Technical Advisory Bulletin - PG9303 Failure to Indicate Fault Dated May 2019
Related Products
Related Categories
Document Transcript
Technical Advisory
PG
x303
PowerG
Wireless
Magnetic Door/Window
Contact Magnet Alignment
Date:
May
15
, 2019
Region:
Global
Product:
PG
x
303
PowerG Wireless
Magnetic
Door/Window Contact
Brand:
PowerG
Background
We have discovered a potential issue concerning the use of the
PG
x303
PowerG Wireless
Magnetic Door/Window Contact. If this contact is installed in such a way that the magnet is
pulled away from the reed switch along the long edge of the contact, this may result in up to a
20-
second delay in
communicating the violation to t
he panel, and if the magnet
is restored prior
to communication, it
may result in the detector missing the violation. The issue is dependent
upon how quickly the magnet is removed from the device. If the magnet is removed slowly,
such as on a sliding door, it is more
possible
that the issue can
occur.
Status
We are working on the root cause of this potential issue as well as
corrective plans.
In the interim, please ensure that the PG
x303
PowerG Wireless M
agnetic Door/Window
Contact is
installed so that the magnet moves away from the reed switch on either the X or Z
axis, shown in the images
below.
To
minimize the potential occurrence of the issue, the PGx
303
PowerG Wireless Magnetic
Door/Window Contact
must be installed vertically on a door that slides open horizontally, or
horizontally on a window that slides open vertically.
Affected Part Numbers
PowerG W
ireless Magnetic Door/Window Contact
Part Number
Description
Version
PG9303
PowerG Wireless
Magnetic
Door/Window Contact, 915 MHz
All units shipped to
date potentially affected
PG9303BR
PowerG Wireless Magnetic
Door/Window Contact, Brown,
915 MHz
PG8303
PowerG Wireless M
agnetic
Door/Window Contact, 868
MHz
PG8303BR
PowerG Wireless M
agnetic
Door/Window Contact, Brown, 868
MHz
PG4303
PowerG Wireless Magnetic
Door/Window Contact, 433MHz
Instructions for install base and warehouse stock
Any
PG
x303
PowerG Wireless Magnetic Door/Window Contact installed with the magnet
moving away from the reed switch on the ‘Y’ axis as in the photo above should be re-
positioned so that the magnet moves away from the reed switch on the ‘X’ or ‘Z’ axis in the
photo above.
Please contact us with any questions regarding this Technical Advisory
using the contact
information provided below
.
Contact Information
Order Entry
1-888-
888
-7838
Sales
Contact your local sales rep. or email
info@dsc.com
Technical Support
North America: +1
-
800
-
387
-
3630
Latin America: +1-
416-
645
-8083
or email:
intrusion
-
support@tycoint.com
Product Manager
Paolo Concetti
Paolo.Concetti@jci.com
Johnson
Controls
5757 N. Green Bay Avenue | P.O. Box 591 Milwaukee, WI 53201 | 441
-
524
-
1200
- Uploaded