm
[3]
0 = no; 1 = partition 1 only; 2 = partition 2 only; 3 = both partitions
∗
∗
∗
∗
85
Cross Zone Timer
[0]
This option not for use in UL installations.
(assign cross zones on zone list 4, using *81 Menu mode)
0 = 15 seconds
6 = 2-1/2 min
#+12 = 8 min
1 = 30 seconds
7 = 3 min
#+13 = 10 min
2 = 45 seconds
8 = 4 min
#+14 = 12 min
3 = 60 seconds
9 = 5 min
#+15 = 15 min
4 = 90 seconds
#+10 = 6 min
5 = 2 minutes #+11 = 7 min
NOTE:
Cross zoning takes effect only after Exit Delay expires.
∗
∗
∗
∗
86
Cancel Verify Keypad Display
[1]
0 = no “alarm canceled” display
1 = display “Alarm Canceled” when system is disarmed after an alarm
has occurred. (To clear the “ALARM CANCELED” display, the
user must enter the security code + OFF again.)
–
4
–
∗
∗
∗
∗
87
Misc. Fault Delay Time
[0]
(used with Configurable Zone Types “digit 6”)
0 = 15 seconds
6 = 2-1/2 min
#+12 = 8 min
1 = 30 seconds
7 = 3 min
#+13 = 10 min
2 = 45 seconds
8 = 4 min
#+14 = 12 min
3 = 60 seconds
9 = 5 min
#+15 = 15 min
4 = 90 seconds
#+10 = 6 min
5 = 2 minutes
#+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm zones
when used in fire and/or UL burglar alarm installation
∗
∗
∗
∗
88
Program Mode Lockout Options
[0]
0 = standard *98 installer code lockout (reentry only by [
∗
] + [#] within
50 seconds after power up)
1 = lockout [
∗
] + [#] reentry after *98 exit (reenter via installer code or
downloader only)
2 = not used
3 = lockout local programming after *98 exit (reenter by downloader only)
∗
∗
∗
∗
89
Event Log Full Report Code
[00]
|
See box above field *59 for report code entries.
∗
∗
∗
∗
90
Event Log Enables
[3]
NOTE
:
System messages are logged when any non-zero entry is made.
0 = None
1 = Alarm/Alarm Restore
2 = Trouble/Trouble Restore
4 = Bypass/Bypass Restore
8 = Open/Close.
Example:
To select “Alarm/Alarm Restore”, and
“Open/Close”, enter 9 (1 + 8); To select all, enter #15.
∗
∗
∗
∗
91
Option Selection
[8, 0]
Options:
0 = None
Options
V21iPSIA
1 = Bell Supervision Processing
Call Wait Disable
4 = AAV UL: must use ADEMCO UVCM module
8 = Exit Delay Restart/Reset UL: must be disabled
#+12 = AAV and Exit Delay Restart/Reset
SIA Guidelines: Exit Delay should be enabled.
V21iPSIA:
Options: Same as listed above.
Call Waiting Disable:
0 = call waiting not used
1 = call waiting disable digits (*70) entered in field *40; (when
selected, the system dials the entry in field *40 only on
alternate dial attempts; this allows proper dialing in the event
call waiting service is later canceled by the user).
∗
∗
∗
∗
92
Phone Line Monitor Enable
[0,0]
UL: see Inst. Instructions for requirements
1
2
Entry 1:
: 0 = disabled, 1-15 = 1 min - 15 min
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14
= 14 min; #+15 = 15 min)
Entry 2
:
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble sound
2 = Same as “1”, plus programmed output device STARTS. If either
partition is armed, external sounder activates also.
NOTE:
If “2” selected, Output Device must either be programmed
to be STOPPED in field
!
80 or STOPPED by Code + # + 8 +
output number.
∗
∗
∗
∗
93
Reports In Armed Period
[1,0]
Per Zone
(Swinger Suppression)
Restrict
V21iPSIA
Restrict Report Pairs:
Report Pairs
Unlimited
0 = Unlimited Reports
Reports Enable
1 = 1 report pair
2 = 2 report pairs
SIA Guidelines: Must be set for option 1 or 2.
V21iPSIA:
Restrict Report Pairs:
1 = 1 report pair; 2 = 2 report pairs
Unlimited Reports Enable:
0 = restrict reports to the setting in entry 1
1 = unlimited reports for zones listed in zone list 7; (use zone list 7
to enter those zones that require unlimited reporting; these
zones ignore the setting in entry 1)
DOWNLOAD INFORMATION (
!
94,
!
95)
∗
∗
∗
∗
94
Download Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits, 0–9; #+11 for '
!
'; #+12 for '#'; #+13 for a 2-
second pause. Do not fill unused spaces. If fewer than 20 digits, exit
field by pressing
!
. To clear entries from field, press
!
94
!
.
UL: downloading may be performed only if a technician is at the site.
Up/downloading via the Internet has not been evaluated by UL.
∗
∗
∗
∗
95
Ring Count For Downloading
[15]
NOTE:
Do not enter “0” if using 4286 Phone Module.
0 = Disable Station Initiated Download;
1–14 = number of rings (1–9, # +10 =10, # +11 =11,
# +12 =12, # +13 =13, # +14 =14);
15 = answering machine defeat (# +15 =15).
∗
∗
∗
∗
96
,
∗
∗
∗
∗
97
Initialize/Reset Defaults
This is a command, not a data field. See page 2.
∗
∗
∗
∗
98
, *99
Exit Commands
This is a command, not a data field. See page 2.
PAGER OPTIONS (
!
160-
!
172)
∗
∗
∗
∗
160
Pager 1 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-sec pause
∗
∗
∗
∗
161
Pager 1 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-second pause.
∗
∗
∗
∗
162
Pager 1 Report Options
[0,0,0]
P1
P2 common
For each partition, select from the following options:
0 = no reports sent
1 = Opens/closes all users
4 = All alarms and troubles
5 = All alarms / troubles, and opens/closes for all users
12 = Alarms / troubles for zones entered in zone list 9
13 = Alarms / troubles for zones entered in zone list 9, and
opens/closes for all users
∗
∗
∗
∗
163
Pager 2 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = 'Q'; #+12 = '#'; #+13 = 2-sec pause
∗
∗
∗
∗
164
Pager 2 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-second pause.
∗
∗
∗
∗
165
Pager 2 Report Options
[0,0,0]
P1
P2 common
See field *162 for reporting options. Select for each partition (use zone
list 10 if using options 12 or 13).
∗
∗
∗
∗
166
Pager 3 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-sec pause
∗
∗
∗
∗
167
Pager 3 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-second pause.
∗
∗
∗
∗
168
Pager 3 Report Options
[0,0,0]
P1
P2 common
See field *162 for reporting options. Select for each partition (use zone
list 11 if using options 12 or 13).
∗
∗
∗
∗
169
Pager 4 Phone No.
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-sec pause
–
5
–
∗
∗
∗
∗
170
Pager 4 Characters
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '
!
'; #+12 = '#'; #+13 = 2-second pause.
∗
∗
∗
∗
171
Pager 4 Report Options
[0,0,0]
P1
P2 common
See field *162 for reporting options. Select for each partition (use zone
list 12 if using options 12 or 13).
∗
∗
∗
∗
172
Pager Delay Option For Alarms
[3]
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes
This delay is for ALL pagers in the system.
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
∗
∗
∗
∗
174
Clean Me Reporting Options
[0]
(for ESL smoke detectors)
0 = disable; 1 = Clean Me signal reports;
NOTE:
If Clean Me is enabled, you must enter “3” in field
!
56
programming for zone 1 response time.
∗
∗
∗
∗
177
Device Duration 1, 2
[0] [0]
(used in *80 Menu mode-Device Actions 5/6)
1
2
0 = 15 seconds
6 = 2-1/2 min
#+11 = 7 min
1 = 30 seconds
7 = 3 min
#+12 = 8 min
2 = 45 seconds
8 = 4 min
#+13 = 10 min
3 = 60 seconds
9 = 5 min
#+14 = 12 min
4 = 90 seconds
#+10 = 6 min
#+15 = 15 min
5 = 2 minutes
∗
∗
∗
∗
181
50/60 Hertz AC Operation
[0]
0 = 60 Hz; 1 = 50 Hz
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
(see Configurable Zone Type Worksheet on page 7)
∗
∗
∗
∗
182
Configurable Zone Type 90
1
2
3
4
5
6
7
8
9
10
Enter the appropriate value for each entry, 1-10, based on the charts
provided on the next page. Each entry is the sum of the values of its
selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
∗
∗
∗
∗
183
Zone Type 90 Report Codes
IMPORTANT:
Use existing Contact ID® codes, if appropriate, or
define unique codes in CID code range 750-789. See important note
in installation instructions.
90 ALARM ID: XXX
TROUBLE ID: XXX
Enter the desired 3-digit Contact ID® report codes for alarms and
troubles occurring on zones assigned to this zone type. Enter the
codes sequentially (all 6 digits). When entering digits, [#] moves
cursor back, [
∗
] moves forward.
NOTE:
Zone alarm report codes (prompt in
∗
56 Menu mode) and
trouble report code (
∗
60) and relevant restore codes (
∗
70,
∗
71) must
be enabled in order for the configurable zone type codes to be
reported.
Press [
∗
] when done to continue.
∗
∗
∗
∗
184
Configurable Zone Type 91
1
2
3
4
5
6
7
8
9
10
See
∗
182 for entries. Press [
∗
] when done to continue.
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
∗
∗
∗
∗
185
Zone Type 91 Report Codes
IMPORTANT:
Use existing Contact ID® codes, if appropriate, or
define unique codes in CID code range 750-789. See important note
in installation instructions.
91 ALARM ID: XXX
TROUBLE ID: XXX
See *183 for entries. Press [
∗
] when done to continue.
KEYPAD OPTIONS *189-*196
KEYPAD NOTES
:
1. Options for keypad 1, address 16 are set by the factory and cannot be
changed.
2. Each keypad must be assigned a unique address. Keypads programmed
with the same address will give unpredictable results.
3. If using Remote Services (IP/GSM feature), one of the keypad addresses
may be used for limited Remote Services features, though a physical
keypad is not installed. See
∗
29 Menu Mode section for enabling Remote
Services.
∗
∗
∗
∗
189
Touch Screen Device
(
AUI)
Enable
[1] [1]
AUI 1 AUI 2 AUI 3 AUI 4
System supports up to four touch screen style keypads (e.g.,
Symphony Advanced User Interface, and 6270 Touch Screen Keypad).
AUI Compatibility Note:
To ensure proper AUI device operation, use
AUI devices with the following rev levels: 6270 series use version
1.0.9 or higher; 8132/8142 (Symphony) series use version 1.1.175 or
higher.
Touch Screen (AUI) device 1: Must set AUI device address to 1
Touch Screen (AUI) device 2: Must set AUI device address to 2
Touch Screen (AUI) device 3: Must set AUI device address to 5
Touch Screen (AUI) device 4: Must set AUI device address to 6
Enter each touch screen keypad’s home partition
0 = disable; 1 = partition 1; 2 = partition 2; 3 = partition 3 (common)
NOTES:
1. Use of touch screen style keypads does not affect the
number of standard keypads supported.
2. If using Remote Services (IP/GSM feature), one of the touch
screen (AUI) addresses may be used for enhanced Remote
Services feature set, though a physical touch screen is not
installed. See
∗
29 Menu Mode section for enabling Remote
Services
.
∗
∗
∗
∗
190
Keypad 2 Device Address 17
[0] [0]
Partition:
Enter partition where:
Part. Sound
0 = keypad disabled; 1-3 = part. no. (3 = com)
Sound:
0 = no suppression
1 = suppress arm/disarm and E/E beeps
2 = Suppress chime beeps only
3 = suppress arm/disarm, E/E, and chime beeps
∗
∗
∗
∗
191
Keypad 3 Device Address 18
[0] [0]
See field
∗
190 for entries.
Partition
Sound
∗
∗
∗
∗
192
Keypad 4 Device Address 19
[0] [0]
See field
∗
190 for entries.
Partition
Sound
∗
∗
∗
∗
193
Keypad 5 Device Address 20
[0] [0]
See field
∗
190 for entries.
