Resideo Honeywell Home Vista-21iPLTE - Programming Guide Dated 8/19
Related Products
Related Categories
Document Transcript
Document ID 800-25359V1A Rev. A
ADEMCO VISTA SERIES
VISTA-
21iPLTE/V21SIALTE
Security System
Programming Guide
800-
25359V1A
8/19
Rev
A
–
2
–
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices
Help Provide Proper Coverage for the Protected Premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fir
e Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be
installed outside of
each separate sleeping area, and on each additional floor of a multi
-floor family living unit, including
basements.
The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.
In addition, we
recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. A
lso, an alarm in the hallway outside may not wake
up the sleeper if the door is closed.
•
Install a smoke detector inside bedrooms
where electrical appliances (such as
portable heaters, air conditioners or
humidifiers) are used.
•
Install a smoke det
ector at both ends of a
hallway if the hallway is more than 40 feet
(12 meters) long.
•
Install smoke detectors in any room where
an alarm control is located, or in any room
where alarm control connections to an AC
source or phone lines are made. If detect
ors
are not so located, a fire within the room
could prevent the control from reporting a
fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA
REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION
APPLIANCES.
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows in a
multi-
level building.
In addition, w
e recommend that radio backup be used in a security system so that alarm signals can still be
sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are
normally sent over the phone lines, if connected to
an alarm monitoring station).
–
3
–
TABLE OF CONTENTS
PROGRAMMING MODE COMMANDS
................................
................................
................................
....................
4
DATA FIELD PROGRAMMING FORM
................................
................................
................................
....................
5
*29 INTERNAL DEVICE MENU MODE
................................
................................
................................
..................
10
Configurable Zone Types Worksheets
................................
................................
................................
................
15
*56 ZONE PROGRAMMING MENU MODE
................................
................................
................................
...........
16
*58 EXPERT ZONE PROGRAMMING MODE
................................
................................
................................
........
16
WIRELESS KEY PROGRAMMING & TEMPLATES................................
................................
..............................
17
*57 FUNCTION KEY PROGRAMMING
................................
................................
................................
..................
17
*79 OUTPUT DEVICE MENU MODE
................................
................................
................................
.....................
18
*80 OUTPUT FUNCTION MENU MOD
E ................................
................................
................................
................
18
*81 ZONE LIST MENU MODE
................................
................................
................................
................................
18
*82 ALPHA DESCRIPTOR PROGRAMMING
................................
................................
................................
........
19
SETTING SCHEDULES
................................
................................
................................
................................
..........
20
AVS SYSTEM ENABLE AND QUICK PROGRAMMING COMMANDS
................................
................................
20
UPLOADING/DOWNLOADING VIA THE INTERNET
................................
................................
...........................
21
ZONE TYPE DEFINITIONS
................................
................................
................................
................................
.... 22
SCHEDULES WORKSHEET
................................
................................
................................
................................
.. 23
*56 ZONE PROGRAMMING WORKSHEET
................................
................................
................................
..........
24
*57 FUNCTION KEY WORKSHEET
................................
................................
................................
.......................
26
OUTPUT RELAYS WORKSHEET FOR
∗
79,
∗
80 and
∗
81.
................................
................................
...................
26
*81 ZONE LISTS WORKSHEET
................................
................................
................................
.............................
27
*80 OUTPUT DEFINITIONS
................................
................................
................................
................................
.... 28
5800 SERIES TRANSMITTER INPUT LOOP IDENTIFICATION
................................
................................
..........
30
TABLE OF DEVICE ADDRESSES
................................
................................
................................
.........................
31
UL NOTICES
................................
................................
................................
................................
...........................
31
SIA QUICK REFERENCE GUIDE
................................
................................
................................
..........................
31
FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENTS
................................
...............
32
TELEPHONE/MODEM INTERFACE
................................
................................
................................
......................
32
–
4
–
TO ENTER PROGRAMMING MODE
(usi
ng an alpha keypad connected to the control)
:
Compatibility: This document applies to systems with microprocessor version 4.21
or higher.
A.
POWER UP, then press [
∗
] and [#] at
the same time, within 50 seconds of powering up (this method must be used if
Q
98
was used to exit program mode).
OR
B.
Enter
Installer Code (4112) then
8 0 0.
PROGRAMMING MODE COMMANDS
Task
Command/Explanation
Go to a Data Field
Press [
∗
] + [Field Number], followed by the required entry.
Entering Data
When the desired field num
ber appears, simply make the required entry. When the last entry
for a field is entered, the keypad beeps three times and automatically displays the next data
field in sequence. If the number of digits that you need to enter in a data field is less than the
maximum digits available (for example, the phone number fields *41, *42), enter the desired
data, then press [
∗
] to end the entry. The next data field number is displayed.
Review a Data Field
Press [#] + [Field Number].
Data will be displayed for that
field number. No changes will be accepted in this mode.
Deleting an Entry
Press [
∗
] + [Field Number] + [
∗
].
(Applies only to fields
∗
40 thru *46, *94, and pager fields)
Initialize Download ID
Press
∗
96.
Initializes download ID and subscriber account num
ber.
Reset Factory Defaults
Press
∗
97.
Sets all data fields to original factory default values.
Zone Programming
Press
∗
56.
Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800
RF tra
nsmitters.
Function Key Programming
Press
∗
57.
Unlabeled keypad keys (known as ABCD keys) for special functions
Zone Programming
(Expert Mode)
Press
∗
58.
Same options as *56 mode, but with fewer prompts. Intended for those familiar
with this type of prog
ramming, otherwise *56 mode is recommended.
Output Device Mapping
Press
∗
79.
Assign module addresses and map individual relays/powerline carrier devices
Output Programming
Press
∗
80.
4229 or
4204 Relay modules, Powerline Carrier devices, or
on
-
board triggers
Zone List Programming
Press
∗
81.
Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Alpha Programming
Press
∗
82.
Zone alpha descriptors
IP/
Cell
Programming
Press
∗
29.
For programming the
IP/
Cell
options
.
Exit Program Mode with
installer code lockout
Press
∗
98.
Exits programming mode and
prevents
re
-
entry by: Installer Code + 8 + 0 + 0.
To reenter programming mode, the system must be powered down, then powered up. Then
use method A above. See field *8
8 for other *98 Program mode lockout options.
Exit Program Mode
Press
∗
99.
Exits programming mode and
allows
re
-
entry by:
Installer Code + 8 + 0 + 0
or
method A above.
Scheduling Mode
Enter code + [#] + 64.
Create schedules to automate various system fu
nctions.
Site
-
Initiated Download
Installer code + [#] + 1
(perform while system is disarmed and in normal mode)
USING REMOTE SERVICES
This control supports Remote Interactive Services (RIS)
such as Total Connect 2.0, Tuxedo/Z
-Wave scenes, and
Home Autom
ation (Control 4, 4232CBM), if supported by
the communication service in use.
•
Remote Interactive Services is automatically enabled in
the control; device address 25 is automatically assigned.
•
Use programming field
∗
189 to enable a remote services
emul
ated keypad address.
•
Use
∗
29 Menu mode to enable the communication
device.
•
If using Total Connect 2.0, use AlarmNet 360
to program
the device and enable TC2 services. Be sure to “send”
the programming data to the Communicator.
SPECIAL PROGRAMMING MES
SAGES
•
OC
= OPEN CIRCUIT (no communication between
Keypad and Control).
•
EE
or
ENTRY ERROR
= ERROR (invalid field number
entered; re-enter valid field number).
•
After powering up,
AC, dI
(disabled) or “
Busy Standby
vx.x
(firmware revision)
Dl
will be d
isplayed after
approximately 4 seconds. This will revert to a “
Ready
”
message in approximately 1 minute, which allows PIRS,
etc. to stabilize.
You can bypass this delay by pressing
[#] + [0].
•
If
E4
or
E8
appears, more zones than the expansion
units can
handle have been programmed. The display
will clear after you correct the programming.
AVS QUICK PROGRAMMING COMMANDS (for AAV sessions using the AVS system)
The
following
commands automatically configure the control for AVS operation.
•
installer code
+ [#] + 03
: enable AVS operation
•
installer code + [#] + 04
: enable AVS operation and enable panel sounds on the AVST speaker
•
installer code + [#] + 05
: remove all programming options set by
[#] + 03 quick command
•
installer code + [#] + 06
: remove all programming options set by
[#] + 04 quick command
Refer to the AVS SYSTEM ENABLE and QUICK PROGRAMMING COMMANDS section for details on the specific options that
are set with each command, depending on the control used.
To select the AAV session communi
cation path (phone line/communication device), see field
∗
55 Dynamic Signaling Priority.
To enable AAV operation, use
∗
91 Options field (option 4).
IMPORTANT:
The Real
-Time Clock must be set before the end of the installation. See procedure in the Setting
the Real
-Time Clock section of this manual.
–
5
–
DATA FIELD PROGRAMMING FORM
Entries apply to the VISTA
-21iPLTE/V21SIALTE controls, except where noted, certain fields have special settings for use with SIA installations
(indicated by
V21SIALTE
with heavy borders and reverse type throughout for easy identification).
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
SIA Guidelines:
Notes in certain fields give instructions for programmi
ng the standard VISTA
-21iPLTE for False Alarm Reduction.
IMPORTANT! Make sure the Real-
Time Clock is set before the end of the installation
.
SIA Installations:
The VISTA
-21iPLTE/V21SIALTE is a certified SIA
-compliant control that meets SIA specifications for False Alarm
Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.
∗
20
Installer Code
[4112]
|
|
|
4 digits, 0000
–9999
For security purposes, the factory d
efault installer code should be
changed.
∗
21
Quick Arm Enable
[0,0]
0 = no; 1 = yes
Part. 1
Part.2
∗
22
RF Jam Option
[0]
0 = no RF Jam detection; 1 = send RF Jam report
UL:
must
be
1 if wireless
device
s are
used
∗
23
Quick (Forced) Bypass
[0,0]
0 = no quick bypass
UL:
must
be
“0”
Part. 1
Part. 2
1 = allow quick bypass (code + [6] + [#] )
∗
24
RF House ID Code
[00,00,00]
|
|
|
00 = disable all wireless keypad usage
Part. 1
Part. 2
Common
01–31 = using 5828
keypad
∗
26
Chime By Zone
/
[6, 7]
KP Sound Enables
1
2
For each entry, enter the sum of the desired options. Example Entry
1: f
or Chime by Zone and System Low Battery sounding, enter 5. To
enable all options, enter 7.
Entry 1
0 =
no “entry 1” keypad trouble sounds, AND no chime by zone
(keypad chimes on fault of any entry/exit or perimeter zone
when chime mode is on)
1 =
Chime by Zone enabled
2 =
Communication Device (LRR) trouble sounding enabled (
if
LTE
-21V
module installed
)
4 =
System Low Battery sounding enabled
7 =
select all entry 1 options
Entry 2
0 =
no “entry 2” keypad trouble sounds
1 =
RF Supervision sounding enabled
2 =
RF Low Battery sounding enabled
4 =
RF Jam sounding enabled
7 =
select all entry 2 options
∗
29
Menu Mode for IP/
Cell
Enable
This is
a Menu Mode command
, not
a data field, for programming IP/
Cell
options
. See respective section later in this document.
∗
31
Single Alarm Sounding Per Zone
[0]
0 = unlimited sounding
(bell output)
; 1 = one alarm sounding per zone
V21SIALTE:
If “0” selected, “alarm sounding per zone” will be the
same as the “number of reports in armed period” set in fiel
d *93 (1 if
one report, 2 if 2 reports, unlimited for zones in zone list 7).
∗
32
Fire Alarm Sounder Timeout
[0]
0 = sound stops at timeout; 1 = no timeout
UL
: must
be
“1”
for
fire
install.
∗
33
Alarm Sounder (Bell) Timeout
[1]
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
∗
34
Exit Delay
[60,60]
|
|
00
- 96 = 0 -
96 secs; 97 = 120 secs
Part. 1
Part. 2
UL:
see
inst.
instr.
for
requirements.
Common zones use part. 1 delay.
SIA Guidelines: Minimum exit delay is 45 seconds
V21SIALTE:
45
- 96 = 45 -
96 se
cs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-second delay.
∗
35
Entry Delay #1
[30,30]
|
|
Common zones use same delay as partition 1.
Part. 1
Part. 2
00
- 96 = 0 -
96 seconds; 97 = 120 secs; 98 = 1
80 secs; 99 = 240 secs
SIA Guidelines: Minim
um entry delay is 30 seconds.
V21SIALTE:
30-96 = 30 -
96 secs; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-second delay.
For UL Residential Burglary Alarm installat
ions, must be set for a
maximum of 30 seconds; entry delay plus dial delay should not
exceed 1 min. For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.
∗
36
Entry Delay #2
[30,30]
|
|
See *35 Entry Delay 1 for entries.
Part. 1
Part. 2
∗
37
Audible Exit Warning
[1,1]
0 = no; 1 = yes
Part. 1
Part. 2
SIA Guidelines: Must be enabled.
V21SIALTE:
Feature always enabled; field does not exist.
∗
38
Confirmation Of
Arming Ding
[0,0]
0 = no; 1 = yes (wired keypads and RF)
Part. 1
Part. 2
2 = yes, RF only
(except 5827/5827BD)
UL:
must
be
“1”
for
UL
Commercial
Burglar
Alarm
inst.
SIA
: Must be enabled with a 2, 2.
∗
39
Power Up In
Previous State
[1]
0 = no, always power up disarmed; 1 = yes, power up in previous state
UL:
must
be
“1”
and
SIA
Guidelines:
must
be
a 1.
V21SIALTE:
Feature always enabled; field does not exist.
DIALER PROGRAMMING (
*40
– *42)
Do not
fill unused spaces. Enter 0
–9; #+11 for '
∗
'; #+12 for '#'; #+13 for a 2
-
second pause. If fewer than the maximum digits entered, exit the field by
pressing [
∗
]. The next data field number is displayed.
∗
40
PABX Access Code or
|
|
|
| |
Call Waiting Disable
Enter up to 6 digits. To clear entries,
press
∗
40
∗
. If call waiting is used, enter call waiting disable digits “
∗
(#+11) 70” plus “# + 13” (pause).
NOTES:
1. The call waiting disable feature cannot be used on a PABX
line.
2. Using Call Waiting Disable on a non-call waiting line will
prevent successful communication to the central station.
V21SIALTE:
If call waiting is used, enter call waiting disable digits as
described above, and also set Call Waiting Disable option in field *91.
∗
41
Primary Phone No.
| | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
∗
42
Secondary
Phone No.
|
| |
|
|
|
|
|
|
| |
|
| |
|
|
|
|
|
Enter up to 20 digits. To clear entries, press *
41*
or *
42*
respectively
.
NOTE:
For fields *43 thru *46:
Enter 0
–9; #+11 for B; #+12 for C; #+13 for
D; #+14 for E; #+15 for F. Enter
[
∗
]
as the fourth digit if a 3
-digit account
number (for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a
4-digit account number for Nos. 0000
-0999. Exit field by pressing
∗
if only 3
digits are used. E.g., For Acct.
B234
, enter: #+11 + 2
+ 3 + 4
–
6
–
∗
43
Partition 1 Primary Acct. No.
| | | / |
| | | |
[FFFFFFFFFF] Enter 4 or 10 digits, as
chosen in *48 Report Format. See box above. To clear entries, press
*
43
*.
∗
44
Part. 1 Secondary Acct. No.
(see field *43
for entries)
| | | / |
| | | |
[FFFFFFFFFF] To clear, press
*
44
*
.
∗
45
Partition 2 Primary Acct. No.
(see field *43 for entries)
| | | / |
| | | |
[FFFFFFFFFF] To clear, press
*
45
*
.
∗
46
Partition 2 Secondary Acct. No.
(see field *43 for entries)
| | | / |
| | | |
[FFFFFFFFFF] To clear, press
*
46
*
.
∗
47
Phone System Select
[1]
If Cent. Sta.
is not
on a WATS line: 0=Pulse Dial; 1=Tone Dial;
if Cent. Sta.
is
on
a WATS line: 2 = Pulse Dial ; 3 = Tone Dial
∗
48
Report Format
[77]
0 = 3+1, 4+1 ADEMCO L/S STANDARD
primary
secondary
1 = 3+1, 4+1 RADIONICS STANDARD; 2 = 4+2 ADEMCO L/S STAND.
3 = 4+2 RADIONI
CS STANDARD
5 = 10
-digit ADEMCO CONTACT ID® REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4
-digit ADEMCO CONTACT ID® REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXP.; 9 = 3+1, 4+1 RADIONICS EXP.
∗
49
Split/Dual Reporting
[0]
0 = Standard/backup reporting
only (all to primary)
Primary Phone No.
2nd Phone No.
1 = Alarms, Restore, Cancel
Others
2 = All except Open/Close, Test
Open/Close, Test
3 = Alarms, Restore, Cancel
All
4 = All except Open/Close, Test
All
5 = All
All
∗
50
Burglary Dialer Delay
[2,0]
Delay Time:
Delay Time
V21SIALTE
0 = no delay
UL:
must
be
“0”
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
SIA Guidelines: delay must be a minimum of 15 seconds.
