Lyric T6 PRO WIFI Thermostat Wiring Diagrams



Related Products

Honeywell T6 Pro Z-Wave - Smart Thermostat
Honeywell T6 Pro Z-Wave
Smart Thermostat
Honeywell T6 Pro WIFI - Smart Programmable WIFI Thermostat in front of box
Honeywell T6 Pro WIFI
Smart Programmable WIFI Thermostat
List Price: $312.00
Our Price: $219.99

Related Categories


Document Transcript

ADDENDUM
33-00324-02
Lyric T6 PRO Wiring Diagrams
WIRING DIAGRAMS
Heat only: Gas or Oil Furnace
Cool only
1H/1C: Gas Furnace
W
R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
M36897
1
COMMON REQUIRED.
G USED FOR INDEPENDENT FAN CONTROL ONLY. MOST HEAT
ONLY, GAS OR OIL FORCED AIR SYSTEMS DO NOT USE A FAN
(G) WIRE.
2
1
2
FURNACE
R/Rc
SWITCH UP
O/B
HEAT ONLY.
GAS OR OIL FURNACE.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
M36898
COOL ONLY.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
AIR-HANDLER
Y
R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
1
O/B
R/Rc
SWITCH UP
M36899
1H/1C GAS FURNACE +
AIR-CONDITIONING.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
W
R
G
C
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE
R/Rc
SWITCH UP
O/B
R
W
Y
G
C
1
1 LYRIC T6 PRO WIRING DIAGRAMS
33-00324—02
2
2H/1C: Gas Furnace
2 Transformer System, 1H/1C: Oil
Furnace
2 Transformer System, Hot Water
Heat with Air-Conditioning (or Hot
Water Coil)
Hot Water Boiler, Heat Only
M36900
2H/1C GAS FURNACE +
AIR-CONDITIONING.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE
R/Rc
SWITCH UP
O/B
1
1
R
W
Y
G
C
W2
M36901
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
OIL FURNACE
R/Rc SWITCH
DOWN
O/B
R
W
Y
G
C
R
1
COMMON REQUIRED FROM COOL TRANSFORMER (AIR HANDLER).
1
AIR HANDLER
2 TRANSFORMER SYSTEM
1H/1C OIL FURNACE +
AIR-CONDITIONING.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
M36902
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
BOILER
R/Rc SWITCH
DOWN
O/B
R
W
Y
G
C
R
1
COMMON REQUIRED FROM COOL TRANSFORMER (AIR-HANDLER).
1
AIR HANDLER
2 TRANSFORMER SYSTEM
HOT WATER HEAT +
AIR-CONDITIONING (OR HOT
WATER COIL).
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
M36903
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
BOILER
R/Rc SWITCH
UP
O/B
R (T)
W (T)
HOT WATER BOILER.
HEAT ONLY.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
1
1
C LYRIC T6 PRO WIRING DIAGRAMS
3
33-00324—02
Hot Water Heat with Power Open
Zone Valve
2H/2C: Gas Furnace
1H/1C: Heat Pump without Aux
Heat
M36904
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
BOILER
R/Rc SWITCH
UP
O/B
R (T)
W (T)
HOT WATER HEAT WITH
POWER OPEN ZONE VALVE.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
C
HONEYWELL V8043
ZONE VALVES
1
TH
TR
TRANSFORMER
R
24 VOLTS
END SWITCH
M36905
2H/2C GAS FURNACE +
AIR-CONDITIONING.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE
R/Rc
SWITCH UP
O/B
1
R
W
Y
G
C
W2
Y2
M36906
1H/1C HEAT PUMP
WITHOUT AUX HEAT.
COMPATIBLE T6 MODELS:
TH6210U2001
TH6220U2000
TH6320U2008
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINIAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
1
R
O
Y
G
C
L
2
3
4
1
2
1
3
4 LYRIC T6 PRO WIRING DIAGRAMS
33-00324—02
4
2H/1C: Heat Pump with Electric
Aux Heat
2H/2C: Heat Pump without Aux
Heat
M36907
2H/1C HEAT PUMP WITH
ELECTRIC AUX HEAT.
COMPATIBLE LYRIC T6 MODELS:
TH6220WF2006
TH6320WF2003
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL
DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE.
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE
THROUGH ROUTER/INTERNET CONNECTION AND LYRIC APP OR WIRE
C7089U1006 TO THE TWO “S” TERMINALS.
MOST HEAT PUMPS SHARE THE SAME SET OF HEAT STRIPS FOR AUX AND EM
HEAT. IN THOSE CASES E ISN’T USED. THE TH320WF2006 MODEL CAN BE
CONFIGURED FOR SEPARATE AUX AND E. IF THIS IS DONE, WIRE ONE SET OF
STRIPS TO E TO BE ENERGIZED IN EM HEAT
AND A DIFFERENT SET OF
STRIPS TO AUX TO BE ENERGIZED IN AUX HEAT.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
R
AUX
L
G
C
O
Y
2
3
4
5
6
7
2
3
4
6
7
5
M36908
2H/2C HEAT PUMP
WITHOUT AUX HEAT.