Partition
Sound
∗
∗
∗
∗
194
Keypad 6 Device Address 21
[0] [0]
See field
∗
190 for entries.
Partition
Sound
∗
∗
∗
∗
195
Keypad 7 Device Address 22
[0] [0]
See field
∗
190 for entries.
Partition
Sound
∗
∗
∗
∗
196
Keypad 8 Device Address 23
[0] [0]
See field
∗
190 for entries.
Partition
Sound
∗
∗
∗
∗
197
Exit Time Display Interval
[0]
0 = no display; 1-5 = seconds between display refresh
NOTE:
If enabled and using only 2-digit fixed-word keypads (e.g.,
6150RF), do not set exit delay time greater than 96 seconds. See Inst.
Instr. for explanation.
TOUCH SCREEN DEVICE NOTE:
If using more than one touch
screen device (e.g., 6270, Symphony) with the system, leave field
*197 Exit Time Display Interval set to the default value “0.” The 6270
automatically displays remaining exit time in one-second increments.
∗
∗
∗
∗
198
Display Partition Number
[0]
(for Alpha Display Keypads)
0 = no; 1 = yes (partition no. appears on Alpha Display)
∗
∗
∗
∗
199
ECP Fail Display
[0]
0 = 3-digit display (“1” + device address)
1 = 2-digit fixed-display as “91”
–
6
–
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-
*185. Configurable zone types 92 and 93 can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for
zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields
*183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
(See note 5 for RF zones)
ENTRY 2
(See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
Auto
Restore
Vent Zone
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = yes
0 = no
8 = yes
Entry 1 = EOL + Open
Entry 2 = Short + auto restore + vent zone
ENTRY 3
(See note 5 for RF zones)
ENTRY 4
(See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
Byp. when
disarmed
Byp. when
armed
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = yes
0 = no
8 = yes
Entry 3 = EOL + Open
Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 5
(See note 5 for RF zones)
ENTRY 6
(See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
Dial Delay
(see field *50)
Fault Delay
(see field *87)
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = use delay
0 = no
8 = use delay
see note 1
Entry 5 = EOL + Open
Entry 6 = Short + dial delay + fault delay
ENTRY 7
ENTRY 8
Display Faults
Power Reset/
Verification
Use Entry
Delay 1/2
Use Exit
Delay
Respond as
Interior Type
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
armed
(show
alarms, trbles,
faults when
disarmed)
3 = never show
any alarms,
trbles, faults
0 = no
4 = power reset
after fault
(by code + OFF)
12 = verification
(see zone
type 16)
0 = no
1 = delay 1
2 = delay 2
0 = no
4 = use exit
delay
0 = no
8 = yes
see note 2
Entry 7 = fault display + power
reset/verification
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
ENTRY 9
ENTRY 10
Alarm Sounds
Use Bell
Timeout
Respond as
Fire Zone
Trouble
Sounds
Chime when
Chime Mode On
0 = none
1 = steady
keypad
2 = steady bell
and keypad
3 = pulsing bell
and keypad
0 = no
4 = yes
see fields *32,
*33
0 = no
8 = yes
see zone type
09; see note 4
0 = none
1 = periodic
beep
2 = trouble
beeps
0 = no
4 = yes
Entry 9 = alarm sounds + bell timeout + fire zone
Entry 10 = trouble sounds + chime
Entries for Fields *182 and *184
Entry Zone Type 90
Zone Type 91
(field *182)
(field *184)
1
2
3
4
5
6
7
8
9
10
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
OPEN
SHORTED
INTACT
EOL
ZONE-003-V0
Zone Conditions Represented
in Entries 1-6
NOTES:
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
“respond as interior zone type” (entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
not display unless the [
∗
] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The “open” option in entries 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for off-
normal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled
pair or on a double-balanced zone
causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones,
both
zones
of the doubled pair must be assigned
the same response to a short.
–
7
–
*56 Zone Programming Menu Mode
(press *56 while in Program mode)
The Zone Programming Worksheet is on page 18.
For each of the following prompts, make the desired entry, followed by the [
∗
] key to accept the entry.
Refer to the Installation and Setup Guide for detailed explanations for each prompt.
SET TO CONFIRM?
0 = no; 1 = yes (See XMIT TO CONFIRM prompt later in this section.)
We
recommend that you confirm the programming of every transmitter.
ENTER ZN NUM.
01-64, 91, 92, 95, 96, 99
To quit,
enter 00 to quit (returns to data field mode).
SUMMARY SCREEN:
System displays a summary of the entered zone’s current programming.
Press [
∗
] to continue.
ZONE TYPE
00 = Not used
07 = 24-Hr Audible
20 = Arm–STAY*
01 = Entry/exit #1
08 = 24-Hr Aux
21 = Arm–AWAY*
02 = Entry/exit #2
09 = Fire
22 = Disarm*
03 = Perimeter
10 = Interior w/Delay
23 = No Alarm Resp
04 = Interior Follower
12 = Monitor Zone
24 = Silent Burglary
05 = Trouble Day/Alarm Night 14 = Carbon Monoxide 77 = Keyswitch
06 = 24-Hr Silent
16 = Fire w/Verify
81 = AAV Monitor
Zone
*5800 button-type transmitters only
90-91 = Configurable
PARTITION
1, 2, or 3-common
REPORT CODE
1-9, 10 for 0, 11 for B, 12 for C, 13 for D, 14 for E, 15 for F
For Contact ID®, enter any non-zero entry as the first digit to enable
reporting for this zone.
To disable the report code for this zone, enter 00.
HARDWIRE TYPE
Appears only for zones 02-08. Zone 1 is automatically set for EOL
operation. Enter the desired hardwire type:
0 = EOL; 1 = NC; 2 = NO; 3 = zone doubling (ZD); 4 = double-balanced
(DB)
RESPONSE TIME
For hardwired zones 01-08. Enter the desired response time for this zone:
0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 secs (see field
∗
174).
NOTE: If zone doubling is being used, the response time selected for zones
02-08 automatically applies to each zone’s associated doubled zone.
INPUT TYPE
Skipped for zones 2-8, and for zones 10-16 if zone-doubling enabled. Enter
the input type: 2 = AW (Aux wired zone); 3 = RF (supervised RF);
4 = UR (unsupervised RF); 5 = BR (unsupervised button type)
NOTE: To change the input type of a previously programmed wireless
device to a wired zone, you must first delete the transmitter’s serial number.
INPUT S/N
Enroll the transmitter’s serial number and loop number as follows:
1. a. Transmit two open/close sequences (for button-type transmitters,
press and release the button twice, waiting about 4 seconds before
pressing the button the second time).
OR
b. Manually enter the 7-digit serial number printed on the label of the
transmitter. Press the [
∗
] key to move to the “L” position, then enter
the loop number.
Use the [A] (Advance) and [B] (Back) keys to move the cursor forward
and back within the screen. Pressing the [C] (Copy) key will insert the
previously enrolled serial number, if desired (used when programming
a transmitter with several input loops).
To delete an existing serial number, enter 0 in the loop number
field. The serial number will change to 0's. If 0 was entered in error,
simply re-enter the loop number or press [#], and the serial number
will return to the display.
2. Press [
∗
] to continue. The system now checks for a duplicate serial/loop
number.
If no duplicate is found, the display shows the serial number and loop
number.
3. Press [
∗
] to continue to confirmation screen.
(prompts continued in next column)
XMIT TO confirm
Appears if you answered “Yes” at the “Set to Confirm” prompt.
Activate the loop input or button that corresponds to this zone.
Press [
∗
] to continue.
If the serial/loop number transmitted does not match the serial number
entered, a display showing the entered and the received serial/loop numbers
appears.
If so, activate the loop input or button on the transmitter once again. If a
match is not obtained, press the [#] key twice and then enter (or transmit)
the correct serial number.
Press [
∗
] to continue
If the serial number transmitted matches the serial number entered,
the keypad will beep 3 times and a summary display will appear,
showing that zone's programming. An “s” indicates that a
transmitter’s serial number has been enrolled.
Press [
∗
] to accept the zone information and continue.
PROGRAM ALPHA?
Press 1 if you want to program descriptors for the zone now, and refer to the
*82 Descriptor Programming section for procedure. To program descriptors
later, enter 0 (no).
Press [
∗
] to return to the ENTER ZN NUM prompt.
∗
∗
∗
∗
58 Expert Zone Programming Mode
(press
∗
∗
∗
∗
58 while in Data Programming mode)
SET TO CONFIRM?
Select whether you want confirmation of wireless device enrollment. (See
“XMIT TO CONFIRM” prompt later in this section.)
We recommend that
you confirm the programming of every transmitter.
SUMMARY SCREEN
Zn ZT P RC HW: RT
01 09 1 10 EL 1
(Typical for Zone 1, initial summary screen)
Zn
ZT P RC IN: L
10 00 1 10 RF: –
(Typical for entered zone number; zone 10 in this example)
System displays summary of zone 1’s current programming.
Enter the zone number being programmed, then press [
∗
]. A summary
screen for that zone is displayed, along with any current programming
values, and the cursor moves to the Zone Type location. The cursor then
automatically moves to the next locations after each entry is made.
Special Function Keys:
•
[A] (Advance) and [B] (Back) keys on the keypad move the cursor
within the screen.
•
[C] (Copy) key will insert the previous zone’s attributes, if desired.
•
[D] key starts the
Wireless Key Programming Templates
menu
(see Wireless Key Programming Templates section that follows this
section).
Sequentially enter Zone Type (ZT), Partition (P), and Report Code (RC; 0-9
only; use
∗
56 menu mode for hex codes), then Hardwire Type (HW) and
Response Time (RT) for basic wired zones 1-8
or
Input Device Type (IN) for
zones 9 and higher (Loop Number [L] is programmed at the INPUT S/N
prompt).
See *56 Zone Programming Menu Mode section described earlier for entry
values.
Press [
∗
] to save the programming and continue. If needed, press the [#]
key to back up without saving.
•
For wireless devices (input types RF, UR, BR), continue to the INPUT
S/N (serial number/loop number) and XMIT TO CONFIRM prompts
described earlier in the
*56 Zone Programming Menu Mode
section.
When done, the display returns to the initial summary screen prompt to
let you program the next zone.
•
For wired devices, the display returns to the initial summary screen
prompt to let you program the next zone.
To Quit,
enter 00 at the zone number location and press [
∗
].
–
8
–
Wireless Key Programming Templates
(press the [D] key from *58 Menu mode Summary Screen)
This procedure programs the wireless keys,
but a key is not active for arming/disarming until it is assigned to a user number
(see
System Operation
section, Assigning Attributes Command in the Installation Instructions).
TEMPLATE ?
Enter desired template number 1–6 (see chart below), then press [
∗
] to
continue.
To exit the Template screen, press [#]. The system returns to the *58 Menu
mode Summary Screen.
TEMPLATE SUMMARY
L 01 02 03 04
T 23 22 21 23
The selected template is displayed.
The top line represents loop numbers, the bottom line represents each
loop’s zone type.
Press [
∗
] to accept template and continue.
PARTITION
Enter the partition (1, 2) in which the key is to be active.
Press [
∗
] to continue.
ENTER START ZONE
The system displays the lowest zone number of the highest available
consecutive 4-zone group.
To start at a different zone number, enter the zone desired, and press [
∗
]. If
the system has four consecutive zones beginning with that zone, the zone
number is displayed. If not, the system will again display a suggested zone
that can be used.
If the required number of consecutive zones is not available at all, the
system will display “00”.
Press [
∗
] to accept.
Continue to the INPUT S/N (serial number/loop number) and XMIT TO
CONFIRM prompts described earlier in the
*56 Menu Mode
section.
IMPORTANT:
When confirmed, the key is not active for arming/disarming
until it is assigned to a user number (using the assigning attributes command,
attribute “4”). See System Operation section in Installation Instructions.
When done, the keypad beeps three times and the display returns to the
ENTER START ZONE prompt to let you enter the starting zone for the next
wireless key.