V21SIALTE:
Delay Time:
1 = 15 seconds; 2 = 30 sec
onds; 3 = 45 seconds
Delay Disable:
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6 (use zone list
6 to enter those zones that require dial delay to be disabled;
these zones ignore the setting in entry 1)
UL: Dial del
ay plus entry delay must not exceed one minute; use
zone list 6 to disable dial delay from appropriate zones, if necessary.
∗
53
SESCOA/Radionics Select
[0]
0 = Radionics (0
-9, B
-F); enter “0” for all non-SESCOA formats
1 = SESCOA (0
-9 only reporting)
∗
54
Dynamic Signaling Delay
[0]
Select delay from 0 to 225 secs, in 15
-sec increments.
0 = no delay (both signals sent); 1 = 15 secs; 2 = 30 secs, etc.
NOTE: If
∗
55 is set to “0,” use min.
30 sec to avoid
redundant
IP
rep
ort.
However, this value may need to be adjusted (ex. 45 secs)
depending on the reporting environment.
For UL Burglar Alarm installations with Line Security, must be “0”
∗
55
Dynamic Signaling Priority
/
[0]
AAV
Enable
0 = Primary Dialer
first
/ using AAV via phone line
1 = IP/
Cell
module
first
/ not using AAV
NOTE
: Dynamic signaling applies only to the primary phone number.
Reports intended for the secondary phone number are not sent via
the communication device.
For UL Commercial Burgl
ary installations that use a DACT and
IP/
Cell
, this field must be “0”.
∗
56
,
∗
57
,
∗
58
Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming,
Function Key Programming, and Expert Mode Zone Programming
respectively. See page 2 and re
spective sections later in this document.
TO PROGRAM SYSTEM ST
ATUS, & RESTORE REPO
RT CODES (
∗
59
thru
∗
68, *70 thru
∗
76,
and
∗
89):
For 3+1 or 4+1 Standard Format:
Enter a code in the
first
box: 1–
9, #+10 for 0, #+11 for
B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 (
not
#+10) in the
first
box will disable a report. A 0 (
not
#+10) in the
second
box will
result in automatic advance to the next field.
For Expanded or 4+2 Format:
Enter codes in
both
boxes (1st and 2nd digits) for 1–
9, 0,
or B
–F, a
s described above.
A 0 (
not
#+10) in the
second
box will eliminate the ex
panded message for that report. A
0 (
not
#+10) in
both
boxes will disable the report.
For Ademco Contact ID® Reporting:
Enter any digit (other than 0) in the
first
box, to
enable zone to report (entries in the
second
boxes are ignored).
A 0 (
not
#+10) in the
first
box disables the report.
UL:
see
installation
instructions
for
requirements
SYSTEM STATUS REPORT CODES
(* 59–
*68)
∗
59
Exit Error Alarm Report Code
[0]
V21SIALTE:
[1]
Always
enabled.
∗
60
Trouble Report Code
[10]
|
∗
61
Bypass Report Code
[00]
|
∗
62
AC Loss Report Code
[10]
|
∗
63
Low Bat Report Code
[10]
|
∗
64
Test
Report Code
[00]
|
Use Scheduling mode to set periodic test reports, or use the
following key commands:
installer code +[#] + [0] + 0 = test report sent every 24 hours
installer code +[#] + [0] + 1 = test report sent once per week
installer code +[#] + [0] + 2 = test report sent every 28 day
Each mode sets schedule 32 to the stated repeat option; first test report
sent 12 hours after command.
∗
65
Open Report Code
[0,0,0]
Part. 1
Part. 2
Common
∗
66
Arm Away/Stay Rpt Code
[0,0,0,0,0,0]
Away
Stay
Away
Stay
Away
Stay
Part. 1
Part. 2
Common
∗
67
RF Trans. Low Bat Report Code
[00]
|
UL:
must
be
enabled
if wireless
devices
are
used
∗
68
Cancel Report Code
[00]
|
V21SIALTE:
[10]
Report
enabled.
∗
69
Recent Closing Report Code
[11]
|
V21SIALTE:
Always enabled.
Field does not apply to other controls.
RESTORE REPORT CODES (
∗
70
–
∗
76)
∗
70
Alarm
/Dynamic
Restore Rpt Code
[0]
Dynamic Restore:
Zone restore occurs when the zone returns to a
normal state or when alarm memory is cleared (system disarm
twice). This allo
ws the faulted zone to send a new alarm if the zone
faults a second time without waiting for bell timeout.
Value
Alarm Restore
Report is Sent to
Central Station
Zone Restores...
0
No
after bell timeout or disarm
twice*
*
1
(also 5, 9, D)
*
Yes
after bell t
imeout or disarm
twice*
*
2
(also 6, A, E)
*
No
upon restore of zone (dynamic
restore) or disarm twice*
*
3
(also 7, B, F)
*
Yes
upon restore of zone (dynamic
restore) or disarm twice*
*
* Equivalent alternatives codes for formats other than ADEMCO Cont
act ID
** Upon clearing of alarm memory
*70 programming information continued on next page.
–
7
–
NOTES:
1. Dynamic Restore applies to all zone types except Configurable Zones and
Monitor Zone Type.
2. The number of times a zone can generate an alarm is controlled by the
following four data fields:
Field
Title
Program Values to allow unlimited alarms
∗
31
Single Alarm
Sounding per
zone
Set to 0 -
Unlimited
∗
50
Burglary Dialer
Delay
Must be 0 (No dialer delay), or multiple faults
during Dialer Delay will be ignored.
∗
59
Exit error
Must be 0, or multiple faults will not occur
within 2 minutes of arming on Delay zones
and Interior Followers.
∗
93
Reports per
Armed period
Set to 0 –
Unlimited reports
∗
71
Trouble Restore Rpt Code
[00]
|
∗
72
Bypas
s Restore Rpt Code
[00]
|
∗
73
AC Restore Rpt Code
[00]
|
∗
74
Low Bat Restore Rpt Code
[00]
|
∗
75
RF Trans. Lo Bat Rst Rpt Code
[00]
|
UL:
must
be
enabled
if wireless
dev
ices
are
used
∗
76
Test Restore Rpt Code
[00]
|
OUTPUT AND SYSTEM SETUP (
∗
77
–
∗
93)
∗
77
Daylight Saving Time
[3][11]
|
Start/End Month
0 = Disabled
1-12 = January
-September (1 = Jan, 2 = Feb, etc)
#+10 = October
; #+11 = November; #+12 = December
∗
78
Daylight Saving Time
[2][1]
|
Start/End Weekend
0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth;
5 = last; 6 = next to last; 7 = third to last
∗
79
,
*80
,
*81
,
*82
Menu Modes
These ar
e Menu Mode commands, not data fields, for Output Device
Mapping, Output Programming, Zone List Programming, and Alpha
Programming.
∗
84
Auto Stay Arm
[3]
0 = no; 1 = partition 1 only; 2 = partition 2 only; 3 = both partitions
∗
85
Cross Zone Timer
[0]
This
option
not
for
use
in UL
installations.
(assign cross zones on zone list 4, using *81 Menu mode)
0 = 15 seconds
6 = 2
-1/2 min
#+12 = 8 min
1 = 30 seconds
7 = 3 min
#+13 = 10 min
2 = 45 seconds
8 = 4 min
#+14 = 12 mi
n
3 = 60 seconds
9 = 5 min
#+15 = 15 min
4 = 90 seconds
#+10 = 6 min
5 = 2 minutes
#+11 = 7 min
NOTE:
Cross zoning takes effect only after Exit Delay expires.
∗
86
Cancel Verify Keypad Display
[1]
0 = no “alarm canceled” display
1 = display “Alarm Canceled” when system is disarmed after an
alarm has occurred. (To clear the “ALARM CANCELED” display,
the user must enter the security code + OFF again.)
NOTE:
Applies only when the Dialer is selected as the primary
communication path (
∗
55
= 0).
∗
87
Misc. Fault Delay Time
[0]
(used with Configurable Zone Types “digit 6”)
0 = 15 seconds
6 = 2
-1/2 min
#+12 = 8 min
1 = 30 seconds
7 = 3 min
#+13 = 10 min
2 = 45 seconds
8 = 4 min
#+14 = 12 min
3 = 60 seconds
9 = 5 min
#+15
= 15 min
4 = 90 seconds
#+10 = 6 min
5 = 2 minutes
#+11 = 7 min
UL: may only be used on non
-burglar alarm/ non
-fire alarm zones
when used in fire and/or UL burglar alarm installation
∗
88
Program Mode Lockout Options
[0]
0 = standard *98
installer code lockout (reentry only by [
∗
] + [#] within
50 seconds after power up)
1 = lockout [
∗
] + [#] reentry after *98 exit (reenter via installer code or
downloader only)
2 = lockout local programming after *98 exit (reenter by downloader
only)
∗
89
Event Log Full Report Code
[00]
|
See box above field *59 for report code entries.
∗
90
Event Log Enables
[3]
NOTE
:
System messages are logged when any non-zero entry is made.
0 = None
1 = Alarm/Alarm Restore
2 =
Trouble/Trouble Restore
4 = Bypass/Bypass Restore
8 = Open/Close.
Example:
To select “Alarm/Alarm Restore”, and
“Open/Close”, enter 9 (1 + 8); To select all, enter #15.
∗
91
Option Selection
[8, 0]
Entry 1 Options
Options
V21SIALTE
0 = None
Call Wait Disable
1 = Bell
Supervision Processing
4 = AAV
UL:
must
use
ADEMCO
UVCM
module
or Honeywell
Home
AVS
system
8 = Exit Delay Restart/Reset
UL:
must
be
disabled
“Exit Delay Restart/Reset” option allows use of the [
∗
] key to restart the exit
delay at any time when the system is armed STAY or INSTANT. This feature
also enables automatic exit delay reset, which resets exit delay if the
entry/exit door is re-
opened and closed before exit delay time expires after
arming AWAY. Automatic Exit Delay Reset occurs only once during an armed
AWAY period.
SIA Guidelines: Exit Delay should be enabled.
#+12 = AAV and Exit Delay Restart/Reset
IMPORTANT:
AAV should not be used when Paging or Alarm
Reports are sent to a se
condary number unless the monitoring zone
option is used (which pauses calls). Otherwise, the call to the
secondary number by the communicator after the alarm report will
prevent the AAV from taking control of the telephone line, and the
AAV “Listen in” se
ssion cannot take place.
V21SIALTE:
Entry 1 Options:
Same as above.
Entry 2 Call Waiting Disable:
0 =
call waiting not used
1 =
use call waiting disable digits (
∗
70) entered in field
∗
40;
(when selected, the system dials the entry in
∗
40 only on
alter
nate dial attempts; this allows proper dialing in case call
waiting service is later canceled by the user).
∗
92
Phone Line Monitor Enable
[0,0]
UL:
see
Inst.
Instructions
for
requirements
1
2
Entry 1:
: 0 = disabled, 1
-15 = 1 min -
15 min
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min; #+13 = 13 min; #+14
= 14 min; #+15 = 15 min)
Entry 2
:
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble sound
2 = Same as “1”, plus programmed output devic
e STARTS. If either
partition is armed, external sounder activates also.
NOTE:
If “2” selected, Output Device must either be
programmed to be STOPPED in field *
80 or STOPPED by Code
+ # + 8 + output number.
∗
93
Reports In Armed Period
[1,0]
Per Zone
(Swinger Suppression)
Restrict
V21SIALTE
Restrict Report Pairs:
Report Pairs
Unlimited
0 = Unlimited Reports
report enabled
1 = 1 report pair
2 = 2 report pairs
SIA Guidelines: Must be set for option 2.
V21SIAL
TE:
Restrict Report Pairs:
1 = 1 report pair; [2 = 2 report pairs]
Unlimited Reports Enable:
0 =
restrict reports to the setting in entry 1
1 =
unlimited reports for zones listed in zone list 7; (use zone list
7 to enter those zones that require unlim
ited reporting; these
zones ignore the setting in entry 1)
DOWNLOAD INFORMATION (*94,
*95)
∗
94
Download Phone No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter up to 20 digits, 0
–9; #+11 for '
∗
'; #+12 for '#'; #+13 for a 2
-
second pause. Do not fill unused spaces. If fewer than 20 digits, exit
field by pressing
∗
. To clear entries from field, press
∗
94
∗
.
UL: downloading may be performed only if a technician is at the site.
Up/downl
oading via the Internet has not been evaluated by UL.
–
8
–
∗
95
Ring Count For Downloading
[15]
0 = Disable Station Initiated Download;
1– 14 = number of rings (1
–9, # +10 =10, # +11 =11,
# +12 =12, # +13 =13, # +14 =14);
15 = answering machine d
efeat (# +15 =15).
∗
96
∗
97
Initialize/Reset Defaults
This is a command, not a data field. See page 2.
∗
98
*99
Exit Commands
This is a command, not a data field. See page 2.
PAGER OPTIONS (
*160-
*172)
∗
160
Pager 1 Phone No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter up to 20 digits. 0
–9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-sec pause
∗
161
Pager 1 Characters
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
0– 9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-second pause.
∗
162
Pager 1 Report Options
[0,0,0]
For each partition, selec
t from the following:
P1
P2 common
0 =
no reports sent
1 =
Opens/closes all users
4 =
All alarms and troubles
5 =
All alarms / troubles, and opens/closes for all users
12 =
Alarms / troubles for zones entered in zone list 9
13 =
Alarms / troubles f
or zones entered in zone list 9, and
opens/closes for all users
∗
163
Pager 2 Phone No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter up to 20 digits. 0
–9; #+11 = 'Q'; #+12 = '#'; #
+13 = 2
-sec pause
∗
164
Pager 2 Characters
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
0– 9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-second paus
e.
∗
165
Pager 2 Report Options
[0,0,0]
P1
P2
common
See field *162 for reporting options. Select for each partition (use
zone list 10 if using options 12 or 13).
∗
166
Pager 3 Phone No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter up to 20 digits. 0
–9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-sec pause
∗
167
Pager 3 Characters
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
0– 9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-second pause.
∗
168
Pager 3 Report Options
[0,0,0]
P1
P2 com
mon
See field *162 for reporting options. Select for each partition (use
zone list 11 if using options 12 or 13).
∗
169
Pager 4 Phone No.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ent
er up to 20 digits. 0
–9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-sec pause
∗
170
Pager 4 Characters
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter the optional prefix characters, up to 16 digits.
0– 9; #+11 = '
∗
'; #+12 = '#'; #+13 = 2
-second pause.
∗
171
Pager 4 Report Options
[0,0,0]
P1
P2 common
See field *162 for reporting options. Select for each partition (use
zone list 12 if using option
s 12 or 13).
∗
172
Pager Delay Option For Alarms
[3]
0 = none; 1 = 1 minute; 2 = 2 minutes; 3 = 3 minutes
This delay is for ALL pagers in the system.
MISCELL
ANEOUS SYSTEM FIELDS (*174
-*181)
∗
174
Clean Me Reporting Options
[0]
(for ESL smoke detectors)
0 = disable; 1 = Clean Me signal reports;
NOTE:
If Clean Me is enabled, you must enter “3” in field Q
56
programming for zone 1 response time.
∗
177
Device Duration 1, 2
[0] [0]
(used in *80 Menu mode-Device Actions 5/6)
1
2
0 = 15 seconds
6 = 2
-1/2 min
#+11 = 7 min
1 = 30 seconds
7 = 3 min
#+12 = 8 min
2 = 45 seconds
8 = 4 min
#+13 = 10 min
3 = 60 seconds
9 = 5 min
#+14 = 12 min
4 = 90 seconds
#+10 = 6 min
#+15 = 15 min
5 = 2 minutes
∗
181
50/60 Hertz AC Operation
[0]
0 = 60 Hz; 1 = 50 Hz
CONFIGURABLE ZONE TYPE OPTIONS (*182
-*185)
(see Configurabl
e Zone Type Worksheet on page 15)
∗
182
Configurable Zone Type 90
1
2
3
4
5
6
7
8
9
10
Enter the appropriate value for each entry, 1-10, based on the charts
provided on the next page. Each entry is the sum of the values of its
sel
ected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL:
Do
not
configure
zones
as a fire
alarm
or UL
burglar
alarm
zone.
∗
183
Zone Type 90 Report Codes
IMPORTANT:
Use existing Contact ID® codes, if appropriate, or
define unique c
odes in CID code range 750
-789. See important note
in installation instructions.
90 ALARM ID: XXX
TROUBLE ID: XXX
Enter the desired 3
-digit Contact ID® report codes for alarms and
troubles occurring on zones assigned to this zone type. Enter the
codes sequentially (all 6 digits). When entering digits, [#] moves
cursor back, [
∗
] moves forward.
NOTE:
Zone alarm report codes (prompt in
∗
56 Menu mode) and
trouble report code (
∗
60) and relevant restore codes (
∗
70,
∗
71) must
be enabled in order for the configur
able zone type codes to be
reported.
Press [
∗
] when done to continue.
