Qolsys TSB #200921 Notice Regarding Installer/Test Mode and PG9936 Smoke/Heat Detectors - Dated 09/21/20



Related Products

DSC PG9936 - PowerG 915MHz Wireless Smoke And Heat Detector
DSC PG9936
PowerG 915MHz Wireless Smoke And Heat Detector
List Price: $190.00
Our Price: $133.99

Related Categories


Document Transcript

TSB #:
200921
DATE:
09/21/20
RE:
NOTICE REGARDING INSTALLER/TEST MODE & PG9936 SMOKE/HEAT DETECTORS
Overview:
Recently, we have discovered a conflict between the “Installer/Test Mode” on the IQ Panel 2+, that is used to
silence the sirens for 30 minutes during installation testing, and the alarm memory LED on PG9936 Smoke/
Heat Detectors (red LED flashing every 4 seconds). When Installer/Test Mode is activated on the IQ Panel 2+ it
can interfere with the PG9936 Smoke/Heat Detector from receiving the Alarm Memory LED reset command
which may result in the detector being left in this state when the testing is completed.
 

Important Note:
A detector in the alarm memory state (red LED flashing once every 4 seconds) is still fully
operational and will detect and report any subsequent fire alarms. While there is no immediate impact to
the detector functionality,
 
we are continuing to investigate the impact that this alarm memory state may
have on the battery life of the PG9936 Smoke/Heat Detectors.
 

Interim Solution:
Option 1: Do not utilize Installer/Test Mode on the Panel; or
 

Option 2: If utilizing Installer/Test Mode, test intrusion sensors first, then disable Installer/Test mode and
proceed to test the PG9936 Smoke/Heat Detectors.
 

In all cases we recommend you validate before leaving the installation that the LED on the PG9936 Smoke/Heat
Detector is not flashing red every 4 seconds. If the LED is flashing you will need to activate/trip the smoke
detector again, then at the IQ Panel 2+ press silence alarm, enter the user code, then disarm the system. The
command from the IQ Panel 2+ will then be sent to the smoke detector to reset the alarm memory LED.
Resolution:
Engineering teams are actively working on the conflict and will be releasing a patch in an upcoming IQ Panel 2+
software revision.
TECHNICAL SERVICE BULLETIN
NOTICE REGARDING INSTALLER/TEST MODE & PG9936 SMOKE/HEAT DETECTORS


Uploaded