Wireless Key Predefined Default Templates
For 5804
Loop
Function
Zone Type
For 5804BD
Loop
Function
Zone Type
TEMPLATE 1
1
No Response
23
TEMPLATE 4
1
No Response
23
2
Disarm
22
2
No Response
23
3
Arm Away
21
3
Arm Away
21
4
No Response
23
4
Disarm
22
TEMPLATE 2
1
No Response
23
TEMPLATE 5
1
No Response
23
2
Disarm
22
2
Arm Stay
20
3
Arm Away
21
3
Arm Away
21
4
Arm Stay
20
4
Disarm
22
TEMPLATE 3
1
24-hour audible
7
TEMPLATE 6
1
24-hour audible
7
2
Disarm
22
2
Arm Stay
20
3
Arm Away
21
3
Arm Away
21
4
Arm Stay
20
4
Disarm
22
*57 Function Key Programming
(press
∗
∗
∗
∗
57 while in Data Programming mode)
The Function Key Worksheet is on page 19.
PRESS KEY TO PGM
Press the desired function key to be programmed, A-D, then press [
∗
] to
continue.
When done, press 0 to exit this mode and return to data field mode.
NOTE:
A key programmed as a function key is no longer available to be
used as an end-user macro key or panic key.
PARTITION
Enter the partition (1-3) in which this function key will be active.
KEY "A" FUNC
Enter the desired function for this key:
00 =
For the Function key selected, the functions are pre-defined as
follows (default):
If A selected = Zone 95 (emergency key, same as [1] [
∗
] pair)
If B selected = Zone 99 (emergency key, same as [
∗
] [#] pair)
If C selected = Zone 96 (emergency key, same as [3] [#] pair)
If D selected = Single-button paging (continued in next column)
KEY "A" FUNC
(continued)
01 = Single-button paging (sends a 999-9999 message to pager)
02 =
Display time
03 =
Arm AWAY (reports as User 00 if closing reports are enabled)
04 =
Arm STAY (reports as User 00 if closing reports are enabled)
05 =
Arm NIGHT-STAY (reports as User 00 if closing reports enabled)
06 =
Step Arming (arms STAY, then NIGHT-STAY if enabled, then
AWAY)
07 =
Output Device Command (for device programmed as system
operation type 66 in *80 Menu Mode)
08 =
Communication Test (sends Contact ID code 601)
09 -12= Macro Keys 1-4 respectively (defined by [#] [6] [6] command)
Press [
∗
] to continue; returns to key number prompt with the next function key letter
displayed.
–
9
–
∗
∗
∗
∗
79 Output Device Menu Mode
(press
∗
∗
∗
∗
79 while in Programming mode)
The *79 Device Mapping Worksheet is on page 19.
ENTER OUTPUT NO.
01-18 = relays/X-10
[
∗
] to continue
OUT NORM LOW
(appears only for triggers 17/18)
0 = no (standard default); sets the output level normally high
1 = yes; sets the output normally low (can be used for resetting 4-wire
smoke detectors)
[
∗
] to return to Output Number prompt
OUTPUT TYPE
0 = delete; 1 = relay (skip to “B” prompt); 2 = Powerline Carrier device (skip
to “A” prompt)
[
∗
] to continue.
A: UNIT No.
(if X-10 was selected as Output Type)
Enter the unit code (01-16, set at the device).
[
∗
] to return to the Output Number prompt continue
B: MODULE ADDR
(if relay was selected as Output Type)
Enter the predefined address for this module (07-15; see Table of Device
Addresses on page 2).
Make sure the module’s DIP switches are set to the selected address.
NOTE:
If using Multi-Mode (IP/GSM feature), select one of the 4204
addresses, though a physical 4204 module is not installed. If using 2-4204
multi-mode option, the second 4204 address is automatically one number
higher than the first one selected. Make sure these addresses are not used
by physical 4204 modules that may be installed. See
∗
29 Menu Mode
section for enabling Multi-Mode.
[
∗
] to continue
REL POSITION
(actual relay number on module)
For 4204 modules, relay numbers are 1-4. For 4229 modules, relay
numbers are 1-2.
NOTE:
If using multi-mode, program the relays to trigger on those system
events to be sent to the user’s email address. See
∗
29 Menu Mode section
for enabling Multi-Mode.
[
∗
] to return to the Output Number prompt for programming the next device
∗
∗
∗
∗
80 Output Function Menu Mode
(press
∗
∗
∗
∗
80 while in Programming mode)
The Output Definition Worksheet is on page 20.
OUTPUT FUNCT. #
Enter the output function number to be defined: 01-48
[
∗
] to continue; 00 = exit
SUMMARY SCREEN
01 A E P Trig
?00 0 0 – ZL=00
This screen displays a summary of the current output programming
A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79
Menu mode to map the device.
[
∗
] to continue
ACTIVATED BY
0 = delete (deletes the output function and any previous programming); a
confirmation prompt appears.
To delete this output definition, press 1. If you do not want to delete this
output, press 0.
1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone
number (go to “C” prompt)
Press [
∗
] to continue
“
A
” (if zone list was selected)
ZN LIST
Enter the desired zone list number (01-08). At the ENTER EVENT prompt,
enter the zone list event that will activate this output (0 = restore; 1 = alarm;
2 = fault; 3= trouble)
Press [
∗
] to continue and skip to the “Output Action” prompt.
“
B
” (if zone type was selected)
ENTER ZN TYPE
Enter the desired zone type. See list below *80 Worksheet for zone types.
At the PARTITION prompt, enter the partition in which this zone type will
occur (0 = any partition; 1 = partition 1; 2 = partition 2; 3 = partition 3).
Press [
∗
] to continue and skip to the “Output Action” prompt.
“
C
”
(if zone number was selected)
ENTER ZN NO.
Enter the desired zone number, then press [
∗
] to continue. At the ENTER
EVENT prompt, enter the zone event that will activate this output (0 =
restore; 1 = alarm/fault/trouble).
Press [
∗
] to continue to the OUTPUT ACTION prompt
∗
∗
∗
∗
80 Menu Mode
(continued)
OUTPUT ACTION
0 = off; 1 = Close for 2 seconds; 2 = Close and Stay Closed; 3 = Continuous
Pulse 1 sec on and 1 sec off
4 = Change Device State; 5 = Duration 1 (see data field *177); 6 = Duration
2 (see data field *177)
Press [
∗
] to continue.
ENTER OUTPUT NO.
Enter the device output number (programmed in *79 Menu Mode) you want
associated with this output.
01-16 = output no.; 17-18 = on-board triggers
Press [
∗
] to continue.
SUMMARY SCREEN
A summary screen appears showing the programmed settings.
Press [
∗
] to return to OUTPUT FUNCTION NUMBER prompt.
*81 Zone List Menu Mode
(press *81 while in Programming mode)
The Zone List Worksheet is on page 19.
ZONE LIST NO.
Enter the zone list number (01-12) to program (or 00 to exit this mode).
Press [
∗
] to continue.
ENTER ZN NUM.
Enter each zone number (01-64) to add to the zone list, followed by pressing
[
∗
] (example, 01
∗
, 02
∗
, 03
∗
).
Press 00 to continue.
IMPORTANT:
Do not include fire zones in zone lists that are used to STOP
device actions.
DEL ZN LIST?
0 = don’t delete list; current zone list remains saved
1 = delete this zone list; All zones in the zone list will be deleted.
[
∗
] to continue
DELETE ZONE?
0 = don’t delete zones; save the entire zone list and return to the Zone List
No. prompt
1 = go to next prompt to delete zones
[
∗
] to continue
ZN TO DELETE?
Enter each zone (01-64) to be deleted from the list, following each with [
∗
].
00 when done to return to the Zone List No. prompt.
*82 Alpha Descriptor Programming
PRE-DEFINED DESCRIPTORS
PROGRAM ALPHA
0 = no (quit Alpha mode)
1 = yes
Press [
∗
] or [#] to continue.
CUSTOM WORDS
0 = no (continue to descriptor programming)
1 = yes (go to custom word programming)
Press 0 to program standard alpha descriptors. The system will then display
the descriptor for zone 1.
To program custom words, press 1 (custom words are described later).
Press [
∗
] to continue.
∗
∗
∗
∗
ZN 01
Descriptor screen for zone 1 appears. To program a descriptor (up to 3
words) for a zone, do the following:
1. Press [
∗
] plus the desired zone number (existing descriptor, if any, is
displayed), then press [
∗
] plus the zone number again (flashing cursor
appears).
2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary List on
page 11 for the first word.
b. Press [6] to accept the word and move the cursor for the next word.
3. Repeat steps 2a and 2b for the second and third words (if used).
4. When all words have been entered, press [8] to save the descriptor for
that zone. The flashing cursor disappears.
5. Repeat steps 1-4 to assign a descriptor for the next zone.
6. When all descriptors have been entered, press [
∗
] + 0 + 0 (or simply
press [#]) after the last descriptor has been saved to return to the
PROGRAM ALPHA? prompt.
Enter 0 (no) at the prompt to exit this mode and return to Data Field mode.
–
10
–
*82 Alpha Descriptor Programming
(continued)
ADDING CUSTOM WORDS (up to 10 words)
For custom words, the keys have the following functions:
[4] moves cursor one space to the left.
[6] moves cursor one space to the right.
[8] saves the new word in the system's memory.
1. Select Custom Word mode (enter 1) when the prompt “CUSTOM WORD ?”
is displayed.
2. Enter the number (01–10, or 11, 12, 13 for partition descriptors– see
below) of the custom word or word string to be created, corresponding to
index numbers 245 - 254 respectively. A cursor appears at the beginning
of the second line.
NOTE:
Custom words 8, 9, and 10 are “reminder words” that can be
programmed to display using Scheduling Mode.
3. Refer to the Character (ASCII) Chart on the next page.
Press [#], followed by the two-digit entry for the first letter you would like
to display (e.g., # 6 5 for “A”). The cursor moves to the right, in position
for the next character.
To delete a character,
simply enter the SPACE character (#32) at the
unwanted character’s location.
4. Repeat Step 3 to create the desired word(s). Each word can be a
maximum of 10 characters (except custom message/partition descriptor
word numbers 11, 12, and 13, which can be a maximum of 16 characters).
5. When the word is complete, press the [8] key to save the custom word(s)
in the vocabulary list and return to the “CUSTOM WORD ?” display.
6. Repeat Steps 1–5 for other custom words to be entered. To change a
custom word, just overwrite it. When all words have been programmed,
enter 0 at the “CUSTOM WORD ?” prompt to return to the Program
Alpha prompt. Enter 0 again to exit Descriptor mode.