∗
184
Configurable Zone Type 91
1
2
3
4
5
6
7
8
9
10
See
∗
182 for entries. Press [
∗
] when done to continue.
UL:
Do
not
configure
zones
as a fire
alarm
or UL
burglar
alarm
zone.
∗
185
Zone Type 91 Report Codes
IMPORTANT:
Use existing Contact ID® codes, if appropriate, or
define unique code
s in CID code range 750
-789. See important note
in installation instructions.
91 ALARM ID: XXX
TROUBLE ID: XXX
See *183 for entries.
Press [
∗
] when done to continue.
–
9
–
∗
188
Keypad Lockout
[1]
0 = disable
1 = enable
Alpha keypad display
:
Line 1 “User Code Error:”
Line 2 “Keys 0-
9 Locked”
Fixed Glass keypad display
:
“CE” (Code Error)
If enabled
:
•
The system locks out the keypad for 15 minutes if 30 keystrokes
are made without a valid user code being detected.
(30 keystrokes = 6 attempts of code + command)
•
While locked out, the message "User Code Error" is displayed on
alpha keypads in the partition that is locked out.
•
Upon lockout, a message is transmitted to the central station
(Contact ID event 461 Wrong Code Entry), as well as bei
ng
logged in the event log.
•
When the 15
-minute lockout window expires, a Restore message
is sent to the Central Station and entered into the Event Log.
•
Lockout period ends and the display clears when lockout time
expires, or an alarm occurs, or entry delay begins.
If disabled
:
•
“Wrong Code Entry” (event 461) message is added to Event Log.
•
No report is sent to the central station.
•
No message is displayed on the keypad.
•
No restore event is entered in the event log.
KEYPAD OPTIONS *189
-*196
KE
YPAD NOTES
:
1. Options for keypad 1, address 16 are set by the factory and cannot be
changed.
2. Each keypad must be assigned a unique address. Keypads programmed
with the same address will give unpredictable results.
3. If using Remote Services (IP/
Ce
ll feature), one of the keypad addresses
may be used for limited Remote Services features, though a physical
keypad is not installed.
See
∗
29 Menu Mode section for enabling Remote
Services.
∗
189
Touch Screen Device
(
AUI)
Enable
[1] [1] [0] [0]
AUI 1
AUI 2
AUI 3
AUI 4
System supports up to four touch screen style keypads (e.g.,
Symphony Advanced User Interface, and 6270 Touch Screen
Keypad).
AUI Compatibility Note:
To ensure proper AUI devi
ce operation,
use AUI devices with the following rev levels: 6270 series use version
1.0.9 or higher; 8132/8142 (Symphony) series use version 1.1.175 or
higher.
Device Addresses:
Touchscreen device 1: Must set to 1
Touchscreen device 2: Must set to 2
Touchscreen device 3: Must set to 5
Touchscreen device 4: Must set to 6
Enter each touch screen keypad’s home partition option 0
-7:
For Touchscreen device usage
0 = disable
1 = partition 1
2 = partition 2
3 = partition 3 (common)
For Remote Serv
ices device usage
5 = part. 1 (auto
-stay arm disabled)
6 = part. 2 (auto
-stay arm disabled)
7 = part. 3 (common; auto-stay arm disabled)
Note for Remote Services Devices:
If using the Remote Services feature of
the communication device, select an option
5-7, depending on the partition
the
Remote Services device is associated with (these options automatically
disable auto
-stay arming when the system is armed from the respective
Remote Services device).
By default, the Total Connect (virtual) keypad will
be set to address 2 in the communicator programming. To avoid a
“Setup/Programming” error message, when installing this system for use with
Total Connect 2.0, the suggested input of 1,5,0,0 assumes this programming
has been left at default and assumes you have a touchscreen keypad
installed for partition 1 at address 1.
Refer to the communication device’s installation instructions for details on
enabling the Remote Services feature.
Remote Services Device Address:
Using an AUI device address for Remote
Se
rvices provides enhanced remote services features, but an actual AUI
device cannot use the same address. If no AUI addresses are available (all
four AUIs are being used), Total Connect 2 cannot be used for remote
services. However, Total Connect 1 can be u
sed by choosing an available
standard keypad address and using the appropriate keypad address field
*190
- *196 to select the Remote Services operating partition (some remote
access features will be unavailable).
NOTES:
1. Use of touch screen style keypads does not affect the number of standard
keypads supported.
2. If using Remote Services (IP/Cell feature), one of the touch screen (AUI)
addresses may be used for enhanced Remote Services feature set, though a
physical touch screen is not installed. See
∗
29 Menu Mode section for enabling
Remote Services
.
∗
190
Keypad 2 Device Address 17
[1] [0]
Entry 1: Partition/ Enable
Part.
Sound
For
Standard Keypad
usage
0 = disable
1 = partition 1
2 = partition
2
3 = partition
3 (common)
For Remote Services device usage
(see note below)
5 = partition. 1 (auto
-stay arm disabled)
6 = partition
2 (auto
-stay arm disabled)
7 = partition
3 (common; auto
-stay arm disabled)
Entry 2: Keypad
Sounds
(for system trouble sound options, see
∗
26)
0 = no suppression
1 = suppress arm/disarm and Entry/Exit beeps
2 = suppress chime beeps only
3 = suppress arm/disarm, Entry/Exit, and chime beeps
Note for Remote Services Devices:
If using the Remote Services
feature of the communication device, sel
ect an option 5
-7,
depending on the partition the Remote Services device is
associated with (these options automatically disable auto
-stay
arming when the system is armed from the respective Remote
Services device). Refer to the communication device’s inst
allation
instructions for details on enabling the Remote Services feature.
∗
191
Keypad 3 Device Address 18
[1] [0]
See field
∗
190 for entries.
Partition
Sound
∗
192
Keypad 4 Device Address 19
[1] [0]
See field
∗
190 for entries.
Partition
Sound
∗
193
Keypad 5 Device Address 20
[1] [0]
See field
∗
190 for entries.
Partition
Sound
∗
194
Keypad 6 Device Address 21
[1] [0]
See field
∗
190 for entries.
Partition
Sound
∗
195
Keypad 7 Device Address 22
[1] [0]
See field
∗
190 for entries.
Partition
Sound
∗
196
Keypad 8 Device Address 23
[1] [0]
See field
∗
190 for entries.
Partition
Sound
∗
197
Exit Time Display Interval
[0]
0 = no display; 1-5 = seconds between display refresh
NOTE:
If enabled and using only 2
-digit fixed-word keypads (e.g.,
6150RF), do not set exit delay tim
e greater than 96 seconds. See
Inst. Instr. for explanation.
TOUCH SCREEN DEVICE NOTE:
If using more than one touch
screen device (e.g., 62
80,
TUXEDO
) with the system, leave field
*197 Exit Time Display Interval set to the default value “0.” The 6280
aut
omatically displays remaining exit time in one
-second increments.
∗
198
Display Partition Number
[0]
(for Alpha Display Keypads)
0 = no; 1 = yes (partition no. appears on Alpha Display)
∗
199
ECP Fail Display
[0]
0 = 3
-digit display (“1” + device address)
1 = 2
-digit fixed-display as “91”
–
10
–
*29 INTERNAL DEVICE MENU MODE
(for Programming IP and Cell Module Options)
This mode programs the Internet connection (IP) and LTE
-21V Module
configuration, collectively referr
ed to as the Internal Device.
NOTE:
The Internal Device is automatically set to address 3 and cannot be
changed.
IMPORTANT:
The use of the IP connection or the LTE
-21V module
requires an AlarmNet
–I account. Please obtain the account
information from the central station prior to programming this module.
The following section describes the programming of the internal device
options using an alpha keypad. Alternatively, these options can be
programmed via the AlarmNet 360 website. After programming is
comp
lete,
the control must be registered
with AlarmNet (via the control’s
RJ45 Internet connection). Refer to the Registration with AlarmNet section
for procedures.
Using an Alpha Keypad as a 7720P Programming Tool
When programming IP/Cell features (with
∗
29 menu mode), the alpha keypad
mimics the functions of the 7720P Programming Tool. See figure at right and
table below for 7720P key functions. Each key has two possible functions: a
normal function and a SHIFT function.
Normal functions:
The numeric value
s labeled directly on the keys and the
left-hand functions shown in diagram on the ABC keys. To perform a normal
key function, simply press the desired key.
SHIFT functions:
Those functions shown in diagram above the numerical
keys and the right
-hand fun
ctions shown on the ABC keys. To perform a
SHIFT key function, press SHIFT key (D key), then press the desired function
key (shift function is indicated by the lit READY LED).
7720P Emulation Template for Alpha Keypads
Normal and SHIFT key Functions While in
∗
29 Menu Mode
Key
Normal Key Function
SHIFT Key Function
(A) = BS/ESC
[BS]: Press to delete entry
[ESC]: Press to quit Program Mode
Also, can reset
EEPROM
defaults
†
(B) =
↓
/
↑
[
↓
]: Scroll dow
n programming
[
↑
]: Scroll up programming
(C) = N/Y
[N]: Press for "NO" answer
[Y]: Press SHIFT
-
Y for "YES" answer
(D) = SHIFT
Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is pressed. Press again for each
SHIF
T function desired.
1/A
[1]: For entering the number 1
[A]: Used for entering C.S. ID number
2/B
[2]: For entering the number 2
[B]: Used for entering C.S. ID number
3/C
[3]: For entering the number 3
[C]: Used for entering C.S. ID number
4/D
[4]: For
entering the number 4
[D]: Used for entering C.S. ID number
5/E
[5]: For entering the number 5
[E]: Used for entering C.S. ID number
6/F
[6]: For entering the number 6
[F]: Used for entering C.S. ID number
7/S
[7]: For entering the number 7
[S]: Press t
o display diagnostic status
8/T
[8]: For entering the number 8
[T]: Press to send TEST messages
9/X
[9]: For entering the number 9
[X]: Press to reset the IP/Cell
[
∗
] / SPACE
[
∗
]: Used to select programming options
[SPACE]: Not used
0
[0]: For entering
the number 0
[#] / ENTER
[#] / ENTER: Press to accept entries
No SHIFT function
†
Active only when the "REVIEW?" prompt is displayed
INTERNAL DEVICE (IP AND CELL) DEFAULT VALUES
OPTION
STANDARD DEFAULT VALUE
ACTUAL ENTRY
1
Internal Device
IP
2
Multi
-
Mode
Disabled
3
Multi
-
Mode Address
?? (if Multi
-
Mode enabled)
4
Primary City ID
??
5
Primary CS ID
??
6
Primary Sub ID
????
7
Remote Access
N
8
Keypad Address (for Remote Access)
?? (if Remote Access enabled)
9
Supervision
24 Hours
10
Cell Rollover Y/N
N (if Cell enabled)
11
Cell 24Hr Tst Y/N
N (if Cell enabled)
12
Old Alarm Time
10 Minutes
13
IP Fault Time
00 Minutes
14
Cell Fault Time
00 Minutes (if Cell enabled)
15
Notify Panel Of
Neither Fault (if IP and Cell enabled)
16
Use DHCP Y/N
Y (if IP or IP/ Cell enabled)
17
NIC IP Address
255.255.255.255 (if DHCP not used)
18
Subnet Mask
255.255.255.255 (if DHCP not used)
19
Gateway IP Addr
255.255.255.255 (if DHCP not used)
20
DNS IP Addr.
255.255.255.255 (if DHCP not
used)
Status and Contact ID Reporting Codes
The Internal Device (IP/Cell) sends status messages to the control panel
for network connectivity failures. Trouble messages are displayed on the
keypad as “Check 103,” with status displayed as “LngRng Radio”
followed
by a 4
-digit keypad display status code, defined below.
Keypad Display Status Codes When “CHECK 103” is Displayed
CODE
DESCRIPTION
0000
Control panel lost communication with internal device
0005
internal device has lost contact with AlarmNet
network
000F
internal device is not registered; account not activated
0019
Cell
module shut down
0400
internal device Power
-
on reset
Contact ID Codes (as displayed at 685) sent to CS via IP/Cell
CODE
DESCRIPTION
E339 C803
Power
-
on reset
E350
C951
Primary communication path failure (Ethernet)**
R350 R951
Primary communication path restore (Ethernet)**
E350 C952
Secondary communication path failure (Cell)**
R350 C952
Secondary communication path restore (Cell)**
E355 C000
Module lost ECP co
mmunication with control
R355 C000
Module restore ECP communication with control
E353 C103
Long range transmitter fault trouble
R353 C103
Long range transmitter fault restore
E359 C950
Communication Failure
R359 C950
Communication Failure Restore
E
365 C0803
Module Firmware Update Success
E366 C0803
Module Firmware Update Failure
R903 C0803
Application Code Update Success
E904 C0803
Application Code Update Failure
** reports only if IP and Cell enabled
–
11
–
Using
∗
29 Menu Mode to Program IP/Cell Opt
ions
Press
∗
29 while in Data Field Programming mode. See the following prompts.
Note for remote services
:
When installing this system for use with Total Connect 2.0, DO NOT USE *29
PROGRAMMING TO FULLY PROGRAM THE COMMUNICATOR to avoid
overwriting any Tot
al Connect settings that may have been previously programmed.
Enter 1 to enable IP/Cell, then the star key (*). If you are installing this system with
an IP connection, press 0 to exit field *29 programming.
If you are installing this
system with LTE-21V only (no IP connection), press 1 to enter program mode and
toggle the Internal Device option to Cell only.
Then exit *
29 programming by
pressing 0.
Enable INT IP/Cell?
0 = No, not using either IP or Cell; 1 = Yes, using IP and/or Cell module
[
∗
] to continue.
NOTE:
Default = 1 (IP and/or Cell)
IMPORTANT:
If using an external communication device, see the
LTE-21V Module
Installation
section of the Installation and Setup Guide (
Inadequate Signal Quality
paragraph) for physical installation of an external
communication device. When
complete, enter 1 at this prompt and enter 1-Prog at the next prompt. Then program
the external device using the Installation and Setup Guide
included with the external
communication device
.
Note for remote services:
If using an IP connection, enable the IP/Cell option,
press
the star
key
[*] to continue and 0 to exit *29 programming menu. DO NOT
FULLY ENTER *29 MENU MODE. Next, program *189 (See *189 for more
information).
Fixed
-Word Keypad Note:
Although programming IP/Cell o
ptions cannot be done
via a fixed-word keypad, IP/Cell can be enabled by doing the following:
Enter
∗
29
(to enter IP/Cell menu mode), then press
1 + [
∗
] + [
∗
]
Programming/Diagnostics Select
1 = Prog (program the IP/Cell options)
2 = Diag (enter diagnostic
mode)
0 = Quit; return to data field programming mode
Internal Device Programming Prompts
The keys used to select and enter options now follow 7720P keypad
emulation. Refer to the table on the previous page for detailed key functions.
[
∗
] = scroll the o
ptions of a particular prompt
[#] = accept the entry and move to the next prompt
[A] = backspace or shift-[A} for escape
[B] = scroll to next prompt or shift
-[B] scroll to previous prompt
[C] = answer No or shift
-[C] answer Yes to prompt
[D] = shift key
Internal Device Selection
Select the type of IP and/or Cell module usage (press [
∗
] to scroll choices):
Disabled (none); IP only;
Cell
module only; IP & Cell
NOTE:
If reconfiguring from IP only to Cell only via the 7720P (or the panel
keypad) a “Forced Serv
er Update” is required.
Exiting programming
causes the device to reset, once reset press [0] via the 7720P (or the
panel keypad). Or, from AN 360, perform a “Get Data” command.
Note for remote services and the LTE-21V:
If you are installing this system w
ith
LTE
-21V only (no IP connection), toggle the Internal Device option to Cell only, then
exit programming as follows without entering the Primary City ID at the next prompt:
After toggling to Cell Only: select Function Key D, then Function Key A, then select the
pound key (#) to exit at the
Review? Y/N
prompt.
[#] to continue
Multi
-Mode (email reporting)
This feature is available only after authorization for it is set via the web-based
programming tool on the AlarmNet 360 website.
Multi
-mode emulates 4204 Relay Module outputs to send up to four (4204
sourced) or up to eight (2
-4204 sourced) reports of system events to the user
via email (email address is entered at the AlarmNet 360 website). Use the
AlarmNet 360 website to customize event titles, if desired. If enabled, a multi
-
mode address must be entered in the next prompt.
Use *79/*80 Menu modes to program each emulated output to trigger a desired
system event that, upon occurrence, will be sent to the user’s email address.
Select the desired multi mode
option:
Disabled =
no email reporting of events
4204 Sourced =
up to four types of events reported (relay numbers 1
-4 report
as events 1-4 respectively)
2-4204 Sourced =
up to eight types of events reported (first module’s relay
numbers 1
-4 report as events 1
-4 respectively; second
module’s relay numbers 1
-4 report as events 5
-8
respectively)
Enhanced Reports = Enables full panel status reporting via email and
reporting to TC2 web services. If used, RIS must be
enabled in field *91; when enabled, addre
ss 25 is
automatically assigned.
[
∗
] key scrolls forward; [backspace] key scrolls backward; [#] to continue
NOTES:
1. Multi
-mode has not been evaluated by UL.
