Honeywell Vista-50P Installation Manual and Setup Guide



Related Products

Honeywell Tuxedo Touch - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch
Talking Color Graphic Wired Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI
Talking Color Graphic Touchscreen Alarm Keypad
Honeywell VISTA-50P - Alarm Control Panel
Honeywell VISTA-50P
Alarm Control Panel
List Price: $702.00
Our Price: $433.99

Related Categories


Document Transcript

VI STA SERI ES VI S T A- 50P / VI S T A- 50P U L
Commercial Burglary Partitioned Security System With Scheduling Installation and Setup Guide

N5944-6V2 5/04 Rev B

ii

Table of Contents
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

List of Figures ...................................................................................................................................... v Conventions Used in This Manual..................................................................................................... vi SECTION 1: General Description ..................................................................................................... 1-1
About the VISTA-50P/VISTA-50PUL .................................................................................................................................1-1 Features .............................................................................................................................................................................1-1 Theory of Partitioning .........................................................................................................................................................2-1 Setting-Up a Partitioned System ........................................................................................................................................2-1 Common Lobby Logic ........................................................................................................................................................2-1 Master Keypad Setup and Operation .................................................................................................................................2-3

SECTION 2: Partitioning................................................................................................................... 2-1

SECTION 3: Installing the Control ................................................................................................... 3-1
Mounting the Control Cabinet ............................................................................................................................................3-1 Installing the Cabinet Lock .................................................................................................................................................3-1 Mercantile Premises Listing Guidelines .............................................................................................................................3-1 Mercantile Safe and Vault Listing Guidelines.....................................................................................................................3-2 Installing the Control's Circuit Board ..................................................................................................................................3-2 Installing the Keypads ........................................................................................................................................................3-3 Installing External Sounders ..............................................................................................................................................3-4 Telephone Line Connections .............................................................................................................................................3-6 Wiring Burglary, Panic, and Smoke Detector Devices to Zones 1-9..................................................................................3-7 Installing V-PLEX Devices ...............................................................................................................................................3-10 Wireless Zone Expansion ................................................................................................................................................3-12 Installing Output Devices .................................................................................................................................................3-16 Installing a Remote Keyswitch .........................................................................................................................................3-17 Remote Keypad Sounder.................................................................................................................................................3-18 Long Range Radio Connected to the J7 Triggers............................................................................................................3-19 Installing a 4100SM..........................................................................................................................................................3-19 Installing the 4286 VIP Module ........................................................................................................................................3-20 Installing the Audio Alarm Verification Module.................................................................................................................3-22 Connecting the Transformer ............................................................................................................................................3-24 Panel Earth Ground Connections ....................................................................................................................................3-25 Determining the Control’s Power Supply Load ................................................................................................................3-26 Determining the Size of the Standby Battery ...................................................................................................................3-28 Program Modes..................................................................................................................................................................4-1 Entering and Exiting Programming Mode...........................................................................................................................4-1 Data Field Programming Mode ..........................................................................................................................................4-1 #93 Menu Mode Programming...........................................................................................................................................4-2 Zone Number Designations ...............................................................................................................................................4-4 Zone Response Type Definitions .......................................................................................................................................4-5 Zone Input Type Definitions ...............................................................................................................................................4-6 Programming for 4100SM ..................................................................................................................................................4-7 Programming for Access Control .......................................................................................................................................4-7 About Data Field Programming..........................................................................................................................................5-1 Programming Data Fields ..................................................................................................................................................5-1 Time Window Definitions ...................................................................................................................................................6-2 Open/Close Schedules Definitions.....................................................................................................................................6-3 Scheduling Menu Mode .....................................................................................................................................................6-4 Time Windows ...................................................................................................................................................................6-6 Daily Open/Close Schedules .............................................................................................................................................6-7 Holiday Schedules .............................................................................................................................................................6-8 Time-Driven Events............................................................................................................................................................6-8 Limitation of Access Schedules .......................................................................................................................................6-11 Temporary Schedules ......................................................................................................................................................6-12

SECTION 4: Programming................................................................................................................ 4-1

SECTION 5: Data Field Descriptions ............................................................................................... 5-1 SECTION 6: Scheduling Options ..................................................................................................... 6-1

iii

Table of Contents
User Scheduling Menu Mode ...........................................................................................................................................6-14

SECTION 7: Downloading Primer .................................................................................................... 7-1
General Information ...........................................................................................................................................................7-1 Getting On-Line with a Control Panel.................................................................................................................................7-2 Direct-Wire Downloading ...................................................................................................................................................7-3 Telco Handoff.....................................................................................................................................................................7-3 General Information ...........................................................................................................................................................8-1 Setting the Time and Date .................................................................................................................................................8-1

SECTION 8: Setting the Real-Time Clock........................................................................................ 8-1 SECTION 9: User Access Codes...................................................................................................... 9-1
General Information ...........................................................................................................................................................9-1 User Codes & Levels of Authority ......................................................................................................................................9-1 Multiple Partition Access ....................................................................................................................................................9-2 Adding a Master, Manager, or Operator Code ...................................................................................................................9-3 Changing a Master, Manager, or Operator Code...............................................................................................................9-4 Adding an RF Key to an Existing User ...............................................................................................................................9-4 Deleting a Master, Manager, or Operator Code .................................................................................................................9-4 Exiting the User Edit Mode.................................................................................................................................................9-4 Battery Test......................................................................................................................................................................10-1 Dialer Test........................................................................................................................................................................10-1 Burglary Walk-Test (Code + [5] TEST) ............................................................................................................................10-1 Armed Burglary System Test ...........................................................................................................................................10-1 Testing Wireless Transmitters .........................................................................................................................................10-2 Trouble Conditions ...........................................................................................................................................................10-3 To the Installer .................................................................................................................................................................10-3

SECTION 10: Testing the System .................................................................................................. 10-1

APPENDIX A: Regulatory Agency Statements................................................................................A-1
UL Installation Requirements ............................................................................................................................................ A-1 UL609 Local Mercantile Premises/Local Mercantile Safe & Vault .................................................................................... A-1 UL365 Police Station Connected Burglar Alarm ............................................................................................................... A-1 UL611/UL1610 Central Station Burglary Alarm ................................................................................................................ A-1 California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup Requirements ........................................ A-2

APPENDIX B: Summary of System Commands..............................................................................B-1 APPENDIX C: Specifications............................................................................................................C-1 APPENDIX D: Contact ID Event Codes............................................................................................D-1 Index ...........................................................................................................................................Index-1 THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY
TABLE OF CONTACT ID EVENT CODES........................................................................................................................ D-1

iv

List of Figures
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Figure 3-1: Installing the Lock ...............................................................................................................................................3-1 Figure 3-2: Cabinet Attack Resistance Considerations ..........................................................................................................3-2 Figure 3-3: Mounting the PC Board .......................................................................................................................................3-2 Figure 3-4: Keypad Connections to Control Panel .................................................................................................................3-3 Figure 3-5: Using a Supplementary Power Supply................................................................................................................3-4 Figure 3-6: Wiring Polarized Fire Devices..............................................................................................................................3-5 Figure 3-7: Wiring Nonpolarized Burglary Devices ...............................................................................................................3-5 Figure 3-8: Telephone Line Connections.................................................................................................................................3-7 Figure 3-9: Wiring Connections for Zones 1-9 ........................................................................................................................3-7 Figure 3-10: 2-Wire Smoke Detector on Zone 1 ......................................................................................................................3-8 Figure 3-11: 4-Wire Smoke Detectors......................................................................................................................................3-9 Figure 3-12: Wiring Latching Glassbreaks to Zone 8 .............................................................................................................3-9 Figure 3-13: Polling Loop Connections to the VISTA-50P/VISTA-50PUL ........................................................................3-11 Figure 3-14: Polling Loop Connections Using One 4297 Extender Module ........................................................................3-12 Figure 3-15: Polling Loop Connections Using Multiple Extender Modules ........................................................................3-12 Figure 3-16: RF Receiver (cover removed) ............................................................................................................................3-14 Figure 3-17: 4204 Relay Module...........................................................................................................................................3-17 Figure 3-18: Remote Keyswitch Wiring ................................................................................................................................3-18 Figure 3-19: Remote Keypad Sounder Wiring......................................................................................................................3-19 Figure 3-20: 4100SM Using a Serial Printer ........................................................................................................................3-20 Figure 3-21: VIP Module Connections..................................................................................................................................3-22 Figure 3-22: UVS Connections to the Control Panel ............................................................................................................3-23 Figure 3-23: 1361 Transformer and Battery Connections ...................................................................................................3-24 Figure 3-24: 1361X10 Transformer Connections .................................................................................................................3-25 Figure 7-1: Direct-Wire Downloading Connections................................................................................................................7-3

v

Conventions Used in This Manual
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Before you begin using this manual, it is important that you understand the meaning of the following symbols (icons).

UL

These notes include specific information that must be followed if you are installing this system for a UL Listed application.

These notes include information that you should be aware of before continuing with the installation, and that, if not observed, could result in operational difficulties.

This symbol indicates a critical note that could seriously affect the operation of the system, or could cause damage to the system. Please read each warning carefully. This symbol also denotes warnings about physical harm to the user. ZONE PROG? 1 = YES 0 = NO 0 Many system options are programmed in an interactive mode by responding to alpha keypad display prompts. These prompts are shown in a single-line box.

/00

Additional system options are programmed via data fields, which are indicated by a “star” (/) followed by the data field number.

PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent Honeywell products.

vi

S E C T I O N

1

General Description
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

About the VISTA-50P/VISTA-50PUL
The VISTA-50P/VISTA-50PUL is an 8-partition, UL Listed control panel with the following features: • • • Supports hardwired, polling loop, and wireless zones Supervision of bells and RF receivers Scheduling capabilities (allows certain operations to be automated)

Features
Hardwire and Optional Expansion Zones
• • • • • Provides 9 hardwire zones. Supports up to 16 2-wire smoke detectors on zone 1. Triggers the built-in sounders on other hardwired smoke detectors if one smoke detector annunciates an alarm. This feature requires a 4204 Relay Module. Supports up to 50 2-wire latching glassbreak detectors on zone 8. Supports up to 77 additional expansion zones using a built-in polling (multiplex) loop. Supports up to 86 wireless zones (fewer if using hardwire and/or polling loop zones). Provides three keypad panic keys: 1 + / (A), / + # (B), and 3 + # (C).


Peripherals Devices
• • • Supports up to 16 addressable devices, (keypads, RF receivers, relay modules, etc.). Provides 16 outputs using 4204 and X-10 devices. The system can activate outputs in response to system events (alarm condition), at a specific time of day, and manually using the #70 Relay Command Mode. Supports the 4286 VIP Module, which allows access to the system from either a remote location or on the premises

UL

The VIP Module is not Listed for use with the VISTA-50P/VISTA-50PUL Control Panel in a UL installation.

Supports the 4146 Keyswitch on any one of the system's 8 partitions.

Arming/Disarming and Bypassing
• • Provides global arming capability (ability to arm all partitions the user code has access to in one command). Supports Exit Error Logic, whereby the system can tell the difference between a regular alarm and an alarm caused by leaving an entry/exit door open. If the system is not subsequently disarmed, faulted E/E zone(s) and/or interior zones are bypassed and the system arms. Supports Recent Close report, which is designed to notify the central station that an alarm has occurred within 2 minutes after the exit delay has expired. Can control 8 separate areas independently, each functioning as if it had its own separate control. Provides a Common Lobby partition, which can be programmed to arm automatically when the last partition is armed, and to disarm when the first partition is disarmed. Provides a Master partition (9), used for the purpose of viewing the status of all partitions at the same time.

Partitioning
• • •

1-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide Scheduling
• • • Can automate system functions, such as arming, disarming, and activation of outputs (e.g., lights). Provides access schedules (for limiting system access to users by time). Provides an End User Output Programming Mode, allowing the user to control outputs.

Access Control
• Provides the capability to trigger a relay for 2 seconds by entering the user code + 0 at a keypad.

System Communication
• Supports ADEMCO Contact ID; ADEMCO High Speed; ADEMCO Express; and 3+1, 4+1, and 4+2 ADEMCO and Sescoa/Radionics Low-Speed formats.

The system is shipped defaulted for Contact ID communication. It is the only format capable of uniquely reporting all 86 zones, as well as openings and closings for all 75 users. This requires central stations to be equipped with the MX8000 receiver or equivalent to fully support all new VISTA-50P/VISTA-50PUL report codes. If you need to update your MX8000 receiver, contact your distributor • Provides an Audio Alarm Verification (AAV) option that permits voice dialog between an operator at the central station and a person at the premises. Supports upload and download capability of program and user information.

Downloading

Event Log
• • • Provides an event log (history log) that can store up to 224 events. Can print the event log on a serial printer using the 4100SM. Can view the event log on an alpha keypad.

Additional Features
• • • • • Provides up to 20 installer-defined, custom words that can be used for zone descriptors. Provides a keypad macro command (macro is a series of keypad commands of up to 16 keystrokes) using the D key by partition. Provides cross-zone capability, which helps prevent false alarms by preventing a zone from going into alarm unless its cross-zone is also faulted within a 5-minute period. Contains a built-in User’s Manual, which provides the end user with a brief explanation of the function of a key when the user presses any of the function keys on the keypad for 5 seconds. Provides trigger outputs, which may interface with Communicator equipment or other devices such as keyswitch LEDs, printer, or pager. At least one 2-line alpha keypad (6160) must be connected to the system for programming (if you are using keypad programming), and must remain connected to the system in order to allow the primary user to program additional user codes into the system at a later time.

1-2

S E C T I O N

2

Partitioning
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Theory of Partitioning
This system provides the ability to arm and disarm up to 8 different areas, as if each had its own control. These areas are called partitions. A Partitioned system allows the user to disarm certain areas while leaving other areas armed, or to limit access to certain areas to specific individuals. Each system user can be assigned to operate any or all partitions, and can be given a different authority level in each. Before anything can be assigned to those partitions, you must first determine how many partitions (1-8) are required. Following are some facts you need to know about partitioning.

Users
Each user may be given access to one or more partitions. If a user is to operate more than one partition and would like to arm/disarm all or some of those partitions with a single command, the user must be enabled for Global Arming for those partitions (when entering user codes). A user with access to more than one partition (multiple access) can "log on" to one partition from another partition's keypad, provided that program field 2*18: Enable GOTO is enabled for each partition he/she wants to log on to from another. A partition can be selected as a "common lobby" partition, and other partitions can affect this partition by causing arming/disarming of this partition to be automated (see “Common Lobby Logic” later in this section).

Keypads
Each keypad must be given a unique "address" and be assigned to one partition. It can also be assigned to Partition 9 if Master keypad operation is desired. (See “Master Keypad Setup and Operation” later in this section.)

Zones
Each zone must be assigned to one partition. The zones assigned to a partition will be displayed on that partition's keypad(s).

Setting-Up a Partitioned System
The basic steps to setting up a partitioned system are described below. If you need more information on how to program the options, see SECTION 4: Programming. 1. 2. 3. Determine how many partitions the system will consist of (programmed in field 2*00). Assign keypads to partitions (Device Programming in the #93 Menu Mode). Assign zones to partitions (Zone Programming in the #93 Menu Mode). 4. 5. 6. Confirm zones are displayed at the keypad(s) assigned to those partitions. Assign users to partitions. Enable the GOTO feature (program field 2*18) for each partition a multiple-access user can log on to (alpha keypad only). Program partition-specific fields (see the Data Field Descriptions section).

7.

Common Lobby Logic
When an installation consists of a partition shared by users of other partitions in a building, that shared partition may be assigned as the "common lobby" partition for the system (program field 1*17). An example of this might be in a medical building where there are two doctors’ offices and a common entrance area (see example that follows explanation). The Common Lobby feature employs logic for automatic arming and disarming of the common lobby. Two programming fields determine the way the common lobby will react relative to the status of other partitions. They are: 1*18 Affects Lobby and 1*19 Arms Lobby.

2-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide
1*18 Affects Lobby (must be programmed by partition) Setting this field to 1 for a specific partition causes that partition to affect the operation of the common lobby as follows: a. b. When the first partition that affects the lobby is disarmed, the lobby is automatically disarmed. The common lobby cannot be armed unless every partition selected to affect the lobby is armed. User #1 has access to Office #1 and the Common Lobby. User #2 has access to Office #2 and the Common Lobby. Office #1 is set up to affect the Common Lobby, but not arm it. Office #2 is set up to affect and arm the Common Lobby. NOTE: In the tables below, the notations in parentheses ( ) indicate the current status of the other partition when the user takes action. Sequence #1:
Office 1 User #1: User #2: User #1: User #2: Disarms (Disarmed) Arms (Armed) Office 2 (Armed) Disarms (Disarmed) Arms Lobby Action Disarms No Change No change Arms

1*19 Arms Lobby (must be programmed by partition) Setting this field to 1 for a specific partition causes that partition to affect the operation of the common lobby as follows: a. b. The common lobby cannot be armed unless every partition selected to affect the lobby is armed. Arming a partition causes the system to automatically attempt to arm the lobby. If any faults exist in the lobby partition, or if another partition that affects the lobby is disarmed, the lobby cannot be armed, and the message "UNABLE TO ARM LOBBY PARTITION" is displayed. You cannot select a partition to "arm" the lobby unless it has first been selected to "affect" the lobby. Do not enable field 1*19 without enabling field 1*18. The following chart sums up how the common lobby partition will operate.
1*18 Affects Lobby 0 1 1 0 1*19 Arms Lobby 0 0 1 1 Disarms when partition disarms? NO YES YES Attempts to arm when partition arms? NO NO YES Can be armed if other partitions disarmed? YES NO NO

Sequence #2:
Office 1 User #2: User #1: User #2: User #1: (Armed) Disarms (Disarmed) Arms Office 2 Disarms (Disarmed) Arms (Armed) Lobby Action Disarms (No change) No Change No Change

Notice that in sequence #1, because Office #2 was the last to arm, the lobby also armed (Office #2 is programmed to affect and arm the lobby). In sequence #2, the lobby could not arm when Office #2 armed, because Office #1, which affects the lobby, was still disarmed. When Office #1 armed, the lobby still did not arm because Office #1 was not programmed to arm the lobby. User #1 would have to arm the lobby manually. Therefore, you would want to program a partition to affect and arm the lobby if the users of that partition are expected to be the last to leave the building. How User Access Codes Affect the Common Lobby Codes with Global Arming If a code is given "global arming" when it is defined (see SECTION 9: User Access Codes), the keypad prompts the user to select the partitions they want to arm. Only the partitions the user has access to are displayed. This allows the user to choose the partitions to be armed or disarmed, and so eliminates the "automatic" operation of the lobby. Keep in mind, however, that if a user attempts to arm all, and another "affecting" partition is disarmed, the user cannot arm the lobby, and the message "UNABLE TO ARM LOBBY PARTITION" is displayed. Codes with Non-Global Arming If a user arms with a non-global code, the lobby partition operation is automatic, as described by fields 1*18 and 1*19.

---ENTRY NOT ALLOWED---

Example Here is an example of how the lobby would react in a typical setup.

OFFICE 1

OFFICE 2

COMMON LOBBY

MAIN ENTRANCE

V128BP-001-V0

2-2

Section 3 - Installing the Control
Other Methods of Arming/Disarming Common Lobby logic remains active when arming or disarming a partition that affects and/or arms the common lobby in one of the following manners: • • • • Quick-Arm Keyswitch Wireless Button Wireless Keypad Auto-Arming/Disarming If scheduling is used to automatically arm and/or disarm partitions, the common lobby partition does not automatically follow another partition that is programmed to arm or disarm the lobby. The lobby must be included as a partition to be armed/disarmed and must be scheduled as the last partition armed. If you are using auto-arming, make sure that the Auto-Arm Delay and Auto-Arm Warning periods, for the lobby partition, (fields 2*05 and 2*06) combined are longer than that of any other partition that affects the lobby. This causes the lobby to arm last.

Arming/Disarming Remotely The lobby does not automatically arm or disarm if a user arms or disarms remotely, via Compass downloading software. The lobby must be armed separately, after arming all affecting partitions first.

Master Keypad Setup and Operation
Although this system has eight actual partitions, it provides an extra partition strictly for the purpose of assigning keypads as Master keypads for the system. Assigning any keypad to Partition 9 in Device Programming in the #93 Menu Mode makes that keypad a Master keypad. A Master keypad reflects the status of the entire system (Partitions 1-8) on its display at one time. This is useful because it eliminates the need for a building security officer to have to log on to various partitions from one partition's keypad to find out where an alarm has occurred. The following is a typical display: SYSTEM 12345678 STATUS RRNNA /B Possible status indications include:
A = Armed Away I = Armed Instant S = Armed Stay R = Ready M = Armed Maximum N = Not Ready

Pressing [/] causes the following display to appear at Partition 1's keypad(s): FAULT 002 LOADING DOCK WINDOW Additional zone faults are displayed one at a time. To display a new partition's status, press [/] + Partition No. The Armed LED on a Master keypad is lit only if all partitions have been armed successfully. The Ready LED is lit only if all partitions are "ready to arm." Neither LED is lit if only some partitions are armed and/or only some partitions are ready. Press [/] + [0] or [/] + [9] to return to the master partition. Otherwise, if no keys are pressed for 2 minutes, the system automatically returns to the master partition The sounder on a Master keypad reflects the sound of the most critical condition on all of the partitions. The priority of the sounds, from most to least critical, is as follows: 1. 2. 3. Pulsing fire alarm sounds Steady burglar alarm sounds Trouble sounds (rapid beeping)

B = Bypassed/Ready / = Alarm/Trouble

To obtain more information regarding a particular partition, enter [/] + Partition No. (e.g., [/] + [4]). This allows viewing only of that partition. In order to affect that partition, the user must use a code that has access to that partition. Also, in order for a user of any partition to log on to Partition 9 to view the status of all partitions, that user must have access to all partitions. Otherwise, access is denied. The following is displayed for a fault condition on Zone 2 (Loading Dock Window) on Partition 1 (Warehouse) when a user logs on from a keypad on Partition 9: WHSE DISARMED HIT / FOR FAULTS

Silence the sounder by pressing any key on the Master keypad or a keypad on the partition where the condition exists. A Master keypad uses the same panics as Partition 1. Master keypad panics are sent to Partition 1, and will activate on Partition 1. Therefore, panics must be programmed for Partition 1.

2-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide

2-4

S E C T I O N

3

Installing the Control
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.

Mounting the Control Cabinet
To mount the control cabinet, perform the following steps: Step 1 Action Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using. DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED. 2 Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose. To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2 Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require ATTACK RESISTANCE, use the COM-UL Commercial Enclosure.

UL

Installing the Cabinet Lock
1. 2. 3. Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until it is held securely by its snap tabs.
PUSH ON LOCK UNTIL IT IS SEATED SECURELY

Use a Part Number K4445 Lock (supplied).
CHECK POSITION
LOCKED PUSH
ADEMCO ADEMCO

SNAP TAB

UNLOCKED

CABINET DOOR BOTTOM

STEP 1

STEP 2

Figure 3-1: Installing the Lock

Mercantile Premises Listing Guidelines
• • • The panel door must be supervised. Mount the clip-on tamper switch (supplied) to the cabinet's right side wall as shown in the diagram below, and wire it to one of the hardwire zones. Use a bell with a tamper-protected housing such as the AB12M. The bell housing's tamper switch and inner tamper linings must also be wired to the hardwire zone. Assign the tampers’ hardwire zone to a burglary partition. Program the hardwire zone for day trouble/night alarm (zone type 5) when only one burglary partition is used. Program it for 24-hr. audible alarm (zone type 7) when more than one burglary partition is used. All wiring between the bell and panel must be run in conduit. Remaining wires do not need to be run in conduit. All wiring that is not run in conduit must exit from the knockout openings on the bottom or back of the cabinet.

• •

cab_lock_snap-001-V0

SNAP TAB

3-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide
• • All unused knockouts must be plugged using the disc plugs and carriage bolts (supplied), as indicated in the diagram below. Fasten the cabinet door to the cabinet backbox using the 18 one-inch-long Phillips-head screws (supplied) after all wiring, programming, and checkout procedures have been completed.
RUN BELL WIRES IN CONDUIT PLUG THIS KNOCKOUT CLIP-ON DOOR TAMPER SWITCH PC BOARD PLUG THIS KNOCKOUT CABINET MOUNTING HOLE (4 PLACES) PLUG THIS KNOCKOUT

TO PLUG AN UNUSED KNOCKOUT OPENING, REMOVE KNOCKOUT AND INSTALL A PAIR OF DISC PLUGS AND A CARRIAGE BOLT AS SHOWN. DISC PLUGS (DIMPLES IN DISC PLUG SHOULD REGISTER INSIDE KNOCKOUT OPENING) CARRIAGE BOLT HEX NUT AND WASHER CABINET SIDE WALL (OUTSIDE)

KNOCKOUT OPENING

PLUG THIS KNOCKOUT

RUN ALL REMAINING WIRE THROUGH HERE

cabattack-001-V1

Figure 3-2: Cabinet Attack Resistance Considerations

Mercantile Safe and Vault Listing Guidelines
• • • Follow the guidelines given above for Mercantile Premises listing. Mount a shock sensor such as Sentrol No. 5402 to the control's backbox. Follow the manufacturer's instructions for proper sensor mounting. This sensor also must be wired to a hardwire zone. For safe and vault applications, a UL Listed contact must be used inside the cabinet through one of the knockouts for pry-off tamper purposes. This sensor also must be wired to a hardwire zone.

Installing the Control's Circuit Board
To install the circuit board in the cabinet, perform the following steps: Step 1 Action Hang the three mounting clips on the raised cabinet tabs. Refer to Figure 3-3 (Detail B). Make sure the clip orientation is exactly as shown in the diagram to avoid damage. This will also avoid problems with insertion and removal of the PC board. 2 3 Insert the top of the circuit board into the slots at the top of the cabinet. Make certain that the board rests in the slots as indicated (Detail A). Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws. Make certain that the mounting screws are tight. This ensures that there is a good ground connection between the PC board and the cabinet. Dress field wiring away from the microprocessor (center) section of the PC board. Use the loops on the left and right sidewalls of the cabinet for anchoring field wiring using tie wraps (Detail C). These steps are important to minimize the risk of panel RF interference with television reception.
DETAIL A SIDE VIEW OF BOARD INSERTED INTO SLOTS DETAIL C SIDE VIEW OF SLOTS
+ + +

Notes:
• •

DETAIL B SIDE VIEW OF SHORT MOUNTING CLIPS (TYP.)
hi_end_mnt-PCB

Figure 3-3: Mounting the PC Board

3-2

Section 3 - Installing the Control

Installing the Keypads

Up to 16 addressable keypads (addresses 00-30) may be used (you may need to use an auxiliary power supply if the 750mA aux. output is exceeded). The 2-line alpha display, 6160may be used.

• •

The length of all wire runs combined, regardless of the wire gauge, must not exceed 2000 feet when unshielded quad conductor cable is used (1000 feet if unshielded cable is run in conduit, which acts a shield, or if shielded cable is used). If more than one keypad is wired to one run, then the above maximum lengths must be divided by the number of keypads on the run (e.g., the maximum length is 225 feet if two keypads are wired on a #22 gauge run).

To wire the keypads, perform the following steps: Step 1 Action Determine wire gauge by referring to the Wire Run Length/Gauge table below. Wire Run Length/Gauge Table Wire Gauge Length #22 gauge 450 feet #20 gauge 700 feet #18 gauge 1100 feet #16 gauge 1750 feet Wire keypads to a single wire run or connect individual keypads to separate wire runs. The maximum wire run length from the control to a keypad, which is homerun back to the control must not exceed the lengths listed in the table. Run field wiring from the control to the keypads (using standard 4-conductor cable of the wire gauge determined in step 1). Connect the keypad(s) to terminals 6, 7, 8, and 9 on the control board, as shown in Figure 3-4.
RED BLACK GREEN YELLOW KEYPADS

2

3 4

6 7 8 9

CONTROL TERMINALS

Figure 3-4: Keypad Connections to Control Panel Addressing the Keypads The keypads will not operate until they are physically addressed and enabled in the system's Device Programming in the #93 Menu Mode. Set each keypad for an individual address (00-30) according to the keypad's instructions. Set an alpha keypad for address 00 and other keypads for higher addresses Each keypad must be set for a different address. • Do not set any keypads to address 31 (nonaddressable mode). They will interfere with other keypads (as well as other devices) connected to the keypad terminals. • If an “OC” or “OPEN CIRCUIT” message is present on a keypad, data from the control is not reaching the keypad. Please check your wiring.