To Assign Partition/Custom Message Descriptors,
use Adding Custom
Words procedure, but: use the following word numbers in step 2:
11 = partition 1; 12 = partition 2; 13 = common lobby
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000
(Word Space)
–
A
–
•
001
AIR
•
002
ALARM
∗
∗
∗
∗
004
ALLEY
005
AMBUSH
•
006
AREA
•
007
APARTMENT
•
009
ATTIC
∗
∗
∗
∗
010
AUDIO
–
B
–
•
012
BABY
∗
∗
∗
∗
•
013
BACK
∗
∗
∗
∗
•
014
BAR
•
016
BASEMENT
∗
∗
∗
∗
•
017
BATHROOM
∗
∗
∗
∗
•
018
BED
•
019
BEDROOM
∗
∗
∗
∗
020
BELL
•
021
BLOWER
•
022
BOILER
023
BOTTOM
025
BREAK
•
026
BUILDING
–
C
–
028
CABINET
•
029
CALL
030
CAMERA
031
CAR
033
CASH
034
CCTV
035
CEILING
036
CELLAR
•
037
CENTRAL
038
CIRCUIT
•
040
CLOSED
∗
∗
∗
∗
•
046
COMPUTER
047
CONTACT
–
D
–
•
048
DAUGHTERS
049
DELAYED
•
050
DEN
∗
∗
∗
∗
051
DESK
•
052
DETECTOR
∗
∗
∗
∗
•
053
DINING
∗
∗
∗
∗
054
DISCRIMINATOR
055
DISPLAY
•
057
DOOR
∗
∗
∗
∗
•
059
DOWN
•
060
DOWNSTAIRS
061
DRAWER
•
062
DRIVEWAY
•
064
DUCT
–
E
–
•
065
EAST
066
ELECTRIC
067
EMERGENCY
∗
∗
∗
∗
068
ENTRY
•
069
EQUIPMENT
•
071
EXIT
∗
∗
∗
∗
072
EXTERIOR
–
F
–
•
073
FACTORY
075
FAMILY
•
076
FATHERS
•
077
FENCE
•
079
FIRE
∗
∗
∗
∗
•
080
FLOOR
∗
∗
∗
∗
081
FLOW
082
FOIL
•
083
FOYER
084
FREEZER
•
085
FRONT
∗
∗
∗
∗
–
G
–
•
089
GARAGE
∗
∗
∗
∗
•
090
GAS
091
GATE
•
092
GLASS
093
GUEST
094
GUN
–
H –
•
095
HALL
∗
∗
∗
∗
•
096
HEAT
098
HOLDUP
099
HOUSE
∗
100
INFRARED
•
101
INSIDE
∗
∗
∗
∗
102
INTERIOR
103
INTRUSION
–
J
–
104
JEWELRY
–
K
–
•
105
KITCHEN
∗
∗
∗
∗
–
L
–
•
106
LAUNDRY
∗
∗
∗
∗
•
107
LEFT
108
LEVEL
•
109
LIBRARY
∗
∗
∗
∗
•
110
LIGHT
111
LINE
•
113
LIVING
∗
∗
∗
∗
•
114
LOADING
115
LOCK
116
LOOP
117
LOW
•
118
LOWER
–
M
–
•
119
MACHINE
121
MAIDS
122
MAIN
∗
∗
∗
∗
•
123
MASTER
∗
∗
∗
∗
•
125
MEDICAL
∗
∗
∗
∗
126
MEDICINE
128
MONEY
129
MONITOR
•
130
MOTHERS
•
131
MOTION
∗
∗
∗
∗
132
MOTOR
–
N
–
•
134
NORTH
135
NURSERY
–
O
–
•
136
OFFICE
∗
∗
∗
∗
•
138
OPEN
∗
∗
∗
∗
139
OPENING
•
140
OUTSIDE
142
OVERHEAD
–
P
–
143
PAINTING
•
144
PANIC
∗
∗
∗
∗
145
PASSIVE
•
146
PATIO
∗
∗
∗
∗
147
PERIMETER
•
148
PHONE
150
POINT
151
POLICE
∗
∗
∗
∗
152
POOL
∗
∗
∗
∗
•
153
POWER
–
R
–
155
RADIO
•
156
REAR
157
RECREATION
159
REFRIGERATION
160
RF
•
161
RIGHT
•
162
ROOM
∗
∗
∗
∗
163
ROOF
–
S
–
164
SAFE
165
SCREEN
166
SENSOR
•
167
SERVICE
•
168
SHED
∗
∗
∗
∗
169
SHOCK
•
170
SHOP
∗
∗
∗
∗
171
SHORT
•
173
SIDE
∗
∗
∗
∗
174
SKYLIGHT
175
SLIDING
∗
∗
∗
∗
•
176
SMOKE
∗
∗
∗
∗
•
178
SONS
•
179
SOUTH
180
SPRINKLER
•
182
STATION
184
STORE
•
185
STORAGE
∗
∗
∗
∗
186
STORY
190
SUPERVISED
∗
∗
∗
∗
191
SUPERVISION
192
SWIMMING
193
SWITCH
–
T
–
194
TAMPER
196
TELCO
197
TELEPHONE
•
199
TEMPERATURE
200
THERMOSTAT
•
201
TOOL
202
TRANSMITTER
–
U
–
•
205
UP
•
206
UPPER
•
207
UPSTAIRS
∗
∗
∗
∗
•
208
UTILITY
∗
∗
∗
∗
–
V
–
209
VALVE
210
VAULT
212
VOLTAGE
–
W
–
213
WALL
214
WAREHOUSE
•
216
WEST
•
217
WINDOW
∗
∗
∗
∗
•
219
WING
220
WIRELESS
–
X
–
222
XMITTER
–
Y
–
223
YARD
–
Z
–
224
ZONE (No.)
•
225
ZONE
∗
∗
∗
∗
•
226
0
•
227
1
•
228
1ST
∗
∗
∗
∗
•
229
2
•
230
2ND
∗
∗
∗
∗
•
231
3
•
232
3RD
∗
∗
∗
∗
•
233
4
•
234
4TH
•
235
5
•
236
5TH
•
237
6
•
238
6TH
•
239
7
•
240
7TH
•
241
8
•
242
8TH
•
243
9
•
244
9TH
245
Custom Word #1
246
Custom Word #2
247
Custom Word #3
248
Custom Word #4
249
Custom Word #5
250
Custom Word #6
251
Custom Word #7
252
Custom Word #8
253
Custom Word #9
254
Custom Word #10
Note:
Bulleted (
•
) words in
boldface type
are those that are also available for use by the 4286 Phone Module. If using a Phone module,
and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
Italicized
words followed by an asterisk indicate those words supported by the 6160V/6150V Voice Keypads
CHARACTER (ASCII) CHART (For Adding Custom Words)
32 (space)
33
!
34
"
35
#
36
$
37
%
38
&
39
'
40
(
41
)
42
*
43
+
44
,
45
–
46
.
47
/
48
0
49
1
50
2
51
3
52
4
53
5
54
6
55
7
56
8
57
9
58
:
59
;
60
<
61
=
62
>
63
?
64
@
65
A
66
B
67
C
68
D
69
E
70
F
71
G
72
H
73
I
74
J
75
K
76
L
77
M
78
N
79
O
80
P
81
Q
82
R
83
S
84
T
85
U
86
V
87
W
88
X
89
Y
90
Z
–
11
–
∗
∗
∗
∗
29 Internal Device Menu Mode
(for Programming IP and GSM Module Options)
This mode is for programming the Internet connection (IP) and GSM Module
configuration, collectively referred to as the Internal Device.
NOTE:
The Internal Device is automatically set to address 3 and cannot be
changed.
IMPORTANT:
The use of the IP connection or the VISTA-GSM module
requires an AlarmNet–I account. Please obtain the account information
from the central station prior to programming this module.
The following section describes the programming of the internal device
options using an alpha keypad. Alternatively, these options can be
programmed via the AlarmNet Direct website. After programming is
complete,
the control must be registered
with AlarmNet (via the control’s
RJ45 Internet connection). Refer to the Registration with AlarmNet section
for procedures.
Using an Alpha Keypad as a 7720P Programming Tool
When programming IP/GSM features (with
∗
29 menu mode), the alpha
keypad mimics the functions of the 7720P Programming Tool. See figure at
right and table below for 7720P key functions. Each key has two possible
functions: a normal function and a SHIFT function.
Normal functions: The numeric values labeled directly on the keys and
the left-hand functions shown in diagram on the ABC keys. To perform a
normal key function, simply press the desired key.
SHIFT functions: Those functions shown in diagram above the numerical
keys and the right-hand functions shown on the ABC keys. To perform a
SHIFT key function, press SHIFT key (D key), then press the desired
function key (shift function is indicated by the lit READY LED).
7720P Emulation Template for Alpha Keypads
1
OFF
4
MAX
7
INSTANT
READY
2
AWAY
5
TEST
8
CODE
0
3
STAY
6
BYPASS
9
CHIME
(B)
A
D
S
ENTER
SHIFT
N / Y
/
BS/ESC
SPACE
B
E
T
C
F
X
#
ARMED
READY
6160-7720P-001-V0
SHIFT
FUNCTION
WHEN LIT
(C)
(D)
(A)
Normal and SHIFT key Functions While in
∗
∗
∗
∗
29 Menu Mode
Key
Normal Key Function
SHIFT Key Function
(A) = BS/ESC
[BS]: Press to delete entry
[ESC]: Press to quit Program Mode
Also, can reset EEPROM defaults
†
(B) =
↓
/
↑
[
↓
]: Scroll down programming
[
↑
]: Scroll up programming
(C) = N/Y
[N]: Press for "NO" answer
[Y]: Press SHIFT-Y for "YES" answer
(D) = SHIFT
Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is pressed. Press again f
or
each SHIFT function desired.
1/A
[1]: For entering the number 1
[A]: Used for entering C.S. ID number
2/B
[2]: For entering the number 2
[B]: Used for entering C.S. ID number
3/C
[3]: For entering the number 3
[C]: Used for entering C.S. ID number
4/D
[4]: For entering the number 4
[D]: Used for entering C.S. ID number
5/E
[5]: For entering the number 5
[E]: Used for entering C.S. ID number
6/F
[6]: For entering the number 6
[F]: Used for entering C.S. ID number
7/S
[7]: For entering the number 7
[S]: Press to display diagnostic status
8/T
[8]: For entering the number 8
[T]: Press to send TEST messages
9/X
[9]: For entering the number 9
[X]: Press to reset the IP/GSM
[
∗
] / SPACE
[
∗
]: Used to select programming options
[SPACE]: Not used
0
[0]: For entering the number 0
[#] / ENTER
[#] / ENTER: Press to accept entries
No SHIFT function
†
Active only when the "REVIEW?" prompt is displayed
Internal Device (IP and GSM) Default Values
The programming default values for
∗
29 Menu Mode are listed in the Table below.
OPTION
STANDARD DEFAULT VALUE
ACTUAL ENTRY
1
Internal Device
IP
2
Primary City ID
??
3
Primary CS ID
??
4
Primary Sub ID
????
5
Supervision
24 Hours
6
GSM Rollover Y/N
N (if GSM enabled)
7
GSM 24Hr Tst Y/N
N (if GSM enabled)
8
Old Alarm Time
10 Minutes
9
IP Fault Time
00 Minutes
10
GSM Fault Time
00 Minutes (if GSM enabled)
11
Notify Panel Of
Neither Fault (if IP and GSM enabled)
12
Use DHCP Y/N
Y (if IP or IP/GSM enabled)
13
NIC IP Address
255.255.255.255 (if DHCP not used)
14
Subnet Mask
255.255.255.255 (if DHCP not used)
15
Gateway IP Addr
255.255.255.255 (if DHCP not used)
16
DNS IP Addr.
255.255.255.255 (if DHCP not used)
Status and Contact ID Reporting Codes
The Internal Device (IP/GSM) sends status messages to the control panel for network connectivity failures. Trouble messages are
displayed on the keypad as
“Check 103,” with status displayed as “LngRng Radio” followed by a 4-digit keypad display status code, defined below.
Keypad Display Status Codes
CODE
DESCRIPTION
0000
Control panel lost communication with internal device
0005
internal device has lost contact with AlarmNet network
000F
internal device is not registered; account not activated
0019
GSM module shut down
0400
internal device Power-on reset
** reports only if IP and GSM enabled
Contact ID Codes (as displayed at 685) sent to CS via IP/GSM
CODE
DESCRIPTION
E339 C803
Power-on reset
E350 C951
Primary communication path failure (Ethernet)**
R350 R951
Primary communication path restore (Ethernet)**
E350 C952
Secondary communication path failure (GSM)**
R350 C952
Secondary communication path restore (GSM)**
E355 C000
Module lost ECP communication with control
R355 C000
Module restore ECP communication with control
E353 C103
Long range transmitter fault trouble
R353 C103
Long range transmitter fault restore
– 12 –
Using
∗
∗
∗
∗
29 Menu Mode to Program IP/GSM Options
Entering
∗
∗
∗
∗
29 Program Mode
Press
∗
29 while in Data Field Programming mode.
The following prompts appear.
Enable INT IP/GSM?
0 = No, not using either IP or GSM; 1 = Yes, using IP and/or GSM module
[
∗
] to continue. NOTE: Default = 1 (IP and/or GSM)
IMPORTANT:
If using an external communication device, see the
VISTA-GSM
Module Installation
section of the Installation and Setup Guide (
Inadequate
Signal Strength
paragraph) for physical installation of an external
communication device. When complete, enter 1 at this prompt and enter 1-Prog
at the next prompt. Then program the external device using the Installation and
Setup Guide included with the external communication device.
Programming/Diagnostics Select
1= Prog (program the IP/GSM options)
2 = Diag (enter diagnostic mode)
0 = Quit; return to data field programming mode
Internal Device Programming Prompts
The keys used to select and enter options now follow 7720P keypad emulation.