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINIAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
1
R
O
Y
G
C
L
2
3
4
1
2
1
3
4 LYRIC T6 PRO WIRING DIAGRAMS
5
33-00324—02
3H/2C Heat Pump with Electric Aux
Heat
Dual Fuel, 2H/1C: Heat Pump
M36909
3H/2C HEAT PUMP WITH
ELECTRIC AUX HEAT.
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL
DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE.
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE
THROUGH ROUTER/INTERNET CONNECTION AND LYRIC APP OR WIRE
C7089U1006 TO THE TWO “S” TERMINALS.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS! THIS
CAN CAUSE HEAT TO RUN CONTINUOUSLY.
MOST HEAT PUMPS SHARE THE SAME SET OF HEAT STRIPS FOR AUX AND EM
HEAT. IN THOSE CASES E ISN’T USED. THE TH6320WF2006 MODEL CAN BE
CONFIGURED FOR SEPARATE AUX AND E. IF THIS IS DONE, WIRE ONE SET OF
STRIPS TO E TO BE ENERGIZED IN EM HEAT AND A DIFFERENT SET OF STRIPS
TO AUX TO BE ENERGIZED IN AUX HEAT.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
HEAT PUMP/
AIR-HANDLER
R/Rc
SWITCH UP
O/B
1
2
3
4
5
6
7
3
4
7
6
5
R
AUX
L
Y
G
O
C
Y2
2
M36910A
DUAL FUEL
2H/1C HEAT PUMP
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL
DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE.
BALANCE POINT LOCKOUT CAN BE DONE THROUGH ROUTER/
INTERNET CONNECTION AND LYRIC APP OR WIRE C7089U1006 TO
THE TWO “S” TERMINALS.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE/
HEAT PUMP
R/Rc
SWITCH UP
O/B
1
R
AUX
L
G
C
O
Y
2
3
4
5
6
2
3
4
6
5 LYRIC T6 PRO WIRING DIAGRAMS
33-00324—02
6
Dual Fuel, 3H/2C: Heat Pump
ERV or HRV Whole House Ventilator
with Built In Transformer
EARD Fresh Air Damper Powered by
Furnace/Air-Handler Transformer
EARD Fresh Air Damper Powered by
a Dedicated Transformer
M36911
DUAL FUEL
3H/2C HEAT PUMP
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
COMMON REQUIRED.
L ONLY CONNECTED IF HEAT PUMP HAS A FAULT TERMINAL.
SOME HEAT PUMPS USE B RATHER THAN O FOR REVERSING VALVE.
DIFFERENT HEAT PUMP MODELS LABEL THE AUXILIARY HEAT TERMINAL
DIFFERENTLY THAN SHOWN. CONSULT HEAT PUMP WIRING GUIDE.
LOCKOUT OF AUX HEAT ON HIGH OUTDOOR TEMPERATURE CAN BE DONE
THROUGH ROUTER/INTERNET CONNECTION AND LYRIC APP OR WIRE
C7089U1006 TO THE TWO “S” TERMINALS.
DO NOT CONNECT ANY WIRE TO W FOR HEAT PUMP APPLICATIONS!
THIS CAN CAUSE HEAT TO RUN CONTINUOUSLY.
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
FURNACE/
HEAT PUMP
R/Rc
SWITCH UP
O/B
1
2
3
4
5
6
3
4
6
5
R
AUX
L
Y
G
O
C
Y2
2
M36912
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
VENTILATOR
O/B
G
R
ERV OR HRV WHOLE
HOUSE VENTILATOR WITH
BUILT IN TRANSFORMER
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
SEE DIAGRAMS ON PAGES 1-4 FOR HEAT/COOL SYSTEM WIRING.
TERMINAL LABELS VARY BY VENT MAKE/MODEL. ON THE HONEYWELL
TRUEFRESH VENTILATORS THEY ARE LABELED R AND G AS SHOWN.
2
U SWITCH
DOWN
M36913
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
EARD
DAMPER
O/B
EARD FRESH AIR DAMPER
POWERED BY FURNACE/
AIR-HANDLER TRANSFORMER
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
SEE DIAGRAMS ON PAGES 1-4 FOR HEAT/COOL SYSTEM WIRING.
EARD DAMPERS USE APPROX. 8 VA. FOLLOW DIAGRAM WITH SEPARATE
TRANSFORMER IF FURNACE TRANSFORMER NOT SIZED TO HANDLE
ADDITIONAL LOAD.
2
U SWITCH
DOWN
C
R
1
2
FURNACE OR
AIR-HANDLER
VENT
VENT
M36914
S
S
Y
Y2
G
C
U
U
A
W2
W
K
Rc
R
L/A
E
AUX
EARD
DAMPER
O/B
EARD FRESH AIR DAMPER
POWERED BY A DEDICATED
TRANSFORMER
COMPATIBLE LYRIC T6 MODELS:
TH6320WF2003
1
SEE DIAGRAMS ON PAGES 1-4 FOR HEAT/COOL SYSTEM WIRING.
EARD DAMPERS USE APPROX. 8 VA. SEE TRANSFORMER INSTRUCTIONS
FOR WIRING PRIMARY WIRES TO UTILITY POWER.
2
U SWITCH
DOWN
C
R
1
2
TRANSFORMER
VENT
VENT LYRIC T6 PRO WIRING DIAGRAMS
7
33-00324—02 LYRIC T6 PRO WIRING DIAGRAMS
Home and Building Technologies
In the U.S.:
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422-3992
customer.honeywell.com
® U.S. Registered Trademark
© 2017 Honeywell International Inc.
33-00324—02 M.S. Rev. 08-17
Printed in United States


Uploaded