3-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Supplementary Power Supply for Additional Keypads When the control’s auxiliary power load for all devices exceeds 750mA, you can power additional keypads from a regulated 12VDC power supply (e.g., AD12612 (1.2A)). Use a UL Listed, battery-backed supply for UL installations. Connect the additional keypads as shown in Figure 3-5, using the keypad wire colors shown. Be sure to observe the current ratings for the power supply used. • Make connections directly to the screw terminals as shown in Figure 3-5. Make no connection to the keypad blue wire (if present). • Be sure to connect the negative (–) terminal on the power supply unit to terminal 7 (–) on the control.
SUPPLEMENTARY POWER SUPPLY + CONTROL TERMINAL STRIP
AUX. AUX. DATA DATA IN OUT + – 6 7 8 9

YELLOW WIRE

YELLOW WIRE

GREEN WIRE

GREEN WIRE

BLACK WIRE

BLACK WIRE

RED WIRE

RED WIRE

IMPORTANT: MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN.

TO SECONDARY KEYPAD

TO MAIN KEYPAD

Figure 3-5: Using a Supplementary Power Supply

Installing External Sounders
The VISTA-50P/VISTA-50PUL provides a bell circuit output for operating fire and burglary alarm notification appliances. The alarm output is rated as follows: 10VDC – 14VDC, 1.7A max, power-limited.

UL

• •

For Household Fire and combination Household Fire/Burglary installations, the total current drawn from the auxiliary power, polling loop, and alarm output combined must not exceed 750mA. For Household Burglary installations, the total current drawn from the alarm output must not exceed 1.7A. A battery must be installed, as it supplies the current for the combined auxiliary power, polling loop, and alarm output in excess of 750mA.

The output has the following options: • • • • Selectable for supervision. Selectable for confirmation of arming ding. Selectable to chime when entry/exit or perimeter zones are faulted. Selectable for no timeout or timeout of 2-30 minutes.

UL

Burglary bell circuits must be programmed for a timeout of 16 minutes or longer.

UL985 Household Fire or Combination Household Fire/Burglary Installations For installations that must provide UL Listed protection, the total combined current drawn from the alarm output, auxiliary power output, and polling loop must not exceed 750mA in order to comply with the battery independence requirements. UL1023 Household Burglary Installations For Household Burglary installations, the total current drawn from the alarm output must not exceed 1.7A. A battery must be installed, as the battery supplies current from the combined auxiliary power, polling loop, and alarm output in excess of 750mA.

3-4

pwr_supply-002-V0

Section 3 - Installing the Control
Non-UL Installations For non-UL installations, the total current drawn from this output can be up to 1.7A. A battery must be installed, as the battery supplies current in excess of 750mA. Up to two 719 sirens can be used wired in parallel.

UL

This control complies with National Fire Protection Association (NFPA) requirements for temporal pulse sounding of fire notification appliances.

Alarm Output Supervision When supervision is enabled, the VISTA-50P/VISTA-50PUL monitors the alarm output wiring for open and short circuit faults while the output is inactive. The system provides a trouble indication (Zone 98) when an open occurs; or when a short occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth ground. The VISTA-50P/VISTA-50PUL indicates the trouble condition regardless of whether the system is armed or disarmed. The zone displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1. The Contact ID event code is 321, Bell Trouble. The trouble is cleared from the display by entering the user code + OFF. Wiring the Alarm Output The wiring of the alarm output depends upon whether you are going to supervise the output or not. Use the appropriate procedure below for your application.

UL

Use only UL Listed sounding devices for UL installations.

Compatible Alarm Indicating Devices
Model Number 719 747 AB12M System Sensor HR System Sensor P2R, P4R Wheelock AS-121575W Device Type Compact Outdoor Siren (not UL Listed) Indoor Siren Bell Horn 12/24V Fire Horn/Strobe 12/24V (2-wire/4-wire) Fire Horn/Strobe Polarizing Diode Yes Yes Yes No No No

1

2

3

+

4

5

-

6

7

8

ALARM SOUNDER OUTPUT: 1-VDC - 13.8VDC 1.7A MAXIMUM

+
BELL

-

HORN

Figure 3-6: Wiring Polarized Fire Devices
POLARIZING DIODES (MUST MOUNT AT INDICATING DEVICE)

PANEL BELL

fire_devices-001-V0

BELL

BELL

HORN

TO OTHER DEVICES

PANEL BELL NONPOLARIZED BURGLARY INDICATING DEVICES POLARIZED FIRE INDICATING DEVICE
non_polar_devices

Figure 3-7: Wiring Nonpolarized Burglary Devices

3-5

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Supervising the Alarm Output To wire the alarm output using the supervision feature, perform the following steps: Step 1 2 3 Action Wire polarized fire-indicating devices to the alarm output as shown in Figure 3-6. Wire nonpolarized burglary indicating devices to the alarm output using a polarizing diode (two 2A diodes supplied), as shown in Figure 3-7. Program Zone 98 with a response type of 05 (trouble by day/alarm by night).

The minimum load on the alarm output must exceed 5mA at 12V for proper supervision operation. Using a Siren Driver To install a siren driver, perform the following steps: Step 1 2 3 4 Action Mount the siren driver in the panel’s cabinet. Wire the siren driver to the control and to the speaker(s). (See the driver’s instructions.) Cut the blue jumper on the upper left-hand corner of the panel’s PC board. Program Zone 98 with no response type (00). If a device such as a siren driver with a high-resistance trigger input (drawing less than 5mA) is used in a UL Household Fire installation, the siren driver must independently supervise siren speaker wiring.

UL

Disabling the Supervision of the Alarm Output To install the alarm output and disable the supervision feature, perform the following steps: Step 1 2 3 Action Wire the devices to terminals 4 and 5, observing polarity if necessary. Cut the blue jumper on the upper left-hand corner of the panel’s PC board. Program Zone 98 with no response type (00).

Telephone Line Connections
Connect the main dialer output to telephone company lines using the RJ31X cables supplied.

UL

The telephone line inputs have overvoltage protection in accordance with UL1459, as specified in UL985/UL1023.

The system is shipped defaulted for Contact ID format. It is the only format capable of uniquely reporting all 86 zones, as well as openings and closings for all 75 users. This requires central stations to be equipped with the MX8000 receiver or equivalent. If you need to update your MX8000 receiver, contact your distributor. To prevent the risk of shock, disconnect phone lines at the telco jack before servicing. If the communicator is connected to a PABX, be sure it has a backup power supply that can support the PABX for 24 hours (central station) or 60 hours (remote station). Many PABXs are not power-backed up, and this can result in a communication failure if power is lost. Reporting Formats The system supports the following formats: ADEMCO Low Speed 3+1; 4+1; 4+2; Sescoa/Radionics 3+1; 4+1; 4+2; ADEMCO 4+2 Express; ADEMCO High Speed; ADEMCO Contact ID

3-6

Section 3 - Installing the Control
Handset 26 27 Incoming Telco Line 28 29

30 EARTH GROUND

TERMINALS ON CONTROL
GREEN (TIP) RED (RING) BROWN (TIP) GREY (RING)

GROUND

DIRECT CONNECT CORD

TIP RING
TIP RJ31X RING JACK

Figure 3-8: Telephone Line Connections

Wiring Burglary, Panic, and Smoke Detector Devices to Zones 1-9
The maximum zone resistance is 100 ohms for zones 1 and 8, and 300 ohms for all other zones (excluding the 2K EOL resistor). To wire burglary and panic devices to zones 1-9, connect sensors/contacts to the hardwire zone terminals (10 through 23). See Figure 3-9. Connect N.C. and N.O. devices as follows: • • Connect N.C. devices in series with the high (+) side of the loop. The 2K EOL resistor must be connected in series with the devices, following the last device. Connect N.O. devices in parallel (across) the loop. The 2K EOL resistor must be connected across the loop wires at the last device.
Red Jumper
ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9

{ {
10 11
ZONE 1

INCOMING TELCO LINE

PREMISES PHONES

PLUG

12

13

14

15

16

17

18

19

20

21

22

23

(Also supports NO/NC Burg contacts)

+
N.C.

-

+
N.C.

+
N.C.

-

+
N.C.

2-WIRE SMOKE DETECTOR LOOP

N.O.

N.O.

N.O.

N.O.

2k EOLR

2k EOLR

2k EOLR

2k EOLR

+

-

Fire Usage

+
N.C.

-

+
N.C.

+

LATCHING TYPE GLASS BREAK DETECTORS

-

Programmable Response (Fast/Normal) Loop

+

GLASS BREAK

SMOKE

N.C.
N.O. N.O. N.O.

N.C.

N.C.

Burg. Usage
N.O. 2k EOLR
hw_zones-001-V0

N.C.

2k EOLR

2k EOLR

2k EOLR

Zone resistance (Excluding EOLR): ZONE 1,8: 100 OHMS MAXIMUM ALL OTHER ZONES: 300 OHMS MAXIMUM

Zone response time: ZONES 1-8: 350mSec-500mSec ZONE 9: Programmable for Fast: 10mSec-15mSec Normal: 350mSec-500mSec (default response)

Figure 3-9: Wiring Connections for Zones 1-9

3-7

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Using 2-Wire Smoke Detectors on Zone 1 Zone 1 can support up to 16 2-wire smoke detectors. The alarm current on zone 1 supports only one smoke detector in the alarmed state. Compatible 2-Wire Smoke Detectors
DETECTOR TYPE 2-Wire Photoelectric Smoke Detector 2-Wire Photoelectric Smoke Detector w/Heat Detector 2-Wire Photoelectric Low Profile Smoke Detector DEVICE MODEL # System Sensor 2W-B System Sensor 2WT-B System Sensor 2151 w/B401 Base

UL

These smoke detectors are UL Listed for use with the VISTA-50P/VISTA-50PUL and are the only 2-wire smoke detectors that may be used.

Wiring 2-Wire Smoke Detectors to Zone 1 2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the last detector. To wire 2-wire smoke detectors to zone 1, perform the following steps: Step 1 2 3 Action Select up to 16 2-wire smoke detectors from the list of compatible detectors. Connect 2-wire smoke detectors across zone 1 terminals (10 and 11) as shown in Figure 3-10. Observe proper polarity when connecting the detectors. Connect the EOL resistor at the last detector in the loop across the zone 1 terminals. The EOL resistor must be connected across the loop wires at the last detector.

(+)
SMOKE 2k EOLR ZONE 1

10
2-WIRE SMOKE DETECTOR

(+)

(-)

11

(-)

Figure 3-10: 2-Wire Smoke Detector on Zone 1 Using 4-Wire Smoke Detectors on Zones 1-8 You may use as many 4-wire smoke detectors as can be powered from the panel's Auxiliary Power output without exceeding the output's rating (750mA). Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be momentarily interrupted using a 4204 Relay Module. Compatible 4-Wire Smoke Detectors Use any UL Listed 4-wire smoke detector that is rated for 10-14VDC operation and that has alarm reset time not exceeding 6 seconds. Some compatible 4-wire smoke detectors are listed below.
DETECTOR TYPE 4-Wire Photoelectric Smoke Detector 4-Wire Photoelectric Smoke Detector w/Heat Detector 4-Wire Photoelectric Smoke Detector w/Sounder & Heat Detector 4-Wire Photoelectric Smoke Detector w/Aux. Relay & Heat Detector 4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Heat Detector 4-Wire Photoelectric Smoke Detector w/Aux. Relay, Sounder & Isolated Heat Detector MANUFACTURER System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor MODEL # 4W-B 4WT-B 4WTA-B 4WTR-B 4WTAR-B 4WITAR-B

3-8

Section 3 - Installing the Control
Wiring 4-Wire Smoke Detectors

UL
Step 1 2 3

Power to 4-wire smoke detectors must be supervised with an EOL device (use a System Sensor EOLR-1 EOL relay module connected as shown in Figure 3-11).

To wire 4-wire smoke detectors to zones 1-8, perform the following steps: Action Select 4-wire smoke detectors (see list of compatible detectors shown previously in this section). Connect detectors (including heat detectors, if used) across terminals of the zone selected. All detectors must be wired in parallel. See Figure 3-11. Connect the EOLR at the last detector in the loop across the zone’s terminals. You must connect the EOLR across the loop wires at the last detector.

TO AUXILIARY POWER TERMINALS

+ + NO CONNECTION

+ 4-WIRE SMOKE DETECTORS EOL POWER SUPERVISION RELAY MODULE EOLR-1 SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST.

NOTES: · PROGRAM THE RELAY TO TRANSFER ON FIRE ZONE RESET (ACTIVATION CODE 54). SEE 4204 RELAY MODULE SECTION FOR DETAILS. · SECOND CODE AND OFF ENTERED AT CONSOLE MOMENTARILY INTERRUPTS DETECTOR POWER.

+

C

NC

NO

RESET HEAT DETECTOR + TO FIRE ZONE TERMINALS

RELAY 1, 2, 3, OR 4 4204 RELAY MODULE

2k EOLR

V128BP-002-V1

Figure 3-11: 4-Wire Smoke Detectors Using 2-Wire Latching Glassbreaks on Zone 8 Zone 8 can support 2-wire glassbreak detectors. The zone provides enough standby current to power up to 50 2-wire glassbreak detectors meeting the requirements listed below. Compatible Glassbreak Detectors Use detectors that meet the following ratings:
Standby Voltage: Standby Resistance: Alarm Resistance: Alarm Current: Reset Time: 5VDC–13.8VDC Greater than 20k ohms (equivalent resistance of all detectors in parallel) Less than 1.1k ohms (see note below) 2mA–10mA Less than 6 seconds

NOTES: • You can use detectors that exceed 1.1k ohms in alarm, provided they maintain a voltage drop of less than 3.8 volts in alarm. • The ASC-SS1 detector has been tested and found to be compatible with these ratings.
GLASSBREAK DETECTOR 2000 OHMS EOLR ZONE 8

21

(+)

LATCHING TYPE GLASS BREAK DETECTOR LOOP

22

(-)

Figure 3-12: Wiring Latching Glassbreaks to Zone 8

3-9

VISTA-50P/VISTA-50PUL Installation and Setup Guide
• • The alarm current provided by zone 8 supports only one glassbreak detector in the alarmed state. Do not use other N.O. or N.C. contacts when using glassbreak detectors on zone 8. Other contacts may prevent proper glassbreak detector operation.

To wire 2-wire latching glassbreak detectors to zone 8, perform the following steps: Step 1 2 3 Action Select compatible 2-wire glassbreak detectors that meet the requirements stated previously. Connect detectors across zone 8 (terminals 21 and 22). See Figure 3-12. Connect the EOL resistor at the last detector in the loop across the zone’s terminals. You must connect the EOL resistor across the loop wires at the last detector.

Installing V-PLEX Devices
The polling loop provides both power and data to the V-PLEX devices, and is constantly monitoring the status of all zones enabled on the loop. The maximum current draw of all devices on the polling loop cannot total more than 64mA (unless the system uses a 4297 Polling Loop Extender Module). Devices that can be programmed via either DIP switches or the built-in unique serial number must be set for the serial number mode operation. All devices on the polling loop must be wired in parallel to the [+] and [-] polling loop terminals of the control panel (24 and 25). You can wire from device to device, or have multiple branches connected directly to the control panel in a star configuration. Compatible Polling Loop Devices
Model Number 4297 5193SD 5193SDT 4208U 4939SN-BR, 4939SN-GY 4191SN-WH 4959SN 4209U 4193SN 4293SN 4190SN IS2500SN DT7500SN Type Extender Module Photoelectric Smoke Detector Devices Photoelectric Smoke Detector w/Heat Detector Universal 8-Zone Expander Serial Number Surface-Mount Reed Contacts Serial Number Recessed Reed Contact Aluminum Overhead Door Contact Universal Group Zoning Module Serialized 2-Zone Expander Serialized 1-Zone Expander Serialized 2-Zone Expander V-Plex Dual Tech V-Plex Dual Tech PIR

UL

• • •

The 4208U must be mounted either inside the control panel’s cabinet or in a separate enclosure that has a tamper-supervised cover. The 4190SN right loop must not be used, and the left loop must be EOLR-supervised. The 4297 must be powered from the control panel’s Auxiliary Power Output or from a UL Listed supplementary power supply.

• •

For new polling loop installations, always use twisted pair wiring. In many cases, existing non-twisted pair wiring may be used, but it is more susceptible to interference from other sources, and may be problematic in installations with long wire runs or in high noise environments. Always locate polling loop wiring at least six inches (15cm) of AC power, telephone, or intercom wiring. The polling loop carries data between the control panel and the devices; interference on this loop can cause an interruption of communication. The polling loop can also cause outgoing interference on the intercom or phone lines. If this spacing cannot be achieved, shielded wire must be used. (Note that the maximum total wire length supported is cut in half when shielded wire is used.)

3-10

Section 3 - Installing the Control
• • No more than 64mA may be drawn on any individual wire run. When a star configuration is used, the total length of all wire runs combined cannot exceed 4000 ft (2000 ft. if you are using unshielded wire in conduit or shielded wire).

IMPORTANT NOTE: If the installation exceeds or deviates from these parameters, refer to the application note on the Honeywell website for additional information. To access the application note: 1. Go to the honeywell.com/security website 2. Click the Honeywell Security & Communications link. 3. Click the Commercial link. 4. Click the Documentation link. 5. Click the V-Plex Application Note. To install polling loop devices, perform the following steps: Step 1 2 3 4 Action Select devices from the list of compatible devices shown previously. Set the DIP switches in the device (if required). Refer to the device’s instructions for the DIP Switch Tables. Mount each device in the desired location. Refer to the device’s instructions. Run wires from the control panel to each device on the polling loop (see Figure 3-13). No individual wire run may exceed the lengths shown in the following table.
Maximum Polling Loop Wire Runs Wire Gauge Max. Length #22 gauge 650 feet #20 gauge 950 feet #18 gauge 1500 feet #16 gauge 2400 feet

5

Wire each device to the polling loop, making sure of the correct polarity (refer to the device’s instructions). NOTE: If you are using serial number devices, and intend to enroll each device through the keypad automatically, wire no more than 25 of these devices to the control at a time. Then power up and program them before connecting the next 25. Leave previously enrolled devices connected. If you intend to manually enter the serial numbers through the keypad or through Compass downloading software, all the devices may be connected before powering up to program.

21

22

23

24
POLLING LOOP

25

POLLING LOOP RATING: 64mA MAXIMUM

+

-

4190SN

TO RIGHT LOOP

5193SD SMOKE

IS2500SN

poll_loop-001-V4

Figure 3-13: Polling Loop Connections to the VISTA-50P/VISTA-50PUL Polling Loop Supervision A short on the polling loop is indicated by a trouble on zone 97 and reports as a trouble condition only. If annunciation is desired, program the zone as type 05. If a device on the polling loop fails (the panel cannot "see" that device), the system displays a trouble condition for all zones on that device. If the panel is armed when a device fails, and the zone is a burglary zone, the will go into alarm

3-11

VISTA-50P/VISTA-50PUL Installation and Setup Guide
A trouble on zone 97 prevents a partition from being armed, unless all polling loop zones on that partition are bypassed.

Using the 4297 Polling Loop Extender The 4297 Polling Loop Extender may be used to provide additional polling loop current, to extend the polling loop wire run length, and/or to provide individual electrically isolated polling loops. Refer to Figures 3-14 and 3-15, to follow. DO NOT use the 4197 Polling Loop Extender module with the VISTA-50P/VISTA-50PUL.

Be sure to include the total current drawn on the polling loop when figuring the total auxiliary load on the panel’s power supply.

INPUT POLLING LOOP CONTROL PANEL
V-PLEX V-PLEX

EXTENSION POLLING LOOP

4297

V-PLEX

V-PLEX

TO OTHER V-PLEX DEVICES

INPUT LOOP LIMITS: • 64 mA MAX. LIMIT CURRENT TO 64mA ON ANY INDIVIDUAL WIRE RUN. • NO MORE THAN 64 DEVICES MAY BE USED. • NO INDIVIDUAL WIRE RUN CAN EXCEED:
GAUGE #22 #20 #18 #16 LENGTH 650 FT 950 FT 1500 FT 2400 FT

EXTENSION POLLING LOOP LIMITS = SAME AS INPUT LOOP

COMBINED INPUT AND EXTENSION LOOP LIMITS: • NO MORE THAN 77 DEVICES COMBINED. • TOTAL LENGTH OF ALL WIRE RUNS ON BOTH LOOPS COMBINED CANNOT EXCEED 6400 FT. 3200 FT. IF USING UNSHIELDED WIRE IN CONDUIT, OR IF USING SHIELDED WIRE

• TOTAL LENGTH OF ALL WIRE RUNS COMBINED CANNOT EXCEED 4000FT. (2000FT. IF USING SHIELDED WIRE)

polling_loop_003-V6

Figure 3-14: Polling Loop Connections Using One 4297 Extender Module
EXTENSION POLLING LOOP #1
• DO NOT CONNECT 4297 MODULES IN SERIES (i.e., DO NOT CONNECT ONE MODULE'S EXTENSION LOOP TO ANOTHER MODULE'S INPUT LOOP.)

4297

V-PLEX

CONTROL PANEL

INPUT POLLING LOOP EXTENSION POLLING LOOP #2

4297
COMBINED INPUT AND EXTENSION LOOP LIMITS: • NO MORE THAN 77 DEVICES COMBINED ON THE INPUT LOOP AND EXTENSION LOOP #1. NO MORE THAN 77 DEVICES COMBINED ON THE INPUT LOOP AND EXTENSION LOOP #2. • TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT LOOP AND EXTENSION LOOP #1 COMBINED CANNOT EXCEED 6400 FT. (3200 FT. IF USING UNSHIELDED WIRE IN CONDUIT, OR SHIELDED WIRE). TOTAL LENGTH OF ALL WIRE RUNS ON THE INPUT LOOP AND EXTENSION LOOP #2 COMBINED CANNOT EXCEED 6400 FT. (3200 FT. IF USING UNSHIELDED WIRE IN CONDUIT, OR SHIELDED WIRE).

polling_loop-004-V3

Figure 3-15: Polling Loop Connections Using Multiple Extender Modules NOTE: The input loop limits stated in Figure 3-14 apply to Figure 3-15 as well.

Wireless Zone Expansion
The following table lists the receivers that may be used and the number of zones they support.
5800 Series Receivers Receiver 5881ENL 5881ENM 5881ENH Zones up to 8 up to 16 up to 86

3-12

Section 3 - Installing the Control
RF System Operation and Supervision The 5800 RF system operation has the following characteristics: • The receiver responds to a frequency of 345MHz. • • • The receiver has a nominal range of 200 feet. Supervised transmitters send a supervisory signal every 70-90 minutes. Zones 88 and 90 are used to supervise the RF reception of receivers 2 and 1, respectively. The reception is supervised for two conditions: 1. 2. The receiver goes “deaf” (doesn’t hear from any transmitter) within a programmed interval of time (defined by program field 1*30). Proper RF reception is impeded (i.e., jamming or other RF interference). The control checks for this condition every 45 seconds. A response type (05 Day/Night) must be programmed for zones 90 (1st receiver) and 88 (2nd receiver) for UL installations.

UL

The control checks the receiver connections about every 45 seconds. The receiver supervisory zone is 91 (1st receiver) and 89 (2nd receiver) NOTE: The zone must be programmed with a response type (e.g., type 05 Day/Night Trouble) before the system supervises the connection to the receiver. Use two identical receivers to provide either a greater area of coverage or redundant protection. They must be set for different addresses. Any zone from 1 to 86 can be used as a 5800 Series wireless zone, with the exception of zone 64 (reserved for a wireless keypad).

• •

RF System Installation Advisories • • • Place the receiver in a high, centrally located area. Do not place it on or near metal objects. This will decrease the range and/or block transmissions. Install the RF receiver at least 10 feet from the control panel or any keypads, to avoid interference from the microprocessors in these units. If dual receivers are used: a. b. c. d. They must be at least 10 feet from each other, as well as from the control panel and remote keypads. Each receiver must be set to a different device address. The receiver set to the lower address is considered the 1st RF receiver for supervisory purposes. The House IDs must be the same.

Using two receivers does not increase the number of transmitters the system can support (85 zones using the 5881ENH, plus a wireless keypad). Installation and Setup of the RF Receivers To install the RF receiver, perform the following steps: Step 1 2 3 4 Action Mount the receiver, following the advisories stated previously. Set the DIP switches in the receiver for the address (01-07). See Figure 3-16. Make sure the address setting is not being used by another device (keypad, relay module, etc.). Connect the receiver’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other end of the harness into the receiver. Refer to the Installation Instructions provided with the receiver for installations regarding antenna mounting, etc.

3-13

VISTA-50P/VISTA-50PUL Installation and Setup Guide
ANTENNAS TO CONTROL'S REMOTE KEYPAD CONNECTION POINTS. USE MAX. of 220 ft. [67m of #22 (0.64mm) WIRE or 550 ft. (168m) of #18 (1mm) WIRE FOR EACH RUN. OBSERVE 20 ft. MAX. FOR COMMERCIAL FIRE INSTALLATIONS. (SEE RECEIVER'S INSTRUCTIONS.) YELLOW RED BLACK GREEN

CIRCUIT BOARD MOUNTING HOLES

INSERT IN RIGHT-HAND TERMINALS

DIP SWITCH WHITE AREAS = SWITCH HANDLES. POSITION 2-4 DETERMINE RECEIVER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS FOR ADDRESS TO USE. DIP SWITCH BELOW SHOWN SET FOR ADDRESS "0."
SWITCH RECEIVER ADDRESS SETTINGS POSITION (" - " MEANS OFF) 0 5 4 ON ON ON ON ON ON ON ON ON ON ON ON FOR FUTURE USE 1 2 3 4 5 6 7

WIRING OPENING

DIP SWITCH

INTERFERENCE INDICATOR LED

PLUG & SOCKET

3 2 1

ON: SETS 5881EH FOR USE IN COMMERCIAL FIRE APPLICATIONS (SEE THE RECEIVER'S INSTRUCTIONS)*. OFF: USE IN NON-COMMERCIAL FIRE INSTALLATIONS. * FOR COMMERCIAL FIRE APPLICATIONS THE PC BOARD MUST BE MOUNTED IN A SEPARATE CABINET (SEE RECEIVER'S INSTRUCTIONS FOR DETAILS).

5881-001-V4

Figure 3-16: RF Receiver (cover removed) Installing the 5800TM Module Installation of this module is necessary only if you are using a 5827 or 5804BD Bi-directional device. The address for the 5800TM must be enabled in the control’s Device Programming in the #93 Menu Mode as a keypad and then assigned to a partition. To install the 5800TM, perform the following steps: Step 1 Action Mount the unit using its accompanying mounting bracket near the RF receiver. The 5800TM must not be installed within the control cabinet. It must be between 1 and 2 feet from the receiver’s antennas. 2 Set the module for the appropriate address. For Address Setting 28 cut the red jumper; for Address 29 cut the white jumper; for Address 30 cut both jumpers. Make sure the address setting is not being used by another device (keypad, relay module, etc.). 3 Connect the module’s wire harness to the keypad terminals (6, 7, 8, and 9). Plug the connector at the other end of the harness into the module.

House ID Sniffer Mode This mode applies only if you are using a wireless keypad (e.g., 5827) or bi-directional devices (e.g., 5804BD). Use the House ID Sniffer mode to make sure you do not choose a House ID that is in use in a nearby system. The House ID must be programmed for the receiver in Device Programming in the #93 Menu Mode. To enter House ID Sniffer mode, enter your Installer Code + [#] + [2]. The receiver now “sniffs” out any House IDs in the area and displays them. Keep the receiver in this mode for about 2 hours. Use a House ID that is not displayed. Exit the Sniffer mode by entering your Installer Code + OFF. As Sniffer mode effectively disables RF point reception, Sniffer mode cannot be entered while any partition is armed.

3-14

Section 3 - Installing the Control
5800 Series Transmitter Setup 5800 Series transmitters have the following characteristics: • Transmitters have built-in serial numbers that must be enrolled in the system using the #93 Menu Mode Programming, or input to the control via the downloader. • Transmitters do not have DIP switches (except 5827, described separately). • Some transmitters, such as the 5816 and 5817, can support more than one “zone” (referred to as loops or inputs). Each loop must be assigned a different zone number. • For button-type transmitters (wireless keys), such as the 5804 and 5804BD, you must assign a unique zone number to each individual button used on the transmitter. Transmitter Input Types All transmitters have one or more unique factory-assigned input (loop) codes. Transmitters can be programmed as one of the following types:
Type RF (Supervised RF) UR (Unsupervised RF) BR (Unsupervised Button RF) Description Sends periodic check-in signals, as well as fault, restore, and low-battery signals. The transmitter must remain within the receiver’s range. Sends all the signals that the RF type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises. These send only fault signals. They do not send low-battery signals until they are activated. The transmitter may be carried off-premises.

Transmitter Supervision Supervised RF transmitters send a check-in signal to the receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised transmitter within a programmed period (field 1∗31), the “missing” transmitter number(s) and “CHECK” or “TRBL” are displayed. Unsupervised RF transmitters (5802MN, 5804) may be carried off the premises. Some transmitters have built-in tamper protection, and annunciate a “CHECK” or “TRBL” condition if covers are removed. If a loss of supervision occurs on a transmitter programmed for Fire, it reports in Contact ID as a Fire Trouble (373), not Loss of Supervision (381), to the central station. Transmitter Battery Life Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation. The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system. Button-type transmitters (e.g., 5801, 5802, 5802CP and 5804) should be periodically tested, as these transmitters do not send supervisory check-in signals. To test the transmitters using the Transmitter ID Sniffer mode and the Go/NoGo Test Mode, see SECTION 10: Testing the System for the procedures.