2. Multi
-mode (email notification) is intended as a convenience for the user,
and does not replace Central Station reporting of critical events (alarms,
troubles, etc.).
Multi
-Mode Address
This prompt appears if Multi Mode is enabled
12-15 =emulated 4204 Relay Module address
25 = automatically assigned if Enhanced Reports selected
If using “2-4204
-sourced,” the address of the second module is automatically assigned
an address one higher than the first module’s address.
NOTE: A 4204 Relay module address is required for multi-mode purposes, but an
actual 4204 Relay module is not used at the selected add
ress.
Primary City ID
NOTE: Account information is provided by the central station administrator.
01-99 (decimal) = 2
-digit primary city code
Primary CS ID
Enter the primary central station's system ID number, 01-FE (HEX)
Primary Sub ID
Enter the 4-digit
customer account number, 0001
-9999 (decimal).
Remote Access
This feature is available only after authorization for it is set via the web-based
programming tool on the AlarmNet 360 website.
Remote Services allow the end user to access their security syste
m from a computer
via the remote services website. Most system functions can then be performed.
[Y] = use remote services; [N] = do not use remote services; [#] to continue
.
Keypad Address (for Remote Access)
This prompt appears if remote access is enabled
. By default, the Total Connect
(virtual) keypad will be set to address 2. To avoid a “Setup/Programming Error”
message, when installing this system for use with Total Connect 2.0, see *189 for
more information.
For enhanced remote access features, choose
an AUI address. If no AUI addresses are
available (all four AUIs are being used), choose an available standard keypad address
(some remote access features will be unavailable).
1, 2, 5, 6 = emulated AUI address
17-23 = emulated standard keypad address
NOTE:
An AUI or standard keypad address is required for remote access purposes,
but an actual AUI device or keypad is not used at the selected address.
Supervision
The supervising station must hear from the IP/Cell at least once during the
supervision period
. AlarmNet transmits a communications failure alarm to the central
station if the supervision message is not received within the period.
This selection sets the supervision timing for one of the following values:
if using IP and/or Cell
if using IP only (not for Cell usage)
•
30 day
•
6 Min
•
24
-hours
•
90 Sec
•
None (no supervision)
•
3 Min
•
75 Sec
•
1 hour
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
Cell Rollover Y/N
Appears only if IP&Cell is selected as Internal Device option.
[Y] =
all messages (including AlarmNet network supervisory messages) are sent
over the Cell network in the event of an Internet failure
[N] =
all messages (except AlarmNet network supervisory messages) are sent
automatical
ly over the Cell network in the event of an Internet failure
Cell 24Hr Tst Y/N
Appears only if IP&Cell is selected as Internal Device option.
[Y] =
have a message sent once a day to verify Cell operation. A "secondary
communication path loss" message is g
enerated if the message is not
successfully delivered.
[N] = disable 24hr test
Old Alarm Time
The old alarm time sets how long an undeliverable alarm is retried for delivery to
AlarmNet. If the message is not validated, it is retried until the old alarm time is
reached or the message is validated. The choices available are:
•
10 Minutes
•
4 Hours
•
15 Minutes
•
8 Hours
•
30 Minutes
•
12 Hours
•
1 Hour
•
24 Hours
•
2 Hours
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
IP Fault Time
Appears only if IP or IP&Cell is selected as Internal Device option.
00-99 = time delay (in minutes) before the control notifies the central station that there
is a loss of contact with the network over the Ethernet (IP) conn
ection.
0 = no delay (valid only If using IP only)
Must be two (2) minutes for UL installations.
Cell Flt Time
Appears only if Cell or IP&Cell is selected as Internal Device option.
00-99 = time delay (in minutes) before the control notifies the central s
tation that a
loss of contact with AlarmNet network has occurred.
0 = no delay (valid only if using Cell only,
Must be two (2) minutes for UL installations.
Notify Panel Of _
Appears only if IP&Cell is selected as Internal Device option.
Select from the following choices:
•
Neither Fault
•
Both IP and Cell must fail before fault code is sent (status code 4005 displayed);
panel receives primary and secondary path failure messages. No message sent if
only one or the other path fails.
To scroll the choices: [
∗
] key scrolls forward; [backspace] key scrolls backward
[#] to continue
NOTE:
IP failure will always be sent to the central station as Primary Path Failure,
and Cell failure will always be sent as Secondary Path Failure
.
–
12
–
IP address information prompts
The following prompts appear only if IP or IP&Cell is selected as Internal Device.
It is recommended to use dynamically allocated IP addresses, but if fixed IP addresses
are desired, contact your network administrator for the appropriate information. Note
that a valid IP address must be entered in each prompt before the system continues to
the next prompt. Entries cannot be left with the default values.
Use DHCP
[Y] = have the IP addresses dynamically allocated (recommended), skip to Review
prompt.
[N] = u
se fixed IP addresses; continue with next prompt
[#] to continue
NIC IP Address
[255.255.255.255]
Enter the 4-part IP address for this device, separating each part with a space ([
∗
]
key, displayed as periods). [#] to continue
Subnet Mask
[255.255.255.255]
Enter the 32
-bit address mask used to indicate the portion (bits) of the IP address
that is being used for the subnet address, separating each part with a space ([
∗
] key,
displayed as periods). [#] to continue
Gateway IP Addr
[255.255.255.255]
Enter the 4-part IP address assigned to the Gateway, separating each part with a
space ([
∗
] key, displayed as periods). If unused set to 0.0.0.0.
[#] to continue
DNS IP Addr
[255.255.255.255]
Enter the 4-part IP address assigned to the DNS (Domain Name System) server,
separating each part with a space ([
∗
] key, displayed as periods). If unused set to
0.0.0.0. [#] to continue
Review? (and Exit
∗
29 Menu mode or Reset Defaults)
You can review the
∗
29 Menu mode options to ensure that the correct entries have
been mad
e. When satisfied, select [N] to exit
∗
29 Menu mode.
To review prompts or exit
∗
29 Menu mode:
[Y] =
review prompts and entries, starting with Internal Device. Use the up/down
arrow keys to scroll through the program fields without changing any of the
value
s. If a value requires change, simply type in the correct value. When the
last field is displayed, the “REVIEW?” prompt appears.
[N] =
Exit *29 menu mode and return to data field programming mode. The prompt
briefly displays “DONE” before returning to data
field mode prompt “Enter
∗
or
#.”
[#] to accept Y or N selection (# alone exits same as N)
To reset
∗
29 Menu mode defaults:
Press [ESC] at the Review prompt to display the “Set Defaults” prompt.
[Y] =
reset
∗
29 menu mode options to factory values; if sel
ected, all programmed
∗
29 Menu mode options are reset to the factory settings
[N] =
cancel reset defaults function
Programming IP/Cell Options via AlarmNet 360 Website
To program the IP/Cell options via the AlarmNet 360 website (if you are already
signed
up for this service), go to: www.alarmnet360.com
Log in and follow the on-screen prompts.
Please have the following information available:
1. Primary City ID (two
-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label inside
module) or MIN number of the device you are replacing
5. Mode of operation of existing module if replacing a "C" series radio.
After programming is complete, y
ou must transfer the data to the module and the
module must be registered. Refer to the Registration section for details.
IP/Cell Diagnostic Commands (
∗
29 Menu Mode)
Diagnostic commands can be used to quickly view your Internet and Cell
connectivity settings and options. For each command press the [shift] key and then
the design
ated command key. For example, press [shift] then [1/A] to display the
software revision screen.
To enter Diagnostic mode:
1. Press
∗
29 while in data field programming mode.
2. Enter “1” at the “Enable IP/Cell” prompt then press [
∗
].
3. Select “2” (Diag) at the next prompt.
4. Enter the desired command at the “Sel Key Command” prompt.
For subsequent commands, enter the next command at the current screen.
To exit Diagnostic mode, press ESC (shift-[A]).
Key
Prompt
Function
[A]
Internal IP/Cell
x.x.xx mm/dd/yy
Software Revision
"x.x.xx" indicates the installed
software Revision. Mm/dd/yy
indicates month, day and year of
the revision.
[B]
MAC xxxxxxxxxxxx
MAC CRC yyyy
MAC Address
“xxxxxxxxxxxx” indicates the
IP/Cell’s unique iden
tification
number. Yyyy indicates the 4 digit
MAC CRC needed to enroll the
device in AlarmNet 360.
[
∗
] to continue to SCID.
SCID xxxxx xxxxx
xxxxx xxxxx
SCID Display
Only if Cell or IP/Cell enabled.
Displays the identification number
assigned to the SIM card (SCID) in
this device.
[
∗
] to continue to IMEI.
IP/Cell Diagnostic Commands (continued)
Key
Prompt
Function
IMEI xxxxxxxx
Xxxxxx x
IMEI Display
Only if Cell or IP/Cell enabled.
Displays the identification num
ber
assigned to the Cell module in
this device.
[
∗
] returns to MAC Address.
[C]
Mon 01 Jan 2006
05:48:39 am
Time
Retrieves the current date and
time from the AlarmNet network in
Greenwich Mean Time (GMT).
This display confirms that the
module is in s
ync with network.
[D]
Physical Link
Good/Bad
Physical Link
Only if IP or IP/Cell enabled.
Indicates if a physical connection
to the internet is detected or not.
[
∗
] to continue to NIC IP address.
NIC IP Address
xxx.xxx.xxx.xxx
IP Information Displ
ays
Displays the device IP address .
[
∗
] to continue to subnet mask.
Subnet Mask
xxx.xxx.xxx.xxx
Displays the 32
-bit address mask
used to indicate the portion (bits) of
the IP Address that is being used
for the subnet address.
[
∗
] to continue to gatew
ay IP.
Gateway IP Addr
xxx.xxx.xxx.xxx
Displays the IP Address assigned
to the Gateway.
[
∗
] to continue to DNS server IP.
DNS Serv IP
xxx.xxx.xxx.xxx
Displays the IP Address assigned
to the DNS (Domain Name
System) server.
[
∗
] to continue to encry
ption test.
Encryption Test
AES
Passed!
Performs a self
-test of the AES
encryption algorithm.
[
∗
] to continue to DHCP.
DHCP
OK
DHCP (Dynamic Host
Configuration Protocol)
OK = server performing okay.
[
∗
] returns to Physical Link prompt.
[E]
LTE
DISPLAYS
RAT SigQual REG
LTE/3G ***** X
LTE Cellular Status Display
Screen 1
RAT
– Radio Access Technology.
– LTE or 3G
SigQual
– Signal Quality (1
-5 “*’)
REG
– Registration status where
“x” can be:
N – Not Registered
H – Regi
stered Home
S – Searching
D – Registration Denied
R – Registered Roaming
? – Unknown Registration
State
If the RAT is LTE, the number of
stars is derived from received
power (RSRP) and the received
quality (RSRQ). The lower
number of stars of the t
wo ratings
is what is displayed as overall
quality.
NOTE
: For adequate signal
strength, must be 2 stars or more.
RSRP
:
Greater than -85dBm = 5 stars
-86dBm to -95dBm = 4 stars
-96dBm to -105dBm = 3 stars
-106dBm to -115dBm = 2 stars
-116dBm and lower = 1 s
tar
RSRQ
:
Greater than -10dB = 5 stars
-11dB to -12dB = 4 stars
-13dB to -14dB = 3 stars
-15dB to -16dB = 2 stars
-17dB and lower = 1 star
[
∗
] to continue to next screen.
–
13
–
RAT RSRP RSRQ
LTE xxxx xxxx
Signal Display for LTE
RAT
– Radio Access
Technology.
RSRP
– Reference Signal
Received Power
RSRQ
– Reference Signal
Received Quality
[
∗
] to continue to next screen.
RSRP MIN MAX
xxxx xxxx xxxx
Min/Max Signal Display for
LTE
RSRP
– Current Reference Signal
Received Power
MIN
– Minimum Receive Signal
Level
MAX
– Maximum Receive Signal
Level
[
∗
] to continue to next screen.
RSRQ MIN MAX
xxxx xxxx xxxx
Min/Max Signal Quality
Display for LTE
RSRQ
– Current Reference Signal
Received Quality
MIN
– Minimum Receive Signal
Quality
MAX
– Maximum Receive Signal
Quality
[
∗
] to continue to next screen.
Cntry Netw TAC
xxx xxx xxxxx
Location Display for LTE
Cntry
– Country Code
Netw
– Network Code
TAC
– Tracking area code
[
∗
] to continue to next screen.
GCel
l Chan
xxxxxx xxxx
Cell Display for LTE
GCell
– Global Cell ID
Chan
– RF Channel number
(EURFCN)
[
∗
] to continue to next screen.
Band Mode
xxx xxxx
LTE Status Display Screen 5
Band
– LTE Band Number
Mode
– LTE Mode either FDD or
TDD
[
∗
] to continue to next screen.
[E]
Operating with 3G Service
RAT RSCP EC/No.
3G -
xxx -
xxxxxx
Signal Display for 3G
RAT
– Radio Access Technology.
RSCP
–Received Signal Code
Power
Ec/N0
– Carrier Noise Ratio (CNR)
[
∗
] to continue to ne
xt screen.
RSCP MIN MAX
xxxx xxx xxxx
Min/Max Signal Display for
LTE
RSRP
– Current Reference Signal
Received Power
MIN
– Minimum Receive Signal
Level
MAX
– Maximum Receive Signal
Level
[
∗
] to continue to next screen.
Cntry Netw
LAC
xxx xxx xxxxx
Location Display for 3G
Cntry
– Country Code
Netw
– Network Code
LAC
– Local area code
[
∗
] to continue to next screen.
Cell Chan PSC
xxxxxx xxxx xxx
Cell Display for 3G
Cell
– Global Cell ID
Chan
– Control Channel in use
PSC
– Primary Sync Code
[
∗
] to continue to next screen.
Second Site RSSI
Available
3G Status Display Screen 5
Secondary Site RSSI availability.
Available or Not Available will be
displayed.
[
∗
] to continue to next screen.
IP/Cell Diagnostic Commands (continued)
Key
Prompt
Function
[F]
Testing Gateway
Redir 1
Network Diagnostic Test
Only if IP or IP/Cell enabled.
Performs a set of network
diagnostics that tests the integrity
of the links between the IP/Cell
and the various
connection points
(Redirs) to AlarmNet.
[S]
ECP
FLT
OK
Status request
OK = normal
i = IP off line
I = IP fault reported
g = Cell off line
G = Cell fault reported
[T]
Test Msg Sent
Test Alarm
Sends a Test alarm to AlarmNet.
Functional for a registered IP/Cell
only. If the device is not
registered, a message is
displayed indicating that the
command cannot be executed.
[X]
Reset CPU Y/N
Reset the IP/Cell.
[N] = return to diagnostic mode
(blank screen = enter next
command or escape).
[Y] =
resets the module (blank
screen = when reset
complete, enter next
command or escape).
[
↑
]
Registering ...
Registration (Shift-
UP arrow)
Registers a programmed IP/Cell
with AlarmNet. If it is configured
to report to AlarmNet, the IP/Cell
will register
with AlarmNet.
[
↓
]
Enter PIN#
Registration with PIN for
Replacement Module (DN
arrow)
Registers a programmed IP/Cell
with AlarmNet if it is configured to
report to AlarmNet.
[0]
Force Server Update
Y/N
Force Upload of
Configuration File to Server
[Y] = force the device to upload its
entire configuration file to
the server.
[N] = cancel the operation.
NOTE: If the internet is not
available, and the module is not
initialized when you enter this
command, the following screen
will be displayed:
Cannot Upload
Try Later! _
Wait for the Signal Quality LEDs
to light, indicating initialization is
complete, and try again.
–
14
–
Registration with AlarmNet
The control must be registered with AlarmNet before internet communication (via IP or Cell) can occu
r. Register the control by using one of these methods
To register, the control must be connected to the Internet.
Register with Alpha Keypad using *29 Menu mode
1. Enter *29 Menu mode, select Diagnostic mode, then press Shift then [
↑
] key (D key followed by the B key). The registration message is sent (“Registering”
displayed) and the control waits for the acknowledgment.
2. “Registration SUCCESS” displayed, indicating successful registration.
Register with Test Switch on control’s PCB (triple
-click)
1. Click the switch three times.
2. Watch the Cell Status LEDs: The Message (yellow) LED and the Status (green) LED will blink slowly in unison while registration is in progress.
3. When registration is complete, the Status (green) LED goes out.
Register with
AlarmNet 360 Website
To register via AlarmNet 360 Website, please go to: www.alarmnet360.com
Log in and follow the on
-screen prompts.
Please have the following information available:
•
Primary City ID (two
-digit number provided by central station)
•
Prim
ary Central Station ID (two
-digit hexadecimal number provided by central station)
•
Primary Subscriber ID (four-digit number provided by central station)
•
MAC ID and MAC CRC number (located on outside of box and on label on control’s PC board)
•
Activation ID (AID) and AID CRC numbers (found on the label on the Cell module or on its carton)
If you are not signed up for this service, click on “Dealer Signup” from the login screen to gain access to the Honeywell Hom
e web-based programming.