Refer to the table on the previous page for detailed key functions. The following
is a summary:
[
∗
] = scroll the options of a particular prompt
[#] = accept the entry and move to the next prompt
[A] = backspace or shift-[A} for escape
[B] = scroll to next prompt or shift-[B] scroll to previous prompt
[C] = answer No or shift-[C] answer Yes to prompt
[D] = shift key
Internal Device Selection
Select the type of IP and/or GSM module usage (press [
∗
] to scroll choices):
Disabled (none); IP only; GSM module only; IP & GSM
[#] to continue
Multi-Mode (email reporting)
This feature is available only after authorization for it is set via the web-based
programming tool on the AlarmNet Direct website.
Multi-mode emulates 4204 Relay Module outputs to send up to four (4204
sourced) or up to eight (2-4204 sourced) reports of system events to the user via
email (email address is entered at the AlarmNet Direct website). Use the
AlarmNet Direct website to customize event titles, if desired. If enabled, a multi-
mode address must be entered in the next prompt.
Use *79/*80 Menu modes to program each emulated output to trigger a desired
system event that, upon occurrence, will be sent to the user’s email address.
Select the desired multi mode option:
Disabled =
no email reporting of events
4204 Sourced = up to four types of events reported (relay numbers 1-4 report
as events 1-4 respectively)
2-4204 Sourced = up to eight types of events reported (first module’s relay
numbers 1-4 report as events 1-4 respectively; second
module’s relay numbers 1-4 report as events 5-8 respectively)
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
NOTES:
1. Multi-mode has not been evaluated by UL.
2. Multi-mode (email notification) is intended as a convenience for the user,
and does not replace Central Station reporting of critical events (alarms,
troubles, etc.).
Multi-Mode Address
This prompt appears if Multi Mode is enabled.
12-15 =emulated 4204 Relay Module address.
If using “2-4204-sourced,” the address of the second module is automatically
assigned an address one higher than the first module’s address.
NOTE: A 4204 Relay module address is required for multi-mode purposes, but
an actual 4204 Relay module is not used.
Primary City ID
NOTE: Account information is provided by the central station administrator.
01-99 (decimal) = 2-digit primary city code
Primary CS ID
Enter the primary central station's system ID number, 01-FE (HEX)
Primary Sub ID
Enter the 4-digit customer account number, 0001-9999 (decimal).
Remote Access
This feature is available only after authorization for it is set via the web-based
programming tool on the AlarmNet Direct website.
Remote Services allow the end user to access their security system from a
computer via the remote services website. Most system functions can then be
performed.
[Y] = use remote services
[N] = do not use remote services
[#] to continue
Keypad Address (for Remote Access)
This prompt appears if remote access is enabled.
For enhanced remote access features, choose an AUI address. If no AUI
addresses are available (all four AUIs are being used), choose an available
standard keypad address (some remote access features will be unavailable).
1, 2, 5, 6 = emulated AUI address
17-23 = emulated standard keypad address
NOTE: An AUI or standard keypad address is required for remote access
purposes, but an actual AUI device or keypad is not used.
Supervision
The supervising station must hear from the IP/GSM at least once during the
supervision period. AlarmNet transmits a communications failure alarm to the
central station if the supervision message is not received within the period.
This selection sets the supervision timing for one of the following values:
if using IP and/or GSM
if using IP only (not for GSM usage)
•
30 day
•
US UL Line (6 Min)
•
24-hours
•
US UL Line (90 Sec)
•
None (no supervision)
•
CN UL Line Lv1 3 (3 Min)
•
CN UL Line Lv1 4 (90 Sec)
•
CN UL Line Lv1 5 (75 Sec)
•
1 hour
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
GSM Rollover Y/N
Appears only if IP&GSM is selected as Internal Device option.
[Y] = all messages (including AlarmNet network supervisory messages) are
sent over the GSM network in the event of an Internet failure
[N] = all messages (except AlarmNet network supervisory messages) are sent
automatically over the GSM network in the event of an Internet failure
GSM 24Hr Tst Y/N
Appears only if IP&GSM is selected as Internal Device option.
[Y] = have a message sent once a day to verify GSM operation. A "secondary
communication path loss" message is generated if the message is not
successfully delivered.
[N] = disable 24hr test
Old Alarm Time
The old alarm time sets how long an undeliverable alarm is retried for delivery
to AlarmNet. If the message is not validated, it is retried until the old alarm time
is reached or the message is validated. The choices available are:
•
10 Minutes
•
4 Hours
•
15 Minutes
•
8 Hours
•
30 Minutes
•
12 Hours
•
1 Hour
•
24 Hours
•
2 Hours
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
IP Fault Time
Appears only if IP or IP&GSM is selected as Internal Device option.
00-99 = time delay (in minutes) before the control notifies the central station that
there is a loss of contact with the network over the Ethernet (IP)
connection.
0 = no delay (valid only If using IP only)
Must be two (2) minutes for UL installations.
GSM Flt Time
Appears only if GSM or IP&GSM is selected as Internal Device option.
00-99 = time delay (in minutes) before the control notifies the central station
that a loss of contact with AlarmNet network has occurred.
0 = no delay (valid only if using GSM only,
Must be two (2) minutes for UL installations.
Notify Panel Of _
Appears only if IP&GSM is selected as Internal Device option.
Select from the following choices:
•
Neither Fault
•
Both IP and GSM must fail before fault code is sent (status code 4005
displayed); panel receives primary and secondary path failure messages.
No message sent if only one or the other path fails.
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
NOTE: IP failure will always be sent to the central station as Primary Path
Failure, and GSM failure will always be sent as Secondary Path Failure.
IP address information prompts
The following prompts appear only if IP or IP&GSM is selected as Internal
Device.
It is recommended to use dynamically allocated IP addresses, but if fixed IP
addresses are desired, contact your network administrator for the appropriate
information. Note that a valid IP address must be entered in each prompt before
the system continues to the next prompt. Entries cannot be left with the default
values.
Use DHCP
[Y] = have the IP addresses dynamically allocated (recommended), skip to
Review prompt.
[N] = use fixed IP addresses; continue with next prompt
[#] to continue
– 13 – NIC IP Address
[255.255.255.255]
Enter the 4-part IP address for this device, separating each part with a space
([
∗
] key, displayed as periods). [#] to continue
Subnet Mask
[255.255.255.255]
Enter the 32-bit address mask used to indicate the portion (bits) of the IP
address that is being used for the subnet address, separating each part with a
space ([
∗
] key, displayed as periods). [#] to continue
Gateway IP Addr
[255.255.255.255]
Enter the 4-part IP address assigned to the Gateway, separating each part with
a space ([
∗
] key, displayed as periods). If unused set to 0.0.0.0.
[#] to continue
DNS IP Addr
[255.255.255.255]
Enter the 4-part IP address assigned to the DNS (Domain Name System)
server, separating each part with a space ([
∗
] key, displayed as periods). If
unused set to 0.0.0.0. [#] to continue
Review? (and Exit
∗
∗
∗
∗
29 Menu mode or Reset Defaults)
You can review the
∗
29 Menu mode options to ensure that the correct entries
have been made. When satisfied, select [N] to exit
∗
29 Menu mode.
To review prompts or exit
∗
∗
∗
∗
29 Menu mode:
[Y] = review prompts and entries, starting with Internal Device. Use the
up/down arrow keys to scroll through the program fields without changing
any of the values. If a value requires change, simply type in the correct
value. When the last field is displayed, the “REVIEW?” prompt appears.
[N] = Exit *29 menu mode and return to data field programming mode. The
prompt briefly displays “DONE” before returning to data field mode
prompt “Enter
∗
or #.”
[#] to accept Y or N selection (# alone exits same as N)
To reset
∗
∗
∗
∗
29 Menu mode defaults:
Press [ESC] at the Review prompt to display the “Set Defaults” prompt.
[Y] = reset
∗
29 menu mode options to factory values; if selected, all
programmed
∗
29 Menu mode options are reset to the factory settings
[N] = cancel reset defaults function
Programming IP/GSM Options via AlarmNet Direct Website
To program the IP/GSM options via the AlarmNet Direct website (if you are
already signed up for this service), go to:
https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx
If you are not signed up for this service, click on “Dealer Sign-Up.
Log in and follow the on-screen prompts.
Please have the following information available:
1. Primary City ID (two-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label
inside module) or MIN number of the device you are replacing
5. Mode of operation of existing module if replacing a "C" series radio.
After programming is complete, you must transfer the data to the module and the
module must be registered. Refer to the Registration section for details.
IP/GSM Diagnostic Commands (
∗
∗
∗
∗
29 Menu Mode)
Diagnostic commands can be used to quickly view your Internet and GSM
connectivity settings and options. For each command press the [shift] key and
then the designated command key. For example, press [shift] then [1/A] to
display the software revision screen.
To enter Diagnostic mode:
1. Press
∗
29 while in data field programming mode.
2. Enter “1” at the “Enable IP/GSM” prompt then press [
∗
].
3. Select “2” (Diag) at the next prompt.
4. Enter the desired command at the “Sel Key Command” prompt.
For subsequent commands, enter the next command at the current screen.
To exit Diagnostic mode, press ESC (shift-[A]).
Key
Prompt
Function
[A]
Internal IP/GSM
x.x.xx mm/dd/yy
Software Revision
"x.x.xx" indicates the installed
software Revision. Mm/dd/yy
indicates month, day and year of
the revision.
[B]
MAC xxxxxxxxxxxx
MAC CRC yyyy
MAC Address
“xxxxxxxxxxxx” indicates the
IP/GSM’s unique identification
number. Yyyy indicates the 4
digit MAC CRC needed to enroll
the device in dealer direct.
[
∗
] to continue to SCID.
SCID xxxxx xxxxx
xxxxx xxxxx
SCID Display
Only if GSM or IP/GSM enabled.
Displays the identification
number assigned to the SIM
card (SCID) in this device.
[
∗
] to continue to IMEI.
IMEI xxxxxxxx
Xxxxxx x
IMEI Display
Only if GSM or IP/GSM enabled.
Displays the identification
number assigned to the GSM
module in this device.
[
∗
] returns to MAC Address.
IP/GSM Diagnostic Commands (continued)
Key
Prompt
Function
[C]
Mon 01 Jan 2006
05:48:39 am
Time
Retrieves the current date and
time from the AlarmNet network
in Greenwich Mean Time (GMT).
This display confirms that the
module is in sync with network.
[D]
Physical Link
Good/Bad
Physical Link
Only if IP or IP/GSM enabled.
Indicates whether the device has
detected a physical connection
to the internet.
[
∗
] to continue to NIC IP address.
NIC IP Address
xxx.xxx.xxx.xxx
IP Information Displays
Displays the IP address
assigned to this device.
[
∗
] to continue to subnet mask.
Subnet Mask
xxx.xxx.xxx.xxx
Displays the 32-bit address mask
used to indicate the portion (bits)
of the IP Address that is being
used for the subnet address.
[
∗
] to continue to gateway IP.
Gateway IP Addr
xxx.xxx.xxx.xxx
Displays the IP Address
assigned to the Gateway.
[
∗
] to continue to DNS server IP.
DNS Serv IP
xxx.xxx.xxx.xxx
Displays the IP Address
assigned to the DNS (Domain
Name System) server.
[
∗
] to continue to encryption test.
Encryption Test
AES
Passed!
Performs a self-test of the AES
encryption algorithm.
[
∗
] to continue to DHCP.
DHCP
OK
DHCP (Dynamic Host
Configuration Protocol)
indicates server is performing
satisfactorily.
[
∗
] returns to Physical Link prompt.
[E]
PriRSSI GPRS REG
-xxxdbm x x
GSM Status Displays
Only if GSM or IP/GSM enabled.
PriRSSI – Primary Site RSSI
level in dbm
GPRS – GPRS Service
availability where “x” can be:
“Y” if GPRS is available
“N” if GPRS is Not available
REG – Registration status
from GSM module where
“x” can be:
N – Not Registered
H – Registered Home
S – Searching
D – Registration Denied
R – Registered Roaming
? – Unknown Reg. State
[
∗
] to continue to next screen.
Cntry Netw LAC
xxx xxx xxxxx
Cntry – Country Code
Netw – Network Code
LAC – Reg. status from GSM.
[
∗
] to continue to next screen.
Cell BaseSt Chan
Xxxxx x xxx
Cell – Base Station ID
BaseSt – Base Station Antenna
Sector
Chan – Control Channel in use
[
∗
] to continue to next screen.