3-15

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Compatible 5800 Series Transmitters
Model 5801 5802 5802CP 5802MN 5802MN2 5804 5804BD 5804BDV 5806/5807/ 5808 5816 5817 5818 5827 5827BD 5853 5890 5890PI Product Panic Transmitter Pendant (Personal Emergency Transmitter) Belt Clip (Personal Emergency Transmitter) Miniature (Personal Emergency Transmitter) Miniature (Personal Emergency Transmitter) Wireless Key Transmitter Wireless Key Bi-directional Transmitter Wireless Key Bi-directional Transmitter with Voice Wireless Photoelectric Smoke Detectors Door/Window Transmitter Multi-Point Universal Transmitter Recessed Transmitter Wireless Keypad Wireless Bi-directional Keypad Glassbreak Detector PIR Detector PIR Detector with Pet Immunity Input Type UR or RF BR Only UR or RF UR or RF BR Only BR Only BR Only RF RF RF RF House ID House ID RF RF RF

Installing Output Devices
The VISTA-50P/VISTA-50PUL support up to 16 outputs. Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). The 4204, and/or X-10 devices may be used as output devices. Installing the 4204 Relay Modules Each 4204 module provides 4 relays with Form C (normally open and normally closed) contacts. The relay module will not operate until the device address you have set the DIP switches for is enabled in the control’s Device Programming in the #93 Menu Mode. To install the relay modules, see Figure 3-17 and perform the following steps: Step 1 2 3 Action Set the 4204’s DIP switches for a device address 01-15. Do not use an address being used by another device (keypads, RF receivers, etc.). Mount the 4204 Module per the instructions provided with them. Connect the module’s wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of harness) to the module. If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire run lengths.
Wire Gauge #22 #20 #18 #16 Maximum Length 125 feet 200 feet 300 feet 500 feet

3-16

Section 3 - Installing the Control
SWITCH NUMBER 4204 ADDRESS SETTINGS ("—" means "OFF") 0
ON ON ON ON

©

OFF

ON

1
— ON ON ON

2
ON — ON ON

3
— — ON ON

4
ON ON — ON

5
— ON — ON

6
ON — — ON

7
— — — ON

8
ON ON ON —

9
— ON ON —

10
ON — ON —

11
— — ON —

12
ON ON — —

13
— ON — —

14
ON — — —

15
— — — —

SWITCH SHOWN FOR ADDRESS "0"

DIP SWITCH FOR SETTING DEVICE ADDRESS AND ENABLING/DISABLING TAMPER

COVER TAMPER (REED) SWITCH TB1 13 14 15 16 YEL BLK GRN RED

Installing X10 Devices X-10 devices are either plugged into standard AC outlets or wired into the AC electrical system by a licensed electrician, depending on the type of device used. Note each device’s House and Unit Code setup, as these codes will be used to program the devices in Output Programming in #93 Menu Mode described in the Programming Guide. X-10 devices require the use of a 1361X10 transformer in place of the regular 1361 transformer. X-10 devices respond to “on” and “off” commands sent from the panel through the 1361X10 transformer. To connect the 1361X10 transformer, see Connecting the Transformer, later in this section.

Installing a Remote Keyswitch
A UL-Listed remote keyswitch, such as the 4146, can be used for remote arming/disarming of the burglary portion of the system and for silencing alarms. The keyswitch can operate in only one particular partition. The keyswitch is wired across zone 7. This zone is no longer available as a protection zone. Be sure to program Zone 7 with a response type (e.g., type 10). Operation • • • A momentary short across zone 7 arms the partition in the AWAY mode, and a short held for more than 1/2 second arms the partition in STAY mode 1. A subsequent short disarms the partition. The keyswitch LEDs indicate the partition’s status (see table below). A momentary short across Zone 7 silences alarm bell and keypad sounds, and disarms the system if it was armed. A subsequent short across Zone 7 clears the alarm memory indication and resets 2-wire smoke and glassbreak detectors (if used). LED Indications
Green On Off Off Off Off Red Off Off On Steady Slow Flash Rapid Flash Indication Disarmed & Ready Disarmed & Not Ready Armed Away Armed Stay Alarm Memory

© © © © ©

1 2 3 4 5

NOT USED

1 2 3 4 5

EITHER OR BOTH CAN BE USED

4204

TB2 RELAY TYPICAL (SHOWN "OFF") RELAY

4

12 11 10 9 8 7 6 5 4 3 2 1

C NC NO C NC NO C NC NO C NC NO

3 2 1

RELAY 4-PIN CONSOLE PLUG

RELAY

DATA IN FROM CONTROL (–) GROUND DATA OUT TO CONTROL (+) 12V
4204-01-V1

Figure 3-17: 4204 Relay Module

3-17

VISTA-50P/VISTA-50PUL Installation and Setup Guide
The keyswitch reports as user 0, if Open/Close reporting is enabled in field .40.

Keyswitch Tamper Operation The tamper switch need not be used for fire or UL Household Burglary installations. For UL Commercial Burglary installations, the tamper switch must be wired to a zone (zone 7 in Figure 3-18). Program that zone for Day Trouble/Night Alarm (response type 5). When the keyswitch is removed from the wall, the tamper switch opens, causing an alarm or trouble on the zone. This also causes the control to disable keyswitch operation until the tamper is restored and the associated partition is disarmed. Wiring for the Remote Keyswitch To install the 4146 keyswitch, perform the following steps: Step 1 2 Action Connect the 4146 to the panel as shown in Figure 3-18. If you are using the tamper, make sure it is connected to a zone.
TO AUX POWER (TERMINAL 6) YELLOW RED (ARMED) 820 ohms RED TO J7 / OUT 2 TO J7 / OUT 4 ZONE WHITE GREEN (READY) 820 ohms BLACK

+

2K ELOR TAMPER SWITCH (CONTACTS CLOSE WHEN SWITCH DEPRESSED).

ZONE LOCK SWITCH (NORMALLY OPEN) 2K ELOR

TO ZONE 7 (+) (TERMINAL 20)

J7_keyswitch

Figure 3-18: Remote Keyswitch Wiring

Remote Keypad Sounder
An optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds produced by the keypad's built-in sounder. The panel will remote all sounds (e.g., alarm, trouble, chime, entry/exit, etc.) produced by the keypad's built-in sounder except for the short beeps associated with keypad key depression. One application of this feature might be to produce chime sounds at a distant location from the panel's keypads.

Remote Keypad Sounder Setup
To setup for a remote keypad sounder, connect the piezo sounder to the panel’s positive auxiliary power output and to Output 1 on the J7 connector as shown in Figure 3-19. Program field 1.46 Auxiliary Output Enable with a [2].

3-18

Section 3 - Installing the Control
J7 CONNECTOR
IF USED. 1. OUT 1 IS NO LONGER USABLE FOR SMOKE DETECTOR RESET OR GROUND START (SEE FIELD 1*46). 2. OUT 2, 3, 4 CAN STILL BE USED TO PROVIDE ALARM STATUS INDICATIONS OR TO OPERATE A KEYSWITCH (SEE FIELD *15).

4142TR CABLE
N/U

1

GRAY (GROUND)

2

YELLOW (OUT 1)

3

BLACK – AMSECO PAL-328N PIEZO SOUNDER +

WHITE (GROUND)

4

RED (OUT 2)

5

GREEN (GROUND)

6

BROWN (OUT 3)

7

TO AUX POWER + TERMINAL 6 10mA CURRENT DRAIN)

RED

BLUE (GROUND)

8

BLACK (OUT 4)

J7_trigcon-001-V0

Figure 3-19: Remote Keypad Sounder Wiring

9

Communicators Connected to the J7 Triggers
These triggers may be used to trip auxiliary alarm signaling equipment such as the 7845i-ent and GSMHS Communicators. The triggers are common to all partitions and must be enabled for each partition (field 2.20). The fire and burglary/audible panic alarm triggers are normally LOW and go HIGH until a User Code + OFF is entered in all enabled partition(s) that display these conditions. The silent panic/duress trigger latches HIGH, except for duress, which is momentary. Refer to the installation instructions that accompany your radio for the connections to the control panel.

Installing a 4100SM
The 4100SM is used to print event log reports to a serial printer. NOTE: See SECTION 4: Programming for the programming details when using the 4100SM. Serial Printer Configurations Configure the serial printer as follows: • 8 data bits, no parity, 1 stop bit • 300 or 1200 baud Connecting the 4100SM to a Serial Printer To connect a serial printer using the 4100SM, refer to Figure 3-20 and perform the following steps: Step 1 2 3 4 5 Action Connect terminal 1 on the 4100SM to the Violet wire on the 4142TR cable. Connect terminal 6 on the 4100SM to the Brown wire on the 4142TR cable. Connect the 4142TR cable to J8 on the control. Connect terminals 8 and 7 of the 4100SM to terminals 6 and 7 (aux. power (+) and (-)), respectively of the control. Connect the UL EDP Listed serial printer to the 4100SM Interface Module. The 4100SM Module is supplied with a 10-foot RS232 cable. A longer cable can be used if the VISTA50P/VISTA-50PUL is separated from the serial printer by more than 10 feet, but the total cable length should be less than 50 feet.

3-19

VISTA-50P/VISTA-50PUL Installation and Setup Guide
1 2 3
YELLOW

4
NU

5

6

7

8

9

J8 CONNECTOR

GR OU ND

PR IN

GREEN OU T6 BROWN GR OU ND BLUE GR OU ND BLACK

VIOLET

GREY

IN 2 TE RD

TR

OU T5

IN 3

RED

4142TR CABLE (SUPPLIED WITH 4100SM) To TB6 Aux. Power (+) (25mA current draw) To TB7 Aux. Power (-) 4100SM SERIAL MODULE
8 7 6 5 4 3 2 1

+ PWR - (GND) RXD not used not used TXD not used DTR RED BLUE WHITE

USE GENDER CHANGER SUPPLIED WITH 4100SM IF PRINTER HAS DB25 MALE CONNECTOR 4100SM JUMPERS (CUT TO SET RESPECTIVE SIGNAL FLOATING)

3M Cable Supplied with 4100SM

RED BLUE WHITE

CD CTS DSR

8 5 6

Figure 3-20: 4100SM Using a Serial Printer NOTE: See the 4100SM Installation Instructions for details concerning the serial printer operation.

Installing the 4286 VIP Module
The 4286 VIP Module is an add-on accessory that permits the user to access the security system (and relays) via a TouchTone telephone. This may be done either from the premises or by calling the premises from a remote location. Only one VIP Module can be used in a security system. This module must be enabled as Device Address 4 in the Device Programming in #93 Menu Mode, and must be assigned to a partition.

UL

The 4286 VIP Module is not permitted in UL installations.

Detailed operating instructions for phone access to the security system are provided with the VIP Module.

The 4286 VIP Module features: • Allows the user to receive synthesized voice messages over the phone regarding the status of the security system. • • • • Allows the user to arm and disarm the security system and perform most other commands using the telephone keypad. Allows the user to control relays using the telephone keypad. Provides voice annunciation over the phone to confirm any command that is entered. Announces many of the same words that would normally be displayed on an alpha keypad under the same system conditions. Refer to the words in bold on the Alpha Vocabulary list found in the #93 Menu Mode in the Programming Guide. Can be supervised for connection to control panel (annunciated and reported as Zone 87).

The 4286 is wired between the control panel and the premises’ handset(s) (see Figure 3-21). It listens for TouchTones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones. During off-premises phone access, it seizes the line from the premises phones and any answering machines. • The VIP module will not operate until the device address (04) is enabled in the control’s Device Programming in #93 Menu Mode. • Do not mount the VIP Module on the cabinet door or attempt to attach it to the PC board.

3-20

4100SM-011-V0

COLOR

FUNCTION

PIN #

SERIAL PRINTER SET FOR: 8 DATA BITS EVEN PARITY STOP BIT 300/1200 BAUD

Section 3 - Installing the Control
To install the VIP module, perform the following steps: Step 1 Action Mount the module in the control cabinet if space is available or, if this is not possible, on the side of the cabinet or adjacent to it. If you mount the VIP Module inside the control cabinet, attach it to the cabinet’s interior surface with 2-faced adhesive tape. You may leave the module’s cover off if it is mounted within the cabinet. If you mount the module outside the cabinet, use the screw holes at the rear to mount horizontally or vertically (2-faced adhesive tape may be used, if preferred). 2 3 4 Affix the 4286 connections label (supplied separately) to the inside of the VIP Module’s cover, if the cover is used. Otherwise, affix the label to the inside of the control cabinet’s door. Make 12V (+) and (–) and data-in and data-out connections from the VIP Module to the control, using the connector cable supplied with the VIP Module. These are the same connections as for remote keypads. Connect the module to the phone line as shown below. See Figure 3-21.
4286 Terminal 1. Phone In (Tip) 2. Phone In (Ring) 3. Phone Out (Tip) 4. Phone Out (Ring) 5. No Connection 6. Audio Out 1∗ 7. Audio Out 1∗ Speaker Speaker Connects to direct connect cord: green wire red wire brown wire gray wire

∗Supported by the 4286 only

Use an RJ31X Jack with the phone cable supplied with the control to make connections to the VIP module. Make connections exactly as shown in Figure 3-12. This is essential, even if the system is not connected to a central station. The 4286 will not function if this is not done. • If touch-tones are not present following phone access to the security system via an on-premises phone, try reversing the pair of wires connected to terminals 3 and 4 on the 4286. • If the phone plug is disconnected from the control, the premise’s phones will not operate.

3-21

VISTA-50P/VISTA-50PUL Installation and Setup Guide
SPEAKER NOTE: IF CONNECTING SINGLE SPEAKER, USE 8-ohm SPEAKER ONLY. IF CONNECTING 2 SPEAKERS, USE 4-ohm or 8-ohm SPEAKERS AND CONNECT IN SERIES.
1 2 3 4 5 6 7

INCOMING TELCO LINE
RING TIP

4286 VIP MODULE
NOTE: 4286 DEVICE ADDRESS IS FACTORY SET TO “4” SPEAKER VOLUME CONTROL
NO CONNECTION

SEE SPEAKER NOTE GREY BROWN
GREEN RED

TIP RJ31X JACK RING

KEYED HEADER TO CONTROL PANEL KEYPAD CONNECTIONS YELLOW NO CONNECTION RED BLACK GREEN

CALLER ID UNIT
EARTH GROUND

PREMISES ANSWERING MACHINE AND PHONES
ANSWERING MACHINE

YELLOW

GREEN

4500 THERMOSTAT

TIP RING TIP RING HANDSET INCOMING TELCO LINE

IMPORTANT NOTE FOR EXISTING INSTALLATIONS: EXISTING WIRES CONNECTED TO THE “HANDSET” TERMINALS ON CONTROL MUST BE MOVED FROM THERE TO TERMINALS 3 AND 4 ON THE 4286. U.S. PATENT No. 4791658

THIS DEVICE COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION No. AC3USA-74659-KX-N RINGER EQUIVALENCE: 1.0B FOR COMPLETE INFORMATION, SEE INSTALLATION INSTRUCTIONS N6431-3 ACCOMPANYING 4286 VIP MODULE
4286_wiring-002-V1

Figure 3-21: VIP Module Connections

Installing the Audio Alarm Verification Module
• • Contact ID code for “Listen-in to Follow” is 606. Contact ID is the only reporting format that will send a “Listen-in to Follow.” If you are also using a 4286 VIP Module, be sure to follow Figure 3-22 when making connections.

The UVS consists of a UVCM and at least one UVST. The UVCM board has a DC power jack and a 34-position terminal block for making connections to a DC power source, UVSTs, telephone lines, music source, or to the 4286 VIP Module; and to a control panel’s voice trigger and bell outputs (if required). Refer Figure 3-22 for wiring connections. For a detailed explanation of the wiring connections and the functions of the DC power jack and terminal block positions, refer to the installation instructions that accompany the UVS. If the phone plug is disconnected from the control, the premise’s phones will not operate. NOTES: • • • When the AAV indicates that the audio alarm verification session is completed, all keypad sounds are restored. Sirens are restored if the alarm timeout period has not expired. As part of its fail-safe software, the control limits all audio alarm verification sessions to 15 minutes. This is because once the session begins, the AAV Module controls the duration. If a new Fire alarm should occur during a session, the control breaks the phone connection and sends the new Fire Alarm report, then re-triggers the AAV Mode. All other dialer messages triggered during ongoing conversation are held until either the AAV Module signals that it is inactive, or the 15-minute timeout occurs.

3-22

Section 3 - Installing the Control

UVCM AND UVST SUMMARY OF CONNECTIONS
Refer to UVS Installation and Setup Guide K4214 for complete information
SW 1 2 3 4 5 6 7 8 SWITCH BANK 1 UVST 1 AUX AUDIO, ON = ENABLED UVST 2 AUX AUDIO, ON = ENABLED UVST 3 AUX AUDIO, ON = ENABLED UVST 4 AUX AUDIO, ON = ENABLED UVST 5 AUX AUDIO, ON = ENABLED UVST 6, ON = OUTSIDE, OFF = INSIDE UVST 7, ON = OUTSIDE, OFF = INSIDE VOICE TRIGGER, ON = IMMED, OFF = CALLBACK SW 1 2 3 4 5 6 7 8 SWITCH BANK 2 FUTURE USE, SET TO ON FUTURE USE, SET TO ON TELEPHONE RING, ON = ENABLED END USER VOICE, ON = DISABLED FUTURE USE, SET TO ON CS CODE LEARN, ON = DISABLED USER CODE LEARN, ON = DISABLED FUTURE USE, SET TO ON NOTE 1: CONNECT TO PROPER EARTH GROUND. NOTE 2: POWER MAY ALSO BE SUPPLIED BY A LISTED CLASS 2 POWER SUPPLY RATED 12VDC, MIN 600mA CONNECTED TO THE UVCM +12VDC IN AND GND TERMINALS.

NOTE 3: SOME CONTROL PANELS USE BUILT-IN TRIGGER AND SOME USE 4204 RELAY MODULE. REFER TO AAV SECTION OF CONTROL PANEL INSTALLATION AND SETUP GUIDE FOR CONNECTION. NOTE 4: EITHER MUSIC SOURCE OR 4286 VIP MODULE CAN BE USED BUT NOT AT THE SAME TIME.
NOTE 5: DO NOT CONNECT IF 4286 VIP MODULE IS USED.

SHIPPED WITH ALL SWITCHES IN "ON" POSITION.
ON ON

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

ALARM TRIG IN

EARTH GND

NOT USED

NOT USED

+12VDC IN

ALTERNATE +12 VDC IN FOR PLUG-IN WALL PACK (SEE NOTE 2)

AUXILIARY AUD ENABLE

SWITCH BANK 1

SWITCH BANK 2

FALLING VOICE TRIG

OUTSIDE UVST PWR

RISING VOICE TRIG

VOICE RELAY POLE

INSIDE UVST PWR

INSIDE UVST PWR

AUXILIARY AUD IN

VOICE RELAY NC

SPKR 1

SPKR 2

SPKR 3

SPKR 4

SPKR 5

SPKR 6

SPKR 7

MIC 1

MIC 2

MIC 3

MIC 4

MIC 5

MIC 6

MIC 7

RING

GND

GND

GND

GND

TIP

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

AUXILIARY AUDIO LEVEL ADJUSTMENT TRIM POT

NOTE 1

MUSIC SOURCE
(OPTIONAL; NOTE 5)

OPTIONAL (NOTE 4)

AUDIO OUT GND

SELECT APPROPRIATE INPUT

(NOTE 2)

(NOTE 2)

CONTROL PANEL
AUX PWR (12VDC) 2-WAY VOICE TRIGGER (SEE NOTE 3) BELL OUTPUT GND RED GREEN

PLUG

RJ31X JACK
RING TIP

TIP RING

INCOMING TELCO LINES

DIRECT CONNECT CORD

INCOMING RING INCOMING TIP HANDSET RING HANDSET TIP

UVST PWR

SPKR

GND

MIC

VOLUME CONTROL DIAL

SPEAKER VOLUME TRIM POT

SPEAKER VOLUME CONTROL

OPTIONAL (NOTE 4)

P3 KEYED HEADER P1

1 2 3 4 5 6 7

UVST
1 2 3 4
TYPICAL 1 OF 7

4286 VIP MODULE
1234

P7 ANSWERING MACHINE

P2

FOR COMPLETE INFORMATION, SEE 4286 VIP MODULE INSTRUCTIONS.

THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

WARNING: TO PREVENT RISK OF ELECTRICAL SHOCK, DISCONNECT TELCO JACK BEFORE SERVICING THIS PANEL.

Figure 3-22: UVS Connections to the Control Panel

3-23

UVCM_UVST-SOC-V1

COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION NO. AC3 USA-40133-SP-T RINGER EQUIVALENCE: 1.0B

BROWN

GRAY

PREMISES ANSWERING MACHINE AND PHONE (S)

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Connecting the Transformer
This product uses the 1361 transformer (1361CN in Canada). If you are using X-10 devices, the 1361X10 transformer interface must be used instead of the regular 1361 transformer. The 1361X10 supplies the control panel with AC, and also sends control pulses through the premises electrical system to control the X-10 devices.

UL

Use 1361CN Transformer in Canadian installations.

Power Limiting Outputs
All outputs are power-limited as per UL985/UL1023. The following table shows the maximum current that may be drawn from each output. Output Auxiliary Power Polling Loop Alarm Output Maximum Current Draw 750mA 64mA 1.7A

For Household Fire or Combination Household Fire/Burglary Installation: The total current drawn from the auxiliary power, the polling loop, and the alarm output combined must not exceed 750mA to comply with the battery independence requirements in UL985. For Household Burglary-Only Installations: The total current drawn from the alarm output may be up to 1.7A. A battery must be installed to supply the current of the combined auxiliary power, polling loop, and alarm output in excess of 750mA. Failure to observe the polling loop current rating will cause polling loop malfunction. Failure to observe the auxiliary power current rating will result in a battery that does not charge properly or possibly a tripped circuit breaker. To connect the transformer to the control, perform the following steps: Step 1 2 3 Action Connect all installed devices to the control. Wire the 1361 Transformer (1361CN in Canada) to the panel (before connecting the battery) as shown in Figure 3-23, or wire the 1361X10 Transformer as shown in Figure 3-24 (if using X-10 devices). Plug the transformer into a 24-hour, uninterrupted, 120VAC, 60Hz outlet. After a few seconds, the keypad display appears.
BATTERY TABS

NOTE: WHEN POWERING UP THE PANEL, PLUG THE TRANSFORMER IN BEFORE CONNECTING THE BATTERY.

Figure 3-23: 1361 Transformer and Battery Connections

3-24

pwr_bat_conn-001-V1

TRANSFORMER 16.5VAC, 40VA ADEMCO No.1361 or 1361X10, if X-10 DEVICES WILL BE USED.

NO CONNECTION

PRIMARY POWER Supplied by a transformer which is rated at 16.5VAC, 40VA. Caution must be taken when wiring this transformer to the panel to guard against blowing the fuse inside the transformer (non-replaceable).

Connect to 12VDC, 4AH or 12VDC, 7AH GEL CELL BATTERY CHARGING VOLTAGE 13.7VDC

RED (+)

1

2

3

Connect to 24hr. source of AC mains

BLK (-)

Section 3 - Installing the Control
X10 TRANSFORMER/INTERFACE 1 2 3 4 5 6 7 8 9 J8 CONNECTOR

YELLOW

BROWN

VIOLET

GREEN

TERMINALS ON CONTROL BOARD

BLACK

WHITE

GRAY

BLUE

RED

4142TR CABLE

1361X10-001-V0

Figure 3-24: 1361X10 Transformer Connections

Panel Earth Ground Connections
In order for the lightning transient protective devices in this product to be effective, the designated earth ground terminal (terminal 30) must be terminated in a good earth ground. Recommended wire gauge for the ground connection is #16 AWG, run no farther than 30 feet. The following are examples of good earth grounds available at most installations: • • Metal Cold Water Pipe: Use a noncorrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured. AC Power Outlet Ground: Available from 3-prong, 120VAC, power outlets only. To test the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL-Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.

The panel requires the earth ground connection for its lightning transient protection devices.

3-25

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Determining the Control’s Power Supply Load
Use the tables that follow to calculate the total current for the Auxiliary Power, the Alarm Output, and the Polling Loop. In each table, multiply each device’s standby and/or alarm current by the number of units used. 1. In Table 1, enter devices used on the polling loop. Calculate total current draw on the polling loop. Current # of Units Total Table 1: Total Polling Loop Current Draw Polling Loop Device

Polling Loop Subtotal (terminals 24 & 25 – 64mA) .
. The total current cannot exceed 64mA. If total load exceeds 64mA, then a 4297 Loop Extender Module can be used. Note that the total number of points connected to the panel cannot exceed 77.

In Table 2, enter devices used on Auxiliary Power. Calculate standby and alarm currents, then add to get Auxiliary Power current subtotal. Table 2: Auxiliary Power Current Load Total Current Device Model # Device Current X # of Units Standby Alarm

Auxiliary Power Subtotal (terminals 6 & 7 – 750mA max.)

3-26

Section 3 - Installing the Control
3. In Table 3, enter devices connected to the Alarm Output. Calculate alarm currents, then add to get the Alarm Output current subtotal. Table 3: Alarm Output Current Load Total Current Device Model # Device Current X # of Units Standby Alarm

XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX Alarm Output Subtotal (terminals 4 & 5 – 1.7A max.) 4. In Table 4, enter the total calculated subtotals of all listed outputs from Tables 1 through 3, then add to get the combined current.

Table 4: Total VISTA-50P/VISTA-50PUL Current Load Total Current Standby Polling Loop Subtotal (see Table 1) Aux. Power Subtotal (see Table 2) Alarm Output Subtotal (see Table 3) VISTA-50P/VISTA-50PUL PCB Current (Includes 2-wire smoke detector loading on zone 1) Alarm

250mA

330mA

Total Current Load

3-27

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Determining the Size of the Standby Battery
The cabinet supplied with the control panel can house batteries of up to 12V, 14AH (two 12V, 7AH batteries wired in parallel). The COM-UL Commercial Enclosure can house batteries of up to 12V, 17.2AH and that may be used with this panel. The total standby current drawn from the auxiliary power and polling loop outputs combined must be limited to 270mA when 14AH batteries are used; and to 390mA when 17.2AH batteries are used.

DO NOT use Gates batteries (sealed lead-acid type). These batteries require a different charging voltage than is supplied by the panel.

UL

Household Fire or Combination Household/Fire/Burglary installations require the use of a backup battery that is capable of providing 24 hours of standby time followed by 4 minutes of alarm time. UL1023 Household Burglaryonly installations require the use of a backup battery that is capable of providing 4 hours of standby time followed by 4 minutes of alarm time.

Use Table 5 to determine the required backup battery capacity and use Table 6 to determine the battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity. 5. Using the total calculated from Table 4, calculate the battery capacity required for the installation.

Table 5: Battery Capacity Calculation Table Capacity Standby Capacity Formula For 4-hour standby time: Total standby current X 4 hours X 1.4 contingency factor. For 24-hour standby time: Total standby current X 24 hours X 1.1 contingency factor. Alarm Capacity For 4-, 5-, or 15-minute alarm time: Total alarm curr. X 0.067 (4 min) 0.250 (15 min) Total Capacity Add standby and alarm capacities Calculated Value

3-28

Section 3 - Installing the Control
6. Use the Battery Selection Table to select the appropriate battery for the installation.

Table 6: Battery Selection Table Capacity 4AH 7AH 12AH Recommended Battery Yuasa NP4-12 Yuasa NP7-12 Yuasa NP12-12 Fits in large mercantile cabinet only. Connect two in parallel. Fits in large mercantile cabinet only. Comment

14AH 17.2AH

Yuasa NP7-12 Yuasa NPG18-12

7.

Connect the battery, referring to Figure 3-23.

The standby battery is automatically tested for 10 minutes every 4 hours, beginning 4 hours after exiting Programming mode. In addition, entry into the Test mode initiates a battery test.

3-29

VISTA-50P/VISTA-50PUL Installation and Setup Guide

3-30

S E C T I O N

4

Programming
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Program Modes
There are two programming modes for the VISTA50P/VISTA-50PUL. These are the Data Field Program Mode and the #93 Menu Mode. The Data Field Program Mode is where many system options are programmed. The #93 Menu Mode is an interactive mode that requires a 2-line alpha keypad (6160). The factory-loaded defaults (.97) enable keypad addresses 00-01 only. A keypad set to one of these addresses must be used to program the system initially. Local keypad programming can be disabled through Compass downloading software. If this is done, Program mode can only be accessed via the downloading software.