Once the control is registered, you may log out of the AlarmNet 360 website.
Register by phone
1. Call 1-800
-222-6525
You will need the following information:
•
MAC
ID and MAC CRC
number (found on the PCB label)
•
Subscriber information (provided by the central statio
n), including a city code, CSID, and a subscriber ID
•
Activation ID (AID) and AID CRC numbers (found on the label on the Cell module or on its carton)
2. When instructed to do so, triple
-click the Test switch to complete the registration.
IP/Cell LED Fu
nctions
Module Cellular Status LED
IP (web) Network LED Functions
Cellular status LED is located on the module’s PC board:
LED Color
LED
Description
STATUS
BLINK PATTERN
Top Green
Ethernet Link/Activity
ON
–
link is active; OFF
–
no link
Voice Session
S
hort blink every second
Middle Green
Link Speed
ON
–
100 MB/S; OFF
–
10 MB/S
Data Session
Short blink every 2 seconds
Yellow
Network Collision
BLINK
–
collision detected; OFF
–
normal
Connected to Cell network
Short blink every 4 seconds
No or de
activated SIM
Long blink every second
IP/Cell Status LED Functions
LED Color
LED
Description
Green
Status
ON
–
control is NOT registered with AlarmNet; OFF
–
control is registered with AlarmNet.
FAST BLINK –
Download session with Compass in progress.
SL
OW BLINK
–
In unison with yellow LED
–
Registration in progress.
Yellow
Message
ON
–
Message transmission pending.
QUICK PERIODIC BLINK -
Normal
FAST BLINK –
Message waiting for network ACK.
SLOW BLINK
–
In unison with green LED
–
Registration in progres
s.
Red
Fault
ON
–
No contact with network; OFF
–
Normal.
SLOW BLINK –
Loss of communication with the panel (ECP fault).
FAST BLINK
–
No network contact AND loss of communication with the panel.
All
FAST BLINK
–
In unison with the Signal Quality Bar Graph
LEDs
–
Hardware Error. Call the AlarmNet Technical
Assistance Center.
Signal Strength and Status LED Meanings
Color
Label
Indication
Red
Signal Quality
ON = signal quality display
OFF = status display
Yellow
mode
OFF = module operating in ECP mode
Gre
en
mode
OFF = module operating in ECP mode
Green
Web
web connection status
ON = connected to web
OFF = no web connection
Green
Cell
Cell service availability
ON = Cell service available
FLASH = Cell in use
OFF = no Cell service (messages sent via SMS)
G
reen
Cell
network carrier registration status
ON = registered with network carrier, no second site available
FLASH = registered with network carrier and second site available, excellent signal quality
BLINK = registered with network carrier and second site
available, acceptable signal quality
SLOW BLINK = registered with network carrier and second site available, low signal quality
OFF = control not registered with network carrier
–
15
–
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-*185.
Configurable zone types 92 and 93 can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for
zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields
*183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
(See not
e 5 for RF
zones)
ENTRY 2
(See note 5 for RF zones)
Response when system disarmed and zone is:
Auto
Restore
Vent Zone
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off
-
normal
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = yes
0 = no
8 = yes
Entry 1 = EOL + Open
Entry 2 = Short + auto restore + vent zone
ENTRY 3
(See note 5 for RF zones)
ENTRY 4
(See note 5 for RF zones)
Response when armed STAY and zone is:
Byp. when
disarmed
Byp. when
armed
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off
-
normal
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = al
arm
2 = trouble
3 = fault
see note 6
0 = no
4 = yes
0 = no
8 = yes
Entry 3 = EOL + Open
Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 5
(See note 5 for RF zones)
ENTRY 6
(See note 5 for RF zones)
Response when armed AWAY and zone is:
Dial
Delay
(see field *50)
Fault Delay
(see field *87)
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off
-
normal
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = use delay
0 = no
8 = use delay
see note 1
Entry 5 = EOL + Open
Entry 6 = Short + dial delay + fault delay
ENTRY 7
ENTRY 8
Display Faults
Power Reset/
Verification
Use Entry
Delay 1/2
Use Exit
Delay
Respond as
Interior
Type
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
armed
(show
alarms, trbles,
faults when
disarmed)
3 = never show
any alarms,
trbles, faults
0 = no
4 = power reset
after fault
(by code + OFF)
12 = verification
(see zone
type 16)
0
= no
1 = delay 1
2 = delay 2
0 = no
4 = use exit
delay
0 = no
8 = yes
see note 2
Entry 7 = fault display + power
reset/verification
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
ENTRY 9
ENTRY 10
Alarm Sounds
Use Bel
l
Timeout
Respond as
Fire Zone
Trouble
Sounds
Chime when
Chime Mode On
0 = none
1 = steady
keypad
2 = steady bell
and keypad
3 = pulsing bell
and keypad
0 = no
4 = yes
see fields *32,
*33
0 = no
8 = yes
see zone type
09; see note 4
0 = none
1 = per
iodic
beep
2 = trouble
beeps
0 = no
4 = yes
Entry 9 = alarm sounds + bell timeout + fire zone
Entry 10 = trouble sounds + chime
Entries for Fields *182 and *184
Entry
Zone Type 90
Zone Type 91
(field *182)
(field *184)
1
2
3
4
5
6
7
8
9
10
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
Zone Conditions Represented
in Entries 1-
6
NOTES:
1.
Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2.
To create an interior type zone, select
“respond as interior zone type” (entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-
4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
3.
Do not set fire zones to respond as a
“fault” (entries 1-
6), otherwise faults will
not display unless the [
∗
] key is pressed.
4.
4219/4229 modules must use EOLRs or
unpredictable results may occur.
5.
RF Zones: The “open” option in entries 1,
3, and 5 is
not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for off-
normal RF zone conditions.
6.
a.
Zone-
Doubling/Double-
Balanced: A
short on either zone of a zone-
doubled
pair or on a double-
balanced zone
causes a tamper condition.
b.
For double-
balanced zones, this entry
must be “0.”
c. For zone-
doubled zones,
both
zones of
the doubled pair must be assigned the
same response to a short.
–
16
–
*56
ZONE PROGRAMMING MENU MODE
(press *56 while in Program mode)
Each protection zone needs to be programmed with various attributes using
∗
56 Zone Programming mode or
∗
58 Expert Programming Mode.
For each of the following prompts, make the desired entry, followed by the [
∗
] key to accept the entry.
Refer to the Installation and Setup Guide for detailed explanations for each prompt.
SET TO CONFIRM?
0 = no; 1 = yes (See XMIT TO CONFIRM prompt later in this section.)
We
recommend that you confirm the programming of every transmitter.
ENTER ZN NUM.
01-64, 91, 92, 95, 96, 99
To quit,
enter 0
0 to quit (returns to data field mode).
SUMMARY SCREEN:
System displays a summary of the entered zone’s current programming.
Press [
∗
] to continue.
ZONE TYPE
00 = Not used
07 = 24
-Hr Audible
20 = Arm
–STAY*
01 = Entry/exit #1
08 = 24
-Hr Aux
21 = Arm
–AWAY*
02 = Entry/exit #2
09 = Fire
22 = Disarm*
03 = Perimeter
10 = Interior w/Delay
23 = No Alarm
Resp
04 = Interior Follower
12 = Monitor Zone
24 = Silent Burglary
05 = Trouble Day/Al
arm Night
14 = Carbon Monoxide
77 = Keyswitch
06 = 24
-Hr Silent
16 = Fire w/Verify
81 = AAV Monitor
Zone
*5800 button-type transmitters only
90-91 = Configurable
PARTITION
1, 2, or 3
-common
REPORT CODE
1-9, 10 for 0, 11 for B, 12 fo
r C, 13 for D, 14 for E, 15 for F
For Contact ID®, enter any non
-zero entry as the first digit to enable
reporting for this zone.
To disable the report code for this zone, enter 00.
HARDWIRE TYPE
Appears only for zones 02-08. Zone 1 is automatically set f
or EOL
operation. Enter the desired hardwire type:
0 = EOL; 1 = NC; 2 = NO; 3 = zone doubling (ZD); 4 = double-balanced
(DB)
RESPONSE TIME
For hardwired zones 01-08. Enter the desired response time for this zone:
0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 secs (see field
∗
174).
NOTE: If zone doubling is being used, the response time selected for
zones 02-08 automatically applies to each zone’s associated doubled
zone.
INPUT TYPE
Skipped for zones 2
-8, and for zones 10
-16 if zone
-doubling enabled.
Ent
er the input type: 2 = AW (Aux wired zone); 3 = RF (supervised RF);
4 = UR (unsupervised RF); 5 = BR (unsupervised button type)
NOTE: To change the input type of a previously programmed wireless
device to a wired zone, you must first delete the transmitte
r’s serial
number.
INPUT S/N
Enroll the transmitter’s serial number and loop number as follows:
1. a. Transmit two open/close sequences (for button-type transmitters,
press and release the button twice, waiting about 4 seconds before
pressing the button t
he second time).
OR
b. Manually enter the 7
-digit serial number printed on the label of the
transmitter. Press the [
∗
] key to move to the “L” position, then enter
the loop number.
Use the [A] (Advance) and [B] (Back) keys to move the cursor
forward and
back within the screen. Pressing the [C] (Copy) key will
insert the previously enrolled serial number, if desired (used when
programming a transmitter with several input loops).
To delete an existing serial number, enter 0 in the loop number
field. The serial number will change to 0's. If 0 was entered in
error, simply re-enter the loop number or press [#], and the serial
number will return to the display.
2. Press [
∗
] to continue. The system now checks for a duplicate serial/loop
number.
If no duplicate is found, the display shows the serial number and loop
number.
3. Press [
∗
] to continue to confirmation screen.
(prompts continued in next column)
XMIT TO confirm
Appears if you answered “Yes” at the “Set to Confirm” prompt.
Activate the loop input or button that corresponds to this zone.
Press [
∗
] to continue.
If the serial/loop number transmitted does not match the serial number
entered, a display showing the entered and the received serial/loop
numbers appears.
If so, activ
ate the loop input or button on the transmitter once again. If a
match is not obtained, press the [#] key twice and then enter (or transmit)
the correct serial number.
Press [
∗
] to continue
If the serial number transmitted matches t
he serial number
entered, the keypad will beep 3 times and a summary display will
appear, showing that zone's programming. An “s” indicates that a
transmitter’s serial number has been enrolled.
Press [
∗
] to accept the zone information and continue.
PROG
RAM ALPHA?
Press 1 if you want to program descriptors for the zone now, and refer to
the *82 Descriptor
Programming section for procedure. To program
descriptors later, enter 0 (no).
Press [
∗
] to return to the
ENTER ZN NUM prompt.
*58
EXPERT ZONE PROGRAMMING MODE
(press
∗
58 while in Data Programming mode)
∗
58 Expert Programming mode provides a faster method of zone
programming than *56 Menu mode, but is recommended only for those
who have had previous experience in programming controls of this type.
SET TO CONFIRM?
Select whether you want confirmation of wireless device enrollment. (See
“XMIT TO CONFIRM” prompt later in this section.)
We recommend that
you confirm the program
ming of every transmitter.
SUMMARY SCREEN
Zn ZT P RC HW: RT
01 09 1 10 EL 1
(Typical for Zone 1, initial summary screen)
Zn
ZT P RC IN: L
10 00
1 10 RF: –
(Typical for entered zone number; zone 10 in this example)
System dis
plays summary of zone 1’s current programming.
Enter the zone number being programmed, then press [
∗
]. A summary
screen for that zone is displayed, along with any current programming
values, and the cursor moves to the Zone Type location. The cursor then
automatically moves to the next locations after each entry is made.
Special Function Keys:
•
[A] (Advance) and [B] (Back) keys on the keypad move the cursor
within the screen.
•
[C] (Copy) key will insert the previous zone’s attributes, if desired.
•
[D] ke
y starts the
Wireless Key Programming Templates
menu
(see Wireless Key Programming Templates section that follows this
section).
Sequentially enter Zone Type
(ZT), Partition (P), and Report Code
(RC; 0
-9
only; use
∗
56 menu mode for hex codes
), then Hardwire Type (HW) and
Response Time (RT) for basic wired zones 1
-8
or
Input Device Type
(IN) for
zones 9 and higher (Loop Number [L] is programmed at the INPUT S/N
prompt).
See *56 Zone Program
ming Menu Mode section described earlier for entry
values.
Press [
∗
] to save the programming and continue. If needed, press the [#]
key to back up without saving.
•
For wireless devices (input types RF, UR, BR), continue to the INPUT
S/N (serial number/l
oop number) and XMIT TO CONFIRM prompts
described earlier in the
*56 Zone Programming Menu Mode
section.
When done, the display returns to the initial summary screen prompt to
let you program the next zone.
•
For wired devices, the display returns to the initial summary screen
prompt to let you program the next zone.
To Quit,
enter 00 at the zone number location and press [
∗
].
–
17
–
WIRELESS KEY PROGRAMMING & TEMPLATES
(press the [D] key from
∗
58 Menu mode Summary Screen)
This procedure programs the wireless keys,
but a key is not active for arming/disarming until it is assigned to a user number
(see
System Operation
section, Assigning Attributes Command in the Installation Instructions).
To program a wireless key,
do the following:
1.
Use Zone programming mode to manually program a zone for each button being used on the wireless key.
OR, use the Template program mode described below to automatically program each button (loop) to a zone type based on the selected wireless key
template number. Wireless key zone numbers range from zone 49
-64.
2.
Enroll the wireless key serial number into the system.
3.
Assign the wireless key to a user number if it is intended to arm/disarm the system. Refer to the assigning attributes command in the
System Operation
section of the Installation Instructions manual.
TEMPLATE ?
Enter desired template
number 1
–6 (see chart below), then press [
∗
] to
continue.
To exit the Template screen, press [#]. The system returns to the *58 Menu
mode Summary Screen.
TEMPLATE SUMMARY
L 01 02 03 04
T 23 22 21 23
The selected template is displayed.
The top line represents loop numbers, the bottom line represents each
loop’s zone type.
Press [
∗
] to accept template and continue.
PARTITION
Enter the partition (1, 2) in which the key is to be active.
Press [
∗
] to continue.
ENTER START ZONE
The system displays the lowest zone number of the
highest available
consecutive 4-zone group.
To start at a different zone number, enter the zone desired, and press [
∗
].
If the system has four consecutive zones beginning with that zone, the
zone number is displayed. If not, the system will again display a suggested
zone that can be used.
If the required number of consecutive zones is not available at all, the
system will display “00”.
Press [
∗
] to accept.
Continue to the INPUT S/N (serial number/loop number) and XMIT TO
CONFIRM prompts described earli
er in the
*56 Menu Mode
section.
IMPORTANT:
When confirmed, the key is not active for arming/
disarming until it is assigned to a user number (using the assigning
attributes command, attribute “4”). See System Operation
section in
Installation Instructions.
When done, the keypad beeps three times and the display returns to the
ENTER START ZONE prompt to let you enter the starting zone for the next
wireless key.
Wireless Key Predefined Default Templates
Template Number
Loop
Function
Zone Type
Template Number
Loop
Function
Zone Type
TEMPLATE 1
1
No Response
23
TEMPLATE 4
1
No Response
23
2
Disarm
22
2
No Response
23
3
Arm Away
21
3
Arm Away
21
4
No Response
23
4
Disarm
22
TEMPLATE 2
1
No Response
23
TEMPLATE 5
1
No Response
23
2
Disarm
22
2
Arm Stay
20
3
Arm Away
21
3
Arm Away
21
4
Arm Stay
20
4
Disarm
22
TEMPLATE 3
1
24-hour audible
7
TEMPLATE 6
1
24-hour audible
7
2
Disarm
22
2
Arm Stay
20
3
Arm Away
21
3
Arm Away
21
4
Arm Stay
20
4
Disarm
22
NOTE:
Some transmitters are not intended for use in UL installations.
Deactivating & Removing a Wireless Key from the System
Deactivate a wireless key by deleting the associated user code: Delete the User Code: Master code + [8] + 2-
digit user no. + [#] [0]
Remove a wi
reless key from the system by deleting one of the wireless key zones using Zone Programming mode:
1. Press
∗
56 while in Program mode then enter a zone number assigned to the wireless key.
2. Scroll through each prompt by pressing [
∗
] until the Input S/N pr
ompt appears.
3. Enter 0 for the loop number and press [
∗
].
4. Exit program mode.
*57
FUNCTION KEY PROGRAMMING
(press
∗
57 while in Data Programming mode)
To assign emergency key functions (function key option “00”), first program the respective emerge
ncy zone number (95 for “A” key, 96 for “C” key, 99 for “B” key)
with the desired zone type using
∗
56 Zone Programming mode, then use
∗
57 Function Key menu mode to assign the desired key.
To use a function key to activate a relay action (
∗
57 Menu mode key function 07), use
∗
79 Menu mode to map the output, and use
∗
80 Menu mode to define the
output’s action; select system operation type “66.”
To use a function key for a user macro, use
∗
57 menu mode to activate the desired key, then define the macro functions using the user code + [#] + [6] [6] command.