Second Site RSSI
-xxxdbm
Secondary GSM Site RSSI level
in dbm.
[
∗
] to continue to next screen.
[F]
Testing Gateway
Redir 1
Network Diagnostic Test
Only if IP or IP/GSM enabled.
Performs a set of network
diagnostics that tests the
integrity of the links between the
IP/GSM and the various
connection points (Redirs) to
AlarmNet.
[S]
ECP
FLT
OK
Status request
OK = normal
i = IP off line
I = IP fault reported
g = GSM off line
G = GSM fault reported
– 14 – IP/GSM Diagnostic Commands (continued)
Key
Prompt
Function
[T]
Test Msg Sent
Test Alarm
Sends a Test alarm to AlarmNet.
Functional for a registered
IP/GSM only. If the device is not
registered, a message is
displayed indicating that the
command cannot be executed.
[X]
Reset CPU Y/N
Reset the IP/GSM.
[N] = return to diagnostic mode
(blank screen = enter next
command or escape).
[Y] = resets the module (blank
screen = when reset
complete, enter next
command or escape).
[
↑
↑
↑
↑
]
Registering ...
Registration (Shift-UP
arrow)
Registers a programmed
IP/GSM with AlarmNet. If it is
configured to report to AlarmNet,
the IP/GSM will register with
AlarmNet.
[
↓
↓
↓
↓
]
Enter PIN#
Registration with PIN for
Replacement Module (DN
arrow)
Registers a programmed
IP/GSM with AlarmNet if it is
configured to report to AlarmNet.
[0]
Force Server Update
Y/N
Force Upload of
Configuration File to Server
[Y] = force the device to upload
its entire configuration file
to the server.
[N] = cancel the operation.
NOTE: If the internet is not
available, and the module is not
initialized when you enter this
command, the following screen
will be displayed:
Cannot Upload
Try Later! _
Wait for the RSSI LEDs to light,
indicating initialization is
complete, and try again.
Registration with AlarmNet
The control must be registered with AlarmNet before internet communication
(via IP or GSM) can occur.
To register, the control must be connected to the Internet.
Register the control by using one of these methods:
Register by phone
1. Call 1-800-222-6525
You will need the following information:
•
MAC ID and MAC CRC number (found on the PCB label)
•
Subscriber information (provided by the central station), including a
city code, CSID, and a subscriber ID
•
Activation ID (AID) and AID CRC numbers (found on the label on
the VISTA-GSM module or on its carton)
2. When instructed to do so, triple-click the Test switch to complete the
registration.
Register with Alpha Keypad using *29 Menu mode
1. Enter *29 Menu mode, select Diagnostic mode, then press Shift then [
↑
]
key (D key followed by the B key). The registration message is sent
(“Registering” displayed) and the control waits for the acknowledgment.
2. “Registration SUCCESS” displayed, indicating successful registration.
Register with Test Switch on control
’
s PCB (triple-click)
1. Click the switch three times.
2. Watch the GSM Status LEDs: The Message (yellow) LED and the Status
(green) LED will blink slowly in unison while registration is in progress.
3. When registration is complete, the Status (green) LED goes out.
Register with AlarmNet Direct Website
To register via AlarmNet Direct Website, please go to:
https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx
.
Log in and follow the on-screen prompts.
Please have the following information available:
•
Primary City ID (two-digit number provided by central station)
•
Primary Central Station ID (two-digit hexadecimal number provided by
central station)
•
Primary Subscriber ID (four-digit number provided by central station)
•
MAC ID and MAC CRC number (located on outside of box and on label
on control’s PC board)
•
Activation ID (AID) and AID CRC numbers (found on the label on the
VISTA-GSM module or on its carton)
If you are not signed up for this service, click on “Dealer Signup” from the
login screen to gain access to the Honeywell web-based programming.
Dealer Sign-Up Direct Link:
https://services.alarmnet.com/AlarmNetDirectP_Sign-Up.
You will be instructed how to proceed upon completing the sign-up form.
Only one sign-up per dealer is required. Once an initial user is established,
additional logins may be created by that user.
Once the control is registered, you may log out of the AlarmNet Direct website.
IP/GSM LED Functions
IP (web) Network LED Functions
LED Color
LED
Description
Top Green
Ethernet Link/Activity
ON – link is active; OFF – no link
Middle Green
Link Speed
ON – 100 MB/S; OFF – 10 MB/S
Yellow
Network Collision
BLINK – collision detected; OFF – normal
IP/GSM Status LED Functions
LED Color
LED
Description
Green
Status
ON – control is NOT registered with AlarmNet; OFF – control is registered with AlarmNet.
FAST BLINK – Download session with Compass in progress.
SLOW BLINK – In unison with yellow LED – Registration in progress.
Yellow
Message
ON – Message transmission pending.
QUICK PERIODIC BLINK - Normal
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – In unison with green LED – Registration in progress.
Red
Fault
ON – No contact with network; OFF– Normal.
SLOW BLINK – Loss of communication with the panel (ECP fault).
FAST BLINK – No network contact AND loss of communication with the panel.
All
FAST BLINK – In unison with the RSSI Bar Graph LEDs – Hardware Error. Call the
AlarmNet Technical Assistance Center.
Signal Strength and Status LED Meanings
Color
Label
Indication
Red
RSSI
ON = signal strength (RSSI) display
OFF = status display
Yel (2)
mode
OFF = module operating in ECPmode
Green
Web
web connection status
ON = connected to web
OFF = no web connection
Green
GPRS
GPRS service availability
ON = GPRS service available
FLASH = GPRS in use
OFF = no GPRS service (messages sent via SMS)
Green
GSM
network carrier registration status
ON = registered with network carrier, no second site available
FLASH = registered with network carrier and second site available, excellent RSSI
BLINK = registered with network carrier and second site available, acceptable RSSI
SLOW BLINK = registered with network carrier and second site available, low RSSI
OFF = control not registered with network carrier
– 15 – Setting Schedules
(Installer Code + [#] + [6] [4])
NOTES:
•
The master code can only access schedules 01-16 and events 00-07.
•
System clock must be set before schedules can be used.
•
Programmed schedules do not take effect until the next scheduled “start”
time. (e.g., if programming a schedule time window for 8AM to 5PM, the
schedule does not take effect until 8AM after the schedule has been
programmed.)
ENTER SCHED NO.
01-16 = end-user schedules; 17-32 = installer-only schedules
[
∗
] to continue.
To Quit,
enter 00.
ENTER EVENT
00 = clear event
01 = Relay On/Off
02 = User Access
03 = Latch Key Report to Pager (sent to all pagers in the user’s partition;
message sent is 777-7777. User must be enabled for paging and
system must be armed before reporting can occur.)
04 = Forced Stay Arming
(
Forced bypass is automatically enabled
regardless of setting in field *23)
05 = Forced Away Arming
(
Forced bypass is automatically enabled
regardless of setting in field *23)
06 = Auto Disarm
07 = Display “Reminder”
10 = Display custom words (if selected, system displays custom words 8, 9,
and 10 at defined time. Can be used as installer’s reminder message
to the end user); programmable by installer only
11 = Periodic Test Report (see key commands in
Test Report Code
, data
field *64
,
to quickly set periodic test reporting intervals); programmable
by installer only
[
∗
] to continue.
DEVICE NUMBER
( for event 1 relay on/off)
01-18; [
∗
] to continue.
GROUP NUMBER
( for event 2 user access)
1-8; [
∗
] to continue.
PARTITION
( for events 3-7,10,12)
0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common
[
∗
] to continue.
START
01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; to select days, position the
cursor under the desired days using the [
∗
] key to move forward, then press
“1” to select the day.
[
∗
] to continue.
STOP
(for events 1 relay on/off; 2 user access; 3 latch key report)
See START for entries. [
∗
] to continue.
REPEAT
0 = do not repeat; 1 = repeat schedule weekly; 2 = repeat schedule biweekly
(every other week); 3 = repeat schedule every third week; 4 = repeat
schedule every fourth week (28 days)
[
∗
] to continue
RANDOMIZE
(for events 01 and 11)
0 = no; 1 = yes
If selected, the scheduled start and stop times will vary within 60 minutes of
the “hour” time. For example, if a schedule is set to start at 6:15pm, it will do
so the first time 6:15pm arrives, but on subsequent days it will start anytime
between 6:00 and 6:59 p.m.
NOTE:
Do not use the random option if the start and stop times are within
the same “hour” setting, otherwise unpredictable results may occur (e.g., the
randomized stop time may occur before the start time).
[
∗
] to continue and return to ENTER SCHED NO. prompt to program the
next schedule.
Setting The Real-Time Clock
The Real-Time Clock must be set before completing the installation.
NOTE:
All partitions must be disarmed before the Real-Time Clock can be set.
1. Master Code + [#] + [6] [3]
2. Press [
∗
] when the time/date is displayed. A cursor appears under the first digit of the hour.
To move cursor ahead, press [
∗
]. To go back, press [#].
•
Enter the 2-digit hour setting, followed by the 2-digit minute setting, then press [1] for PM or [2] for AM.
•
Enter the last two digits of the current year, followed by the 2-digit month setting and the 2-digit day setting.
3. To exit, press [
∗
] when cursor is at the last digit, or wait 30 seconds.
Uploading/Downloading Via The Internet
This control supports upload/download programming capability via the Internet by using the AlarmNet network and Compass
downloading software. The control must be connected to the Internet (via the on-board RJ45 connector or VISTA-GSM module),
have all IP features programmed (
∗
29 Menu mode), and be registered with AlarmNet.
The following is required at the Downloading Office:
•
Broadband Internet Access and Broadband (Cable/DSL) Modem
•
Broadband (Cable/DSL) Router (optional, if connecting more than one device to the Internet)
•
Computer running Compass Downloading Software version that supports Internet upload/download for this control.
To perform upload/download functions:
1. Connect the computer to the Internet and start the Compass downloading software.
2. Open the control’s account, then select the Communications function and click the
Connect
button.
3. At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is checked.
4. Click
Connect
. The Internet connection to the control is made automatically via AlarmNet.
5. Once connected, use the Compass downloading software as normal to perform upload/download functions.
AVS System Enable and Quick Programming Commands
Applies to an AVS system using an ECP connection to the control.
1. Install the AVS module according to its instructions.
2. Use one of the control’s AVS Quick Program commands as follows (see Quick Program Command Results below for
results of each command):
•
installer code + [#] + 0 + 3:
enable AVS operation without panel sounds on the AVST speaker
•
installer code + [#] + 0 + 4:
enable AVS operation and enable panel sounds on the AVST speaker
3. Use data field
∗
55 Dynamic Signaling Priority to enable the reporting path for AAV communication.
4. To undo the Quick Command programming, use the following commands:
•
installer code + [#] + 0 + 5
: remove all options set by [#] + 03 quick command
•
installer code + [#] + 0 + 6
: remove all options set by [#] + 04 quick command
– 16 – AVS Quick Program Command Results
When either the #03 or #04 Quick Program command is used, the following are automatically programmed and no longer
available for other control panel purposes.
Pre-Programmed
#03 Command
#04 Command
Output Function No.
(
∗
80 mode)
46 (zone type 60, relay 15)
47 (zone type 61, relay 16)
48 (zone type 62, relay 16)
Same as #03 plus:
41 (zone type 14, relay 13)
42 (zone type 22, relay 13)
43 (zone type 39, relay 14)
44 (zone type 33, relay 14)
45 (zone type 22, relay 14
Output Relay No.
(
∗
79 mode)
15 (addr 11, relay pos 2)
16 (addr 11, relay pos 1)
Same as #03 plus:
13 (addr 11, relay pos 4)
14 (addr 11, relay pos 3)
Protection Zone
(
∗
56/
∗
58 mode)
4229 zn 48 (zt 81, addr 11)
Same as #03 command
Device Address
address 11 (AVS module)
Same as #03 command
Data Field
∗
91
AAV enabled
AAV enabled
SCHEDULES WORKSHEET
(installer code + [#] + [6] [4];
master code can only access schedules 01-16 and events 00-07
No.