Entering and Exiting Programming Mode
Enter Programming mode using either method a or b: a. Press both the [.] and [#] keys at the same time within 30 seconds after power is applied to the control. Exit the Programming mode by either method a or b: a. Press [.] + [9] + [8]. Exiting by this method prevents the installer code from being used to reenter Programming mode. Only method “a” can be used to re-enter Programming mode. Press [.] + [9] + [9]. Exiting by this method permits the installer code to be being used to reenter Programming mode.

b.

Enter the Installer Code + [8] + [0] + [0] keys. The factory installer code can be changed once in the Program mode (field .00). NOTE: The default for the Installer Code is 4140.

b.

Data Field Programming Mode
In the Data Field Program Mode you may access any field simply by entering either [.] or [#] + the field number: • • To write or change information in a field press [.] + the field number (.03). To read the information in a field press [#] + the field number (#03). displayed along with a “100” or “200,” indicating which page of program fields is accessed. To access the next level of programming fields, perform the following steps: Step 1 2 Action Press .94. Press [/] + [XX], where XX = the last two digits of the program field, and make the desired entry.

When the entries for a field are completed, the keypad beeps three times and advances to the next field. Summary of Data Field Programming Commands
.91 .92 .93 .94 .99 .98 Select partition for programming partition-specific fields Display the software revision level of the control panel Enter Menu mode programming Go to next page of fields Go back to previous page of fields or exit Programming Mode with no installer code lockout Exit Programming Mode with Installer Code lockout

NOTES: Press .94 to move to 2nd page, (fields 1.01 - 1.76); press .99 to move back to 1st page. Press .94 to move to 3rd page (fields 2.00 - 2.21); press .99 to move back to 2nd page

Entry Errors
• • If an address is improperly entered, the keypad displays “FC.” If a program entry is improperly entered (for example, a larger number than is permitted), the keypad display will go blank.

Moving Between Programming Levels
The data fields are grouped into three levels (referred to as “pages”). The first page is accessed as soon as Programming Mode is entered. The second and third pages of data fields are indicated at the keypad by a 1 and 2, respectively, in front of the 2-digit field address. “ALT PROGRAM MODE” is

In either of the above cases, simply re-enter [.] + the correct field number and then enter the correct data.

4-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide Programming System-Wide Data Fields
Values for some programming fields are system-wide (global), and some can be different for each partition (partition-specific). The partition-specific programming fields are automatically skipped when programming the global fields. If the system has only 1 partition, the partition-specific fields are not automatically skipped. To program system-wide data fields, perform the following steps: Step 1 Action Enter Program Mode: Installer Code + 8 0 0. The following display appears: Program Mode .Fill # View – 00 2 3 If the control has not been programmed before, enter .97 to load factory defaults. Press [.] and enter the first field number to be programmed (for example, .00, Installers Code). Make the desired entry. When the field is complete, the keypad beeps three times and advances to the next field. If you do not want to change the next field, press [.] and enter the next field number to be programmed. First Page of fields (.00 - .90) To change to the next page of fields, press .94. To return to the previous page of fields, press .99. 4 Press .99 or .98 to exit Program Mode. NOTE: If the number of digits that you enter in a data field is fewer than the maximum permitted (for example, a phone number), the keypad displays the last entry and waits. To proceed, enter [.] + the next data field you wish to program. 4

Programming Partition-Specific Data Fields
To program partition-specific data fields once in Program Mode, do the following: Step 1 2 3 Action Enter Program Mode: Installer Code + 8 0 0 Press .91, which will prompt you for the partition number desired. Enter a partition-specific field number (e.g., .09) to begin programming. When the first field’s entry is completed, the next partition-specific field is automatically displayed. When all partition-specific fields are programmed, the system returns to the global programming fields (page 1 fields). Repeat this procedure for each partition in the installation.

NOTE: To return to the global program fields before finishing all fields, enter any global field number. Programming Partition-Specific Fields Press .91 to select a partition. ↓ Enter the partition to be programmed. ↓ Enter a partition-specific field number and make entry. ↓ After partition-specific fields are programmed, press .91 to select next partition. Enter any global field number to return to the global fields at any time.

#93 Menu Mode Programming
The #93 Menu Mode is an interactive mode through which much of the system’s programming is done. In this mode, there are “question and answer” prompts that can be accessed once Data Field Program Mode has been entered. These prompts require a 2-line alpha keypad (6160). After programming all system-related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu-driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.

4-2

Section 4 – Programming
Below is a list of the main menus. For details refer to the VISTA-50P/VISTA-50PUL Programming Guide.

MAIN MENU
ZONE PROG? 1 = YES 0 = NO 0

OPTIONS
For programming the following: • • • • • • Zone Number Zone Response Type Partition Number for Zone Dialer report code for zone Input Device Type for zone (whether RF, polling loop, etc.) Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.

EXPERT MODE? 1 = YES 0 = NO 0

Same as Zone Programming except: • • Done with a minimum number of keystrokes. Can program wireless keys using pre-defined templates.

ALPHA PROG? 1 = YES 0 = NO 0

For entering alpha descriptors for the following: • • • • • Zone Descriptors Installer’s Message Custom Words Partition Descriptors Relay Descriptors

DEVICE PROG? 1 = YES 0 = NO 0

For defining the following device characteristics for addressable devices, including keypads, RF receivers (5881), output relay modules (4204), and 4286 VIP Module: • • • • Device Address Device Type Keypad Options (including Partition assignment) RF House ID

RELAY PROG? 1 = YES 0 = NO RLY VOICE DESCR? 1 = YES 0 = NO CUSTOM INDEX ? 1 = YES 0 = NO 0 0 0

For defining output device functions.

For entering voice descriptors for relays to be used with the 4286 VIP Module.

For creating custom word substitutes for VIP Module annunciation.

Following is a list of commands used while in the Menu Mode:

#93 Menu Mode Programming Commands
#93 [.] [#] 0 1 00, or 000+[.] Enters Menu Mode. Serves as [ENTER] key. Press to have keypad accept entry. Backs up to previous screen. Press to answer NO. Press to answer YES. Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.

4-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Zone Number Designations
The VISTA-50P/VISTA-50PUL supports up to 86 zones of hardwire, polling loop and/or wireless protection, distributed among up to 8 partitions. The following table lists the zone numbers and the types of sensors that can be used with each, and some alternate functions of the zones.
Zone 1 5 7 8 1-9 9 1-86 10-86 95 96 99 Function 2-wire Smoke Detectors (if used) Audio Alarm Verification (if used) Keyswitch (if used) Latching-Type Glassbreak Detectors (if used) Traditional Hardwired Zones Selectable for fast response devices (if used) 5800 Series Wireless Devices Polling Loop Devices . + 1 Panic # + 3 Panic . + # Panic 92, 95 – 99 Duress and Keypad Panics 97: 98: 92: 95: 96: Zone Type 09 03 03 04 03 03 03 03 03 00 00 Zone # 88 89 90 91 92* 95 96 97 98 99 Zone Type 00 00 00 00 N/A 00 00 05 00 06 99:

Zone Index
The zones are designated as follows: ZONE # RANGE
01 – 86 87, 88, 89, 90, 91, 97 & 98

ZONE FUNCTION
Protection zones System Supervisory Zones

ACTUAL ZONE
As indicated 87: 88: 89: 90: 91: VIP Module Supervision 2nd Wireless Receiver – not receiving signals 2nd Wireless Receiver – not talking to control 1st Wireless Receiver – not receiving signals 1st Wireless Receiver – not talking to control Polling Loop (short circuit) Bell Supervision Duress 1 + . panic (A key) 3 + # panic (C key) . + # panic (B key)

Zone Defaults
Zone # 01 02 03 04 05 06 07 08 09 10–86 87 *

Supervisory zones should be given a response type of 05 (Trouble by Day, Alarm by Night).

Zone 92 is the Duress zone. Programming of the zone response type is not applicable. This zone requires only the report code programming.

Communication Defaults
*45 *46 *47 *48 *49 *50 PRIMARY FORMAT SECONDARY FORMAT [1] ADEMCO Contact ID [1] ADEMCO Contact ID [0]
Secondary

*51 *52

DUAL REPORTING [0] [0] [0]
Bypass

[0] no [0] [0]
standard

LOW SPEED FORMAT (Prim) [0] ADEMCO Low Speed LOW SPEED FORMAT (Sec.) [0] ADEMCO Low Speed CHECKSUM VERIFICATION [0]
No checksum Primary

STANDARD/EXPANDED REPORT FOR PRIMARY [0]
Trbl Alarm Rstr Opn/Cls Low Bat

*53

STANDARD/EXPANDED REPORT FOR SECONDARY [0] [0] [0]
Bypass

[0]
Trbl

[0]

[0]

standard

SESCOA/RADIONICS SEL.

[0] Radionics

Alarm Rstr

Opn/Cls Low Bat

4-4

Section 4 – Programming Communication Defaults for Zones
ZONE # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 1st 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 01 02 03 04 05 06 07 08 09 10 11 2nd 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 ZONE # 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 1st 12 13 14 15 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 01 02 03 04 05 06 07 2nd 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 ZONE # 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 1st 08 09 10 11 12 13 14 15 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 01 02 03 2nd 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 ZONE # 79 80 81 82 83 84 85 86 87 88 89 90 91 92 (DURESS) 95 96 97 98 99 ALARM RST. TROUBLE TRBLE. RST BYPASS BYP. RST. 1st 04 05 06 07 08 09 10 11 00 00 00 00 00 11 00 00 00 00 06 00 00 00 00 00 2nd 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00

Zone Response Type Definitions

Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. There are three keypad-activated zones (panic keys; see note) for each partition, a polling loop supervision zone, and four RF supervisory zones, two for each RF receiver installed. Zone types are defined below. Type 00: Zone Not Used Program with this zone type if the zone is not used. Type 01: Entry/Exit #1 Burglary Provides entry delay whenever the zone is faulted and the system is armed in the AWAY or STAY mode. When the panel is armed in the INSTANT or MAXIMUM mode, no entry delay is provided. Exit delay begins whenever the control is armed, regardless of the arming mode selected. These delays are programmable. Assign this zone type to zones that are used for primary entry to and exit from the facility.

Type 02: Entry/Exit #2 Burglary Provides a secondary entry delay, if the system is armed in the AWAY or STAY modes and the zone is faulted. When the panel is armed in the INSTANT or MAXIMUM mode, no entry delay is provided. Secondary exit delay begins whenever the control is armed, regardless of the arming mode selected. These delays are programmable. Assign this zone type to zones that are used for entry and exit of the facility and require more time than the primary entry and exit point. Delay times for this zone type must be greater than those for zone type 01 (e.g., a garage, loading dock, or basement door). Type 03: Perimeter Burglary Provides an instant alarm if the zone is faulted and the system is armed in the AWAY, STAY, INSTANT, or MAXIMUM mode. Assign this zone type to all exterior door and window zones.

4-5

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Type 04: Interior Follower Provides a delayed alarm (using the programmed entry delay time) if an entry/exit zone is faulted first. Otherwise it produces an instant alarm. It is active when the system is armed in the AWAY or MAXIMUM mode, but the MAXIMUM mode eliminates the entry delay. Interior Follower zones are automatically bypassed when the panel is armed in the STAY or INSTANT mode. Assign this zone type to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon entry or exit (to and from the keypad). Type 05: Trouble by Day/Alarm by Night Provides an instant alarm if the zone is faulted and the system is armed in the AWAY, STAY, INSTANT, or MAXIMUM mode. During the disarmed state (day), the system annunciates a latched trouble sounding from the keypad (and a central station report, if desired). Assign this zone type to a zone that contains a foilprotected door or window (such as in a store), or to a zone covering a sensitive area such as a stock room or drug supply room. It can also be used on a zone in an area where immediate notification of an entry is desired. Type 06: 24-Hour Silent Alarm Sends a report to the central station but provides no keypad display or sounding. Assign this zone type to a zone containing an Emergency button. Type 07: 24-Hour Audible Alarm Sends a report to the central station and provides an alarm sound at the keypad and an audible external alarm. Assign this zone type to a zone containing an Emergency button. Type 08: 24-Hour Auxiliary Alarm Sends a report to central station and provides an alarm sound at the keypad only. (No bell output is provided.) Assign this zone type to a zone an Emergency button or one containing monitoring devices such as water sensors or temperature sensors. Type 09: Supervised Fire (Without Verification) Provides a fire alarm on a short circuit and a trouble condition on open circuit. A fire alarm produces a pulsing of the bell output. A zone of this type is always active and cannot be bypassed. Type 10: Interior with Delay Provides entry and exit delays (using the programmed entry and exit delay times) when armed in the AWAY mode. Provides only exit delay when armed in the MAXIMUM mode (no entry delay). Interior with Delay zones are automatically bypassed when the panel is armed in the STAY or INSTANT mode. Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit delay zone was tripped first. Assign this zone type to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon entry or exit (to and from the keypad). Type 20: Arm-STAY (5800 Series devices only) Causes the system to arm in the STAY mode when the zone is activated. Type 21: Arm-AWAY (5800 Series devices only) Causes the system to arm in the AWAY mode when the zone is activated. Type 22: Disarm (5800 Series devices only) Causes the system to disarm when the zone is activated. Type 23: No Alarm Response Used on a zone when an output relay action is desired, but with no accompanying alarm (e.g., for lobby door access).
NOTE FOR PANIC KEYS: Keypad panic zones share the same zone response type for all 8 partitions, but panics may be individually enabled for each partition. IMPORTANT! FAULT ANNUNCIATION Polling loop and RF troubles (zones 88, 89, 90, 91, and 97) report as trouble conditions only, and as such, should be assigned zone type 05 if annunciation is desired. See Polling Loop Supervision and RF System Operation and Supervision in SECTION 3 Installing the Control for more information.

Zone Input Type Definitions
Each zone must be assigned an input type, which defines the where the system will “look” for status of the zone (RF receiver, polling loop, etc.). Zone input types are defined below. Type 01 Hardwired (HW) Reserved for the built-in hardwired zones 1-9. Type 03 Supervised RF (RF) Select for 5800 Series RF transmitters that will be supervised for check-in signals. The transmitter must remain within the receiver’s range. Type 04 Unsupervised RF (UR) Select for 5800 Series RF transmitters that will not be supervised for check-in signals. The transmitter may therefore be carried off-premises.

4-6

Section 4 – Programming
Type 05 Unsupervised Button RF (BR) Select for 5800 Series RF transmitters specifically designed for this input type. Check the transmitter’s instructions for proper programming of the input type. These transmitters send only fault signals. They do not send low-battery signals until they are activated. The transmitter may be carried off-premises. Type 06 Serial Number Polling Loop (SL) Select for polling loop devices with a built-in serial number. Type 07 DIP Switch Loop (DP) Select for polling loop devices that use DIP switches for programming the zone number of the device. Type 08 Polling Loop Right Loop (PS) Select for the second loop of two-zone polling loop devices (e.g., 4190SN).

Programming for 4100SM
• • 1.70 Event Log Types (1=enable; 0=disable 1.71 12/24-Hour Time Stamp (0=12 hr; 1=24 hr) • • 1.72 Printer On-line (0=disable; 1=enable) 1.73 Printer Baud Rate (0=1200; 1=300)

Programming for Access Control
The VISTA-50P/VISTA-50PUL can be used to trigger an access point (i.e., door strike) for 2 seconds by entering User Code + [0]. To program the VISTA-50P/VISTA-50PUL for StandAlone access control, perform the following steps: Step 1 2 3 4 5 Action Enter Output Programming in the #93 Menu Mode. Program the output type as 1, or 2. For type 1, program the ECP address and relay number. For type 2, program the house and unit codes. Program the relay number in field 1∗76 (partition-specific).

See Output Programming in the Programming Guide for a detailed explanation.

4-7

VISTA-50P/VISTA-50PUL Installation and Setup Guide

4-8

S E C T I O N

5

Data Field Descriptions
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

About Data Field Programming
The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column, followed by a “Title and Data Entries column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields. The “Explanation” column provides explanatory information and special notes where applicable. NOTE: Refer to the Programming Guide for the default values. They are not listed in this section.

Use the Programming Guide to record the data for this installation.

Programming Data Fields
Data field programming involves making the appropriate entries for each of the data fields. Start Data Field programming by entering the installer code + 8 + 0 + 0.

FIELD

TITLE and DATA ENTRIES Installer Code
Enter 4 digits, 0-9

EXPLANATION
The Installer Code is a 4-digit code reserved for installation company use. This is the only code that can be used to enter the Program Mode from the keypad. This code cannot be used to disarm the system if it isn’t used to arm the system. This code cannot be used to re-enter Program Mode if Program Mode is exited by the *98 command. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Entry delay defines the delay time that allows users to re-enter the premises through a door that has been programmed as an entry delay door and disarm the system without sounding an alarm. The system must be disarmed within this period or an alarm will occur. NOTE: The delay may not exceed 45 seconds for UL installations.

*00

*02 *03 *04 *05 *09

Response Types for Zones 01–08 Response Types for Zones 09–16 Response Types for Zones 17–24 Response Types for Zones 25– 27, 97, 95, 96, and 99 Entry Delay #1 (partition-specific)

Enter 01-15 multiplied by 15 seconds. 00 = no delay.

*10 *11

Enter 01-15 multiplied by 15 seconds. 00 = no delay. Enter 01-15 multiplied by 15 seconds. 00 = no delay.

Exit Delay #1 (partition-specific)

Exit delay defines the delay period that allows users to leave the premises through a door that has been programmed as an entry/exit delay door after arming the system without setting off the alarm. Entry Delay #2 is used for a secondary door requiring a longer delay than those assigned to Entry Delay #1. NOTE: The delay may not exceed 45 seconds for UL installations.

Entry Delay #2 (partition-specific)

5-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES Exit Delay #2 (partition-specific) EXPLANATION
Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned to Exit Delay #1. NOTE: The delay may not exceed 60 seconds for UL installations. Defines the length of time the Bell Output and the keypad’s sounder will sound for all audible alarms. Must be minimum 16 minutes for UL Commercial Burglary installations.

*12 *13

Enter 01-15 multiplied by 15 seconds. 00 = no delay.

Enter 01-15 multiplied by 2 minutes. 00 = no timeout.

Alarm Sounder Duration (partition-specific)

*14 *15

Zone 9 Fast/Slow Response
0 = slow 350ms 1 = fast 10ms

Select the response time for devices connected to zone 9.

Enter 1-8 partition keyswitch is being used. Enter 0 if the keyswitch is not used.

Keyswitch Assignment

The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer available as protection zone). The fire and panic alarm voltage triggers (J7) automatically become ARMING and READY status outputs for the Keyswitch LEDs. Openings/closing report as user “0” if enabled in field *40.

*16

Confirmation of Arming Ding (partition-specific)
0 = disable 1 = enable

If enabled, produces ½-second external alarm sounding (“ding”) at the end of exit delay (or after kissoff from the central station, if sending closing reports). Must be 1 for UL installations. If enabled, sounding at the keypad (rapid beeping) occurs when AC power is lost (sounding occurs about 2 minutes after actual AC loss).

*17 *19

AC Loss Keypad Sounding
0 = disable 1 = enable

Randomize AC Loss Report
0 = disable 1 = enable

If enabled, randomizes AC loss reporting between 10 and 40 min. after an actual AC loss. If disabled, AC loss reporting about 2 minutes after actual AC loss. Selecting this option helps prevent an overload of AC loss messages at the central station during a community blackout.

*20

VIP Module Phone Code

1-9 = first digit of access code ∗ or # = second digit of access code (enter 11 for “∗”, or 12 for “#”) To disable enter 00 for the 1st digit

If a 4286 Voice Module is being used, enter the 2-digit phone code used to access the system. Must be disabled for UL installations.

*21

Prevent Fire Timeout
0 = disable (timeout) 1 = enable (no timeout)

If enabled, there is no timeout of the alarm sounder duration for all fire zones, regardless of partition, so that fire sounding continues until the system is reset. If disabled, (timeout) the normal burglary sounder duration (field .13) applies to fire alarms.

*22

Keypad Panic Enables (partitionspecific)
0 = disable 1 = enable

If enabled, the keypad panics (zones 95, 96, and 99) may be used in this partition. There are 3 entries in this field, one for each panic.

*23

Multiple Alarms (partitionspecific)
0 = disable 1 = enable

If enabled, allows more than one alarm sounding for a given zone during an armed period. NOTE: that multiple alarm soundings will not occur more frequently than allowed by the programmed alarm sounder duration. This has no impact on the number of communication messages transmitted. Must be 1 for UL installations.

5-2

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES Ignore Expansion Zone Tamper
0 = disable (tamper detection) 1 = enable (no tamper detection)

EXPLANATION
If disabled, the system monitors the tampers on expansion zones. NOTE: Only applicable to certain polling loop sensors with tamper switches or 5800 Series transmitters. Must be 0 for UL installations.

*24

*25

Burglary Trigger for Response Type 8
0 = disable 1 = enable

If enabled, allows triggering of Output 3 (pin 7) of the J7 header to include zone response type 8 (24-hr. auxiliary).

*26

Intelligent Test Report
0 = disable 1 = enable

If enabled, no test report is sent if any other type of report was sent since the last test report. If disabled, test reports are sent at the set intervals, regardless of whether or not any other report has been sent. Must be 0 for UL applications.

*27 *28

Test Report Interval

Enter 001-999 for the test report interval in hours. Enter 000 for no test report.

If a test report is desired, enter a test code in Report Code Programming in #93 Menu Mode. Set first test report time in field *83. Maximum Test report interval is 024 for UL installations. If enabled, the system, upon power-up, reverts to its status prior to a complete power loss. If disabled, the system always powers up in a disarmed state. NOTE: Neither authority level 0 nor 5 can be used to disarm the system if the control powers up armed. Must be 1 for UL applications.

Power-Up in Previous State
0 = disable 1 = enable

*29

Quick Arm (partition-specific)
0 = disable 1 = enable

If enabled, allows arming of the burglary system in AWAY, STAY, INSTANT, or MAXIMUM mode by using the [#] key instead of the user code. NOTES: When armed, the system reports closing as User 0 if Open/Close reporting for User #2 (typically a Master level user) was enabled for a given partition. If Quick Arm is used, the Installer Code and Authority Level 5 codes cannot disarm the system.

*30 *31 *32

TouchTone or Rotary Dial
0 = disable 1 = enable

Select the dialing method for the system

PABX Access Code
Enter 00-09; B-F (11-15)

This field is used to enter up to four 2-digit numbers representing the prefix needed to obtain an outside telco line. If not required, enter nothing and proceed to next field. Enter a 3- or 4-digit (depending on report format) primary subscriber account number. Each number requires a 2-digit entry so as to allow entry of hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data only in the first 3 locations, and enter * in the fourth location. Enter the primary central station phone number, up to 17 digits. This is the phone number the control will use to transmit Alarm and status messages to the central station. Do not fill unused spaces. NOTE: Backup reporting is automatic only if a secondary phone number is entered.

Primary Subscriber’s Account Number (partition-specific)
Enter 00-09; B-F (11-15)

*33

Primary Phone Number

Enter 0-9; #11 for *, #12 for #, #13 for a 2second pause.

5-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES Secondary Phone Number
Enter 0-9; #11 for *, #12 for #, #13 for a 2second pause.

EXPLANATION
Enter the secondary phone number, up to 17 digits. The secondary phone number is used if communication on the primary number is unsuccessful, or if split/dual reporting is desired. Do not fill unused spaces. NOTE: If this field is programmed, a secondary subscriber account number (field *90) must also be programmed.

*34

*35 *36

Download Phone Number

Enter 0-9; #11 for *, #12 for #, #13 for a 2second pause.

Enter the downloading phone number, up to 17 digits. Do not fill unused spaces. NOTE: This field is applicable only if downloading is utilized. Enter eight digits. NOTE: This field is applicable only if downloading is utilized.

Download ID Number

Make entries as 2-digit numbers as follows: 00=0 01=1 02=2 03=3 04=4 05=5 06=6 07=7 08=8 09=9 10=A 11=B 12=C 13=D 14=E 15=F

*37

Download Command Enables
0 = disable 1 = enable

Enabling a function means that you are able to perform that function via the Compass Downloading software. Functions are as follows: Dialer Shutdown; System Shutdown; Not Used; Remote Bypass; Remote Disarm; Remote Arm; Upload Program; Download Program. For UL installations, all entries must be 0.

*38

Enter a zone number (01-86). Enter 00 if all zones (except fire zones) can be bypassed.

Prevent Zone XX Bypass (partition-specific)

Enter two digits for zone that cannot be bypassed by the user. NOTES: The actions manual bypass, and STAY/INSTANT arming modes cannot bypass any zone programmed in this field. If enabled, whenever the Installer Code is used to arm or disarm the partition, an open/close report is sent to the central station.

*39

Enable Open/Close Report for Installer Code (partition-specific)
0 = disable 1 = enable

*40

Enable Open/Close report for Keyswitch
0 = disable 1 = enable

If enabled, whenever the keyswitch is used to arm or disarm the partition, an open/close report is sent to the central station.

*41

Normally Closed or EOLR (Zones 2-8)
0 = disable 1 = enable

If disabled, end-of-line resistors must be used on zones 2-8. If enabled end-of-line resistors cannot be used and only normally closed devices must be used. Must be 0 for UL installations. Enter the time the system waits for dial tone before dialing. Applies if true dial tone is not selected in field *43. Must be 0 for UL installations.

*42

Enter the wait time for dial tone detection: 0 = 5 seconds; 1 = 11 seconds; 2 = 30 seconds.

Dial Tone Pause

*43

Dial Tone Detection
0 = disable 1 = enable

If enabled, the system waits for true dial tone. If no dial tone is detected, control dials at end of pause programmed in field *42. If disabled, the system pauses for seconds entered in field *42, then dials. NOTE: Disabling may be necessary in high-noise environment telco networks where noise can be confused with dial tone, resulting in premature dialing.

5-4

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES Ring Detection Count
Enter 00 to disable ring detection. Enter 01-14 for ring counts of 1-14. Enter 15 to select Answering Machine Defeat Mode

EXPLANATION
Only applicable if using a 4286 VIP Module and/or if station-initiated downloading will be used. NOTES: Do not enter 00 if a 4286 is installed. In the Answering Machine Mode, the caller should let the phone ring once, then hang up, and call again within 30 seconds. The system, upon hearing one ring followed by nothing, does not answer the first call, but readies itself to pick up on the first ring of the next incoming call that is received within 30 seconds (i.e., the downloader calling again). Must be 00 for UL installations.

*44

*45 *46 *47 *48 *49

0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed; 3=ADEMCO Express

Primary Format

Enter the reporting format for the primary telephone number.

Low Speed Format (Primary)
0 = ADEMCO Low Speed 1 = Sescoa/Radionics

Enter the low speed format for the primary telephone number.

0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed; 3=ADEMCO Express

Secondary Format

Enter the reporting format for the secondary telephone number.

Low Speed Format (Secondary)
0 = ADEMCO Low Speed 1 = Sescoa/Radionics

Enter the low speed format for the secondary telephone number.

Checksum Verification

Enter 2 digits, one for the primary and one for the secondary. 0 = disable 1 = enable

If enabled, the system for either or both primary/secondary formats sends a verification digit to validate the message at the receiver without having to send two message rounds. Selection is valid for 3+1, 4+1, and 4+2 reports.

*50

Sescoa/Radionics Select
0 = disable 1 = enable

If disabled, selects Radionics, which uses hexadecimal 0-9, B-F reporting. If enabled, selects Sescoa, which uses only numeric reporting (0-9). NOTE: The selection applies to both primary and secondary phone numbers. If enabled, all reports are to be sent to both primary and secondary phone numbers. NOTE: If used with Split Reporting option 1 (1*34), alarms go to both primary and secondary numbers, while all other reports go to secondary only. If used with Split Reporting option 2, alarms go to both lines, open/close and test messages go to secondary only, while all other reports go to primary. This field has six entries as follows: Alarm, Restore, Bypass, Trouble, Open/Close, Low Battery. If enabled, expanded reports are sent to the primary phone number if low speed format is selected in field *45. NOTE: Expanded overrides 4+2 format. This field has six entries as follows: Alarm, Restore, Bypass, Trouble, Open/Close, Low Battery. If enabled, expanded reports are sent to the secondary phone number if low speed format is selected in field *47. NOTE: Expanded overrides 4+2 format.

*51

Dual Reporting
0 = disable 1 = enable

*52

Standard/Expanded Reporting Primary
0 = disable 1 = enable

*53

Standard/Expanded Reporting Secondary
0 = disable 1 = enable

5-5

VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES Alarm Code for Zones 01–08 ID Digit for Zones 01–08 Alarm Code for Zones 09–16 ID Digit for Zones 09–16 Supervisory and Restore Codes for Zones 01–16
Enter 00-15.