NOTE:
For SIA Compliance, panic functions for the A, B, and C function keys must be disabled, leaving the 1+*, 3+#, and *+# as pani
cs.
PRESS KEY TO PGM
Press the desired function key to be programmed, A
-D, t
hen press [
∗
] to
continue.
When done, press 0 to exit this mode and return to data field mode.
NOTE:
A key programmed as a function key is no longer available to be
used as an end
-user macro key or panic key.
PARTITION
Enter the partition (1
-3) in which this function key will be active.
KEY "A" FUNC
Enter the desired function for this key:
00 =
For the Function key selected, the functions are pre
-defined as
follows (default):
If A selected = Zone 95 (emergency key, same as [1] [
∗
] pair)
If B selected = Zone 99 (emergency key, same as [
∗
] [#] pair)
If C selected = Zone 96 (emergency key, same as [3] [#] pair)
If D selected = Single
-button paging
KEY "A" FUNC (continued)
01 =
Single-button paging (sends a 999
-9999 message to pager)
02 =
Display time
03 =
Arm AWAY (reports as User 00 if closing reports are enabled)
04 =
Arm STAY (reports as User 00 if closing reports are enabled)
05 =
Arm NIGHT-STAY (reports as User 00 if closing reports enabled)
06 =
Step Arming (arms STAY, then NIGHT
-STAY if enabled, then AWAY)
07 =
Output Device Command (for device programmed as system
operation type 66 in *80 Menu Mode)
08 =
Communication
Test (sends Contact ID code 601)
09
-12= Macro Keys 1
-4 respectively (defined by [#] [6] [6] comm
and)
Press [
∗
] to continue; returns to key number prompt with the next function
key letter displayed.
–
18
–
*79
OUTPUT DEVICE MENU MODE
(press
∗
79 while in Programming mode)
Use *79 Menu Mode to assign output numbers and map them to
device address
es.
The system also provides installer
-defined output functions, which can be
assigned to any of the physical outputs. The action of any one of the
outputs can be based on as many of these functions as desired. Use
∗
80
Menu Mode to define ou
tput functions.
ENTER OUTPUT NO.
01-18 = relays
[
∗
] to continue
OUT NORM LOW
(appears only for triggers 17/18)
0 = no (standard default); sets the output level normally high
1 = yes; sets the output normally low (can be used for resetting 4
-wire
smoke det
ectors)
[
∗
] to return to Output Number prompt
Power Reset:
This control does not automatically reset power to 4
-wire
smoke detector zones, so you must use a relay (e.g., 4204
, 4229)
or
on-board trigger to reset power (also required for fire verification).
OUTPUT TYPE
0 = delete; 1 = relay (skip to “B” prompt); 2 = Powerline Carrier device (skip
to “A” prompt)
[
∗
] to continue.
A: UNIT No.
(
if X
-10 was selected as Output Type)
Enter the unit code (01-16, set at the devic
e).
[
∗
] to return to the Output Number prompt continue
B: MODULE ADDR
(
if relay was selected as Output Type)
Enter the predefined address for this module (07
-15; see Table of Device
Addresses
later in this manual
).
Make sure the mod
ule’s DIP switches are set to the selected address.
NOTE:
If using Multi
-Mode (IP/
Cell
feature)
, select
one of the 4204
addresses
, though a physical 4204 module
is not installed
at the selected
address
. If using 2
-4204 multi
-mode option, the second 4204 address is
automatically one number higher than the first one selected.
Make sure
these addresses are not used by physical 4204 modules that may be
installed.
See
∗
29 Menu Mode section for enabling
Multi
-Mode.
[
∗
] to continue
REL POSITION
(ac
tual relay number on module)
For 4204
modules, relay numbers are 1
-4. For 4229
modules, relay
numbers are 1
-2.
NOTE:
If using multi
-mode,
program
the
relay
s to trigger on those system
events to be sent to the user’s email address
. (4204 option = up to 4
events; 2
-4204 option = up to 8 events)
See
∗
29 Menu Mode section for
enabling Multi
-Mode.
[
∗
] to return to the Output Number prompt for programming the next device
*80
OUTPUT FUNCTION MENU MODE
(press
∗
80 while in Programming mode)
Use this mode to program up to 48 output function definitions that provide
automated control of any of the output devices, based on events occurring
on individual zones or zones assigned to certain zone types.
OUTPUT FUNCT. #
Enter the output function number to be defined: 01-48
[
∗
] to continue; 00 = exit
SUMMARY SCREEN
01 A E P Trig
?00 0 0 – ZL=00
This screen displays a summary of the current output programming
A =
Output Action; E = Triggering event; P = Partition; Trig = Trigger type
Question mark indicates the device shown has not been mapped. Use *79
Menu mode to map the device.
[
∗
] to continue
ACTIVATED BY
0 = delete (deletes the output function and any previous programming); a
confirmation prompt appears.
To delete this output definition, press 1. If you do not want to delete this
output, press 0.
1 = zone list (go to “A” prompt); 2 = zone type (go to “B” prompt); 3 = zone
number (go to “C” prompt)
Press [
∗
] to continue
“
A
” (if zone list was selected)
ZN LIST
Enter the desired zone list number (01
-08). At the ENTER EVENT prompt,
enter the zone list event that will activate this output (0 = restore; 1 = alarm;
2 = fault; 3= trouble)
Press [
∗
] to continue and s
kip to the “Output Action” prompt.
“
B
” (if zone type was selected)
ENTER ZN TYPE
Enter the desired zone type. See list below *80 Worksheet for zone types.
At the PARTITION prompt, enter the partition in which this zone type will
occur (0 = any partition; 1 = partition 1; 2 = partition 2; 3 = partition 3).
Press [
∗
] to continue and skip to the “Output Action” prompt.
*80 Menu Mode
(continued)
“
C
”
(if zone number was selected)
ENTER ZN NO.
Enter the desired zone number, then press [
∗
] to continue. At the ENTER
EVENT prompt, enter the zone event that will activate this output (0 =
restore; 1 = alarm/fault/trouble).
Press [
∗
] to continue to the OUTPUT ACTION prompt
OUTPUT ACTION
0 = off; 1 = Close for 2 seconds; 2 = Close and Stay Closed; 3 =
Continuous Pul
se 1 sec on and 1 sec off
4 = Change Device State; 5 = Duration 1 (see data field *177); 6 = Duration
2 (see data field *177)
Press [
∗
] to continue.
ENTER OUTPUT NO.
Enter the device output number (programmed in *79 Menu Mode) you want
associated with thi
s output.
01-16 = output no.; 17-18 = on-board triggers
Press [
∗
] to continue.
SUMMARY SCREEN
A summary screen appears showing the programmed settings.
Press [
∗
] to return to OUTPUT FUNCTION NUMBER prompt.
*81
ZONE LIST MENU MODE
(press *81 while in Pr
ogramming mode)
Zone lists let you group individual zones for use with certain system
actions.
List
No.
Used for...
1, 2
general purpose (GP)
3
chime
-
by
-
zone (see field *26 to enable option)
4
cross zones (see note at right)
5
night stay zones
6
genera
l purpose
V21SIALTE
: dial delay disable
7
general purpose
V21SIALTE
: unlimited reports
8
general purpose
9
zones that activate Pager 1
10
zones that activate Pager 2
11
zones that activate Pager 3
12
zones that activate Pager 4
Notes
•
Any list
may include any or all of the system's zone numbers.
•
A zone list can be assigned to more than one output relay.
•
Zone List 4: When creating zone list 4 for cross zoning, include only
zones assigned to zone types 3, 4, or 5. Do not include zones that have
delays (entry/exit zones, interior w/delay) or 24
-hour zones, as these
zone types may produce unpredictable operation and may not function
as intended. See field *85 for Cross Zone Timer option.
•
Zone List 6:
V21SIALTE
: See field *50 for Dial Delay Dis
able option.
•
Zone List 7:
V21SIALTE
: See field *93 for Unlimited Reports option.
ZONE LIST NO.
Enter the zone list number (01-12) to program (or 00 to exit this mode).
Press [
∗
] to continue.
ENTER ZN NUM.
Enter each zone number (01
-64) to add to the zone list, followed by
pressing [
∗
] (example, 01
∗
, 02
∗
, 03
∗
).
Press 00 to continue.
IMPORTANT:
Do not include fire zones in zone lists that are used to
STOP device actions.
DEL ZN LIST?
0 = don’t delete list; current zone li
st remains saved
1 = delete this zone list; All zones in the zone list will be deleted.
[
∗
] to continue
DELETE ZONE?
0 = don’t delete zones; save the entire zone list and return to the Zone List
No. prompt
1 = go to next prompt to delete zones
[
∗
] to con
tinue
ZN TO DELETE?
Enter each zone (01
-64) to be deleted from the list, following each with [
∗
].
00 when done to return to the Zone List No. prompt.
–
19
–
*82
ALPHA DESCRIPTOR PROGRAMMING
PRE
-DEFINED DESCRIPTORS
PROGRAM ALPHA
0 = no (quit Alpha mode)
1 =
yes
Press [
∗
] or [#] to continue.
CUSTOM WORDS
0 = no (continue to descriptor programming)
1 = yes (go to custom word programming)
Press 0 to program standard alpha descriptors. The system will then display
the descriptor for zone
1.
To program custom words, press 1 (custom words are described later).
Press [
∗
] to continue.
∗
ZN 01
Descriptor screen for zone 1 appears. To program a descriptor (up to 3
words) for a zone, do the following:
1. Press [
∗
] plus the desired zone number (existing descriptor, if any, is
displayed), then press [
∗
] plus the zone number again (flashing cursor).
2. a. Press [#] plus the 3-digit number from the Alpha Vocabulary
List
on
page
19
for the first word
.
b. Press [6] to accept the word and move the cursor for the next word.
3. Repeat steps 2a and 2b for the second and third words (if used).
4. When all words have been enter
ed, press [8] to save the descriptor for that
zone. The flashing cursor disappears.
5. Repeat steps 1
-4 to assign a descriptor for the next zone.
6. When all descriptors have been entered, press [
∗
] + 0 + 0 (or simply press
[#]) after the last descriptor has been saved to return to the PROGRAM
ALPHA? prompt.
Enter 0 (no) at the prompt to exit this mode and return to Data Field mode.
ADDING CUSTOM WORDS
(up to 10 words)
For custom words, the keys have the following functions:
[4]
mov
es cursor one space to the left.
[6]
moves cursor one space to the right.
[8]
saves the new word in the system's memory.
1. Select Custom Word mode (enter 1) when the prompt “CUSTOM WORD ?” is
displayed.
2. Enter the number (01
–10, or 11, 12, 13 for parti
tion descriptors
– see
below) of the custom word or word string to be created, corresponding to
index numbers 245 -
254 respectively. A cursor appears at the beginning of
the second line.
NOTE:
Custom words 8, 9, and 10 are “reminder words” that can be
pro
grammed to display using Scheduling Mode.
3. Refer to the Character (ASCII) Chart on the next page.
Press [#], followed by the two
-digit entry for the first letter you would like to
display (e.g., # 6 5 for “A”).
Press [6] to adv
ance the cursor to the right,
in position for the next
character.
To delete a character,
simply enter the SPACE character (#32) at the
unwanted character’s location.
4. Repeat Step 3 to create the desired word(s). Each word can be a maximum
of 10 characte
rs (except custom message/partition descriptor word numbers
11, 12, and 13, which can be a maximum of 16 characters).
5. When the word is complete, press the [8] key to save the custom word(s)
in the vocabulary list and return to the “CUSTOM WORD ?” display.
6. Repeat Steps 1
–5 for other custom words to be entered. To change a
custom word, just overwrite it. When all words have been programmed,
enter 0 at the “CUSTOM WORD ?” prompt to return to the Program Alpha
prompt. Enter 0 again to exit Descriptor mod
e.
To Assign Partition/Custom Message
Descriptors,
use Adding Custom
Words procedure, but:
use the following word numbers in step 2:
11 = partition 1; 12 = partition 2; 13 = common lobby
ALPHA VOCABULARY LIST
(For Entering Zone Descriptors)
000
(Word Space)
– A –
•
001
AIR
•
002
ALARM
∗
004
ALLEY
005
AMBUSH
•
006
AREA
•
007
APARTMENT
•
009
ATTIC
∗
010
AUDIO
– B –
•
012
BABY
∗
•
013
BACK
∗
•
014
BAR
•
016
BASEMENT
∗
•
017
BATHROOM
∗
•
018
BED
•
019
BEDROOM
∗
020
BELL
•
021
BLOWER
•
022
BOILER
023
BOTTOM
025
BREAK
•
026
BUILDING
– C –
028
CABINET
•
029
CALL
030
CAMERA
031
CAR
033
CASH
034
CCTV
035
CEILING
036
CELL
AR
•
037
CENTRAL
038
CIRCUIT
•
040
CLO
SED
∗
•
046
COMPUTER
047
CONTACT
– D –
•
048
DAUGHTERS
049
DELAYED
•
050
DEN
∗
051
DESK
•
052
DETECTOR
∗
•
053
DINING
∗
054
DISCRIMINATOR
055
DISPLAY
•
057
DOOR
∗
•
059
DOWN
•
060
DOWNSTAIRS
061
DRAWER
•
062
DRIVEWAY
•
064
DUCT
– E –
•
065
EAST
066
ELECTRIC
•
067
EMERGENCY
∗
068
ENTRY
•
069
EQUIPMENT
•
071
EXIT
∗
072
EXTERIOR
– F –
•
073
FACTORY
075
FAMILY
•
076
FATHERS
•
077
FENCE
•
079
FIRE
∗
•
080
FLOOR
∗
081
FLOW
082
FOIL
•
083
FOYER
084
FREEZER
•
085
FRONT
∗
– G –
•
089
GARAGE
∗
•
090
GAS
091
GATE
•
092
GLASS
093
GUEST
•
094
GUN
– H –
•
095
HALL
∗
•
096
HEAT
098
HOLDUP
•
099
HOUSE
∗
100
INFRARED
– I –
•
101
INSIDE
∗
102
INTERIOR
103
INTRUSION
– J –
104
JEWELRY
– K –
•
105
KITCHEN
∗
– L –
•
106
LAUNDRY
∗
•
107
LEFT
108
LEVEL
•
109
LIBRARY
∗
•
110
LIGHT
111
LINE
•
113
LIVING
∗
•
114
LOADING
115
LOCK
116
LOOP
117
LOW
•
118
LOWER
– M –
•
119
MACHINE
121
MAIDS
•
122
MAIN
∗
•
123
MASTER
∗
•
125
MEDICAL
∗
126
MEDICINE
128
MONEY
129
MONI
TOR
•
130
MOTHERS
•
131
MOTION
∗
132
MOTOR
– N –
•
134
NORTH
135
NURSERY
– O –
•
136
OFFICE
∗
•
138
OPEN
∗
139
OPENING
•
140
OUTSIDE
142
OVERHEAD
– P –
143
PAINTING
•
144
PANIC
∗
145
PASSIVE
•
146
PATIO
∗
147
PERIMETER
•
148
PHONE
150
PO
INT
•
151
POLICE
∗
•
152
POOL
∗
•
153
POWER
– R –
155
RADIO
•
156
REAR
157
RECREATION
159
REFRIGERATION
160
RF
•
161
RIGHT
•
162
ROOM
∗
163
ROOF
– S –
164
SAFE
165
SCREEN
166
SENSOR
•
167
SERVICE
•
168
SHED
∗
169
SHOCK
•
170
SHOP
∗
171
SHORT
•
173
SIDE
∗
174
SKYLIGHT
•
175
SLIDING
∗
•
176
SMOKE
∗
•
178
SONS
•
179
SOUTH
180
SPRINKLER
•
182
STATION
184
STORE
•
185
STORAGE
∗
186
STORY
190
SUPERVISED
∗
191
SUPERVISION
192
SWIMMING
193
SWITCH
– T –
194
TAMPER
•
196
TELCO
197
TELEPHONE
•
199
TEMPERATURE
200
THERMOSTAT
•
201
TOOL
202
TRANSMITTER
– U –
•
205
UP
•
206
UPPER
•
207
UPSTAIRS
∗
•
208
UTILITY
∗
– V –
209
VALVE
210
VAULT
212
VOLTAGE
– W
–
213
WALL
214
WAREHOUSE
•
216
WEST
•
217
WINDOW
∗
•
219
WING
220
WIRELESS
– X –
222
XMITTER
– Y –
•
223
YARD
– Z –
224
ZONE (No.)
•
225
ZONE
∗
•
226
0
•
227
1
•
228
1ST
∗
•
229
2
•
230
2ND
∗
•
231
3
•
232
3RD
∗
•
233
4
•
234
4TH
•
235
5
•
236
5TH
•
237
6
•
238
6TH
•
239
7
•
240
7TH
•
241
8
•
242
8TH
•
243
9
•
244
9TH
245
Custom Word #1
246
Custom Word #2
247
Custom Word #3
248
Custom Word #4
249
Custom Word #5
250
Custom Word #6
251
Custom Word #7
252
Custom Word #8
253
Custom Word #9
254
Custom Word #10
Note:
Italicized
words followed by an asterisk indicate those words supported by the 6160V Voice Keypads
.
