Resideo LTEM-PA / LTEM-PV Auxiliary Wiring Guide - Dated 2021
Related Products
Related Categories
- Cellular Alarm Communicators
- LTE Cellular Communicators
- Verizon LTE Cellular Communicators
- LTE Cellular Communicators
- Internet Alarm Communicators
- Dual-Path Alarm Communicators
- Cellular Alarm Communicators
- AT&T LTE Cellular Communicators
Document Transcript
1
|
P a g e
For more information: resideo.com
©
202
1
Resideo Technologies, Inc
LTEM
-
P
S
ERIES
C
OMMUNICATOR
VISTA
12
VDC
A
UXIL
I
ARY
W
IRING
G
UIDE
When connecting
an LTEM
-
PA or LTEM
-
PV communicator to 12 VDC
auxil
i
ary power,
ensure that the
power supplied meets the current requirements for the
configuration of modules being used.
Connection
to the control panel can be made using the terminal connections
or
a
previously
installed CDMAX or
GSMX4G 4
-
wire harness.
The chart below provides active current requirements for all configurations.
Current requirements for pre
viously installe
d
X
-
style
commumicators are: GSMX4G
–
250mA, and
CDMAX
–
300mA.
LTEM
-
P Series Current Drain Specifications
-
Powered by 12 VDC Aux Power
Model and Configuration
Battery
Installed
Input
Voltage
Active
Current
LTEM
-
PV / PA
with no modules
Yes
12
VDC
263 mA
No
12 VDC
195 mA
*
with PROLTE
-
V /
-
A
Yes
12 VDC
270 mA
No
12 VDC
203 mA
*
with PROWIFIZW
Yes
12 VDC
338 mA
No
12 VDC
270 mA
*
with PRODCM
Yes
12 VDC
304 mA
No
12 VDC
236 mA
*
with PROWIFIZW & PRODCM
Yes
12 VDC
379 mA
No
12 VDC
311
mA
*
with PROLTE
-
V /
-
A & PRODCM
Yes
12 VDC
311 mA
No
12 VDC
244 mA
*
with PROLTE
-
V /
-
A & PROWIFIZW
Yes
12 VDC
345 mA
No
12 VDC
278 mA
*
LTEM
-
PV / PA with ALL modules
Yes
12 VDC
386 mA
No
12 VDC
319 mA
*
*
Note
:
If powered by the panel, you must remove the battery and disable
radio
Low Battery Reporting
Chart 1
Figure 1
Figure 2
For UL Listed installations, the communicator must be powered by the provided
9VDC
Power Adapter only.
12VDC power connection will invalidate
UL Listing.
2
|
P a g e
For more information: resideo.com
©
202
1
Resideo Technologies, Inc
C
URRENT
C
ALCULATION
W
ORKSHEET
Use the
worksheet below to add up the current for each device connected to the
control panel
auxil
i
ary power
.
After totaling
the current requirement for Keypads, Expanders, and Sensors, transfer
the totals to the Summar
y section.
Next, s
ubtract the total
s
from the panels auxil
i
ary power value.
Use
Chart 1 to determin
e
the current draw
the
LTEM
-
P in your configuration. Finally, subtract the
LTEM
-
P
Current
from the
Available Current
.
If the result is greater than zero, you may power the LTEM
-
P from
the con
trol panel.
Device Model
Alarm
Current
No. of
Devices
Total
Current
6128
120 mA
x
=
6128RF
120 mA
x
=
6139
100 mA
x
=
6148
45 mA
x
=
6150
70 mA
x
=
6150RF
105 mA
x
=
6150V
160 mA
x
=
6160
150 mA
x
=
6160RF
150 mA
x
=
6160V
190 mA
x
=
6160PX
165 mA
x
=
6162
120 mA
x
=
6162V
190 mA
x
=
6162RF
210 mA
x
=
6460S/6460W
150 mA
x
=
6280
255 mA
x
=
6290
270 mA
x
=
Tuxedo (TUXW/S)
340 mA
x
=
TuxWiFi
340 mA
x
=
TuxedoW
270 mA
x
=
Other Keypad
x
=
Other Keypad
x
=
K E Y P A D S
Total Keypad Current
Device Model
Alarm
Current
No. of
Devices
Total
Current
4219 Zone Expander
30 mA
x
=
4229 Zone Expander
100 mA
x
=
4204 Relay Module
175 mA
x
=
5881EN Receiver
60 mA
x
=
5883H Transceiver
80 mA
x
=
Other
x
=
Other
x
=
E X P A N D E R S
Total Expander Current
Device Model
Alarm
Current
No. of
Devices
Total
Current
4-Wire Smoke Detectors
x
=
4-Wire CO Detectors
x
=
Motion Detectors
x
=
Glassbreak Detectors
x
=
Other
x
=
Other
x
=
S E N S O R S
Total Sensors Current
- Uploaded