EXPLANATION
Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. This field has five two-digit entries as follows: Alarm Restore, Trouble, Trouble Restore, Bypass, and Bypass Restore. Enter the report code 01-15 for each type of report. Enter 00 for no report. NOTE: Each report code is the same for zones 01-16. When using 4+2 format, the system uses the ID digit of the zone (fields *55 and *57). Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. This field has five two-digit entries as follows: Alarm Restore, Trouble, Trouble Restore, Bypass, and Bypass Restore. Enter the report code 01-15 for each type of report. Enter 00 for no report. NOTE: Each report code is the same for zones 17-32. When using 4+2 format, the system uses the ID digit of the zone (fields *60 and *62). Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. This field has five two-digit entries as follows: Alarm Restore, Trouble, Trouble Restore, Bypass, and Bypass Restore. Enter the report code 01-15 for each type of report. Enter 00 for no report. NOTE: Each report code is the same for zones 33-48. When using 4+2 format, the system uses the ID digit of the zone (fields *65 and *67). Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details.

*54 *55 *56 *57 *58

*59 *60 *61 *62 *63

Alarm Code for Zones 17–24 ID Digit for Zones 17–24 Alarm Code for Zones 25–32 ID Digit for Zones 25–32 Supervisory and Restore Codes for Zones 17–32
Enter 00-15.

*64 *65 *66 *67 *68

Alarm Code for Zones 33–40 ID Digit for Zones 33–40 Alarm Code for Zones 41–48 ID Digit for Zones 41–48 Supervisory and Restore Codes for Zones 33–48
Enter 00-15.

*69

Alarm Code for Zones 49–56

5-6

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES ID Digit for Zones 49–56 Alarm Code for Zones 57–64 ID Digit for Zones 57–64 Supervisory and Restore Codes for Zones 49–64
Enter 00-15.

EXPLANATION
Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. This field has five two-digit entries as follows: Alarm Restore, Trouble, Trouble Restore, Bypass, and Bypass Restore. Enter the report code 01-15 for each type of report. Enter 00 for no report. NOTE: Each report code is the same for zones 49-64. When using 4+2 format, the system uses the ID digit of the zone (fields *70 and *72). Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. This field has five two-digit entries as follows: Alarm Restore, Trouble, Trouble Restore, Bypass, and Bypass Restore. Enter the report code 01-15 for each type of report. Enter 00 for no report. NOTE: Each report code is the same for zones 17-32. When using 4+2 format, the system uses the ID digit of the zone (fields *75 and *77). This field has eight entries, one for each zone type. Select the zone types that will send Restore reports.

*70 *71 *72 *73

*74 *75 *76 *77 *78

Alarm Code for Zones 81–88 ID Digit for Zones 81–88 Alarm Code for Zones 89–99 ID Digit for Zones 89–99 Supervisory and Restore Codes for Zones 81–99
Enter 00-15.

*79

Zone Type Restores for Zone Types 1-8
0 = disable 1 = enable

*80

Zone Type Restores for Zone Types 9, and 10
0 = disable 1 = enable

This field has three entries, one for each zone type. Select the zone types that will send Restore reports.

*81 *82 *83

Non-Alarm Report Codes (First Digit)
Enter 00-15.

This field has ten two-digit entries as follows: Close, Open Low Battery, Low Battery Restore, AC Loss, AC Restore, Test, Power-up, Cancel, and Program Tamper. Enter the report code 01-15 for each type of report. Enter 00 for no report. This field has ten two-digit entries as follows: Close, Open, Low Battery, Low Battery Restore, AC Loss, AC Restore, Test, Power-up, Cancel, and Program Tamper. Enter the report code 01-15 for each type of report. Enter 00 for no report. Enter the day and time that the first Test report shall be transmitted. Enter 00 in all locations if the Test report is to be sent immediately upon exiting. Enter 00 in the day location if the report is to be sent at the next occurrence of the time that is set.

Non-Alarm Report Codes (Second Digit)
Enter 00-15.

Enter 00-07the for day (01 = Monday) Enter 00-23 for the hour Enter 00-59 for the minutes

First Test Report Time

5-7

VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES Swinger Suppression (partitionspecific) EXPLANATION
This option limits the number of messages (alarms or troubles) sent for a specific zone in an armed period. Must be 00 for UL installations.

*84

Enter 01-15. Enter 00 for unlimited reports

*85

Enable Dialer Reports for Panics & Duress (partition-specific)
0 = disable 1 = enable

This field has four entries as follows: Zone 95, 96, 99, Duress Enable for each partition that the panics and duress reporting is desired. NOTE: Non-zero report code must be assigned to zone 92 (duress) to enable Duress reporting. Select the type of warning for the entry delay period.

*87 *88

Entry Warning (partition-specific)
0 = 3 short beeps 1 = slow continuous beeps

Burglary Alarm Communicator Delay (partition-specific)
0 = no delay 1 = 16-second delay

Select the delay, if any, for burglary alarm communications. Must be 0 for UL installations.

*89 *90

Restore Report Timing
0 = instant 1 = after bell timeout 2 = when system is disarmed

Select the time when restore reports are sent after an alarm. Must be 2 for UL installations.

Secondary Subscriber Account Number (partition-specific)
Enter 00-09; B-F (11-15)

Enter a 3- or 4-digit (depending on report format) primary subscriber account number. Each number requires a 2-digit entry so as to allow entry of hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data only in the first 3 locations, and enter * in the fourth location. NOTE: This field must be programmed if a secondary phone number is used (field *34). This account number can be the same as the primary account number.

1*01 1*02 1*03 1*04 1*05 1*06 1*07 1*08

Response Types for Zones 28–32 Response Types for Zones 33–40 Response Types for Zones 41–48 Response Types for Zones 49–56 Response Types for Zones 57–64 Response Types for Zones 65–72 Response Types for Zones 73–80 Response Types for Zones 81–87

Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details.

5-8

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES Response Types for Zones 88–91 Lobby Partition EXPLANATION
Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Select the Common Lobby Partition.

1*09 1*17 1*18 1*19

0 = none 1-8 = partition number

Affects Lobby (partition-specific)
0 = disable 1 = enable

If enabled, causes lobby partition to disarm when this partition disarms. NOTE: This partition must be armed before lobby can be armed. If enabled, arming this partition causes the system to attempt to arm the lobby partition automatically. To enable this field, field 1*18 must also be enabled (partition-specific). NOTES: The lobby cannot be armed unless all partitions programmed for “affect” (field 1*18) is already armed. If his field is enabled, Field 1*18 for this partition must also be enabled.

Arms Lobby (partition-specific)
0 = disable 1 = enable

1*20

Exit Error Logic Enable
0 = disable 1 = enable

Exit Error Logic functions as follows: the system at the end of the exit delay, if a door is left open or an interior zone is faulted, starts the entry delay period, and sounds the bell(s), siren(s), and keypad sounders for the duration of entry delay. This gives the user time to re-enter the premises and disarm the system before exit error occurs. If the user does not re-enter the premises and disarm the system, the system bypasses the faulted entry/exit and/or interior zone(s). The rest of the system is armed. In addition, the following dialer reports are sent to the central station if programmed: Exit Error by User (not sent when is using ADEMCO High Speed format) Entry/Exit or Interior Alarm with the zone number Bypass reports

UL 1*21

Exit Error Logic is not suitable for use in a UL installation.

Exit Delay Reset
0 = disable 1 = enable

If enabled, when the panel is armed, the normal exit delay begins. After the user exits, closes the door and then re-enters the premises, the exit delay time is reset to the programmed value. NOTES: Exit Delay Reset is designed to allow an operator to re-enter the premises to retrieve a forgotten item without triggering an alarm. This feature may only be activated once after arming.

UL

Exit Delay Reset is not suitable for use in a UL installation.

5-9

VISTA-50P/VISTA-50PUL Installation and Setup Guide Cross-Zoning
Cross Zoning is designed so that a combination of two zones must be faulted within a 5-minute period of each other (whereas the first zone remains faulted, when the second zone trips) to cause an alarm on either zone. This prevents momentary faults from one of the zones from causing an alarm condition. You can select four "sets" of cross-zones (programmed in data fields 1*22, 1*23, 1*24, and 1*25), keeping in mind the following: • Both zones in each set must protect the same area. • When cross-zoning motion sensors, both device's areas of protection must be situated so that both units will trip at the same time if their shared protected area is violated. • • Both zones in each set must be in the same partition. A fire zone must only be crossed to another fire zone protecting the same physical area (see warning below). DO NOT cross-zone a fire zone with a burglary zone under any circumstance. Cross a fire zone with another fire zone only, and BOTH must be protecting the same physical area (no walls or partitions separating them). Consult NFPA 72 standard for exact spacing requirements. We recommend that spacing between fire cross-zones be no farther than 30 ft.

Conditions That Affect Cross-Zone Operation
• • • • If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not apply. If an entry/exit zone is paired with an interior follower zone, be sure to enter the entry/exit zone as the first zone of the pair. This ensures that the entry delay time is started before the follower zone is processed. If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being faulted. If a relay is programmed to activate on either an alarm or trouble, both zones must trip before the relay will activate, and both zones must restore for the relay to deactivate (if relay is programmed to deactivate on a Zone List Restore).

If the one of the zones trips and the second zone does not trip within the 5-minute period, an “error” message is reported to the central station. The Contact ID event code is 378.

FIELD

TITLE and DATA ENTRIES
Enter 01-86 Enter 00,00 to disable

EXPLANATION
Select the first pair of cross zones, which must both be faulted within a 5minute period to cause an alarm. Must be 00,00 for UL installations. Select the second pair of cross zones, which must both be faulted within a 5-minute period to cause an alarm. Must be 00,00 for UL installations. Select the third pair of cross zones, which must both be faulted within a 5minute period to cause an alarm. Must be 00,00 for UL installations. Select the fourth pair of cross zones, which must both be faulted within a 5-minute period to cause an alarm. Must be 00,00 for UL installations. Select when the RF transmitter low-battery condition should display and audible beep annunciate on the keypad. Must be 1 for UL installations.

1*22 1*23 1*24 1*25 1*28

Cross Zoning Pair One

Enter 01-86 Enter 00,00 to disable

Cross Zoning Pair Two

Enter 01-86 Enter 00,00 to disable

Cross Zoning Pair Three

Enter 01-86 Enter 00,00 to disable

Cross Zoning Pair Four

RF Transmitter Low Battery Sound
0 = disarmed state only 1 = both armed and disarmed states

5-10

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES RF Transmitter Low Battery Reporting
0 = disable 1 = enable

EXPLANATION
If enabled, the system sends a Trouble message for RF transmitter lowbattery condition to the central station. NOTE: The Trouble message will be sent for a transmitter supervision failure, independent of this selection. Must be 1 for UL.

1*29

1*30

RF Receiver Supervision Checkin Interval
Enter 02-15 times 2 hours (4-30 hours). 00 = disable receiver supervision.

Select the check-in monitoring interval for the RF receiver(s). Failure of a receiver to receive any RF signal within the time entered results in the activation of the response type programmed for zone 90 for the first receiver and zone 88 for the second receiver and their related communication reports. Maximum is 2 (4 hr) for UL installations.

1*31

RF Transmitter Check-in Interval
Enter 02-15 times 2 hours (4-30 hours). 00 = disable transmitter supervision.

Select the check-in monitoring interval for the RF transmitters. Failure of an individual transmitter to send a supervision signal within the time entered will result in a trouble response and related communication report. Maximum is 2 (4 hr) for UL.

1*33 1*34

TouchTone with Rotary Backup
0 = disable 1 = enable

If enabled, the system reverts to rotary dialing if communicator is not successful in dialing using TouchTone DTMF on first attempt.

Communicator Split Reporting

Select the type of split reporting for system communication. NOTE: See *51 for split/dual reporting combinations.

0 = Split Reporting disabled 1 = Alarm, Alarm Restore, and Cancel reports to primary, all others to secondary 2 = Open/Close and Test reports to secondary, all other reports to primary

1*35 1*36 1*37 1*38 1*39

Alarm Code for Zones 65–72 ID Digit for Zones 65–72 Alarm Code for Zones 73–80 ID Digit for Zones 73–80 Supervisory and Restore Codes for Zones 65–80
Enter 00-15.

Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. Skip this field. Use #93 Menu Mode, Zone Programming to program the response types. Refer to the Programming Guide for details. This field has five two-digit entries as follows: Alarm Restore, Trouble, Trouble Restore, Bypass, and Bypass Restore. Enter the report code 01-15 for each type of report. Enter 00 for no report. NOTE: Each report code is the same for zones 65-80. When using 4+2 format, the system uses the ID digit of the zone (fields 1*35 and 1*38). This field has seven two-digit entries as follows: Arm STAY, Time/Date set or Event Log Reset, Event Log 50% or 90% Full, Event Log Overflow, Exit Error (Zone), Exit Error (User) and Recent Close. Enter the report code 01-15 for each type of report. Enter 00 for no report. This field has seven two-digit entries as follows: Arm STAY, Time/Date set or Event Log Reset, Event Log 50% or 90% Full, Event Log Overflow, Exit Error (Zone), Exit Error (User) and Recent Close. Enter the report code 01-15 for each type of report. Enter 00 for no report.

1*40 1*41

Non-Alarm Report Codes (First Digit)
Enter 00-15.

Non-Alarm Report Codes Report Codes (Second Digit)
Enter 00-15.

5-11

VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES Call Waiting Defeat
0 = disable 1 = enable

EXPLANATION
If enabled, the system defeats Call Waiting on the first outgoing call attempt to both the primary and secondary numbers. NOTES: After the panel's initial call to report the alarm, the panel may attempt to make an additional call, perhaps for a cancel or a zone restoral. If Call Waiting is not defeated, an operator at the central station attempting to contact the premises (to verify whether the alarm is valid) hears the phone ringing indefinitely and must to dispatch on the call. DO NOT enable this feature unless Call Waiting is being used.

1*42

1*43

Permanent Keypad Display Backlighting (partition-specific)
0 = disable 1 = enable

If enabled, backlighting for the keypad display remains on at all times. Otherwise the backlighting comes on when a key is pressed. NOTE: When a key is pressed, display backlighting turns on for all keypads in that partition. If enabled, when more than 40 key depressions are received without a valid sequence (arm, disarm, etc.), the control panel disables the wireless keypad. Once a valid key sequence is received from a wired keypad the inhibit is removed. If enabled, the system produces slow beeping from the keypads during exit delay and reverts to rapid beeping during the last 10 seconds of the exit delay. NOTE: The duration of the beeping is the programmed value of field *10 regardless of which entry/exit zone is used to exit the premises. Select the mode for output 1 on the J7 triggers. NOTES: Only one of the options may be active within the system. Selection 1 is produced only when all partitions are armed. Selection 2 applies only to the partition enabled in field *15. If enabled, the system produces chime annunciation on the external alarm sounder.

1*44

Wireless Keypad Tamper Detect
0 = disable 1 = enable

1*45

Exit Delay Sounding (partitionspecific)
0 = disable 1 = enable

1*46

Auxiliary Output Mode

0 = ground start output. 1 = open/close trigger. 2 = keypad sounds at an auxiliary sounder. 3 = AAV module.

1*47

Chime on External Siren (partition-specific)
0 = disable 1 = enable

1*48 1*49 1*52

Wireless Keypad Assignment
0 = none 1-8 = partition number

Select the partition in which RF keypad is used.

Suppress Transmitter Supervision Sound
0 = disable 1 = enable

If enabled, no trouble soundings occur on the keypad for transmitter check-in failures. Must be 0 for UL. If enabled, Cancel reports are sent when the system is disarmed after an alarm, regardless of how much time has gone by. If disabled, Cancel reports are sent within Bell Timeout period only. NOTE: This option must be enabled so Cancel reports are always sent. Select whether a callback from the control panel is required for downloading. Must be 0 for UL installations. If enabled, the system arms/disarms in accordance with the button’s user’s global arming settings.

Send Cancel If Alarm + Off (partition-specific)
0 = disable 1 = enable

1*53 1*57

Disable Download Callback
0 = callback required 1 = no callback required

Enable 5800 RF Button Global Arm
0 = disable 1 = enable

5-12

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES Enable 5800 RF Button Force Arm
0 = disable 1 = enable

EXPLANATION
If enabled, allows the RF button user to force a bypass of all faulted zones when arming the system. NOTE: When attempting to arm the system, the keypad beeps once after the button is pressed if any faulted zones are present. The user should then press the button again within 4 seconds to force-bypass those zones and arm the system. If enabled, zone 5 is used for 2-way audio (AAV). Must be 0 for UL installations. NOTE: Zone 5 cannot be used as protection zone. This field has five entries as follows: Alarm, Check, Bypass, Open/Close, and System. If enabled, the system logs those events into the event log.

1*58

1*60 1*70 1*71 1*72 1*73 1*74 1*75 1*76

Zone 5 Audio Alarm Verification
0 = disable 1 = enable

Event Log Types
0 = disable 1 = enable

12/24 Hour Type Stamp Format
0 = 12-hour 1 = 24-hour

Select the type of time stamping for the event log.

Event Log Printer On-Line Mode
0 = disable 1 = enable

If enabled, the system prints the events as they occur. If disabled, the system prints the log only upon request.

Printer Baud Rate
0 = 1200 1 = 300

Select the baud rate for the serial printer.

Relay Timeout XXX Minutes

Enter 000-127 times 2 minutes (000-254).

This is used for #80 Menu Mode Time-Driven event relay command numbers “04/09” and Output Programming in the #93 Menu Mode Programming output command “56.” This is used for #80 Menu Mode Time-Driven event relay command numbers “05/10” and Output Programming in the #93 Menu Mode Programming command “57.” If enabled, the assigned relay closes for 2 seconds when the user enters his code and presses 0. Must be 00 for UL installations. NOTE: See SECTION 3: Installing the Control for enhanced access control capabilities. Enter the number of partitions used in the system.

Relay Timeout YYY Seconds
Enter 000-127 seconds.

Access Control Relay (partitionspecific)
01-16 = relay number 00 = relay not used.

2*00 2*01

Number of Partitions
Enter 1-8.

Daylight Saving Time Start/End Month
0 = disable 1 = enable

Enter the months (00-12) in which daylight saving time starts and ends. Enter 00, 00 if daylight saving time does not apply to the user’s region. Standard setting for U.S. is 04,10.

2*02

Daylight Saving Time Start/End Weekend
0 = disable 1 = enable

Enter the start and end weekends for daylight saving time as follows: 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last. Standard setting for U.S. is 1,5.

UL

Fields 2*05 – 2*08 must be set to 0 for UL installations.

5-13

VISTA-50P/VISTA-50PUL Installation and Setup Guide FIELD TITLE and DATA ENTRIES Auto-Arm Delay (partitionspecific) EXPLANATION
This is the time between the end of the arming window and the start of auto-arm warning time (field 2*06).

2*05

00 = no delay. 01-14 times 4 minutes (04-56) delay. 15 = no auto arming.

2*06

Auto-Arm Warning Period (partition-specific)
01-15 times 1-minute warning. 00 = no warning period.

This is the time that the user is warned by a keypad sounding and display to exit the premises prior to auto arming of the system.

2*07

Auto-Disarm Delay (partitionspecific)
00 = no delay. 01-14 times 4 minutes (04-56) delay. 15 = no auto disarming.

This is the time between the end of the disarming window and the start of auto disarming of the system.

2*08

Force Arm Enable for Auto-Arm (partition-specific)
0 = disable 1 = enable

If enabled, the system automatically bypasses any faulted zones when it attempts to auto-arm. If disabled, the system will not auto-arm.

2*09

Open/Close Reports by Exception (partition-specific)
0 = disable 1 = enable

If enabled, Open/Close reports are sent only if the openings/closings occur outside the arm and disarm windows. NOTES: Open reports are also suppressed during the closing window in order to prevent false alarms if the user arms the system, then re-enters the premises, for example to retrieve a forgotten item. Openings and closings are still recorded in the event log. This field must be set to 1 if No Opening and No Closing reports are to be sent.

2*10

Allow Disarming Only During Arm/Disarm Windows (partitionspecific)
0 = disable 1 = enable

If enabled, disarming of the system is allowed only during the arming/ disarming windows, or if the system is in alarm (if 2*11 is set to 1). NOTE: This applies only to Operator-level users. Installer, Master, and Manager-level users can disarm the system at any time.

2*11

Allow Disarm Outside Window if Alarm Occurs
0 = disable 1 = enable

If enabled, allows the system to be disarmed outside the programmed disarm (opening) window if an alarm has occurred. Otherwise disarming is allowed only during the disarm window. NOTE: Used only if field 2*10 is enabled. This field has eight two-digit entries as follows: Early Opening, Early Closing, Late Opening, Late Closing, No Opening (late to open), No Closing (late to close), Auto-Arm Failure, and Access Schedule Changed. Enter the report code 01-15 for each type of report. Enter 00 for no report. This field has eight two-digit entries as follows: Early Opening, Early Closing, Late Opening, Late Closing, No Opening (late to open), No Closing (late to close), Auto-Arm Failure, and Access Schedule Changed. Enter the report code 01-15 for each type of report. Enter 00 for no report. If enabled, this partition can be accessed from another partition’s keypad using the GOTO command.

2*13 2*14 2*18

Scheduling Report Codes (First Digit
Enter 00-15.

Scheduling Report Codes Report Codes (Second Digit)
Enter 00-15.

Enable GOTO for this Partition (partition-specific)
0 = disable 1 = enable

5-14

Section 5 – Data Field Descriptions FIELD TITLE and DATA ENTRIES Use Partition Descriptor
0 = disable 1 = enable

EXPLANATION
If enabled, the normal keypad display will include a partition number and four-digit descriptor.

2*19 2*20

Enable J7 Triggers for Partition (partition-specific)
0 = disable 1 = enable

If enabled, the J7 triggers function for this partition.

2*21

Supervision Pulses for LRR
0 = disable 1 = enable

There are three entries in this field as follows: Fire, Burglary/Audible Panic, Silent Panic/Duress. If enabled, causes the control to send periodic short pulses on the J7 radio triggers to the LRR. The LRR uses these pulses to determine that its connection to the control is still intact. Must be 1 for UL installations.

5-15

VISTA-50P/VISTA-50PUL Installation and Setup Guide

5-16

S E C T I O N

6

Scheduling Options
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

UL
General

• •

You must program Bypass and Auto-Arm Fail reports for UL installations. Auto-disarming is not permitted in UL installations.

The scheduling features allow certain operations to be automated, such as arming, disarming, bypassing of zones, and activating relay outputs. The system uses time windows (a programmed period of time with a start and stop time) for defining open/close schedules, holiday schedules, user-defined temporary schedules, and access schedules for users. Scheduled events are programmed by user-friendly menu modes of programming (#80, #81, #83, and #93 modes), explained in detail in this section. These menus take you step by step through the options.

Auto Arming
The system can automatically arm (AWAY Mode) a partition at the end of a pre-determined closing (arming) time window. Auto Arming can be delayed three ways: by use of the Auto-Arm Delay, the Auto-Arm Warning, or by manually extending the closing (arming) time window with a keypad command. The system can also automatically bypass any open zones when auto arming.

Auto-Arm Delay
Auto-Arm Delay provides a delay (grace period) before auto arming. It starts at the end of the closing time window. The delay is set in 4-minute increments, up to 56 minutes in partition-specific program field 2*05. At the expiration of this delay, the Auto-Arm Warning will start.

Auto-Arm Warning
The Auto-Arm Warning causes the keypad sounder to warn the user of an impending Auto-Arm. The warning can be set from 1 to 15 minutes prior to the arming in partition-specific program field 2*06. During this period the keypad beeps every 15 seconds and displays “AUTO ARM ALERT.” During the last 60 seconds, the keypads beep every 5 seconds. The panel arms at the conclusion of the Auto-Arm Warning period.

Extend Closing Window
A user can manually delay the arm (closing) time window by 1 or 2 hours. This is done by entering a keypad command (User Code + #82), which then prompts the user to enter the desired extension time of 1 or 2. This feature is useful if a user must stay on the premises later than usual. The Auto-Arm delay and warning periods begin at the end of the extension.

Force Arm
The Force Arm option causes the panel to attempt to bypass any faulted zones prior to auto arming (panel performs a force-arm). This option is set in partition-specific program field 2*08.

Auto Disarming
The system can automatically disarm a partition at the end of a pre-determined opening (disarm) time window. The disarming time can be delayed by using the Auto-Disarm Delay feature.

6-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide Disarm Delay
Auto-Disarm Delay provides a delay before auto disarming. This delay is added to the end of the disarm time window. The delay is set in 4-minute increments, up to 56 minutes, in partition-specific program field 2*07.

Restrict Disarming
This option allows disarming by users only during the disarm time window and during the arming time window (in case user needs to re-enter premises after manually arming the partition). This option is set in partition-specific field 2*10. If field 2*10 is set, we highly recommend setting field 2*11, as well. This field allows the partition to be disarmed outside the arm/disarm time windows only if the partition is in alarm.

Exception Reports
This option allows the reporting of openings and closings to the central station only if the arming and disarming occurs outside of the predetermined opening and closing time windows. It is set in partition-specific field 2*09. The system can be programmed to send Failed to Open and Failed to Close reports if the partition is not armed or disarmed by the end of the corresponding time window.

Limitation of Access of Users by Time
A user’s access to the system can be limited to a certain time period. Outside this time, that user’s code is inactive. The system provides up to 8 access schedules, each consisting of two time windows (typically one for opening, one for closing) for each day of the week and two time windows for holidays. The access schedules are programmed in the #80 Menu Mode, and enabled when a user’s access code is added to the system. If a user tries to operate the system outside the schedule, the alpha keypad displays “Access Denied.”

Time-Driven Events
The system can automatically activate and de-activate relays at predetermined times to turn lights or other devices on and off. The Time-Driven events can be activated at different times in relation to a time window: • At the beginning of a time window • At the end of a time window • During a time window (on at beginning of window, off at end) • At both the beginning and end of the time window (e.g., to sound a buzzer at the beginning and end of a coffee break) The system can perform the same actions on a daily basis, or can perform an action only once (e.g., turn on the porch light this Wednesday at 8:00 PM). The system also provides up to 20 programmable “timers” available to the end user for the purpose of activating output devices at preset times and days.

Time Window Definitions
Scheduled events are based on time windows, (periods of time) during which an event may take place. The system supports up to 20 time windows, each defined by a “Start” time and a “Stop” time. The windows are shared by all 8 partitions, and are used when programming the various schedules (open/close, limitation of access), as well as for Time-Driven event control.

Scheduling Example
A store that has the following hours:
Monday to Friday Saturday Sunday Holidays Monday to Friday Saturday Sunday & Holidays 9am to 6pm 10am to 4pm Closed Closed Open (disarm) Close (arm) Open (disarm) Close (arm) Closed 8am to 9am 6pm to 6:30pm 9am to 10am 4pm to 4:30pm

The owner desires the following time windows to allow time for employees to arm or disarm the system:

6-2

Section 6 – Scheduling Options
For this schedule, the four time windows need to be programmed:
Window 1 2 3 4 Start 8am 9am 4pm 6pm Stop 9am 10am 4:30pm 6:30pm Purpose Monday-Friday open window Saturday open window Saturday close window Monday-Fri. close window

Using the #80 Menu Mode, the installer can program open/close schedules by assigning a time window to a day of the week (windows are entered as 2-digit entries)
Mon Op/Cl 01/04 Tue Op/Cl 01/04 Wed Op/Cl 01/04 Thu Op/Cl 01/04 Fri Op/Cl 01/05 Sat Op/Cl 02/03 Sun Op/Cl 00/00 Hol Op/Cl 00/00

NOTE: 00 is entered for those days on which the store is closed. Employees can arm and disarm the system, when programmed, within the open and close time windows without causing a report to be sent to the central station (reporting by exception, field 2*09). The system can be programmed to automatically arm/disarm in case an employee fails to arm/disarm manually (auto-arm/auto-disarm).

Open/Close Schedules Definitions
General
The open/close scheduling is controlled by one of three schedules. Each schedule consists of one time window for openings and one time window for closings. There are three types of schedules available: Daily, Holiday, and Temporary.

Daily Schedule
Each partition can have one daily schedule consisting of one opening window and one closing window per day.

Holiday Schedule
A holiday schedule overrides the regular daily schedule on selected holidays throughout the year. The opening and closing windows are programmed in the daily schedule, but the holidays themselves are defined in Holiday Schedule Programming in the #80 Menu Mode.

Temporary Schedule
The temporary schedule provides a method for the end user to override the daily and holiday schedules. It consists of one opening window and one closing window for each day of the week. The schedule takes effect for up to one week, after which it is automatically deactivated. This schedule is programmed using the #81 Temporary Schedule Menu Mode.

Additional Schedules
Additional opening and closing schedules can be programmed using the Time-Driven Event Programming. For example, a schedule for normal store openings/closings can be programmed with a daily open/close schedule, and another open/close schedule for a lunch hour can be programmed using the Time-Driven event schedule programming. Refer to “Time-Driven Events” later in this section for detailed information.

Open/Close Reports by Exception
The system can help reduce communication traffic to the central station by using the Open/Close Reports by Exception feature. The Open/Close by Exception option suppresses these reports from being sent to the central station if an arm or disarm is done within the expected time window. Reports are only sent if the arm or disarm occurs outside the assigned time window. The system keeps a record of all openings/closings in its event log. If a disarming occurs during a closing window (for example, a person who arms the system forgets something and has to re-enter), the Opening report (although outside of the opening window) will not be sent (as long as that disarming occurs within the closing window). This option is programmed in partition-specific program field 2*09.