Bullet and
bold
words indicate those words supported by the 6280W, 6280S, and Tuxedo Touch™ series keypads.
CHARACTER (ASCII) CHART
(For Adding Custom Words)
32 (space)
33
!
34
"
35
#
36
$
37
%
38
&
39
'
40
(
41
)
42
*
43
+
44
,
45
–
46
.
47
/
48
0
49
1
50
2
51
3
52
4
53
5
54
6
55
7
56
8
57
9
58
:
59
;
60
<
61
=
62
>
63
?
64
@
65
A
66
B
67
C
68
D
69
E
70
F
71
G
72
H
73
I
74
J
75
K
76
L
77
M
78
N
79
O
80
P
81
Q
82
R
83
S
84
T
85
U
86
V
87
W
88
X
89
Y
90
Z
– 20
–
SETTING SCHEDULES
(Installer Code + [#] + [6] [4])
NOTES:
•
The master code can only access schedules 01
-16 and events 00
-07.
•
System clock must be set before schedules can be used.
•
Programmed
schedules do not take effect until the next scheduled “start”
time. (e.g., if programming a schedule time window for 8AM to 5PM, the
schedule does not take effect until 8AM after the schedule has been
programmed.)
ENTER SCHED NO.
01-16 = end
-user schedul
es; 17
-32 = installer
-only schedules
[
∗
] to continue.
To Quit,
enter 00.
ENTER EVENT
00 = clear event
01 = Relay On/Off
02 = User Access
03 = Latch Key Report to Pager (sent to all pagers in the user’s partition;
message sent is 777
-7777. User must be enabled for paging and
system must be armed before reporting can occur.)
04 = Forced Stay Arming
(
Forced bypass is automatically enabled
regardless of setting in field *23)
05 = Forced Away Arming
(
Forced bypass is automatically enabled
regardless of set
ting in field *23)
06 = Auto Disarm
07 = Display “Reminder”
10 = Display custom words (if selected, system displays custom words 8,
9, and 10 at defined time. Can be used as installer’s reminder
message to the end user); programmable by installer only
11 =
Periodic Test Report (see key commands in
Test Report Code
, data
field *64
,
to quickly set periodic test reporting intervals);
programmable by installer only
[
∗
] to continue.
DEVICE NUMBER
( for event 1 relay on/off)
01-18; [
∗
] to continue.
GROUP NUMBER
( for event 2 user access)
1-8; [
∗
] to continue.
PARTITION
( for events 3-
7,10,12)
0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common
[
∗
] to continue.
START
01-12 = hour; 00
-59 = minute; 0 = AM; 1 = PM; to select days, position t
he
cursor under the desired days using the [
∗
] key to move forward, then
press “1” to select the day.
[
∗
] to continue.
STOP
(for events 1 relay on/off; 2 user access; 3 latch key report)
See START for entries. [
∗
] to continue.
REPEAT
0 = do not repe
at; 1 = repeat schedule weekly; 2 = repeat schedule
biweekly (every other week); 3 = repeat schedule every third week; 4 =
repeat schedule every fourth week
(28 days)
[
∗
] to continue
RANDOMIZE
(for events 01 and 11)
0 = no; 1 = yes
If selected, the scheduled start and stop times will vary within 60 minutes of
the “hour” time. For example, if a schedule is set to start at 6:15pm, it will
do so the first time 6:15pm arrives, but on subsequent days it will start
anytime between 6:00 and 6:59 p.m.
NOTE:
Do no
t use the random option if the start and stop times are within
the same “hour” setting, otherwise unpredictable results may occur (e.g.,
the randomized stop time may occur before the start time).
[
∗
] to continue and return to ENTER SCHED NO. prompt to program the
next schedule.
AVS
SYSTEM ENABLE AND QUICK PROGRAMMING COMMANDS
Applies to an AVS system using an ECP connection to the control.
1.
Install the AVS module according to its instructions.
2.
Use one of the control’s AVS Quick Program commands as
follows (see Quick Program Command Results below for results of each
command):
•
installer code + [#] + 0 + 3:
enable AVS operation without panel sounds on the AVST speaker
•
installer code + [#] + 0 + 4:
enable AVS operation and enable panel sounds on the AVST speaker
3.
Use data field
∗
55 Dynamic Signaling Priority to enable the reporting path for AAV communication.
4.
To undo the Quick Command programming, use the following commands:
•
installer code + [#] + 0 + 5
: remove all options set by [#] + 03 quick command
•
installer code + [#] + 0 + 6
: remove all options set by [#] + 04 quick command
AVS Quick Program Command Results
When either the #03 or #04 Quick Program command is used, the following are automatically programmed and no longer available for other
control panel purposes.
Pre
-
Programmed
#03 Command
#04 Command
Output Function No.
(
∗
80 mode)
46 (zone type 60, relay 15)
47 (zone type 61, relay 16)
48 (zone type 62, relay 16)
Same as #03 plus:
41 (zone type 14, relay 13)
42 (zone type 22, relay 13)
43 (zone type 39, relay 14)
44 (zone type 33, relay 14)
45 (zone type 36, relay 14)
Output Relay No.
(
∗
79 mode)
15 (addr 11, relay pos 2)
16 (addr 11, relay pos 1)
Same as #03 plus:
13 (addr 11, relay pos 4)
14 (addr 11, relay pos 3)
Pro
tection Zone
(
∗
56/
∗
58 mode)
4229 zn 48 (zt 81, addr 11)
Same as #03 command
Device Address
address 11 (AVS module)
Same as #03 command
Data Field
∗
91
AAV enabled
AAV enabled
– 21
–
SETTING THE REAL
-TIME CLOCK
The Real-
Time C
lock must be set before completing the installation.
NOTE:
All partitions must be disarmed before the Real
-Time Clock can be set.
1.
Master Code + [#] + [6] [3]
2.
Press [
∗
] when the time/date is displayed. A cursor appears under the first digit of the hour.
To move cursor ahead, press [
∗
]. To go back, press [#].
•
Enter the 2-
digit hour setting, followed by the 2-
digit minute setting, then press [1] for PM or [2] for AM.
•
Enter the last two digits of the current year, followed by the 2-
digit month setting and the 2-
digit day setting.
3.
To exit, press [
∗
] when cursor is at the last digit, or wait 30 seconds.
UPLOADING/DOWNLOADING VIA THE INTERNET
This control supports upload/download programming capability via the Internet by using the AlarmNet network and Compass downloading
software. The control must be connected to the Internet (via the on-
board RJ45 connector or Cell
module), have all IP features programmed (
∗
29
Menu mode), and be registered with A
larmNet.
The following is required at the Downloading Office:
•
Broadband Internet Access and Broadband (Cable/DSL) Modem
•
Broadband (Cable/DSL) Router (optional, if connecting more than one device to the Internet)
•
Computer running Compass Downloading Software version that supports Internet upload/download for this control.
To perform upload/download functions:
1.
Connect the computer to the Internet and start the Compass downloading software.
2.
Open the control’s account, then select the Communicati
ons function and click the
Connect
button.
3.
At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is checked.
4.
Click
Connect
. The Internet connection to the control is made automatically via AlarmNet.
5.
Once connected, use the Compass downloading software as normal to perform upload/download functions.
– 22
–
ZONE TYPE DEFINITIONS
Zone types define the way in which the system responds to faults in each zone.
Type 00 Zone Not Used
Program a zone with this zone type if the zone is not used.
Type 01 Entry/Exit Burglary #1
•
Assign to zones that are used for primary entry and exit.
•
Provides entry delay when zone is faulted if control is armed in the
Away, Stay, or Night-
Stay modes.
•
No entry delay provided when the panel is armed in the
Instant/Maximum mode.
•
Entry delay #1 is programmable for each partition (field *35).
•
Exit delay begins whenever the control is armed, regardless of the
arming mode selected, and is programmable (field
Q
34).
Type 02 Entry/Exit Burglary #2
•
Assign to zones that are used for entry and exit and require more
time than the primary entry/exit point.
•
Provides a secondary entry delay, similar to entry delay #1.
•
Entry delay #2 is programmable for each partition (field *36).
•
Exit delay is same as described for Type 01.
Type 03 Perimeter Burglary
•
Assign to all sensors or contacts on exterior doors and windows.
•
Provides an instant alarm if the zone is faulted when the panel is
armed in the Away, Stay, Night-
Stay, Instant or Maximum modes.
Type 04 Interior Follower
•
Assign to a zone covering an area such as a foyer, lobby, or
hallway through which one must pass upon entry (to and from the
keypad).
•
Provides a delayed alarm (using the programmed entr
y 1 time) if
the entry/exit zone is faulted first. Otherwise this zone type gives
an instant alarm.
•
Active when the panel is armed in the Away mode.
•
Bypassed automatically when the panel is armed in the Stay or
Instant modes; if armed in Night-
Stay m
ode, zones assigned to
zone list 05 (night-
stay zone list) are not bypassed when system
armed in Night-
Stay mode.
Type 05 Trouble by Day/Alarm by Night
•
Assign to a zone that contains a foil
-protected door or window
(such as in a store), or to a zone cov
ering a sensitive area such
as a stock room, drug supply room, etc.
•
Can also be used on a sensor or contact in an area where
immediate notification of an entry is desired.
•
Provides an instant alarm if faulted when armed in the Away, Stay,
Night-
Stay, Instant or Maximum (night) modes.
•
During the disarmed state (day), the system will provide a latched
trouble sounding from the keypad (and a central station report, if
desired).
Type 06 24-
hr Silent Alarm
•
Usually assigned to a zone containing an emergency button.
•
Sends a report to the central station but provides no keypad
display or sounding.
Type 07 24-
hour Audible Alarm
•
Assign to a zone that has an emergency button.
•
Sends a report to the central station, and provides an alarm sound
at the k
eypad, and an audible external alarm.
Type 08 24-
hour Auxiliary Alarm
•
Assign to a zone containing an emergency button, or to a zone
containing monitoring devices such as water or temperature
sensors.
•
Sends a report to the central station and provides
an alarm sound
at the keypad. (No bell output.)
Type 09 Supervised Fire
•
Provides a fire alarm on short circuit and a trouble condition on
open circuit. A fire alarm produces a pulsing bell output.
•
This zone type is always active and cannot be bypass
ed.
Type 10 Interior w/Delay
•
Provides entry delay (using the programmed entry time), if tripped
when the panel is armed in the Away mode.
•
Entry Delay 1 begins whenever sensors in this zone are violated,
regardless of whether or not an entry/exit del
ay zone was tripped
first.
•
Bypassed when the panel is armed in the Stay or Instant modes; if
armed in Night-
Stay mode, zones assigned to zone list 05 (night-
stay zone list) are not bypassed when system armed in Night-
Stay
mode.
Type 12 Monitor Zone
•
Works as a dynamic monitor of a zone fault/trouble (not alarm). In
the case of a short/open, the message, "*ALARM*
-24 Hr. Non-
Burg. -
#XXX " (where XXX is the zone number) will be sent to the
Central Station. The system keypad will display a “check”
message indicating the appropriate zone (but keypad beeping
does not occur). Upon restoral of the zone, the message,
"*RESTORE*-
24 Hr. Non-
Burg. -
#XXX
" is
sent to the Central
Station.
•
The “check” message will automatically disappear from the
keypad dynamical
ly, when the zone restores; a user code + off
sequence is not needed to reset the zone.
•
Faults of this zone type are independent of the system, and can
exist at the time of arming without interference.
•
Since this is a “trouble” zone type, do not use this zone type with
relays set to activate upon “alarm.”
Type 14 24 Hour Carbon Monoxide Monitor
•
Assigned to any zone with a carbon monoxide detector.
•
A carbon monoxide alarm produces keypad and detector
sounding (does not affect bell output).
•
Alw
ays active and cannot be bypassed.
Type 16 Fire w/Verification
•
Provides a fire alarm when zone is shorted, but only after the
alarm is verified to help eliminate false alarms due to electrical or
physical transients.
•
Verifies alarm by resetting smoke detectors after short is detected
(removes power 7 seconds for zone 1, 3 seconds for trigger
output). Another short circuit within 90 seconds triggers fire alarm,
otherwise first alarm is ignored.
•
Provides a trouble response when zone is open.
Type 20 A
rm
-Stay (BR only)
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when
arming or disarming.
•
User number for button must be assigned.
Type 21 Arm
-Away (BR only)
•
Arms the system
in Away mode when the zone is activated.
•
Pushbutton units send the user number to the central station when
arming or disarming.
•
User number for button must be assigned.
Type 22 Disarm (BR only)
•
Disarms the system when the zone is activated.
•
User
number for button must be assigned.
Type 23
*
No Alarm Response
•
Can be used on a zone when an output relay action is desired, but
with no accompanying alarm (e.g., lobby door access).
Type 24 Silent Burglary
•
Usually assigned to all sensors or contacts on exterior doors and
windows where bells and/or sirens are NOT desired.
•
Provides an instant alarm, with NO audible indication at any
keypad or external sounder, if the zone is faulted when the system
is armed in the Away, Stay, Instant, or Maximum m
odes.
•
A report is sent to the central station.
Type 77 Keyswitch
•
Assign to zone wired to a keyswitch.
•
Do not use input type “BR” devices with this zone type.
Type 81 AAV Monitor Zone (for AVS)
•
Assign to zone connected to AVS module.
•
Monitors 2-
way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting
stops, except for fire alarms, which immediately terminate the
voice session and cause a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if
bell timeout has not expired) and stopped reports are sent.
Types 90-
93 Configurable
Allows for various custom responses. Options include response to
entry/exit delays, response opens/shorts, types of alarm/trouble
sounding, dial
delay, and unique Contact ID report codes. Types 92
and 93 can only be programmed via downloader. UL installations:
Zone Types 90 -
93 may not be used as fire or burglar alarm zones
on fire or UL burglar alarm installations.
*
The system can still be armed
when these zone types are in a
faulted condition.
– 23
–
SCHEDULES WORKSHEET
(installer code + [#] + [6] [4];
master code can only access schedules 01-16 and events 00-07
No.
Event
(see list below)
Device No.
for “01” events:
enter 01
-18
Group No.
for “02” events:
enter 1
-8
Partition
for “04
-06”
events:
enter 1, 2, or 3
Start Time/ Days
Stop Time/ Days
Repeat
(1-4)
Random
(yes/no)
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Events:
Master/Installer
Installer Only
00 = clear event
04 = forced STAY arm
10 = display custom words 8-10
01 = device on/off
05 = forced AWAY arm
11 = periodic test report
02 = user access
06 = auto disarm
03 = latch key report
07 = display “reminder”
Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourt
h week
(28 days)
– 24
–
*56 ZONE PROGRAMMING WORKSHEET
[default shown in brackets]
Zone
Zn Type
Part.
Report
Hardwire
Type
Rsp. Time
Location
1
[09]
[1]
[EOL]
[1]
2
[01]
[1]
[EOL]
[1]
3
[03]
[1]
[EOL]
[1]
4
[03]
[1]
[EOL]
[1]
5
[03]
[1]
[EOL]
[1]
6
[03]
[1]
[EOL]
[1]
7
[03]
[1]
[EOL]
[1]
8
[03]
[1]
[EOL]
[1]
Zone
Zn Type
Part.
Report
Input Type
Loop
Se
rial No.
Location
9
[1]
[RF]
10
[1]
[RF]
11
[1]
[RF]
12
[1]
[RF]
13
[1]
[RF]
14
[1]
[RF]
15
[1]
[RF]
16
[1]
[RF]
17
[1]
[RF]
18
[1]
[RF]
19
[1]
[RF]
20
[1]
[RF]
21
[1]
[RF]
22
[1]
[RF]
23
[1]
[RF]
24
[1]
[RF]
25
[1]
[RF]
26
[1]
[RF]
27
[1]
[RF]
28
[1]
[RF]
29
[1]
[RF]
30
[1]
[RF]
31
[1]
[RF]
32
[1]
[RF]
33
[1]
[RF]
NOTES:
Zone Type: see chart in
∗
56 Zone Programming
Menu mode section.
Report Code: enabled if
first digit is a non
-zero
number
Hardwire Type (zns 2
-8):
0 = EOL
3 = ZD
1 = NC
4 = DB
2 = NO
Input Type:
2 = AW (zones 9
-48)
3 = RF (zones 9-48)
4 = UR (zones 9-48)
5 = BR (zones 49-64)
NOTE:
Zones 9-16 not
available if zone
doubling enabled.
Response Time:
0 = 10msec
1 = 350msec
2 = 700msec
3 = 1.2 sec
Reserved Zones
91 =
addressable device
report
enable/disable
default zone type =
[05].
92 =
Duress report
enable/disable
– 25
–
Zone
Zn Type
Part.
Report
Input Type
Loop
Serial No.