Event
Device No. Group No. Partition
Start Time/
Stop Time/
Repeat Random
(see list below)
for “01” events:
for “02” events: for “04-06” events:
Days
Days
(1-4)
(yes/no)
enter 01-18
enter 1-8
enter 1, 2, or 3
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Events:
Master/Installer
Installer Only
00 = clear event
04 = forced STAY arm
10 = display custom words 8-10
01 = device on/off
05 = forced AWAY arm
11 = periodic test report
02 = user access
06 = auto disarm
03 = latch key report
07 = display “reminder”
Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth
week (28 days)
– 17 – *56 ZONE PROGRAMMING WORKSHEET
[default shown in brackets]
Zone
Zn Type
Part.
Report
Hardwire
Type
Rsp. Time
Location
1
[09]
[1]
[EOL]
[1]
2
[01]
[1]
[EOL]
[1]
3
[03]
[1]
[EOL]
[1]
4
[03]
[1]
[EOL]
[1]
5
[03]
[1]
[EOL]
[1]
6
[03]
[1]
[EOL]
[1]
7
[03]
[1]
[EOL]
[1]
8
[03]
[1]
[EOL]
[1]
Zone
Zn Type
Part.
Report
Input Type
Loop
Serial No.
Location
9
[1]
[RF]
10
[1]
[RF]
11
[1]
[RF]
12
[1]
[RF]
13
[1]
[RF]
14
[1]
[RF]
15
[1]
[RF]
16
[1]
[RF]
17
[1]
[RF]
18
[1]
[RF]
19
[1]
[RF]
20
[1]
[RF]
21
[1]
[RF]
22
[1]
[RF]
23
[1]
[RF]
24
[1]
[RF]
25
[1]
[RF]
26
[1]
[RF]
27
[1]
[RF]
28
[1]
[RF]
29
[1]
[RF]
30
[1]
[RF]
31
[1]
[RF]
32
[1]
[RF]
33
[1]
[RF]
34
[1]
[RF]
35
[1]
[RF]
36
[1]
[RF]
37
[1]
[RF]
38
[1]
[RF]
39
[1]
[RF]
40
[1]
[RF]
41
[1]
[RF]
42
[1]
[RF]
43
[1]
[RF]
44
[1]
[RF]
45
[1]
[RF]
46
[1]
[RF]
47
[1]
[RF]
48
[1]
[RF]
49
[1]
[BR]
50
[1]
[BR]
51
[1]
[BR]
52
[1]
[BR]
53
[1]
[BR]
54
[1]
[BR]
55
[1]
[BR]
56
[1]
[BR]
57
[1]
[BR]
58
[1]
[BR]
59
[1]
[BR]
60
[1]
[BR]
61
[1]
[BR]
62
[1]
[BR]
63
[1]
[BR]
64
[1]
[BR]
95
[00] N/A
**
N/A
N/A N/A
keypad [1] / [
∗
]
96
[00] N/A
**
N/A
N/A N/A
keypad [3] / [#]
99
[06] N/A
**
N/A
N/A N/A
keypad [
∗
] / [#]
** Emergency key zones 95, 96, and 99 report the partition of the keypad used to activate the emergency zones.
NOTES:
Zone Type: see chart in
∗
56 Zone Programming
Menu mode section.
Report Code: enabled if
first digit is a non-zero
number
Hardwire Type (zns 2-8):
0 = EOL
3 = ZD
1 = NC
4 = DB
2 = NO
Input Type:
2 = AW (zones 9-48)
3 = RF (zones 9-48)
4 = UR (zones 9-48)
5 = BR (zones 49-64)
NOTE:
Zones 9-16 not
available if zone
doubling enabled.
Response Time:
0 = 10msec
1 = 350msec
2 = 700msec
3 = 1.2 sec
Reserved Zones
91 =
addressable device
report enable/disable
default zone type =
[05].
92 =
Duress report
enable/disable
– 18 – *57 FUNCTION KEY WORKSHEET
Option
Function
A
P1 P2 com
B
P1 P2 com
C
P1 P2 com
D
P1 P2 com
Comments
01
Paging
02
Time Display
03
Arm AWAY
04
Arm STAY
05
Arm NIGHT-STAY
06
Step Arming
07
Device Activation
Device:
08
Comm. Test
09
Macro Key 1
Assign each macro key to only a single partition.
†
10
Macro Key 2
Assign each macro key to only a single partition.
†
11
Macro Key 3
Assign each macro key to only a single partition.
†
12
Macro Key 4
Assign each macro key to only a single partition.
†
00
Emergency Keys:
zone 95
zone 99
zone 96
paging
Personal Emergency
n/a
Silent Alarm
n/a
Audible Alarm
n/a
Fire
n/a
Emergency Keys:
A = paired keys [1] / [
∗
] (zone 95); B = paired keys [
∗
] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
† There are only four macros system-wide.
OUTPUT RELAYS/POWERLINE CARRIER (X-10) DEVICES WORKSHEET FOR
∗
∗
∗
∗
79,
∗
∗
∗
∗
80 and
∗
∗
∗
∗
81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗
∗
∗
∗
79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE
OUTPUT TYPE
Relay
X10
Relay
X10
Output
No.
Module
Addr.
Pos
(1-4)
Unit
No.
Description
Output
No.
Module
Addr.
Pos
(1-4)
Unit
No.
Description
01
09
02
10
03
11
04
12
05
13
06
14
07
15
08
16
17
On-Board Trigger 1
norm output =
18
On-Board Trigger 2
norm output =
!
81
ZONE LISTS WORKSHEET
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
NOTE:
Record desired zone numbers below, noting that a list may include
any
or
all
of system's zone numbers.
List No. Used For
...
Contains These Zones
...
01
General Purpose (GP)
02
General Purpose
03
Chime-by-Zone or GP
(see field *26 for Chime-by-Zone option)
04
Cross Zones or GP
(see field *85 for Cross Zone Timer option)
05
Night-Stay Zones or GP
06
Dial Delay Disable or GP
V21iPSIA:
see field *50 for Dial Delay Disable option
07
Unlimited Reports or GP
V21iPSIA:
see field *93 for Unlimited Reports option
08
General Purpose
09
Zones activating pager 1
10
Zones activating pager 2
11
Zones activating pager 3
12
Zones activating pager 4
– 19 –
!
80
OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
Notes:
1.
For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
2.
For Powerline Carrier devices (plcd), field
!
27 must be programmed with a House Code.
3
. Tampers of expansion units cannot be used to operate devices.
Activation Type and Detail
Event (for zone list/activated by)
Output
Function
Number
(1-48)
Activated by
0=delete
1=zn list
2=zn type
3=zn no.
Zone List
(ZL)
1-8 = list
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
01-64
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 = partition 2
3 = common
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
By Zone No.
0 = restore
1 = alrm/flt/trbl
Action
0 = off
1 = close 2 secs
2 = stay closed
3 = pulse
4 = toggle
5 = duration 1
††
6 = duration 2
††
Output
Number
1-18
Device
Type
R = relay
T = trigger
X = X10
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
ZONE TYPE/SYSTEM OPERATION
–
Choices for Zone Types are:
00 = Not Used
05 = Trouble Day/Alarm Night 10 = Interior w/Delay
24 = Silent Burglary
01 = Entry/Exit#1
06 = 24 Hr Silent
12 = Monitor Zone
77 = Keyswitch
02 = Entry/Exit#2
07 = 24 Hr Audible
14 = Carbon Monoxide§§
81 = AAV Monitor Zone
03 = Perimeter
08 = 24 Hr Aux
16 = Fire w/Verification
90-91 = Configurable
04 = Interior Follower 09 = Fire
23 = No Alarm Response
§§ when used with an output function,
the carbon monoxide zone type
activates only upon CO alarms. Does
not activate for trouble conditions.
Choices for System Operation are:
20 = Arming–Stay
38 = Chime
58 = Duress
21 = Arming–Away
39 = Any Fire Alarm
60 = AAV Trigger
22 = Disarming (Code + OFF)
40 = Bypassing
61 = AVS/GSMV session begin §
31 = End of Exit Time
41 = **AC Power Failure
62 = AVS/GSMV session end §
32 = Start of Entry Time
42 = **System Battery Low
66 = Function key†
33 = Any Burglary Alarm
43 = Communication Failure
67 = Bell Failure
36 = **At Bell Timeout***
52 = Kissoff
68 = TELCO Line Fault
54 = Fire Zone Reset
78 = Keyswitch red LED†††
79 = Keyswitch green LED†††
Note:
In normal operation mode:
Code + # + 7 + NN Key Entry
starts
Device
Code + # + 8 + NN Key Entry
stops
Device
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
†† Duration is set in program field *177.
††† Device action not used for these choices.
§ automatically set when appropriate AVS Quick
Command performed.
–
20
–
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated have one or more unique factory assigned input (loop) ID numbers. Each of the inputs requir
es its own
programming zone
(e.g., a 5804's four inputs require four programming zones).
For information on any transmitter not shown, refer to the instructions accompanying that transmitter for details regarding loo
p numbers, etc.
UL NOTE
:
The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP,
5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
LOOP 1
5806/5806W3
5808/5808LST/5808W3
ENROLL AS
"RF"
LOOP 1
5809
ENROLL AS
"RF"
5818MNL
ENROLL AS
"RF"
LOOP 1
LOOP 1
5814
ENROLL AS
"RF"
5800-003-V0
LOOP 1
(MOTION)
5897-35
ENROLL AS
"RF"
5890/5890PI
ENROLL AS
"RF"
LOOP 1
5 8 0 2 M N
ENROLL AS
"UR" OR "RF"
5805-6
ENROLL AS
"BR"
5 8 0 4 B D / 5 8 0 4 B DV
ENROLL AS
"BR"
SET HOUSE ID
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP
3
LOOP 1
LOOP 2
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5804/5804E
ENROLL AS "BR"
5817
ENROLL AS
"RF"
LOOP 2
(AUX.
CENTER)
LOOP 1
(PRIMARY)
LOOP 3
(AUX.
RIGHT)
5816
ENROLL AS
"RF"
LOOP 1
(TERMINALS)
LOOP 1
(TERMINALS)
LOOP 2
(REED)
5816MN
ENROLL AS
"RF"
LOOP 1
(TERMINALS)
ALTERNATE
POSITION FOR
LOOP 2
LOOP 2
(REED)
LOOP 3
(TERMINALS)
5828/5828V
SET HOUSE ID
5815
ENROLL AS
"RF"
5820/5820L
ENROLL AS
"RF"
5 8 1 9 S ( W H S & B R S )
ENROLL AS
"RF"
LOOP 1
(INTERNAL
SHOCK
SENSOR
LOOP 2
(REED)
5819
ENROLL AS
"RF"
LOOP 2
(REED)
LOOP 3
(TERMINALS)
LOOP 1
(TERMINALS)
5 8 0 0 WAV E
S E T H O U S E I D
E N R O L L A S " R F "
5800Micra
E N R O L L A S " R F "
5800CO
E N R O L L A S " R F "
5801
E N R O L L A S
" U R O R " R F "
5800SS1
E N R O L L A S " R F "
LOOP 3
LOOP 1
LOOP 2
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
5894PI
ENROLL AS
"RF"
5 8 0 2 M N 2
ENROLL AS
"UR" OR "RF"
LOOP 1
LOOP 1
LOOPS
1 - 3
LOOP 1
LOOP 1
LOOP 1
LOOP
1
LOOP 1
LOOP
1
LOOP
1
5878
ENROLL AS
"BR"
5853
ENROLL AS
"RF"
A
R
M
E
D
R
E
A
D
Y
4
3
2
1
OFF
ON
5821
ENROLL AS
"RF"
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
LOOP 1
LOOP 2
LOOP 3
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
SERIAL #1
LOOP 2
SERIAL #1
LOOP 1
SERIAL #2
LOOP 2
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
SERIAL #1
LOOP 2
SERIAL #1
LOOP 1
SERIAL #2
LOOP 2
3
A
W
A
Y
STA
Y
1
2
4
OFF
ON
LOOP 2
(REED)
LOOP 2
(REED)
SERIAL #2 - LOOP 1 = ON + 4 BUTTONS
LOOP 4 = 3 + 4 BUTTONS
SERIAL #2 - LOOP 1 = ON + 4 BUTTONS
LOOP 4 = 3 + 4 BUTTONS
–
21
–
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields
∗
35,
∗
36) cannot be greater than 30 seconds for UL Residential Burglar Alarm
installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm
installations, total entry delay may not exceed 45 seconds.