6-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide Example of Open/Close Exception Reporting & Scheduling
The following chart gives an example of how the Open/Close by Exception reporting works. 6:01PM 5:59AM 6AM 9AM 9:01AM 3:59PM 4PM 6PM 6:01PM 5:59AM
Early Opening reports are sent if system is manually disarmed before opening window begins. Early and Late Opening and Closing reports are programmable options in the Report Code Programming. They are not dependent on the programming of the Exception Reporting option. Opening Window No reports are sent if system is disarmed during this time window. If an arming occurs, a Closing report is sent to the central station regardless of how the Exception Reporting option is set. Auto-disarm delay begins. Auto-disarm occurs after delay (if auto-disarm is enabled). Missed Opening reports are sent if manual disarming has not occurred at expiration of opening window. Late Opening reports are sent if disarm occurs after the opening window expires. Early Closing reports are sent if manual arming occurs before the closing window begins. Missed Opening/Closing type reports are programmed in the Report Code Programming. The Exception Reporting option must be set for these to be sent. Closing Window No reports are sent if system is armed* during this time window. * or disarmed if user needs to reenter premises. Auto-arm delay begins. Auto-arm warning begins. Auto-arm occurs after warning expires (if autoarm is enabled). Missed Closing reports are sent if manual arming has not occurred at expiration of closing window. Late Closing reports are sent if system is manually armed after the closing window expires.

Scheduling Menu Mode
The #80 Scheduling Menu Mode is used to program most of the scheduling and timed-event options. Enter Installer Code + [#] + [8] + [0] from the normal operating mode. NOTE: Only users with an Installer or Master level user code may enter the #80 mode. The following can be programmed while in this mode: • time windows • open/close schedules to each partition • holiday schedules • Time-Driven events (for system functions and relay activation) • limitation of access schedules Some scheduling features are programmed in Data Field Programming Mode (Installer Code + 8 0 0 0). Some features are programmed in the #93 Menu Mode. The programming scheduling fields are listed below.
System-Wide Fields: 1*74 –1*75 Relay timeout values 2*01-2*02 Daylight saving time options Allow disarming outside window if alarm 2*11 occurs Partition-Specific Fields: 1*76 Access control relay for this partition 2*05 Auto-arm delay value 2*06 Auto-arm warning time 2*07 Auto-disarm delay value 2*08 Force-arm enable 2*09 Open/Close Reporting by Exception 2*10 Restrict disarm only during windows

Event-driven options are programmed using Output Programming in #93 Menu Mode. Relay activation can also be TimeDriven and that those are programmed using the #80 Menu Mode. Refer to the Time-Driven Event Programming later in this section for the procedure.

6-4

Section 6 – Scheduling Options Steps to Program Scheduling Options
This section contains examples of the worksheets only. For complete worksheets, see the Programming Guide accompanying this Installation and Setup Guide. In order to use #80 Scheduling Menu Mode, use the worksheets to do the following: 1. 2. 3. 4. 5. Define time windows (up to 20) Define the daily open/close schedules (one schedule per day, per partition) Define the holidays to be used by the system (up to 16) Define limitation of access times (up to 8 schedules) Define the Time-Driven events (up to 20)

NOTE: Temporary schedules are programmed using #81 Menu Mode. Use #80 Scheduling Menu Mode to perform the following functions: 6. 7. 8. 9. Program the time windows Program the open/close schedules Program the Time-Driven events Program the access schedules

Scheduling Menu Structure
To program schedules, enter Scheduling Program Mode: Installer Code + [#] + [80]. (Installer or Master level user code.) Scheduling Program Mode can be entered only when all partitions are disarmed. There are 6 sections of scheduling menus accessed via #80, as shown below. Entering 1 at a displayed main menu prompt selects that menu section. Prompts for programming that scheduling feature then appear. Enter 0 to skip a section and display the next menu option.

PROMPT
Time Window ? 1 = YES 0 = NO O/C Schedules ? 1 = YES 0 = NO Holidays ? 1 = YES 0 = NO Timed Events ? 1 = YES 0 = NO 0 0 0 0

EXPLANATION
Upon entering Schedule Menu Mode, this prompt appears. Enter 1 to program time windows. Refer to Time Windows Programming later in this section for detailed procedures. Enter 0 to move to the “O/C Schedules?” prompt. Enter 1 to program opening and closing schedules. Refer to Open/Close Schedules Programming later in this section for detailed procedures. Enter 0 to move to the “Holidays?” prompt. Enter 1 to program holiday schedules. Refer to Holiday Schedule Programming later in this section for detailed procedures. Enter 0 to move to the “Timed Events?” prompt. Enter 1 to program timed events for relay outputs, additional schedules, and other system functions. Refer to Time-Driven Event Programming later in this section for detailed procedures. Enter 0 to move to the “Access Sched?” prompt. Enter 1 to program access schedules. Refer to Limitation of Access Schedules Programming later in this section for detailed procedures. Enter 0 to move to the “Quit?” prompt. Enter 1 to quit #80 Scheduling Menu Mode and return to normal operating mode. 0 Enter 0 to make any changes or review the scheduling programming options. If you press 0, the “Time Window?” prompt is displayed.

Access Sched. ? 1 = YES 0 = NO 0

Quit ? 1 = YES 0 = NO

6-5

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Time Windows
The system provides 20 time windows that are defined with start and stop times. These windows are used for various
open/close and access schedules, as well as for output controls, and are the basis of the scheduling system. These windows are shared among all 8 partitions.

Time Windows Worksheet
The following worksheet is an example of the worksheet found in the Programming Guide. This worksheet will help you define time windows and scheduling aspects of this system before you program them. Note that time windows can span midnight; for example, from 11 PM to 1 AM. Time Window Number 1 2 3…..20 A time window must have a start and a stop time. Start Time (HH:MM) Stop Time (HH:MM)

Time Windows Programming
Enter Scheduling Mode by entering Installer Code + [#] + [80]. The keypad displays the Time Window Programming prompt.

PROMPT
Time Window ? 1 = YES 0 = NO Time Window # ? 01-20, 00 = Quit 01 01 TIME WINDOW 00:00AM 00:00AM 0

EXPLANATION
Enter 1 at this main menu prompt to program time windows.

Enter the 2-digit time window number (01-20) to be programmed. Press [.] to accept the entry. Enter 00 + [.] at the “Time Window #?” prompt to quit time window programming and display the “Quit ?” prompt. If you entered a time window number, the cursor is now positioned on the tens of hours digit of the start of window entry. Enter the desired start of window hour and press [.]. The cursor moves to the minutes position. Enter the desired minutes and press [.]. Toggle the AM/PM indication by pressing any key 0-9 while the cursor is under the A/P position and then press [.]. Repeat this to program the stop of window entry. When the entry is completed, the “Time Window #?” prompt is displayed again. Enter the next time window number to be programmed and repeat the procedure.

Quit ? 1 = YES 0 = NO 0

Enter 0 at the Quit ? prompt to return to the main menu choices and continue programming. Enter 1 to quit Scheduling Menu Mode.

Because the time windows are shared among all partitions, it is important to make sure that changing a time window does not adversely affect desired actions in other partitions.

6-6

Section 6 – Scheduling Options

Daily Open/Close Schedules
Each partition can be assigned one daily open/close schedule, plus a holiday schedule. Temporary schedules are programmed separately, using the #81 Temporary Schedule Menu Mode. To program additional open/close schedules, see Time-Driven Events Programming later in this section for the procedure.

Open/Close Schedule Worksheet
The following worksheet is an example of the worksheet found in the Programming Guide. Write the previously defined time window numbers for open and close for each partition.
Part 1 2 3…8 Mon Op Cl Tues Op Cl Wed Op Cl Thur Op Cl Op Fri Cl Op Sat Cl Sun Op Cl Op Hol Cl

Open/Close Schedule Programming
After entering Scheduling Menu Mode, press [0] until the “O/C Schedules?” prompt appears.

PROMPT
O/C Schedules ? 1 = YES 0 = NO Partition # ? 01-08, 00 = Quit 01 0

EXPLANATION
Enter 1 to program opening and closing schedules.

Enter the appropriate partition number for which the following open/close schedules will apply. Enter 00 + [.] at the “Partition #?” prompt to quit open/close schedules programming and display the “Quit ?” prompt. Enter the time window number 01-20 for the displayed day’s opening schedule beginning with Monday. Enter 00 if no schedule is desired for a particular day. As the number is keyed in, the actual time that has been stored for that window number is displayed as a programming aid. Press [.] to accept the entry.

Mon P1 OP WIND.? 00:00 00:00 00

Mon P1 CL WIND.? 00:00 00:00 00

Enter the time window number for the displayed day’s closing schedule. As the number is keyed in, the actual time that has been stored for the window number is displayed. Press the [.] key to accept the entry. The keypad now prompts for Tuesday’s open/close schedule. Follow the procedure for Monday’s prompts. When the last day of the week has been programmed, the holiday opening and closing window prompts are displayed. Repeat the procedure for the holiday opening and closing time windows. Press the [.] key to accept the entry. When the entries are completed, the “Partition #?” prompt is displayed again. Repeat this procedure for each partition in the system.

Tue P1 OP WIND.? 00:00 00:00 00

Hol P1 OP WIND.? 00:00 00:00 00

Quit ? 1 = YES 0 = NO 0

Enter 0 at the “Quit ?” prompt to return to the main menu choices and continue programming. Enter 1 to quit Scheduling Menu Mode.

6-7

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Holiday Schedules
A holiday schedule overrides the regular daily open/close schedule on the programmed holidays throughout the year. The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. List the desired holidays in a Month/Day format on the worksheet. Check the partitions for which these holidays apply.

Holiday Schedule Worksheet
The following worksheet is an example of the worksheet found in the Programming Guide.
HOL 1 2 3…16 Month/Day / / 1 2 3 Partition 4 5 6 7 8

Holiday Schedule Programming
After entering Scheduling Menu Mode, press [0] until the “Holidays ?” prompt appears.

PROMPT
Holidays ? 1 = YES 0 = NO HOLIDAY NUMBER ? 01-16,00=Quit 01 01 ENTER DATE 00/00 0

EXPLANATION
Enter 1 to program holiday schedules.

Enter the 2-digit holiday number (01-16) to be programmed and press [.] to accept entry. Enter 00 + [.] at the “Holiday Number?” prompt to quit the holiday menus and display the “Quit ?” prompt. The cursor is now positioned on the tens of months digit. Enter the appropriate month, then press [.] to proceed to the day field. Enter the appropriate day for the holiday. Press [.] to accept the entry.

Part ? 12345678 Hit 0-8 x x

Holidays can be set for any partition, as follows. Press [0] to turn all partitions on or off, or use keys 1-8 to toggle the letter “x” under the partition to which this holiday will apply. Press the [.] key when all desired partitions have been assigned. The “Holiday Number?” prompt is displayed again. Repeat the procedure for each holiday to be programmed.

Quit ? 1 = YES 0 = NO 0

Enter 0 at the “Quit ?” prompt to return to the main menu choices and continue programming. Enter 1 to quit Scheduling Menu Mode.

Time-Driven Events
These schedules are used to activate outputs, bypass zones, etc. based on time. There are 20 of these schedules that may be programmed for the system, each governed by the previously defined time windows. The actions that can be programmed to automatically activate at set times are: relay commands, arm/disarm commands, zone bypassing commands, and open/close access conditions.

Time-Driven Events Worksheet
The following worksheet is an example of the worksheet found in the Programming Guide. Fill out the worksheet using the steps outlined below.
Sched Num. 1 2 3…20 Time Window M T W Days T F S S H Action Desired Action Specifier Activation Time

6-8

Section 6 – Scheduling Options
1. 2. Enter the schedule number (01-20) and time window number (01-20), and note the day of the week the action is desired. Enter the code for the desired action and action specifier. The action codes represent the events that are to take place when the scheduled time is reached. Each action also requires an action specifier, which defines what the action will affect (relay, relay group, partition, zone list, user group). The action specifier varies, depending on the type of action selected. The following is a list of the Action Codes (desired actions) used when programming Time-Driven events. Note that these codes are independent of the relay codes programmed during Output Programming in the #93 Menu Mode.
Action Relay On Relay Off Relay Close for 2 seconds Relay Close XX minutes (set in field 1*74) Relay Close YY seconds (set in field 1*75) Relay Group On Relay Group Off Relay Group Close for 2 seconds Relay Group Close XX minutes (set in field 1*74) Relay Group Close YY seconds (set in field 1*75) Action Specifier Relay # Relay # Relay # Relay # Relay # Relay Group # Relay Group # Relay Group # Relay Group # Relay Group #

Relay Commands
Action Code 01 02 03 04 05 06 07 08 09 10

Arm/Disarm Commands
Action Code 20 21 22 23 24 Action Arm-STAY Arm AWAY Disarm Force Arm STAY (Auto-bypass faulted zns) Force Arm AWAY (Auto-bypass faulted zns) Action Specifier Partition(s) Partition(s) Partition(s) Partition(s) Partition(s)

• • •

The auto-arm warning (field 2*06) applies when using Time-Driven events to auto-arm. Temporary schedules do not override an auto-arming or auto-disarming programmed in Time-Driven events. The auto-arming window cannot be extended using the Installer Code + #82 Mode.

Bypass Commands
Action Code 30 31 Action Auto bypass – Zone list Auto unbypass – Zone list Action Specifier Zone list # Zone list #

Open/Close Windows
Action Code 40 41 42 Action Enable Opening Window by partition Enable Closing Window by partition Enable Access Window for access group Action Specifier Partition(s) Partition(s) Access Group

3.

Enter the desired activation time (when the action is to take place). Select from:
Description Beginning of time window. End of time window. During time window active period only (on at beginning of window, off at end). For example, if bypass is selected to activate during the window, zones in a zone list are bypassed at the beginning of the window and unbypassed at the end of the window. Beginning and end of time window (e.g., a coffee break buzzer). In this example, if relay pulse is selected, the relay pulses for 2 seconds at the beginning of the window, signaling the beginning of the coffee break. At the end of the window it pulses again, signaling the end of coffee break.

Activation Time 1 2 3

4

6-9

VISTA-50P/VISTA-50PUL Installation and Setup Guide Time-Driven Event Programming
The following menu items must first be programmed in Output Programming in the #93 Menu Mode: Enter Relay No. Output Group Restriction Output Type ECP Address Relay No. House Code Unit Code (reference identification number) (if applicable) (V-Plex, 4204/4204CF, or X-10) (4204/4204CF) (4204/4204CF) (X-10) (X-10)

After entering Scheduling Menu Mode, press [0] until the “Timed Events ?” prompt appears.

PROMPT
Timed Events ? 1 = YES 0 = NO TIMED EVENT # ? 01-20, 00=Quit 01 0

EXPLANATION
Enter 1 to program timed events.

Enter the timed event number to be programmed (01-20). Press [.]. The system then prompts the user to enter the desired action to be taken. Enter 00 at the “TIMED EVENT #?” prompt to quit the timed event menus and display the “Quit ?” prompt.

01 ACTION ? none 00

Enter the action code for this timed-event number from the list at the left. This could be an output command, an arming command, or any other Time-Driven event. Press [.] to accept the entry. The prompt for the action specifier appears. EXPLANATION Actions 01-05 If you selected actions 01-05, the prompt at the right appears. Enter the relay number. Press [.] to accept entry. The “Time Window ?” prompt appears. ACTION SPECIFIER 01 RELAY # ? 00

ACTION CODES
01=Relay On 02=Relay Off 03=Relay Close for 2 seconds 04=Relay Close XX minutes 05=Relay Close YY seconds 06=Relay Group On 07=Relay Group Off 08=Relay Group Close for 2 seconds 09=Relay Group Close XX minutes 10=Relay Group Close YY seconds 20=Arm-STAY 21=Arm AWAY 22=Disarm 23=Force Arm STAY 24=Force Arm AWAY 40=Enable Open Window by Part. 41=Enable Close Window by Part.

Actions 06-10 If you selected actions 06-10, the prompt at the right appears. Enter the relay group number. Press [.] to accept entry. The “Time Window ?” prompt appears.

01 RELAY GRP # ? 00

Actions 21-24 and 40-41 If you selected actions 21-24 or 40-41, the prompt at the right appears. Enter the partition to which the action applies. Enter 0 to select all partitions. Enter a partition number again to deselect it. Press [.] to accept entry. The “Time Window ?” prompt appears.

PART? 12345678 HIT 0-8 X X

6-10

Section 6 – Scheduling Options
ACTION CODES
30=Auto bypass – Zone list 31=Auto unbypass – Zone list

EXPLANATION Actions 30-31 If you selected actions 30-31, the prompt at the right appears. Enter the zone list number that contains the zones to be bypassed or unbypassed. Press [.] to accept entry. The “Time Window ?” prompt appears.

ACTION SPECIFIER 01 ZONE LIST ? ENTER 01-08 01

42=Enable Access Window for Access group(s)

Action 42 If you selected action 42, the prompt at the right appears. Enter the group number to which the time window will apply. Press [.] to accept entry. The “Time Window ?” prompt appears.

GROUP ? 12345678 HIT 0-8 X

PROMPT
01 Time Window ? 00:00 00:00 01

EXPLANATION
Enter the time window number (01-20) for which this timed event is to occur. As the number is keyed in, the actual time that has been stored for the time window number is displayed. Press [.] to accept entry. Enter the activation time from 1-10 (listed below). As the number is keyed in, the activation time is displayed. The choices are: 1: Trigger at the start of the window. 2: Trigger at the end of the window. 3: Take effect only for the duration of the window. 4: Trigger at both the start and the end of the window. Example: coffee break buzzer. Press [.] to accept entry.

01 Active time ? 0

Days ? MTWTFSSH Hit 0-8 x x

The system then asks for which days the event is to be activated. Press 0 to toggle all days on or off; or press keys 1-8 to toggle the letter “x” under the day on or off (Monday = 1, Holiday = H = 8). When all entries have been made, the “TIMED EVENT #?” prompt is displayed again. Repeat the procedure for each timed event for the installation.

Quit ? 1 = YES 0 = NO 0

Enter 0 at the “Quit ?” prompt to return to the main menu choices and continue programming. Enter 1 to quit Scheduling Menu Mode.

Limitation of Access Schedules
Limitation of Access is a means by which a user’s access code is limited to working during a certain period of time. The system provides 8 Access Schedules, each of which consists of two time windows for each day of the week and two time windows for holidays (typically, one for an opening time window and the second for a closing time window). A user, required to follow a schedule, would be assigned to an access group of the same number (e.g., schedule 1= group 1). The user’s access code is assigned to a group when that user is added to the system. If no limitations apply, enter 0.

Limitation of Access Schedule Worksheet
Enter the appropriate time window numbers for each access schedule.
Acc Sch 1 2 3…8 Mon W1 W2 Tues W1 W2 Wed W1 W2 Thurs W1 W2 W1 Fri W2 W1 Sat W2 Sun W1 W2 Hol W1 W2

NOTE: The holidays used for the access groups are the same as those defined in the holiday schedule.

6-11

VISTA-50P/VISTA-50PUL Installation and Setup Guide Limitation of Access Schedules Programming
To program access schedules enter Scheduling Menu Mode Installer Code + # 80. After entering Scheduling Menu Mode, press [0] until the “Access Sched. ?” prompt appears.

PROMPT
Access Sched. ? 1 = YES 0 = NO ACCESS SCHED # ? 01-08, 00 = Quit 01 0

EXPLANATION
Enter 1 to program access schedules.

Enter the access control schedule number between 01 and 08. Press [.] to accept entry. Enter 00 at the “Access Sched #?” prompt to quit the access control menus and display the Quit ? prompt. Enter the first time-window number (01-20) for this access schedule for the displayed day. As the number is keyed in, the actual time that has been stored for the window is displayed. Press [.] to continue. Enter the second time-window number from 01-20 for this access schedule for the displayed day. As the number is keyed in, the actual time that has been stored for the window is displayed. Press [.] to continue. Repeat the procedure for the other days of the week. When the last day of the week has been programmed, the windows for holidays may be entered.

MON A1 Window 1? 00:00 00:00 00

MON A1 Window 2 ? 00:00 00:00 00

TUE A1 Window 1? 00:00 00:00 00

Hol A1 Window 1 ? 00:00 00:00 00

Enter the first time-window number for holidays for this access schedule. As the number is keyed in, the actual time that has been stored for the window is displayed. Press [.] to continue. Enter the second time-window number for holidays for this access schedule. As the number is keyed in, the actual time that has been stored for the window is displayed. Press [.] to continue. Enter 0 at the “Quit ?” prompt to return to the main menu choices and continue programming. 0 Enter 1 to quit Scheduling Menu Mode.

Hol A1 Window 2 ? 00:00 00:00 00

Quit ? 1 = YES 0 = NO

Temporary Schedules
Each partition can be assigned a temporary schedule, which overrides the regular open/close schedule (and the holiday schedule). This schedule takes effect as soon as it is programmed, and remains active for up to one week. Only users with the authority level of manager or higher can program temporary schedules. A temporary schedule affects only the partition from which it is entered. Temporary schedules can also be reused at later dates simply by scrolling (pressing [#]) to the “DAYS?” prompt and activating the appropriate days. This should be considered when defining daily time windows.

6-12

Section 6 – Scheduling Options Temporary Schedule Worksheet
Partition/Windows 1 Disarm Window Start Time Stop Time Arm Window Start Time Stop Time 2…8 Start Time Stop Time Arm Window Start Time Stop Time HH:MM HH:MM HH:MM HH:MM HH:MM HH:MM HH:MM HH:MM Mon Tue Wed Thu Fri Sat Sun

Disarm Window

Temporary Schedules Programming
Enter User Code + [#] + 81 to enter this mode.

PROMPT
Mon DISARM WIND. 00:00AM 00:00AM

EXPLANATION
This prompt is for entering the start and end times of the disarm (opening) window for Monday. Upon entry of this mode, the cursor is positioned on the tens of hours digit of the start time of the disarm window. Enter the desired hour. Press [.] to move to the minutes field. The minutes are entered in the same manner. Press [.] to move to the AM/PM position. Pressing any key in the 0-9 range toggles the AM/PM indication. Repeat the procedure for the stop time entry. Press [.] to store the entries and move to the arming (closing) window for Monday. Pressing [#] scrolls you through the prompts without making any changes.

Mon ARM WINDOW 00:00AM 00:00AM

This prompt is for entering the start and end times of the arm (closing) window for Monday. The cursor is positioned on the tens of hours digit of the start time of the arm window. Enter the hour. Press [.] to move to the minutes field. The minutes are entered in the same manner. Press [.] to move to the AM/PM position. Pressing any key in the 0-9 range toggles the AM/PM indication. Repeat the procedure for the stop time entry. After the windows for that day have been completed, the system prompts for disarm and arm time windows for the next day. Press [#] if no changes are desired.

Tue DISARM WIND. 00:00AM 00:00AM Days ? MTWTFSS Hit 0-7 x x

Repeat the procedure described above for all days of the week. When all the windows for all the days have been completed, the system prompts for which days of the schedule are to be activated. This is the prompt that actually activates the temporary schedule. To select the days to be activated, enter 1-7 (Monday = 1). An “X” appears under that day, indicating the temporary schedule for that day is active. Entering a day’s number again deactivates that day. Pressing 0 toggles all days on/off. The temporary schedule is in effect only for the days highlighted with the letter “x” under them. As the week progresses, the selected days are reset to the inactive state, but all other entries for the temporary schedule remain programmed. Press [.] to store the entries or press [#] to exit the Temporary Schedule Entry Mode without making any changes.

6-13

VISTA-50P/VISTA-50PUL Installation and Setup Guide

User Scheduling Menu Mode
The system provides up to 20 “timers” available to the end user to control output devices. The output devices themselves are programmed into the system by the installer during Output Programming in the #93 Menu Mode. The end user needs only to know the output device number and its alpha descriptor. The installer may set certain outputs to be “restricted” during Output Programming (this prevents the end user from controlling doors, pumps, bell outputs, etc.) To enter this mode, the user enters User Code + [#] + 83.

PROMPT
Output Timer # ? 01-20, 00=Quit 01 06 07:00P 11:45P PORCH LITE 04

EXPLANATION
Enter the output timer number to be programmed (01-20). Press [.] to accept entry and move to the next prompt. Enter 00 to quit and return to normal operating mode. If that timer number has already been programmed, a summary screen appears. In this example: 06 = Timer # 07:00PM = Start Time 11:45PM = Stop Time PORCH LITE = Descriptor for Output Device # 4 04 = Output Device # affected by this timer Press [.] to continue.

06 ENTER OUTPUT# PORCH LITE 04

Enter the desired output number (01-96). As the number is entered, the descriptor for that output device is displayed. Press [.] to continue.

Entering 00 as the output number deletes the timer (Timer 06, in this example) and displays an output descriptor of “None.” Output devices are programmed via #93 Menu Mode.

PROMPT
06 ON TIME ? 07:00 PM

EXPLANATION
The cursor is positioned on the tens of hours digit of the ON time. Enter the desired hour. Press [.] to move to the minutes field. The minutes are entered in the same manner. The AM/PM indication is toggled by hitting any key from 0-9 while the cursor is under the AM/PM position. Press [.] to continue.

06 OFF TIME ? 11:45 PM

The cursor positioned on the tens of hours digit of the OFF time. Enter the desired hour. Press [.] to move to the minutes field. The minutes are entered in the same manner. The AM/PM indication is toggled by hitting any key in the 0-9 range while the cursor is under the AM/PM position. Press [.] to continue.

06 DAYS? MTWTFSS HIT 0-7 x x

To select the days to be activated, enter 1-7 (Monday = 1). An “x” appears under that day, indicating the output for that day is active. Entering a day’s number again deactivates that day. Pressing 0 toggles all days on/off. The outputs are in effect only for the days highlighted with the letter “x” under them. As the week progresses, the selected days are reset to the inactive state, unless the permanent option is selected (next screen prompt). When completed, press [.] to continue.

06 Permanent ? 0 = NO,1 = YES 0

Selecting “Permanent” (1) means that this schedule will be in effect on a continuous basis. Selecting 0 means that this schedule will be in effect for one week only. The letter “x” under the day is then cleared, but all other entries for the output device remain programmed. Press [.] to accept entry. The system quits User Scheduling Mode and returns to normal operating mode.

6-14

S E C T I O N

7

Downloading Primer
(Remote Downloading is not a UL Listed feature)
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

General Information
Downloading allows the operator to remotely access, program, and control the security system over normal telephone lines. Anything that can be done directly from the keypad can be done remotely, using the COMPASS downloading software. To communicate with the control panel, the following is required: 1. IBM PC-compatible 486 33MHz PC or better with 30 MB of available hard disk space and at least 8MB of RAM (12MB is preferred). Windows 3.X, Windows 95, 98, or Windows NT. One of the following modems: • • • • • • ADEMCO CIA Hayes Smartmodem 1200 (external: level 1.2 or higher; internal: level 1.1 or higher) Hayes Optima 24 + Fax 96 external Hayes Optima 336 BizComp Intellimodem 1200 w/volume BizComp Intellimodem 2400 4. 3.

Access Security
The following four levels of protection guard the control against compromise while it is being accessed from a remote location: 1. Security code handshake: The subscriber’s account number as well as an 8-digit ID number (known only to the office) must be matched between the control and computer. Hang-up and callback: The control panel “hangs up” and calls the computer back at the preprogrammed number only if the security codes match. Data encryption: All data that is exchanged between the computer and control is encrypted to reduce the possibility of anyone “tapping” the line and corrupting data. Operator access levels: Operators may be assigned various levels of access to the downloader, each having its own log-on code. The access levels allow the operators read/write capabilities of the customers’ account information. For a detailed explanation of the access levels, see the downloading software User Manual. Each time the control panel is accessed successfully, a Callback Requested report is sent to the central station, if Opening reports are programmed. When the system is downloading, the keypad displays “MODEM COMM.” After each download or save an automatic time stamp is done, to indicate the last download (or save) and the operator ID number. A complete hard copy of each individual account can be obtained by connecting a printer to the computer. Refer to your computer Owner’s Manual or contact your dealer for printer recommendations.

2.

2.

Other brands are not compatible, even if claimed to be 100% compatible. 3. COMPASS DOWNLOADING software available on CD ROM with a complete User’s Manual. It may also be downloaded from the Honeywell web page. The web address is www.honeywell.com/security. Internal modems must have a 4-position DIP switch. Modems with a 6-position DIP switch will not work.