Location
34
[1]
[RF]
35
[1]
[RF]
36
[1]
[RF]
37
[1]
[RF]
38
[1]
[RF]
39
[1]
[RF]
40
[1]
[RF]
41
[1]
[RF]
42
[1]
[RF]
43
[1]
[RF]
44
[1]
[RF]
45
[1]
[RF]
46
[1]
[RF]
47
[1]
[RF]
48
[1]
[RF]
49
[1]
[BR]
50
[1]
[BR]
51
[1]
[BR]
52
[1]
[BR]
53
[1]
[BR]
54
[1]
[BR]
55
[1]
[BR]
56
[1]
[BR]
57
[1]
[BR]
58
[1]
[BR]
59
[1]
[BR]
60
[1]
[BR]
61
[
1]
[BR]
62
[1]
[BR]
63
[1]
[BR]
64
[1]
[BR]
95
[00]
N/A**
N/A
N/A
N/A
keypad [1] / [
∗
]
96
[00]
N/A**
N/A
N/A
N/A
keypad [3] / [#]
99
[06]
N/A**
N/A
N/A
N/A
keypad [
∗
] / [#]
** Emergency key zones 95, 96, and 99 report the par
tition of the keypad used to activate the emergency zones.
– 26
–
*57 FUNCTION KEY WORKSHEET
Option
Function
A
P1
P2
com
B
P1
P2
com
C
P1
P2
com
D
P1
P2
com
Comments
01
Paging
02
Time Display
03
Arm AWAY
04
Arm ST
AY
05
Arm NIGHT-STAY
06
Step Arming
07
Device Activation
Device:
08
Comm. Test
09
Macro Key 1
Assign each macro key to only a single partition.
†
10
Macro Key 2
Assign each macro key to only a single partition.
†
11
Macro Key 3
Assign each macro key to only a single partition.
†
12
Macro Key 4
Assign each macro key to only a single partition.
†
00
Emergency Keys:
zone 99
zone 9
6
paging
Personal Emergency
n/a
Silent Alarm
n/a
Audible Alarm
n/a
Fire
n/a
Emergency Keys:
A = paired keys [1] / [
∗
] (zone 95); B = paired keys [
∗
] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
† The
re are only four macros system
-
wide.
OUTPUT RELAYS WORKSHEET FOR
∗
79,
∗
80 and
∗
81.
Applicable only if Relay Devices are to be used.
∗
79 RELAY DEVICE MAPPING (Must program before using *80)
OUTPUT TYPE
OUTPUT TYPE
Relay
X10
Relay
X10
Output
No
.
Module
Addr.
Pos
(1
-
4)
Unit
No.
Description
Output
No.
Module
Addr.
Pos
(1
-
4)
Unit
No.
Description
01
09
02
10
03
11
04
12
05
13
06
14
07
15
08
16
17
On
-
Board Trigge
r 1
norm output =
18
On
-
Board Trigger 2
norm output =
– 27
–
*81
ZONE LISTS WORKSHEET
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear
in sequence.
NOTE:
Record desired zone numbers below, noting that a list may include
any
or
all
of system's zone numbers.
List No.
Used For...
Contains These Zones...
01
General Purpose (GP)
02
General Purpose
03
Chime-
by-Zone or GP
(see field *26 for
Chime
-by
-Zone option)
04
Cross Zones or GP
(see field *85 for Cross Zone Timer option)
05
Night-
Stay Zones or GP
06
Dial Delay Disable or GP
V21SIALTE:
see field *50 for Dial Delay Disable option
07
Unlimited Reports or GP
V21SIALTE:
see field *93 f
or Unlimited Reports option
08
General Purpose
09
Zones activating pager 1
10
Zones activating pager 2
11
Zones activating pager 3
12
Zones activating pager 4
–
28
–
*80
OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
Notes:
1.
For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
2.
For Powerline Carrier devi
ces (plcd), field *
27 must be programmed with a House Code.
3
. Tampers of expansion units cannot be used to operate devices.
Output
Function
Number
(1-48)
Activation Type and Detail
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 =
partition 2
3 = common
Event (for zone list/activated by)
Action
0 = off
1 = close 2
secs
2 = stay closed
3 = pulse
4 = toggle
5 = duration 1
††
6 = duration 2
††
Output
Number
1-18
Device
Type
R = relay
T = trigger
X = X10
Activated
by
0=delete
1=zn list
2=zn type
3=zn no.
Zone List
(ZL)
1
-8 = list
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
01-
64
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
By Zone No.
0 = restore
1 = alrm/flt/trbl
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
–
29
–
Output
Function
Number
(1-48)
Activation Type and Detail
Partition
Number
(P)
(if using ZT trig)
0 = any
1 = partition 1
2 =
partition 2
3 = common
Event (for zone list/activated by)
Action
0 = off
1 = close 2
secs
2 = stay closed
3 = pulse
4 = toggle
5 = duration 1
††
6 = duration 2
††
Output
Number
1-18
Device
Type
R = relay
T = trigger
X = X10
Activated
by
0=delete
1=zn list
2=zn type
3=zn no.
Zone List
(ZL)
1
-8 = list
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none
01-
64
By Zone List
0 = restore
1 = alarm
2 = fault
3 = trouble
By Zone No.
0 = restore
1 = alrm/flt/trbl
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
ZONE TYPE/SYSTEM OPERATION –
Choices for Zone Types are:
00 = Not Used
05 = Trouble Day/Alarm Night
10 = Inte
rior w/Delay
24 = Silent Burglary
01 = Entry/Exit#1
06 = 24 Hr Silent
12 = Monitor Zone
77 = Keyswitch
02 = Entry/Exit#2
07 = 24 Hr Audible
14 = Carbon Monoxide§§
81 = AAV Monitor Zone
03 = Perimeter
08 = 24 Hr Aux
16 = Fire w/Verification
90-91 = Configurable
04 = Interior Follower
09 = Fire
23 = No Alarm Response
§§ when used with an output function,
the carbon monoxide zone type
activates only upon CO alarms. Does
not activate for trouble conditions.
Choices for System Operation are:
20 = Ar
ming
–Stay
38 = Chime
58 = Duress
21 = Arming
–Away
39 = Any Fire Alarm
60 = AAV Trigger
22 = Disarming (Code + OFF)
40 = Bypassing
61 = AVS/
Cell
session begin §
31 = End of Exit Time
41 = **AC Power Failure
62 = AVS/
Cell
session end
§
32 = Start of Entry Time
42 = **System Battery Low
66 = Function key†
33 = Any Burglary Alarm
43 = Communication Failure
67 = Bell Failure
36 = **At Bell Timeout***
52 = Kissoff
68 = TELCO Line Fault
54 = Fire Zone Reset
78 = Keyswitch red LED†††
79 = Keysw
itch green LED†††
Note:
In normal operation mode:
Code + # + 7 + NN Key Entry
starts
Device
Code + # + 8 + NN Key Entry
stops
Device
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
†† Duration is set in program fi
eld *177.
††† Device action not used for these choices.
§ automatically set when appropriate AVS Quick
Command performed.
–
30
–
5800 S
ERIES TRANSMITTER INPUT LOOP IDENTIFICATION
All of the transmitters illustrated have one or more unique factory assigned input (loop) ID numbers.
Each of the inputs requires
its own programming zone
(e.g., a 5834-4's
four inputs r
equire four programming zones).
For information on any transmitter not shown, refer to the instructions accompanying that transmitter for details regarding l
oop
numbers, etc.
UL NOTE
:
The following transmitters are not intended for use in UL installations: 5819S and 5819S
BR.
–
31
–
TABLE OF DEVICE ADDRESSES
This Device
Uses Address
Reports as ††
Enabled By...
RF Receiver
00
100
∗
56 zone programming: input device type entry
AUI 1 (touchscreen)
01
n/a
automatic if AUI enable field *189 enabled for AUI 1
AUI
2 (touchscreen)
02
n/a
automatic if AUI enable field *189 enabled for AUI 2
AUI 3 (touchscreen)
05
n/a
automatic if AUI enable field *189 enabled for AUI 3
AUI 4 (touchscreen)
06
n/a
automatic if AUI enable field *189 enabled for AUI 4
Internal IP/
C
ell
Device
03
103
automatic if installed and enabled in menu mode
∗
29
Zone Expanders (4219/4229):
module 1 (for zones 09 -
16)
module 2 (for zones 17 -
24)
module 3 (for zones 25 -
32)
module 4 zones 33 -
40
module 5 zones 41
-
48
07
08
09
10
11
107
108
109
110
111
∗
56 zone programming: input device type entry, then:
automatic if zone no. 9
-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay assigned
automatic if zone no. 25-32 entered as AW type or relay assigned
automatic if zone no. 33-40 entered as AW type or relay assigned
automatic if zone no. 41
-
48 entered as AW type or relay assigned
Relay Modules (4204):
module 1
module 2
module 3
module 4
12
13
14
15
112
113
114
115
∗
79 output device programming: devic
e address prompt:
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
Keypads:
keypad 1
keypad 2
keypad 3
keypad 4
keypad 5
keypad 6
keypad 7
keypad 8
16
17
18
19
20
21
22
23
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
data field programming as listed below:
always enabled, all sounds enabled.
data field
∗
190
data field
∗
191
data field
∗
192
data field
∗
193
data field
∗
194
data field
∗
195
data field
∗
196
RIS Communication
25
n/a
automa
tic if Remote Interactive Services enabled in field
∗
91
†† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
AUI devices are not supervised and therefore do not report.
UL NOTICES
1.
Entry Delay No. 1 and No. 2 (fields
∗
35,
∗
36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and
entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may
not
exceed 45 seconds.
2.
For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total exit delay time must not
exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time must not exceed 120 seconds.
3.
The maximum number of reports per armed period (field
∗
93) must be set to “0” (unlimited) for UL installations.
4.
Periodic testing (see scheduling mode) must be at least every 24 hours.
5.
Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.).
6.
All parti
tions must be owned and managed by the same person(s).
7.
All partitions must be part of one building at one street address.
8.
If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9.
For UL commercial burglar
alarm installations the control unit must be protected from unauthorized access. The tamper switch
installed to protect the control unit enclosure door is suitable for this purpose.
10.
Remote downloading without an alarm company technician on-
site (unattended downloading) is not permissible for UL installations.
11.
Auto-
disarming is not a UL Listed feature.
12.
As
SIA
limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications
, the
following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring location, or
to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm
the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13.
This control is not intended for bank safe and vault applications.
SIA QUICK REFERENCE GUIDE
1.
*31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number of reports in
armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).
2.
*34 Exit Delay: Minimum exit delay is 45 seconds.
3.
*35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4.
*37 Audible Exit Warning: Feature always enabled; field does not exist.
5.
*39 Power Up in Previous State: Must be “1,” power up in previous state.
6.
*40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91 must be set.
7.
*50 Burglary Dial Delay: Delay must be minimum of 30 seconds.
8.
*59 Exit Error Alarm Report Code: Always enabled.
9
*68 Cancel Report Code: Default is “code enabled.”
10.
*69 Recent Closing Report Code: Always enabled.
11.
*91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be set to “1” (
enabled).
12.
*93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13.
Cross zone timer is set in field
∗
85; cross zone pairs are assigned in zone list 4 using
∗
81 Zone List mode.
14.
Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code reporting by
programming zone 92 using
∗
56 Zone Programming mode.
15.
Fire alarm verification is a built-
in system feature when a zone is programmed for zone type 16.
††
Addressable devices are identified by “1” plus the device
address when reporting. Enter report code for zone 91 to
enable device r
eporting (default = enabled). See field
∗
199
for addressable device (ECP) 3-
digit/2
-digit identification
keypad display options.
AUI devices are not supervised and therefore do not report.
–
32
–
FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENTS
The user shall not make any changes or modifications
to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized
changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC r
equirements and has been found acceptable for use. The FCC requires the following statement for your
information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordanc
e with the manuf
acturer's
instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing
device in accordance with the specifications in Part 15 of FCC Rules, which are designed t
o provide reasonable protection against such interference in a
residential installation. However, there is no guarantee that interference will not occur in a particular installation. If th
is equipment does cause interference to
radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one
or more of the following measures:
• If using an indoor antenna,
replace it with a quality outdoor antenna.
• Reorient the rece
iving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet
so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES
-003.
Cet appareil numérique de la classe B est conforme à la norme NMB
-003 du Canada.
INDUSTRY CANADA (IC) STATEMENTS
This device complies with FCC Part 15 and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2)
This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soum
is aux conditions
suivantes: (1) Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interférence re
çue y compris les interférences
causant une réception indésirable.
Responsible Party / Issuer of Supplier’s Declaration of Conform
ity:
Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate
Center Drive., Melville, NY 11747, Ph: 516
-577-2000
Partie responsable / Émetteur de la déclaration de conformité du
fournisseur :
Ademco Inc., une filiale de Resideo Technologies, Inc.,
2 Corporate Center Drive., Melville, NY 11747, Tél. 516
577
-2000
TELEPHONE/MODEM INTERFACE
FCC Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC
registration number
and
Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone
-company
-provided coin service. Connection to
party lines is subject to state tariffs. This equipment is
hearing
-aid compatible.
Industry Canada
NOTICE
: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunicati
ons network
protective,
operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). T
he Department
does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users s
hould ensure that it is permissible to be connected to the facilities of the local telecommunications company. The
equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above condit
ions may
not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alteratio
ns made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and
internal metallic water pipe
system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution
: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or electrician, as
appropria
te.
Ringer Equivalence Number Notice:
The
Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may con
sist of any combination of devices subject only to the requirement that the sum
of the Ringer Equivalence Numbers of all the devices does not exceed 5.
Industrie Canada
AVIS:
l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection,
d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives au
matériel terminal. Le Ministère n’assure to
utefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterpris
e locale de télécommunication. Le
matériel doit égale
ment être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est possible que la co
nformité
aux conditions énoncées ci
-dessus n’empêche pas la dégradation du service dans certaines situations.
Les réparations de m
atériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de télécommunications
peut
demander à l’utilisateur de
débrancher un appareil à la suite de réparations ou de modifications effectuées par l’utilisateur
ou à cause de mauvais
fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électriqu
e, de lignes téléphoniques et des
canalisations d’eau métalliques, s’il y en a, sont raccor
dés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissement :
L’utilisateur ne doit pas tenter de faire ces raccordements lui
-même; il doit avoir racours à un service d’inspection des installations
électriques, o
u à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie
(IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui peuvent être
raccordés à une interface. La terminaison d’une interface téléphonique peut c
onsister en une combinaison de quelques dispositifs, à la seule condition que
la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.
RF EXPOSURE WARNING
The LTE
-21V
module must be installed to provide a separation distance of at least 7.8 in. (20 cm) from all persons and must
not be co-
located or operating in conjunction with any other antenna or transmitter except in accordance with FCC multi
-
transmitter product procedures.
–
33
–
WARNING
-
THE LIMITATIONS OF THIS ALARM SYS
TEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or ot
her emergency. Any
alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
•
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an
alarm warning device.
•
Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery
-
operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC
will not work if their AC power supply
is cut off for any reason, however briefly.
•
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has
been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
•
A user may not be able to reach a panic or emergency button quickly enough.
•
While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not acti
vate or provide early
warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Managem
ent Agency.
Some of the reasons smoke detectors used in conjunction with this System may not work are as foll
ows. Smoke detectors may have been
improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in
chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors al
so may not sense a fire on another level of a residence
or building. A second floor detector, for example, may not sense a first floor or basement fire. Finally, smoke detectors hav
e sensing
limitations. No smoke detector can sense every kind of fire every
time. In general, detectors may not always warn about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable material
s, overloaded
electrical circuits, children playing with mat
ches, or arson. Depending on the nature of the fire and/or location of the smoke detectors, the
detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or
death.
•
Passive
Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive
Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected
in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings,
floors, closed
doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spray
ing of any material on the mirrors, windows
or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection performance can
decrease.
•
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed
or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken
or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo,
radio, ai
r conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-
impaired
people.
•
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of
service. Telephone lines are also subject to compromise by sophisticated intruders.
•
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves
from the
emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
•
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 10
years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system
should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and remote keypad) should be
tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries
may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as
humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given
installation. This
wireless
system, however, can identify a true low
-battery situation, thus allowing time to arrange a change of battery to maintain protection for that
given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate,
but an alarm system is not a substitute for insurance.
Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure thei
r lives and
property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about
these developments.
–
34
–
NOTES
–
35
–
NOTES
The product should not be disposed of with other household waste. Check for the nearest authorized collection
centers or authorized
recyclers. The correct disposal of end-of
-life equipment will help prevent potential negative
consequences for the environment and human health.
SUPPORT, WARRANTY, & PATENT INFORMATION
For the latest documentation and online support information, please go to:
https://mywebtech.honeywellhome.com/
For the latest warranty information, please go to:
https://www.security.honeywellhome.com/hsc/r
esources/wa/index.html
For patent information, see https://www.resideo.com/patent
MyWebTech
Warranty
Patents
The Honeywell Home Trademark is used under license from Honeywell International Inc.
This product is manufactured by Resideo Technologies, Inc.
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
2019 Resideo Technologies, Inc.
www.resideo.com
Ê800
-
25359V1AaŠ
800
-
25359
V1A
8
/19
Rev
A
- Uploaded