2. For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay
time must not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time
must not exceed 120 seconds.
3. The maximum number of reports per armed period (field
∗
93) must be set to “0” (unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA
max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The
tamper switch installed to protect the control unit enclosure door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible
for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential
applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote
monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to
enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
SIA Quick Reference Guide
1. *31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number
of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
2. *34 Exit Delay: Minimum exit delay is 45 seconds.
3. *35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4. *37 Audible Exit Warning: Feature always enabled; field does not exist.
5. *39 Power Up in Previous State: Must be “1,” power up in previous state.
6. *40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91
must be set.
7. *50 Burglary Dial Delay: Delay must be minimum of 30 seconds.
8. *59 Exit Error Alarm Report Code: Always enabled.
9 *68 Cancel Report Code: Default is “code enabled.”
10. *69 Recent Closing Report Code: Always enabled.
11. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be
set to “1” (enabled).
12. *93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13. Cross zone timer programming is set in field
∗
85; cross zone pairs are assigned in zone list 4 using
∗
81 Zone
List mode.
14. Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code
reporting by programming zone 92 using
∗
56 Zone Programming mode.
15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.
–
22
–
TABLE OF DEVICE ADDRESSES
This Device
Uses Address Reports as
††
Enabled By
...
RF Receiver
00
100
∗
56 zone programming: input device type entry
AUI 1 (touchscreen)
01
n/a
automatic if AUI enable field *189 enabled for AUI 1
AUI 2 (touchscreen)
02
n/a
automatic if AUI enable field *189 enabled for AUI 2
AUI 3 (touchscreen)
05
n/a
automatic if AUI enable field *189 enabled for AUI 3
AUI 4 (touchscreen)
06
n/a
automatic if AUI enable field *189 enabled for AUI 4
Internal IP/GSM Device
03
103
automatic if installed and enabled in menu mode
∗
29
4286 Voice Module
04
104
automatic if phone module access code field *28 enabled
Zone Expanders (4219/4229):
module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 zones 33 - 40
module 5 zones 41 - 48
07
08
09
10
11
107
108
109
110
111
∗
56 zone programming: input device type entry, then:
automatic if zone no. 9-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay assigned
automatic if zone no. 25-32 entered as AW type or relay assigned
automatic if zone no. 33-40 entered as AW type or relay assigned
automatic if zone no. 41-48 entered as AW type or relay assigned
Relay Modules (4204):
module 1
module 2
module 3
module 4
12
13
14
15
112
113
114
115
∗
79 output device programming: device address prompt:
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
Keypads:
keypad 1
keypad 2
keypad 3
keypad 4
keypad 5
keypad 6
keypad 7
keypad 8
16
17
18
19
20
21
22
23
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
data field programming as listed below:
always enabled, all sounds enabled.
data field
∗
190
data field
∗
191
data field
∗
192
data field
∗
193
data field
∗
194
data field
∗
195
data field
∗
196
5800TM Module
28
n/a
automatic
†† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable ad
dressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad displa
y options.
–
23
–
CLASS 2 PLUG-IN TRANSFORMER
16.5VAC, 40VA
(e.g. ADEMCO No. 1361)
(USE No. 1361CN IN CANADA)
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL
FIRE
PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
BATTERY
MARCH PARK, QUINCY, MA
02169).
PRINTED INFORMATION DESCRIBING
PROPER INSTALLATION, OPERATION,
TESTING, MAINTENANCE, EVACUATION
PLANNING AND REPAIR SERVICE IS TO BE
PROVIDED WITH THIS EQUIPMENT.
24-HR BATTERY STANDBY REQUIRED FOR
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HRS
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
FOR COMPLETE
INFORMATION,
SEE INSTRUCTIONS
K14488 OR LATER.
ALARM OUTPUT
10.5
–
13.8VDC, 2A MAX. (600mA
MAX. FOR UL USAGE,
INCLUDING AUX POWER)
STEADY FOR BURGLARY/PANIC,
TEMPORAL PULSE SOUNDING
FOR FIRE. CAN USE ADEMCO
No. 702 SIREN, OR 12V BELL).
SEE INSTRUCTIONS.
TO INTERNET
CONNECTION
CHARGING VOLTAGE 13.8VDC. MAXIMUM
CHARGING CURRENT 650mA.
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
KEYPAD CURRENTS.
BATTERY
12V, 4AH
IP/GSM SWITCHES
TEST STATUS
LED
INDICATOR
CONNECTION OF THE FIRE ALARM SIGNAL
TO A FIRE ALARM HEADQUARTERS OR A
CENTRAL STATION SHALL BE PERMITTED
ONLY WITH THE PERMISSION OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
THE BURGLAR ALARM SIGNAL SHALL NOT
BE CONNECTED TO A POLICE EMERGENCY
NUMBER.
GND
Z5
Z4
GND
Z3
Z2
GND
Z1+
YEL
GRN
AUX
AC
AC
BELL
GND
GND
RING
TIP
RING
TIP
Z8
GND
Z6
Z7
12
3
78
11
12
17
20
21
22
23
24
25
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
CONNECT CORD)
BLACK: KEYPAD GROUND (- ) RETURN
RED: KEYPAD PWR ( + )
GREEN: DATA IN FROM KEYPAD
YELLOW: KEYPAD DATA OUT
KEYPADS AND OTHER
ADDRESSABLE
DEVICES AND/OR
EXPANDER MODULES
(UP TO 40
ADDITIONAL ZONES)
4219, 4229, 4204: SET
DIP SW ADDR. 7-15
5881: SET DIP SW TO
ADDR. "0".
SEE MODULE'S
INSTRUCTIONS
(GRAY)
(GREEN)
(RED)
INCOMING
PHONE LINE
HANDSET
ZONE 1
ZONE 2
HI
LO
HI
LO
ZONE 3
ZONE 4
HI
LO
HI
LO
ZONE 5
ZONE 6
HI
LO
HI
LO
ZONE 7
ZONE 8
HI
LO
HI
LO
•
MAX LOOP RESISTANCE:
(EACH ZONE) 300 OHMS
(PLUS EOLR)
•
•
RESPONSE, ZONES 1-8:
10, 350, OR 700 MSEC
(PROGRAMMABLE)
8-PIN CONNECTOR
FOR 1361X10 TRANS.
AND ON-BOARD TRIGGERS
SEE INSTRUCTIONS.
78
(BROWN)
}
}
ZONE 1 CAN BE USED FOR 2-WIRE SMOKE DETECTORS
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
SOUNDER.
NOTE:
KEYPAD (S)
CURRENT (IN BOTH
PARTITIONS) AND
ALL OTHER DEVICES
DRAWING POWER
FROM TERMS 4 & 5
MUST BE INCLUDED
IN AUX CURRENT
DRAIN CALCULATIONS.
AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
(500mA MAX.
FOR UL
INSTALLATIONS)
ALL OUTPUTS
ARE POWER
LIMITED.
}
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
2000
OHMS
EOLR
SYNC
COM
DATA
GND
+12 AUX
18
19
16
15
14
13
10
9
6
4
1 2 3 4
5
6
OUTPUT 18
(TRIG. 2)
OUTPUT 17
(TRIG. 1)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS
ON ZONE 1 IS 16; DETECTORS MUST HAVE
COMPATIBILITY IDENTIFIER AS "A".
ZONE
PAIRS
2 / 10
3 / 11
4 / 12
5 / 13
6 / 14
7 / 15
8 / 16
ADEMCO VISTA-21iP / VISTA-21iPSIA
SUMMARY OF CONNECTIONS
13
12
14
10
11
6.2k
ZONE 10
3k
ZONE 2
2k
2k
2k
ZONE 3
2k
2k
2k
ZONE 4
TYPICAL WIRING FOR
ZONE DOUBLING
TYPICAL WIRING FOR
DOUBLE BALANCED ZONE
REMOTE KEYPADS
CAN USE 6150 OR 6160
KEYPADS. LOCAL
PROGRAMMING
MUST BE DONE WITH A
6160, BUT NEED NOT
REMAIN IN THE SYSTEM
(SET TO ADDRESS 16).
5
BLK
DOC LOAD NO.: 3
WARNING:
TO PREVENT RISK OF SHOCK,
DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.
FOR CONNECTION OF OPTIONAL 4286 VIP MODULE
TO PHONE TERMINALS, SEE INSTRUCTIONS.
COMPLIES WITH FCC RULES, PART 68. FCC REGISTRATION
NO. 5GBUSA-44003-AL-E RINGER EQUIVALENCE: 0.1B.
ALL DEVICES AND
ACCESSORIES USED IN A
CANADIAN INSTALLATION
MUST BE LISTED FOR
USE IN CANADA
POWER SHUTDOWN NOTE:
SYSTEM SHUTS DOWN
SENSOR DETECTION
PROCESSING IF
CONTROL'S VOLTAGE
DROPS BELOW 9.6V.
4-WIRE SMOKE DETECTOR CONNECTIONS
+
+
2000
OHMS
EOLR
HEAT
DETECTOR
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
VIOLET
AUX PWR
OUTPUT
TERMINALS
5
4
+
BLK
TO ZONE TERM. ( )
TO ZONE TERM. ( )
RELAY
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
PROGRAM RELAY
AS ZONE TYPE 54
(FIRE ZONE RESET)
+
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
N.C.
N.O.
TO OUTPUT 17
PROGRAM OUTPUT 17 FOR
"OUT NORM LOW" = YES IN
79 MENU MODE AND AS ZONE
TYPE 54 IN 80 MENU MODE
MAX. CURRENT = 100 mA
OR
ASSEMBLED IN MEXICO
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER
OPERATION OF THIS SYSTEM. IN ADDITION, THIS
SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.
*CA38A IN CANADA
BATTERY FUSE
FOR REPLACEMENT,
USE SAME VALUE
(e.g. 300-01802)
4A
BLACK
RED
(FLYING LEADS FOR
BATTERY CONNECTION)
TO
1361X10
TRANS
GSM MODULE (OPTIONAL)
Z1-
CAUTION:
ESD SENSITIVE DEVICE
To guard against static discharge damage while installing this module, briefly touch
a chassis ground point in the Control Panel cabinet to discharge any static buildup.
Avoid performing this installation while standing on a carpeted floor because a
carpeted floor increases the possibility of static buildup.
RJ45
C O N N E C TO R
ETHERNET LINK/ACTIVITY (ON=YES; OFF=NO)
LINK SPEED (ON=100 MB/S; OFF=10 MB/S)
NETWORK COLLISION (BLINK=DETECTED; OFF= NORMAL)
GRN
GRN
YEL
STATUS (ON=NOT REGISTERED; OFF = REGISTERED)
MESSAGE
FAULT (ON=NO NETWORK CONTACT; BLINK = PANEL FAULT)
GRN
YEL
RED
IP (WEB)
NETWORK
LEDs
IP/GSM STATUS LEDs
RSSI
MODE 1
MODE 2
WEB
GPRS
GSM
SIGNAL STRENGTH
AND STATUS LEDs
RED
YEL
YEL
GRN
GRN
GRN
RSSI
MINIMUM
LIT
ON = RSSI
OFF = STATUS; ON = RSSI
OFF = NO WEB CONNECTION; ON = CONNECTED TO WEB
OFF = NO GPRS SERVICE; FLASH = GPRS IN USE; ON = GPRS AVAILABLE
OFF = NOT REGISTERED w/CARRIER; BLINK/ON = REGISTERED w/NETWORK CARRIER
OFF = ECP MODE
STATUS LED INDICATIONS
TO 110VAC
UNSWITCHED OUTLET (24HR)
USE 1361X10 TRANSFORMER INTERFACE
IN PLACE OF 1361 OR 1361CN WHEN POWER
LINE CARRIER DEVICES ARE BEING USED.
(SEE INSTRUCTIONS FOR CONNECTIONS)
INTERNAL
IP/GSM
JUMPER
ON
OFF
V21iPSIA-SOC-V2
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2008 Honeywell International Inc.
www.
honeywell.com/security
ÊK14488PRV2>Š
K14488PRV2 6/09 Rev. A
- Uploaded