NOTES: •

• •

7-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Getting On-Line with a Control Panel
At the protected premises, the control panel must be connected to the existing telephone line (refer to SECTION 3: Installing the Control). No programming of the panel is required before downloading to an initial installation unless you are performing an unattended download. When establishing a connection between the computer and the control panel, the following occurs: Stage 1 What Happens The computer calls up the control panel. (The phone number for each customer must be entered into the customer’s account file on the computer.) The control panel answers the phone call at the pre-programmed ring count and executes a handshake with the computer. The computer sends a request for callback to the control, unless callback is not required. The panel acknowledges the request and hangs up. During the next few seconds, the control processes the request, making sure certain encrypted information received from the computer matches its own memory. Upon a successful match, the control panel seizes the phone line and calls the computer back, unless callback is not required. (The phone number to which the computer’s modem is connected must be programmed into the control field .35.) The computer answers, usually by the second ring, and executes a handshake with the panel. The panel then sends other default information to the computer. If this information matches the computer’s information, a successful link is established. The system is now “on-line” with the computer. • 2 To download a control without programming any information, perform the following steps: Step 1 Action Enter the Installer Code + [#] + [5]. The panel temporarily enables a ring count of 5 and sets the Download Callback option to “1” (callback not required). From the computer, call the panel using the downloader software set to “First Communication” Mode. The downloader establishes a session with no callback. The panel information can then be downloaded.

2

On-Line Control Functions
The following functions can be performed while on-line with a control panel (see field *37): • • • • Arm the system in the AWAY Mode; disarm the system Bypass a zone Force the system to accept a new program download Shut down communication (dialer) functions (for nonpayment of monitoring fees in an owned system) Shut down all security system functions (for nonpayment for a leased system) Inhibit local keypad programming (prevents takeover of your accounts) Leave a message for customer NOTE: Messages sent to the control panel from the downloader will be viewable at ALL partitions. • • Command the system to upload a copy of its resident program to the office Read: arming status, AC power status, list of faulted zones, list of bypassed zones, 224 event log, list of zones currently in alarm, list of zones currently in trouble, and ECP equipment list Set the real-time clock

3 4

5

• • •

6

7

Alarms and Trouble responses and reports are disabled during actual uploading or downloading sessions. If you are on-line, but not actively uploading or downloading, all alarms report immediately. All other reports are delayed until you complete the session. The keypads remain active when on-line with a control, but are inactive during actual uploading or downloading sessions.

7-2

Section 24 - Downloading Primer

Direct-Wire Downloading
The VISTA-50P/VISTA-50PUL can be downloaded without using a modem or telephone line by using a 4100SM Serial Module and Compass Downloading Software. The direct-wire downloading connection is to be temporary, and is not part of the permanent installation. Direct-wire downloading is meant as a tool for the installer during the installation process. The connections between the control and the 4100SM are different than those shown in the 4100SM Installation Instructions. See Figure 71 for the correct connections. In addition, in place of the green wire, referred to in step 2 of the “IN CASE OF DIFFICULTY” section of the 4100SM Instructions, use the violet wire instead. Connector J8 on the main PC board (see the Summary of Connections diagram on the inside back cover of this manual) is intended to be interfaced to either a local serial printer (see SECTION 3: Installing the Control) or a computer. Make connections to a computer as shown below. Note that the violet wire connection for a computer differs from that used when connecting a serial printer.

1

2

3

4 NU

5

6

7

8

9

J8 CONNECTOR
YELLOW BROWN VIOLET GREEN BLACK

GRAY

R

ND

ND

ND OU GR

BLUE

RED

OU

OU

T5

T6

2

3

IN

IN

GR

GR

INT

OU

OU

PR

GR

OU

ER

ND

DT

4142TR CABLE (SUPPLIED WITH 4100SM) 4100SM SERIAL MODULE To TB6 Aux. Power (+) (25mA current draw) To TB7 Aux. Power (-)
8 7 6 5 4 3 2 1

+ PWR - (GND) RXD not used not used TXD not used not used
BLUE WHITE

RED

Figure 7-1: Direct-Wire Downloading Connections

Telco Handoff
Telco handoff is another method of getting on-line with the downloader. The installer or customer enters the User Code + [#] + [1], while on the phone line with the computer’s modem phone line. The customer will get cut-off and the panel and download computer will establish a connection.

7-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide

7-4

S E C T I O N

8

Setting the Real-Time Clock
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

General Information
This system provides a real-time clock, which must be set in order for the system’s event log to keep track of events by time and date. It must also be set in order to execute scheduling programs (Time-Driven events). Use a 6160 alpha keypad to set the real-time clock, or set the clock via the downloader software. Only users with Installer or Master authority level can set the clock.

Setting the Time and Date
To set the real time clock, perform the following steps: Step 1 Action Enter Installer or Master Code + [#] 63. Typical display shows: TIME/DATE –– THU 12:01 AM 01/01/90 The day of the week is automatically calculated based on the date entered. Time and date entries are made by simply entering the appropriate hour, minute, month, day and year. Press [.] to move the cursor to the right of the display, to the next position. Press [#] to move the cursor to the left of the display, to the previous position. 2 3 4 Enter the correct hour. Then press [.] to move to the “minutes” field. Enter the correct minutes. Press [.] to move to the AM/PM position. Press any key 0-9 to change AM to PM, or PM to AM. Press [.] to move cursor to the “month” field position. Enter the correct month using a 2-digit entry. Press [.] to move cursor to the “day” field position. Enter the correct day using a 2-digit entry. Press [.] to move cursor to the “year” field position. Enter the correct year. Press [.] to continue. Press [.] to exit the real-time clock edit mode.

5

6

7

8-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide

8-2

S E C T I O N

9

User Access Codes
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

General Information
The VISTA-50P/VISTA-50PUL allows a total of 75 security access codes to be allocated. Each security access code is identified by a user ID number. Regardless of the number of partitions each code has access to, it occupies only one user slot in the system. If a particular code is not used in all partitions, that user ID number cannot be used again. The Quick Arm feature can also be programmed (partition-specific program field *29). The Quick Arm feature allows the user to arm the system by pressing the [#] key instead of the security code. The security code must always be entered to disarm the system. A user code other than the installer code must be programmed in order for the Quick Arm feature to function.

User Codes & Levels of Authority
Each user of the system can be assigned a level of authority, which authorizes the user for certain system functions. A user can have different levels of authority within different partitions Use the “View Capabilities” keypad function (User Code + [.] + [.]) to view the partitions and authority levels for which a particular user is authorized. These levels are described below.

Level 0: Installer (User 1) Code
• • Programmed in field *00 (default = 4-1-4-0). Installer Open/Close reporting selected in field *39. Can perform all system functions (arm, disarm, bypass, etc.), but cannot disarm if armed by another code (or by Quick Arm). Can add, delete, or change all other codes, and can select Open/Close reports for any user. Is the only code that can be used to enter program mode. The Installer Code can be prevented from reentering the Program Mode by exiting using ∗98. Must program at least one Master Code during initial installation. Master Codes are codes intended for use by the primary user(s) of the system. Can perform all normal system functions. Can be used to assign up to 73 lower-level codes, which can be used by other users of the system. Cannot assign anybody a level of 0 or 1. May change his own code. Can add, delete, or change Manager or Operator Codes. Each user’s code can be individually eliminated or changed at any time. Open/Close reporting is automatically the same as that of the Master who is adding the new user.

Level 2: Manager Codes
• • Can perform all system functions (arm, disarm, bypass, etc.) programmed by Master. May add, delete, or change other users of the system below this level (Manager cannot assign anybody a level of 0, 1, or 2). May change his own code. Open/Close reporting is automatically the same as that of the Manager who is adding the new user. Can operate a partition, but cannot add or modify any user code (see table below). Level 3 4 5 • Title Operator A Operator B Operator C Functions Permitted Arm, Disarm, Bypass Arm, Disarm Arm, Disarm only if armed with same code

• •

• •

Levels 3-5: Operator Codes

Level 1: Master Codes
• • • • •

Operator C (sometimes known as the Babysitter Code) cannot disarm the system unless the system was armed with that code. This code is usually assigned to persons who may need to arm and disarm the system at specific times only (e.g., a babysitter needs to control the system only when babysitting).

9-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide Level 6: Duress Codes
• Sends a silent alarm to a central monitoring station if the user is being forced to disarm (or arm) the system under threat (system must be connected to a central station). When the system’s Auxiliary Voltage Triggers are connected to another communication’s media (Derived Channel/Long Range Radio), note that duress is signaled on the same trigger that signals silent panic (whereas duress has its own unique report when digitally communicated). Assigned on a partition-by-partition basis, and can be any code or codes desired. General Rules on Authority Levels and Changes
The following rules apply to users when making modifications within the system based on the user code authority levels: • Master Codes and all lower-level codes can be used interchangeably when performing system functions within a partition (a system armed with a user’s temporary code can be disarmed with the Master Code or another user’s temporary code), except the Operator Level C Code described above. A user may not delete or change the user code of the SAME or HIGHER authority than that which he is assigned. A user (levels 0, 1 and 2 only) may only ADD users to a LOWER authority level. A user may assign other users access to only those partitions to which he himself has access. A user code can be DELETED or CHANGED only from within the partition it was created in. User numbers must be entered in 2 digits. Single-digit user numbers must, therefore, always be preceded by a “0” (e.g., 03, 04, 05, etc.). Make sure the end user understands this requirement. Temporary codes are entered as 4-digit numbers.

Duress Reporting NOTE: A non-zero report code for zone 92 (duress) must be programmed, and partition-specific field *85 duress location enabled, to enable Duress reporting. • The Duress report-triggering logic activates on the 5th key depression (such as OFF), not the 4th key depression (last digit of code). Duress reports are not triggered if the 5th key is a [*], such as when you perform a GOTO or view the capabilities of a user.

• • • • •

Open/Close Reporting Note: When a user is added, the system prompts for Open/Close reporting capability only if the installer is adding the new user. When a Master or Manager adds a new user, the new user’s Open/Close reporting is the same as that of the Master or Manager who is adding the user. If Open/Close reports are required to be selectable by the Master or Manager, the Installer should assign two Master or Manager user codes: one with Open/Close reporting enabled, and one without. Note that Open/Close reporting of Quick Arm is enabled if User 02 is enabled for Open/Close reporting, and that Quick Arm reports as User 00. In order for Quick Arm reports to be sent for all partitions, User 02 must have authority and Open/Close must be enabled for all partitions. If a code with access to all partitions is not desired, it is suggested that user 02 be assigned authority level 5 in all partitions, and that the code be kept secret. Authority level 5 cannot disarm the system unless armed by that user. ADEMCO Contact ID format is capable of reporting Users 01-75 uniquely. If any other report format is used, only user numbers 01 – 15 can uniquely report to the central station. Users 16 – 75 will report as User 15.

Multiple Partition Access
Each user is programmed for a primary (home) partition. A user can also be given access to operate one or more additional partitions. Within each partition, each user may be programmed to have different levels of authority. For example, User 03, the VP of Engineering, could be assigned to work within the Engineering Department (Partition 1) of ABC Manufacturing. Because he needs the full capabilities in his area, he is assigned as a MASTER with Level 1 authority. He must also be able to gain access to the manufacturing area (Partition 2) on an emergency basis. You can set this up easily by requesting that he also be assigned to Partition 2, with a level of authority set lower, such as Level 4 (OPERATOR Level B). The control automatically assigns him the same user number within Partition 2. EXAMPLE OF MULTIPLE PARTITION ACCESS
Part 1 User 3 Level 1 Master Part 2 User 3 Level 4 Oper B Part 3 Part 4 Part 5 Part 6 Part 7 Part 8

In the above example, User 3 has MASTER authority in Partition 1 and OPERATOR B authority in Partition 2. His user number is the same for both partitions. Note that if a user number is already being used in a partition, the system will automatically assign a new user an unused number. Also notice that no access is allowed for this user into Partitions 3 – 8. Attempts to access these partitions would be denied automatically.

9-2

Section 9 – User Access Codes

Adding a Master, Manager, or Operator Code
During user code entry, normal key depressions at other keypads in a partition are ignored. However, panic key depression causes an alarm and terminates user entry. Enter Installer Code†+ [8] + new user no. (02-75) + new user’s code †Or Master or Manager Code, but the code must be a higher level of authority than the code being changed (e.g., a Manager Code can add an Operator-level Code, but cannot add a Master or another Manager Code). Keypad prompts for the authority level for this user.

PROMPT
User Number = 03 Enter Auth. Level

EXPLANATION
Enter the level number as follows: 1 = Master 2 = Manager 3 = Operator Level A 4 = Operator Level B 5 = Operator Level C 6 = Duress Keypad then prompts for Open/Close reporting option for this user.

Open/Close Rep.? 0 = NO , 1 = YES Access Group? Enter 0-8 RF Button ? 0=NO , 1=YES Enter Button ZN # (01-86) Multi-Access ? 0 = NO , 1 = YES Global Arm ? 0 = NO , 1 = YES

Press 0 (NO) or 1 (YES), depending on whether or not arming/disarming by this user will trigger Opening and Closing reports. This prompt appears only if the Installer Code is used to add a user. If access schedules have been programmed, this prompt appears. Enter the user’s access group number (1-8) if this user should have limited access to the system. Enter 0 if no access group should be assigned. If a 5800 Series button transmitter has been enabled for arming/disarming functions, and is not assigned to a user, this prompt appears. Press 0 (NO) or 1 (YES). If you answered “yes” to the RF button question, the zone number for the button is requested. Enter any one of the zone numbers assigned to the button transmitter as AWAY, STAY, or DISARM. The system then assigns all buttons of the transmitter to this user number. Press 0 (NO) if the user is to have access to this partition only. Press 1 (YES) if the user is to have access to more than one partition. If NO, the program exits this mode. If YES, the keypad prompts for the Global Arm option for this user. Press 0 (NO) or 1 (YES), depending on whether this user will be allowed to arm more than one partition via Global Arm prompts. The keypad now prompts for the user’s access to the next partition. Press 0 (NO) or 1 (YES), depending on whether this user will have access to the displayed partition number. If NO, the keypad displays this prompt for the next partition number in sequence. If YES, the keypad prompts for the following: • User’s authority level in the displayed partition (see Authority Level prompt above). • Open/Close option for this user in the displayed partition (see Open/Close prompt above). • Global Arm option for this user in the displayed partition. When all partitions have been displayed, the keypad will scroll through all partitions to which access has been assigned, and will display the user number, authority level, open/close and global arm options that were programmed for each partition to which the user was granted access. For example: Note that the “G” following the authority level indicates that the global arm feature is enabled for this user in the displayed partition, and that the period at the end of the second line indicates Open/Close reporting is enabled for this user in the displayed partition. The “. ” indicates the partition from which the user may be changed or deleted.

Part. 2 – SHOP ? 0 = NO , 1 = YES

Part. 1 A0. WHSE User 03 Auth=3G.

9-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide

Changing a Master, Manager, or Operator Code
Enter Installer Code*+ [8] + new user no. (02-75) + new user’s code *Or Master or Manager Code, but the code must be a higher level of authority than the code being changed (e.g. a Manager Code can add an Operator-level Code, but cannot add a Master or another Manager Code).

PROMPT
User Number = 03 NEW USER?

EXPLANATION
The system detects that the user number is already assigned, and prompts if this is a new user. Press 0 (NO). The system then confirms that the change is allowed based on authorization level.

Adding an RF Key to an Existing User
To add an RF key to an existing user, or to change a user’s global arm option, first delete that user’s code, then re-add the user code as described in the “Adding a Master, Manager, or Operator Code” paragraph.

Deleting a Master, Manager, or Operator Code
Enter your code*+ [8] + new user no. (02-75) + your code again *Or Master or Manager Code, but the code must be a higher level of authority than the code being changed (e.g. a Manager Code can add an Operator-level Code, but cannot add a Master or another Manager Code).

PROMPT
OK TO DELETE 03? 0=NO 1=YES

EXPLANATION
The system prompts to confirm that you want to delete this user. Press 0 (NO) or 1 (YES). If you answered “yes,” that user’s code is removed from all partitions to which it was assigned, and all authorization levels and other information about that user are deleted. Note that a user can be deleted only by a user with a higher authority level. A user cannot delete himself.

A user code can be deleted only from the partition through which it was entered. If an attempt is made to delete from another partition, the message “User [XX] Not Deleted” is displayed.

Exiting the User Edit Mode
Press either [/] or [#], or don’t press any key for 10 seconds.

9-4

S E C T I O N

1 0

Testing the System
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Battery Test
When AC power is present, the VISTA-50P/VISTA50PUL runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery test every 4 hours to check on the battery’s condition. If the VISTA-50P/VISTA-50PUL finds that the battery voltage is low (less than approximately 11.5V), it initiates a keypad “SYSTEM LOBAT” display and a rapid keypad beeping sound. It also sends a Low Battery report to the central station (if programmed). The keypad is cleared by entering any security code + OFF, and a Restore report is sent to the central station if the situation has been corrected.

Dialer Test
The VISTA-50P/VISTA-50PUL may be programmed to automatically transmit test reports to a central station at intervals ranging from once per hour to once per 9999 hours (field .27). UL requires the test report to be transmitted at least once every 24 hours. The system can be programmed to send the first report at any time of the day, or on any day of the week (field .83).

Burglary Walk-Test (Code + [5] TEST)
This test causes the system to sound keypad beeps in response to faults on zones for the purpose of allowing proper zone operation to be checked without triggering alarms. This test can be activated by any-level user by entering the corresponding security code and pressing TEST while the burglary portion of the system is disarmed. UL requires that this test be conducted on a weekly basis. When this test is first entered, the system activates the alarm output for 3 seconds. The system sends a Start of Walk-Test message to the central station. The keypad displays “Burg Walk Test in Progress” and sounds a single beep every 15 seconds while the test remains active. Open and close each protected door and window in turn. Each action should produce 3 beeps from the keypad. Walk in front of any motion detectors. Listen for three beeps when the detector senses movement. The keypad displays the zone number and alpha descriptor while a door or window remains open or while a detector remains activated. The system automatically issues a Zone 8 Glassbreak Detector Power Reset about 10 seconds after it finds a fault on this zone, to allow faulted detectors to be reset. To end this test, enter any security code and press OFF. An End of Walk-Test message is sent to the central station.

Armed Burglary System Test
Alarm messages are sent to the central station during the armed system tests. Notify the central station that a test will be in progress. To perform an armed burglary test, proceed as follows: Step 1 2 A display of “COMM. FAILURE” indicates a failure to communicate (no kissoff by the receiver at the central station after the maximum number of transmission attempts is tried). If this occurs, verify that the phone line is connected, the correct report format is programmed, etc. 3 4 Action Notify the central station that a test of the system is being performed. Arm the system. Fault one or more zones. Silence alarm sounder(s) each time by entering the code and pressing OFF. NOTE: The system must be rearmed after each code + off sequence. Check that entry/exit delay zones provide the assigned delay times.

5

10-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Step 6 Action Check the keypad-initiated alarms, if programmed, by pressing the panic key pairs (. and #, 1 and ., and/or 3 and #). The word ALARM and a descriptor “99” are displayed for . and #. If [1] and [.] are pressed, “95” is displayed; if [3] and [#] are pressed, “96” is displayed. 7 If the system has been programmed for audible emergency, the keypad emits a loud, steady alarm sound. Silence the alarm by entering the security code and pressing OFF. If the system has been programmed for silent panic, there are no audible alarms or displays. A report is sent to the central station, however. Notify the central station that all tests are finished, and verify results with them.

8

Testing Wireless Transmitters
Transmitter ID Sniffer Mode
Use the Transmitter Sniffer Mode to test that transmitters have all been properly programmed.

Go/No Go Test Mode
Checking the transmitters in this mode assists in determining good mounting locations, and verifies that the RF transmission has sufficient signal amplitude margin for the installed system. • All partitions containing wireless transmitters must be placed in the test mode for sensitivity reduction of the RF receiver (50% sensitivity). Otherwise, the RF receiver remains at full strength. Make sure that all partitions are disarmed when performing this test, as the wireless receiver gain is reduced in half.

If a transmitter does not have its serial number “enrolled,” it will not turn off its zone number.

To enter the Transmitter ID Sniffer Mode, proceed as follows: Step 1 Action Enter Installer Code + [#] + [3]. The keypad displays all zone numbers of wireless units programmed into the system. Fault each wireless zone, causing each device to transmit. As the system receives a signal from each of the transmitters, the zone number of that transmitter disappears from the display. 3 Enter Installer Code + OFF to exit the Sniffer Mode.

To enter the Go/No Go Test Mode, proceed as follows: Step 1 2 Action Enter Installer Code + [5]. Fault each wireless transmitter, causing each device to transmit. NOTE: If a single receiver is used, the keypad beeps three times to indicate signal reception. If two receivers are used, the keypad beeps once if the first receiver received the signal, twice if the second receiver received the signal, and three times if both receivers heard the signal. 3 If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in either direction is all that is required. Enter Installer Code + OFF to exit the Go/No Go Test Mode.

2

4

10-2

Section 10 – Testing The System

Trouble Conditions
Check Messages
Display CHECK Description This indicates that a problem exists on the zone number displayed. Zone trouble may be caused by one of the following conditions: • A hardwired fire zone is open (broken wire). • A Day/Night zone (zone type 5) is faulted. • A polling loop zone is not seen by the control panel. • A polling loop zone has been tampered (cover removed on a VPlex device). • A wireless zone has not checked in during the time programmed in field 1.31. • A 5800 Series transmitter has been tampered (cover removed). • A system trouble exists (RF receiver, bell output, etc.). If the problem has been corrected, enter an OFF sequence (Security Code + OFF) twice to clear the display.

Power Failure
Display AC LOSS POWER LED is off Description This indicates that the system is operating on battery power only. Check to see that the circuit breaker for the branch circuit that your system’s transformer is wired to has not been accidentally turned off. Instruct the user to call a service representative immediately if AC power cannot be restored.

Other System Messages
Display COMM FAILURE LO BAT Description This indicates that a failure occurred in the telephone communication portion of your system. This indicates that a low-battery condition exists in the wireless transmitter displayed. Pressing any key silences the audible warning sound. This indicates that a low-battery condition exists with the system’s backup battery. This indicates that the system has more wireless zones programmed than the wireless receiver can support. If this is not corrected, none of the zones in the system will be protected. If additional wireless zones are desired, use an appropriate receiver. This indicates that the control is on-line with a remote computer.

SYSTEM LO BAT RCVR SETUP ERROR

MODEM COMM

To the Installer
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system. The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be included for a specific program of frequent testing (at least weekly) to ensure the system’s proper operation at all times.

Turning the System over to the User
Fully explain the operation of the system to the user by going over each of its functions, as well as the User’s Manual supplied. In particular, explain the operation of each zone (entry/exit, perimeter, interior, fire, etc.). Be sure the user understands how to operate any emergency feature(s) programmed into the system.

10-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide Contacting Technical Support
PLEASE, before you call Technical Support, be sure you: • • • • • • READ THE INSTRUCTIONS! Check all wiring connections. Determine that the power supply and/or backup battery are supplying proper voltages. Verify your programming information where applicable. Verify that all keypads and devices are addressed properly. Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. • Note your customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively.

Technical Support:.................................................... 1-800-645-7492 (8 a.m.-8 p.m. EST) World Wide Web Address: ......................................... http:// www.honeywell.com/security

10-4

A P P E N D I X

A

Regulatory Agency Statements
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

UL Installation Requirements
The following requirements apply to both UL Residential and UL Commercial Burglary installations: • • • • All partitions must be owned and managed by the same person(s). All partitions must be part of one building at one street address. The audible alarm device(s) must be placed where it/they can be heard by all partitions. The control cabinet must be protected from unauthorized access. This can be done by installing a tamper switch on the cabinet door (not supplied with VISTA-50P/VISTA-50PUL) or by installing a UL Listed passive infrared detector positioned to detect cabinet access. Wire the selected device to any EOLR-supervised zone (Zone 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be used for multiple-partitioned systems. Remote downloading and auto-disarming are not UL Listed features.

NOTE: UL Commercial Burglary installations require the attack resistant cabinet. Use COM-UL Commercial Enclosure.

UL609 Local Mercantile Premises/Local Mercantile Safe & Vault
Use the following guidelines for a Local Mercantile Premises/Local Mercantile Safe & Vault installation: • • All zones must be configured for EOLR supervision (.41=0). Wireless sensors may not be used. If 4190SN V-Plexs are used set field .24 to “0” to enable tamper detection. Attach a door tamper switch (supplied) to the VISTA-50P/VISTA-50PUL cabinet backbox. For safe and vault installations, a shock sensor (not supplied) must also be attached to the backbox. (Also see SECTION 3: Installing the Control) Wire an AB12M Bell/Box to the bell output. Bell wires must be run in conduit. Program the bell output for a timeout of 16 minutes or longer timeout and for confirmation of arming ding. (Also see SECTION 3: Installing the Control.) Wire the VISTA-50P/VISTA-50PUL tamper switch and AB12M Bell/Box tamper switches to any EOLR-supervised zone (zones 1-8). Program this zone for day trouble/night alarm (type 05) or 24-hour audible alarm (type 07) response. The 24-hour alarm response must be used for multiple-partitioned systems. Entry delays must not exceed 45 seconds, and exit delays must not exceed 60 seconds.

• •

UL365 Police Station Connected Burglar Alarm
Follow the instructions for UL609 local installations given above.

For Systems without Line Security
• • • You may use the VISTA-50P/VISTA-50PUL dialer alone, or the 7845i-ent Communicator alone. When using the dialer, program it to send Burglary Alarm, Low Battery, and Communicator Test reports. Field .27 must be set to “0024” (or less). If you are using the 7845i-ent, connect it to the VISTA-50P/VISTA-50PUL burglary/audible panic alarm trigger.

For Systems with Line Security
• • You must use a GSMHS Communicator. Connect the GSMHS Communicator to the VISTA-50P/VISTA-50PUL burglary/audible panic alarm trigger.

UL611/UL1610 Central Station Burglary Alarm
Follow the instructions for UL609 Local installations given above.

A-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide For Systems without Line Security
• • You must use the VISTA-50P/VISTA-50PUL’ dialer with a 7845i-ent Communicator. Connect the control’s burglary/audible panic alarm trigger (on J7 header) and the 659EN’s phone line monitor output to the 7845i-ent Communicator. The 7845i-ent Communicator will send a report to the central station when a telephone line fault condition is detected. Also connect the 7845i-ent Communicator’s fault output to one of the VISTA-50P/VISTA-50PUL’ EOLR-supervised zones (i.e., 1-8). Program this zone for a trouble by day/alarm by night (type 05) or a 24-hour alarm (type 07, 08) response to radio faults. Program the control’s dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports.

For Systems with Line Security
Follow the instructions for Systems without Line Security, except use the GSMHS Communicator in place of the 7845ient.

California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup Requirements
The California State Fire Marshal and UL have regulations that require all residential fire alarm control panels to have backup battery with sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. The VISTA-50P/VISTA-50PUL can meet this requirement without using a supplemental power supply, provided that the panel’s outputs (including the current drawn from the auxiliary power output terminals) are limited as shown below: • • • Output current is limited to 750mA maximum total auxiliary power, polling loop, and bell output current. Maximum auxiliary current is 300mA (including polling loop current). A 14AH battery is used. (Yuasa model NP7-12 recommended; use two connected in parallel.) A dual-battery harness is provided with the 4100EOLR Resistor Kit (kit also contains EOL resistors having spade lug/heat shrink tubing construction approved by UL and CSFM for fire zone usage). Both batteries fit inside the panel’s cabinet.

A-2

Appendix A – Regulatory Agency Statements

FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/TV technician for help. INDUSTRY CANADA (IC) STATEMENTS This device complies with RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. This Class B digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.

IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS
In the event of telephone operational problems, disconnect the control panel by removing the plug from the RJ31X (CA38A in Canada) wall jack. We recommend that you demonstrate disconnecting the phones on installation of the system. Do not disconnect the phone connection inside the control panel. Doing so will result in the loss of your phone lines. If the regular phone works correctly after the control panel has been disconnected from the phone lines, the control panel has a problem and should be returned for repair. If upon disconnection of the control panel, there is still a problem on the line, notify the telephone company that it has a problem and request prompt repair service. The user may not under any circumstances (in or out of warranty) attempt any service or repairs to the system. It must be returned to the factory or an authorized service agency for all repairs.

FCC PART 68 NOTICE
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company. This equipment uses the following jacks: An RJ31X is used to connect this equipment to the telephone network. The REN is used to determine the quantity of devices that may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area. If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe necessary. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice in order for you to make the necessary modifications in order to maintain uninterrupted service. If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty information. If the trouble is causing harm to the telephone network, the telephone company may request that you remove the equipment from the network until the problem is resolved. There are no user serviceable components in this product, and all necessary repairs must be made by the manufacturer. Other repair methods may invalidate the FCC registration on this product. This equipment cannot be used on telephone company-provided coin service. Connection to Party Line Service is subject to state tariffs. This equipment is hearing-aid compatible. When programming or making test calls to an emergency number, briefly explain to the dispatcher the reason for the call. Perform such activities in the off-peak hours, such as early morning or late evening.

A-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide CANADIAN EMISSIONS STATEMENTS This Class B digital apparatus complies with Canadian ICES-003 NOTICE The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may cause the telecommunications company to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas. Caution: Users should not attempt to make such connections themselves, but should contact an appropriate electric inspection authority, or electrician, as appropriate. NOTICE: The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5. AVIS L’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection, d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur. Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de télécommunication. Le matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est possible que la conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations. Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de télécommunications peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par l’utilisateur ou à cause de mauvais fonctionnement. Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques et des canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales. Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des installations électriques, ou à un électricien, selon le cas. AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui peuvent être raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.

A-4

A P P E N D I X

B

Summary of System Commands
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

User Code Commands

Add A User Code = User Code + 8 + New User Number + New User’s Code Change a Code = User Code + 8 + User Number + New User’s Code Delete a User’s Code = Your User Code + 8 + User Number to Be Deleted + Your Code Again View User Capability = User’s Code + [.] + [.] Set Real-Time Clock (Installer, Master Only) = Code + [#] + 63

Programming Commands

Site Initiated Download = User Code + [#] + 1. Direct-Wire Download Enable = User Code + [#] + 5. Enter Program Mode = Installer Code + 800. Enter Interactive Program Mode = Installer Code + 800 + [#] + 93 Exit Program Mode = .99 or .98.

Event Logging Commands

Event Log Display = Code + [#] + 60 (Installer or Master Only) Event Log Print = Code + [#] + 61 (Installer or Master Only) Clear Event Log = Code + [#] + 62 (Installer or Master Only) House ID Sniffer Mode = Code + [#] + 2 (Installer Only) Transmitter ID Test = Code + [#] + 3 (Installer Only) Go/No Go Test = Code + 5 (Test Key) Partition GOTO GOTO Home Partition Panics User Code + [.] + Partition Number 0-8. User Code + [.] + 0. [.] + 1 or A Key (Zone 95). [.] + [#] or B Key (Zone 99). [#] + 3 or C Key (Zone 96). View Downloaded Messages Display All Zone Descriptors Display User Self Help Press 0 for 5 Seconds. Press [.] for 5 Seconds. Hold Any Key for 5 Seconds.

Wireless System Commands

Additional Commands

Relay Control Commands Scheduling Commands

Activate Output Device as Programmed = User Code + [#] + 71. Activate Output Device as Programmed = User Code + [#] + 72. Activate Output Device Manually = User Code + [#] + 70. Installer-Programmed Schedule Events = Installer Code + [#] + 80 (Installer or Master Only). Temporary Schedule Editing = User Code + [#] + 81 (Installer, Master, Manager Only). Extend Closing Window = User Code + [#] + 82 (Installer, Master, Manager Only). End User Output Device Programming = User Code + [#] + 83.

Access Control Commands

Activate Access Relay for Current Partition = User Code + 0.

B-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide

B-2

A P P E N D I X

C

Specifications
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

VISTA-50P/VISTA-50PUL CONTROL
Physical: Standard Cabinet (included) 12 1/2" W x 14 1/2" H x 3" D UL Cabinet (optional) Electrical: Voltage Input: Alarm Sounder Output: Auxiliary Power Output: Backup Battery: Standby Time: Circuit Protectors: From 1361 Plug-In Transformer (use 1361CN in Canada) or 1361X10 transformer (for X-10 installations) rated 16.5VAC, 40 VA. 10VDC-13.8VDC, 1.7A max. (UL1023, UL609 installations); 750mA less aux. current draw (UL985 installations). 9.6VDC-13.8VDC, 750mA max. For UL installations, the accessories connected to the output must be UL Listed, and rated to operate in the above voltage range. 12VDC, 4AH or 7AH gel cell. YUASA NP4-12 (12V, 4AH) or NP7-12 (12V, 7AH) recommended. 4 hours min. with 750mA aux. load using 7AH battery. PTC circuit breakers are used on battery input to protect against reverse battery connections and on alarm sounder output to protect against wiring faults (shorts). A solid-state circuit breaker is used on auxiliary power output to protect against wiring faults (shorts). Digital Communicator Formats Supported: Line Seize: Ringer Equivalence: FCC Registration No.: ADEMCO High Speed, ADEMCO 4 + 2 Express, ADEMCO Low Speed, ADEMCO Contact ID, Sescoa and Radionics Low Speed Double Pole 0.7B AC398U-68192-AL-E 14 1/2" W x 18" H x 4.3" D (use COMM-UL Commercial Enclosure)

Remote Keypad
6160 Physical: Width: Height: Depth: Electrical: Voltage Input: Current Drain: Interface Wiring: RED: BLUE: GREEN: YELLOW: BLACK: 12VDC input (+) auxiliary power Not Used Data to control panel Data from control panel Ground and (-) connection from supplemental power supply 12VDC 150mA 7.437 inches 5.25 inches 1.312 inches

C-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide

C-2

A P P E N D I X

D

Contact ID Event Codes
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

TABLE OF CONTACT ID EVENT CODES
Code 110 121 122 123 131 132 133 134 135 150 301 302 305 306 309 321 332 333 373 374 380 381 382 383 384 401 Definition Fire Alarm Duress Silent Panic Audible Panic Perimeter Burglary Interior Burglary 24-Hour Burglary Entry/Exit Burglary Day/Night Burglary 24-Hour Auxiliary AC Loss Low System Battery System Reset Program Tamper Battery Test Fail Bell 1 Trouble Poll Loop Short-Trouble Expansion Module Failure Fire Loop Trouble Exit Error by Zone Trouble (global) Loss of Supervision (RF) Loss of V-PLEX Supervision V-PLEX Sensor Tamper RF Transmitter Low Battery O/C by User Code 403 406 407 408 409 411 441 451 452 453 454 455 457 459 570 602 606 607 621 622 623 624 625 631 632 Definition Power-Up Armed/Auto-Arm Cancel by User Remote Arm/Disarm (Download) Quick Arm Keyswitch O/C Callback Requested Armed STAY Early Open/Close Late Open/Close Fail to Open Fail to Close Auto-Arm Fail Exit Error by User Recent Close Bypass Communicator Test Listen-In to Follow Burglary Walk-Test Event Log Reset Event Log 50% Full Event Log 90% Full Event Log Overflow Time/Date Reset Exception Schedule Change Access Schedule Change

D-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide

D-2

Index
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • #93 Menu Mode Programming...................................... 4-2 #93 Menu Mode Programming Commands .................. 4-3 12/24 Hour Type Stamp Format.................................. 5-13 1361 .....................................................................3-25, C-1 1361CN Transformer................................................... 3-25 1361X10 transformer.................................. 3-17, 3-25, C-1 24-hour Audible Alarm Type 07..................................... 4-6 24-hour Auxiliary Alarm Type 08 ................................... 4-6 24-hour Silent Alarm Type 06........................................ 4-6 2-Wire Latching Glassbreak Detectors ....................... 3-10 2-Wire Smoke Detectors ............................................... 3-7 4100SM ................................................................ 3-20, 4-7 4100SM Serial Module .................................................. 7-3 4146 ............................................................................ 3-18 4197 Polling Loop Extender ........................................ 3-12 4204 and 4204CF Relay Modules............................... 3-17 4286 VIP Module......................................................... 3-20 4297 Polling Loop Extender ........................................ 3-12 4-Wire Smoke Detectors ............................................... 3-8 5800 Series Transmitters ............................................ 3-16 5800TM Module .......................................................... 3-15 5869 ..................................................................... 1-1, 3-13 5881 RF Receivers...................................................... 3-14 6160 ..............................................................................C-1 719 ................................................................................ 3-4 747 ................................................................................ 3-4 Alarm Code for Zones 65–72 ...................................... 5-11 Alarm Code for Zones 73–80 ...................................... 5-11 Alarm Code for Zones 81–88 ........................................ 5-7 Alarm Code for Zones 89–99 ........................................ 5-7 Alarm Output Current Load ......................................... 3-27 Alarm Output Supervision ............................................. 3-4 Alarm Sounder Duration................................................ 5-2 Allow Disarm Outside Window if Alarm Occurs .......... 5-14 Allow Disarming Only During Arm/Disarm Windows... 5-14 ALPHA PROG ............................................................... 4-3 Arm/Disarm Commands................................................ 6-8 Arm-Away Type 21........................................................ 4-6 Arms Lobby ............................................................ 2-2, 5-9 Arm-STAY Type 20 ....................................................... 4-6 Audio Alarm Verification Module ................................. 3-22 Auto Arming .................................................................. 6-1 Auto Disarming.............................................................. 6-1 Auto-Arm Delay.................................................... 5-14, 6-1 Auto-Arm Warning ........................................................ 6-1 Auto-Arm Warning Period ........................................... 5-14 Auto-Disarm Delay ...................................................... 5-14 Auxiliary Output Enable...................................... 3-18, 3-19 Auxiliary Output Mode ................................................. 5-12 Auxiliary Power Current Load...................................... 3-26

B
BACK-UP BATTERY.....................................................C-1 Battery Capacity Worksheet ....................................... 3-27 Battery Selection Table ............................................... 3-28 Battery Test................................................................. 10-1 Burglary Alarm Communicator Delay............................ 5-8 Burglary Trigger for Response Type 8 .......................... 5-3 Burglary Walk Test...................................................... 10-1 Button RF .................................................................... 3-16 Button RF (BR) Type 05................................................ 4-7 Bypass Commands ....................................................... 6-8

A
AAV ............................................................................. 3-22 AB12. ............................................................................ 3-1 ABB1031 ....................................................................... 3-4 AC Loss Keypad Sounding ........................................... 5-2 AC Outlet Ground........................................................ 3-26 Access Group............................................................... 9-3 Access Control ....................................................... 1-2, 4-7 Access Control Commands........................................... B-1 Access Relay Number................................................. 5-13 Access Schedules......................................................... 6-5 Action Code................................................................... 6-8 Action Specifier ............................................................. 6-8 Activation Time.............................................................. 6-8 Adding a User Code ...................................................... 9-3 Adding an RF Key to a User Code ................................ 9-4 Addressing the Keypads ............................................... 3-3 ADEMCO 4+2 Express.................................................. 3-6 ADEMCO 4+2 EXPRESS..............................................C-1 ADEMCO CONTACT ID ................................................C-1 ADEMCO HIGH SPEED................................................C-1 ADEMCO Low Speed.................................................... 3-6 ADEMCO LOW SPEED ................................................C-1 Affects Lobby ......................................................... 2-2, 5-9 Agency Statements ....................................................... A-1 Alarm Code for Zones 01–08 ........................................ 5-6 Alarm Code for Zones 09–16 ........................................ 5-6 Alarm Code for Zones 17–24 ........................................ 5-6 Alarm Code for Zones 25–32 ........................................ 5-6 Alarm Code for Zones 33–40 ........................................ 5-6 Alarm Code for Zones 41–48 ........................................ 5-6 Alarm Code for Zones 49–56 ........................................ 5-7

C
Cabinet Lock ................................................................. 3-1 California State Fire Marshal (CSFM) ........................... A-2 Call Waiting Defeat ..................................................... 5-12 Callback ........................................................................ 7-2 Callback Requested ...................................................... 7-1 CANADIAN EMISSIONS STATEMENTS ...................... A-4 Changing a User Code.................................................. 9-4 Check Messages......................................................... 10-3 Checksum Verification .................................................. 5-5 Chime on External Siren ............................................. 5-12 CIRCUIT PROTECTORS ..............................................C-1 Code + TEST [5] ......................................................... 10-1 Cold Water Pipe.......................................................... 3-26 COMM FAILURE......................................................... 10-3 Common Lobby............................................................. 2-1 Communication Defaults ............................................... 4-4 Communicator Split Reporting Selection .................... 5-11 Compass Downloading Software .................................. 7-3 COMPASS downloading software................................. 7-1

Index-1

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Compatible 2-Wire Smoke Detectors............................ 3-7 Compatible 4-Wire Smoke Detectors............................ 3-8 Compatible 5800 Series Transmitters ......................... 3-16 Compatible Alarm Indicating Devices ........................... 3-4 Compatible Glass Break Detectors ............................. 3-10 Compatible Polling Loop Devices ............................... 3-11 Confirmation of Arming Ding ......................................... 5-2 Contact ID ..................................................................... 1-2 CONTACT ID EVENT CODES ......................................D-1 Contacting Technical Support ..................................... 10-4 Control Unit Power Supply Load ................................. 3-26 Conventions Used in This Manual.................................... vi Cross Zoning Pair Four ............................................... 5-10 Cross Zoning Pair One................................................ 5-10 Cross Zoning Pair Three ............................................. 5-10 Cross Zoning Pair Two................................................ 5-10 Cross-Zoning............................................................... 5-10 CUSTOM INDEX ........................................................... 4-3 event log...................................................................... 3-20 Event Log ...................................................................... 1-2 Event Log Printer On-Line Mode................................. 5-13 Event Log Types ......................................................... 5-13 Event Logging Commands............................................ B-1 Exception Reports......................................................... 6-2 Exit Delay #1 ................................................................. 5-1 Exit Delay #2 ................................................................. 5-2 Exit Delay Reset............................................................ 5-9 Exit Delay Sounding.................................................... 5-12 Exit Error ....................................................................... 1-1 Exit Error Logic Enable ................................................. 5-9 Exiting the User Edit Mode............................................ 9-4 EXPERT MODE ............................................................ 4-3 Extend Closing Window ................................................ 6-1 External Sounders......................................................... 3-4

F
FCC Part 15 STATEMENT............................................ A-3 FCC PART 68 NOTICE................................................. A-3 FCC REGISTRATION NO.............................................C-1 First Communication ..................................................... 7-2 First Test Report Time .................................................. 5-8 Force Arm ..................................................................... 6-1 Force Arm Enable for Auto-Arm.................................. 5-14

D
Data Encryption............................................................. 7-1 Data Field Descriptions ................................................. 5-1 Data Field Programming Mode ..................................... 4-1 Daylight Saving Time Start/End Month........................ 5-13 Daylight Saving Time Start/End Weekend .................. 5-14 Deleting a User Code .................................................... 9-4 DEVICE PROG ............................................................. 4-3 Dial Tone Detection....................................................... 5-5 Dial Tone Pause............................................................ 5-4 Dialer Test ................................................................... 10-1 DIGITAL COMMUNICATOR..........................................C-1 DIP Switch Loop (DP) Type 07...................................... 4-7 Direct-Wire Downloading .............................................. 7-3 Disable Download Callback......................................... 5-12 Disarm Delay................................................................. 6-1 Disarm Type 22 ............................................................. 4-6 Download Command Enables....................................... 5-4 Download ID Number .................................................... 5-4 Download Phone Number ............................................. 5-4 Downloading.................................................................. 7-1 Downloading Access Security ....................................... 7-1 Downloading Requirements .......................................... 7-1 Dual Reporting .............................................................. 5-5 Duress Codes Level 6 ................................................... 9-2 Duress Reporting .......................................................... 9-2

G
General Description ...................................................... 1-1 Getting On-Line with a Control Panel............................ 7-2 Global Arm ? ................................................................. 9-3 Go/No Go Test Mode .................................................. 10-2 Mercantile Premises Listing .......................................... 3-1 Mercantile Safe and Vault Listing.................................. 3-2

H
Hardwire and Optional Expansion Zones...................... 1-1 Hardwired (HW) Type 01 .............................................. 4-6 Holiday Schedule .......................................................... 6-3 Holiday Schedule Programming.................................... 6-7 Holiday schedules ......................................................... 6-4 Holiday Schedules ........................................................ 6-6 House ID Sniffer Mode................................................ 3-15

E
Earth Ground............................................................... 3-26 Enable 5800 RF Button Force Arm ............................. 5-13 Enable 5800 RF Button Global Arm ............................ 5-13 Enable Dialer Reports for Panics & Duress .................. 5-8 Enable GOTO for this Partition.................................... 5-15 Enable J7 Triggers for Partition................................... 5-15 Enable Open/Close Report for Installer Code ............... 5-4 Enable Open/Close report for Keyswitch ...................... 5-4 Entering/Exiting Programming Mode............................. 4-1 Entry Delay #1............................................................... 5-1 Entry Delay #2............................................................... 5-1 Entry Warning ............................................................... 5-8 Entry/Exit #1 Type 01 .................................................... 4-5 Entry/Exit #2 Type 02 .................................................... 4-5

I
ID Digit for Zones 01–08 ............................................... 5-6 ID Digit for Zones 09–16 ............................................... 5-6 ID Digit for Zones 17–24 ............................................... 5-6 ID Digit for Zones 25–32 ............................................... 5-6 ID Digit for Zones 33–40 ............................................... 5-6 ID Digit for Zones 41–48 ............................................... 5-6 ID Digit for Zones 49–56 ............................................... 5-7 ID Digit for Zones 57–64 ............................................... 5-7 ID Digit for Zones 65–72 ............................................. 5-11 ID Digit for Zones 73–80 ............................................. 5-11 ID Digit for Zones 81–88 ............................................... 5-7 ID Digit for Zones 89–99 ............................................... 5-7 Ignore Expansion Zone Tamper.................................... 5-3 Installer (User 1) Code Level 0 ..................................... 9-1

Index-2

Installer Code ................................................................ 5-1 Installing V-PLEX Devices........................................... 3-11 Installing the Control ..................................................... 3-1 Intelligent Test Report ................................................... 5-3 Interior w/Delay Type 10 ............................................... 4-6 Interior, Follower Type 04.............................................. 4-6

Operator Access Levels ................................................ 7-1 Operator Codes Levels 3-5 ........................................... 9-1 Output Device Control Commands ............................... B-1 Output Devices............................................................ 3-17 Overvoltage Protection.................................................. 3-6

K
Keypad Panic Enables .................................................. 5-2 Keypads ................................................................. 2-1, 3-3 Keyswitch .................................................................... 3-18 Keyswitch Assignment .................................................. 5-2 Keyswitch Tamper....................................................... 3-19

P
PA400 ........................................................................... 3-4 PABX Access Code ...................................................... 5-3 Partitioned System ........................................................ 2-1 Partitioning ............................................................. 1-2, 2-1 Perimeter Type 03......................................................... 4-5 Peripherals Devices ...................................................... 1-1 Permanent Keypad Display Backlighting .................... 5-12 Phone Module Access Code......................................... 5-2 polling loop.................................................................. 3-11 Polling Loop Current Draw .......................................... 3-26 Polling Loop Right Loop (PS) Type 08.......................... 4-7 Polling Loop Supervision............................................. 3-12 Power Failure .............................................................. 10-3 Power-Up in Previous State .......................................... 5-3 Prevent Fire Timeout..................................................... 5-2 Prevent Zone XX Bypass .............................................. 5-4 Primary Format ............................................................. 5-5 Primary Phone Number................................................. 5-4 Primary Subscriber’s Account Number ......................... 5-3 Printer Baud Rate........................................................ 5-13 Printer Configurations ................................................. 3-20 Program Modes............................................................. 4-1 Programming................................................................. 4-1 Programming Commands ............................................. B-1 PROGRAMMING COMMANDS .................................... 4-1 Programming Entry Errors ............................................ 4-2 Programming Partition-Specific Data Fields ................. 4-2 Programming Scheduling Options ................................ 6-4 Programming System-Wide Data Fields....................... 4-2

L
Limitation of Access ...................................................... 6-2 Limitation of Access Schedules .................................. 6-10 Limitation Of Access Schedules Programming ........... 6-10 LINE SEIZE ...................................................................C-1 List of Figures....................................................................v LO BAT........................................................................ 10-3 Lobby Partition .............................................................. 5-9 Long Range Radio to J7 Triggers ............................... 3-20 Low Speed Format (Primary) ........................................ 5-5 Low Speed Format (Secondary) ................................... 5-5

M
Manager Codes Level 2 ................................................ 9-1 Master Codes Level 1 ................................................... 9-1 Master Keypad .............................................................. 2-3 MODEM COMM.................................................... 7-1, 10-3 modems ........................................................................ 7-1 Mounting the Control Cabinet........................................ 3-1 Multi-Access ? ............................................................... 9-3 Multiple Alarms.............................................................. 5-2 Multiple Partition Access ............................................... 9-2

Q
Quick Arm .............................................................. 5-3, 9-1

N
No Alarm Response Type 23 ........................................ 4-6 Non-Alarm Report Codes (First Digit) .................. 5-7, 5-11 Non-Alarm Report Codes (Second Digit) ...................... 5-7 Non-Alarm Report Codes Report Codes (Second Digit).......................................................... 5-12 Non-UL Installations ...................................................... 3-4 Normally Closed or EOLR (Zones 2-8) ......................... 5-4 Number of Partitions ................................................... 5-13

R
RADIONICS LOW SPEED............................................C-1 Randomize AC Loss Report.......................................... 5-2 RCVR SETUP ERROR ............................................... 10-3 Real-Time Clock............................................................ 8-1 Recent Close................................................................. 1-1 Regulatory Agency Statements..................................... A-1 Relay commands .......................................................... 6-8 RELAY PGM ................................................................. 4-3 Relay Timeout XXX Minutes ....................................... 5-13 Relay Timeout YYY Seconds ...................................... 5-13 Remote Keypad Sounder............................................ 3-19 Reporting Formats ........................................................ 3-6 Response Types for Zones 01–08 ................................ 5-1 Response Types for Zones 09–16 ................................ 5-1 Response Types for Zones 17–24 ................................ 5-1 Response Types for Zones 25–27, 97, 95, 96, and 99 ....................................................................... 5-1 Response Types for Zones 28–32 ................................ 5-8

O
OC or OPEN CIRCUIT .................................................. 3-3 On-Line Control Functions ............................................ 7-2 Open/Close Reporting................................................... 9-2 Open/Close Reports by Exception ....................... 5-14, 6-3 Open/Close Schedule ................................................... 6-3 Open/Close Schedule Programming............................. 6-6 Open/Close Schedules .......................................... 6-4, 6-6 Open/Close Windows.................................................... 6-8

Index-3

VISTA-50P/VISTA-50PUL Installation and Setup Guide
Response Types for Zones 33–40 ................................ 5-8 Response Types for Zones 41–48 ................................ 5-8 Response Types for Zones 49–56 ................................ 5-8 Response Types for Zones 57–64 ................................ 5-8 Response Types for Zones 65–72 ................................ 5-8 Response Types for Zones 73–80 ................................ 5-8 Response Types for Zones 81–87 ................................ 5-9 Response Types for Zones 88–91 ................................ 5-9 Restore Report Timing .................................................. 5-8 Restrict Disarming......................................................... 6-1 RF Button ? ................................................................... 9-3 RF Receiver Supervision Check-in Interval................. 5-11 RF System Installation Advisories............................... 3-14 RF System Operation and Supervision ....................... 3-13 RF Transmitter Check-in Interval ................................ 5-11 RF Transmitter Low Battery Reporting ........................ 5-11 RF Transmitter Low Battery Sound ............................. 5-11 Ring Count .................................................................... 7-2 Ring Detection Count .................................................... 5-5 RINGER EQUIVALENCE ..............................................C-1 RJ31X............................................................................ 3-6 RJ31X jack .................................................................. 3-21 RLY VOICE DESCR...................................................... 4-3 SYSTEM LO BAT........................................................ 10-3 System LoBat”............................................................. 10-1 System Messages....................................................... 10-3 System Sensor MA 12/24D ........................................... 3-4 System Sensor P12575 ................................................ 3-4

T
Telco Handoff................................................................ 7-3 Telephone Line Connections ........................................ 3-6 TELEPHONE OPERATIONAL PROBLEMS ................. A-3 Temporary Schedule..................................................... 6-3 Temporary Schedules ................................................. 6-11 Temporary Schedules Programming .......................... 6-12 Test Report Interval....................................................... 5-3 Testing The System .................................................... 10-1 Time Driven Events....................................................... 6-2 Time Driven Events Worksheet .................................... 6-7 Time Window Definitions .............................................. 6-2 Time Windows ....................................................... 6-4, 6-5 Time Windows Programming........................................ 6-5 Timed Events ................................................................ 6-5 Time-Driven Event Programming .................................. 6-8 Time-Driven Events....................................................... 6-7 Time-Driven Events Programming ................................ 6-7 TouchTone or Rotary Dial ............................................. 5-3 TouchTone with Rotary Backup .................................. 5-11 Transformer Connections............................................ 3-25 Transmitter Battery Life............................................... 3-16 Transmitter ID Sniffer Mode ........................................ 10-2 Transmitter Input Types .............................................. 3-16 Transmitter Supervision .............................................. 3-16 Trouble by Day/Alarm by Night Type 05 ....................... 4-6 Trouble Conditions ...................................................... 10-3 Turning the System Over to the User.......................... 10-3

S
Scheduling ............................................................. 1-2, 6-1 Scheduling Commands ................................................. B-1 Scheduling Menu Mode................................................. 6-4 Scheduling Menu Structure ........................................... 6-4 Scheduling Report Codes (First Digit .......................... 5-14 Scheduling Report Codes Report Codes (Second Digit).......................................................... 5-15 Secondary Format......................................................... 5-5 Secondary Phone Number ............................................ 5-4 Secondary Subscriber Account Number ....................... 5-8 Send Cancel If Alarm + Off ......................................... 5-12 serial number devices ................................................. 3-11 Serial Number Polling Loop (SL) Type 06..................... 4-7 Serial Printer ............................................................... 3-20 SESCOA .......................................................................C-1 Sescoa/Radionics ......................................................... 3-6 Sescoa/Radionics Select .............................................. 5-5 Siren Driver ................................................................... 3-5 Smoke Power Reversal Module .................................... 3-8 Specifications ................................................................C-1 Standard/Expanded Reporting Primary......................... 5-5 Standard/Expanded Reporting Secondary.................... 5-6 Standby Battery Size................................................... 3-27 Supervised Fire (Without Verification) Type 09............. 4-6 Supervised RF............................................................. 3-16 Supervised RF (RF) Type 03 ........................................ 4-6 Supervision Pulses for LRR ........................................ 5-15 Supervisory and Restore Codes for Zones 01–16 ........ 5-6 Supervisory and Restore Codes for Zones 17–32 ........ 5-6 Supervisory and Restore Codes for Zones 33–48 ........ 5-6 Supervisory and Restore Codes for Zones 49–64 ........ 5-7 Supervisory and Restore Codes for Zones 65–80 ...... 5-11 Supervisory and Restore Codes for Zones 81–99 ........ 5-7 Supplementary Power Supply ....................................... 3-3 Suppress Transmitter Supervision Sound................... 5-12 Swinger Suppression .................................................... 5-8 System Commands ....................................................... B-1 System Communication ................................................ 1-2

U
UL Installation Requirements ........................................ A-1 UL1023 Household Burglary Installations ..................... 3-4 UL365 Police Station Connected Burglar Alarm ........... A-1 UL609 Local Mercantile Premises/Local Mercantile Safe & Vault .......................................................................... A-1 UL611/UL1610 Central Station Burglary Alarm ............ A-2 UL985 Household Fire or Household Fire/Burglary Installations ............................................................... 3-4 UNABLE TO ARM LOBBY PARTITION ........................ 2-2 Unsupervised RF ........................................................ 3-16 Unsupervised RF (UR) Type 04 .................................... 4-6 Use Partition Descriptor .............................................. 5-15 User Access Codes....................................................... 9-1 User Code Authority Levels .......................................... 9-1 User Code Commands.................................................. B-1 User Code Rules........................................................... 9-2 User Scheduling Menu Mode ...................................... 6-12 Users............................................................................. 2-1

V
View Capabilities........................................................... 9-1 VIP Module.................................................................. 3-20 VIP Module Phone Code............................................... 5-2

Index-4

VISTA-50P/VISTA-50PUL Current Load ..................... 3-27

Y
Yuasa .......................................................................... 3-28

W
Wheelock AS-121575W ............................................... 3-4 Wire Run Length/Gauge ............................................... 3-3 Wireless Keypad Assignment ..................................... 5-12 Wireless Keypad Tamper Detect ................................ 5-12 Wireless System Commands ........................................ B-1 Wireless Zone Expansion ........................................... 3-13 Wiring Devices to Zones 1-9 ......................................... 3-6 Wiring the Alarm Output................................................ 3-4 Wiring the Keypads ....................................................... 3-3 Worksheets to calculate the total current.................... 3-26 World Wide Web Address........................................... 10-4

Z
Zone 5 Audio Alarm Verification.................................. 5-13 Zone 87 ....................................................................... 3-21 Zone 9 Fast/Slow Response ......................................... 5-2 Zone Defaults................................................................ 4-4 Zone Index .................................................................... 4-4 Zone Input Type Definitions .......................................... 4-6 Zone Number Designations .......................................... 4-4 ZONE PROG.............................................................vi, 4-3 Zone Response Type Definitions .................................. 4-5 Zone Type Restores for Zone Types 1-8 ...................... 5-7 Zone Type Restores for Zone Types 9, and 10............. 5-7 Zones ............................................................................ 2-1

X
X-10 Devices ............................................................... 3-17

Index-5

WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. • Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly. • Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path. • A user may not be able to reach a panic or emergency button quickly enough. • While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death. • Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection performance can decrease. • Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people. • Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders. • Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately. • This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 20 years, the electronic components could fail at any time. The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be tested as well. Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system. Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property. We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments.

For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa

2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747
Copyright © 2011 Honeywell International Inc. www.honeywell.com/security

ÊN5944ÊN5944-6V2EŠ
N5944-6V2 5/04 Rev B


Uploaded