2GIG FF1e-345 - Programming Guide Dated 2023



Related Products

2GIG FF1e-345 - Encrypted Smoke and CO Detector Takeover Module for GC2e and GC3e
2GIG FF1e-345
Encrypted Smoke and CO Detector Takeover Module for GC2e and GC3e
List Price: $98.00
Our Price: $78.99

Document Transcript

2GIG-FF1E-345
AUDIO DETECTOR
OPERATION
The FireFighter sensor is designed to listen to any smoke, carbon, or combo
detector. It is one of the e-Series devices from Nice North America, providing
enhanced security with encrypted communications to the control panel using
the 345Mhz frequency. Once confirmed as an alarm, the FireFighter sensor
will transmit a signal to the alarm control panel which, if connected to a
central monitoring station, will dispatch the fire department.
WARNING:
This audio detector is intended only for use with smoke,
carbon and combo detectors but it does not detect the presence of
smoke, carbon, heat or fire directly.
INSTALL BATTERY
Install battery (packaged separately) into FireFighter sensor base with correct
polarity.
ENROLLING
To enroll the sensor, set your panel into program mode. Refer to your specific
alarm panel instruction manual for details on these menus. For control panels
with an automatic learn feature press and release the
Learn
button located in
the center of the circuit board next to the tamper switch. Do not use the tamper
switch to enroll FireFighter. Alternatively, the serial number can be manually
entered into the panel. The number printed on the device is the serial number
for the smoke detection portion, whereas for the CO portion, you simply add
one (1) to that number. See Figure 1 above for location of
Learn
button.


To enroll for fire signal detection, press and release the
Learn
button.
Repeat as required. This uses Loop 1 of the serial number printed on
the device. Program the sensor on the panel as sensor type 24-Hour
Fire (09).


To enroll for Carbon Monoxide signal detection, press the
Learn
button
for 2 seconds. Repeat as required. This uses Loop 1 of the serial
number plus 1. Program the sensor type on the panel as 24-Hour Carbon
Monoxide (14).
The equipment code is “2069” for 2GIG systems See Figure 3 for location of
Learn
button.
CLOSING SENSOR (see Figure 3)
After battery is installed and sensor is Enrolled, close sensor as shown in
Figure 3 and fasten together with two (2) screws (packaged separately).
MOUNTING (see Figures 4 & 5)
Included with this device is a mounting bracket, hardware and double sided
tape. For proper operation ensure the side of the device with the small holes is
directly facing the sounder holes on the smoke detector. Secure the mounting
bracket to the wall or ceiling using the two mounting screws or double sided
tape provided. Secure the sensor to the mounting bracket by sliding tabs
into base of sensor.
FireFighter must be mounting within 6 inches of the
detector for optimal operation as shown in Figure 5.
WARNING:
Non-interconnected smoke detectors require an audio
detector by each smoke detector sounder.
This equipment should be installed in accordance with Chapter  2 of
the National Fire Alarm Code, ANSI/NFPA 72, (National Fire Protection
Association, Battery March Park, Quincy, MA 02269).Printed information
describing proper installation, operation, testing, maintenance, evacuation
planning, and repair service is to be provided with this equipment.
Warning -
Owner’s instruction notice:
Not to be removed by anyone except occupant.
TESTING
During the first hour after powering up, the FireFighter is in test mode. This
allows you to use the
Test
button on the Smoke, CO or Combo unit to test
the system. After the first hour, the FireFighter requires at least two valid
patterns from the detector to validate the alarm, which may not be possible
via the detector
Test
button. To test the audio detection, press and hold
the detector’s
Test
button for at least 30 seconds to ensure that FireFighter
has had sufficient time to identify the alarm pattern and lock into alarm. For
combo units, the detector will typically sound the smoke temporal then the
CO temporal pattern. In test mode, the FireFighter will detect both and send
two transmissions to the panel. Ensure the FireFighter sensor cover is on and
that you wear hearing protection.


NOTE:
It is possible that FireFighter can hear other detectors in close
proximity so it is important to choose and to install the FireFighter close
to a detector that is relatively isolated from other detectors of the same
type. If this is not possible, FireFighter will still function, however it will
take longer to register and transmit an alarm to the panel. Detectors to
avoid are typically ones mounted in hallways outside of bedrooms that
will also have additional detectors nearby.


NOTE:
This system must be checked by a qualified technician at least
once every three (3) years. Please test the unit once per week to ensure
proper functionality.
PRINTER’S INSTRUCTIONS:
INSTR,INSTL,2GIG-FF1E-345 - P/N: 10024471 Rev-C - INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 8.500” x 11.000” - TOL. ±0.125”- SCALE: 1-1 - SIDE 1 OF 2
FIREFIGHTER
SENSOR BASE
INSTALL BATTERY
CHECK POLARITY
Slide to
Remove
INSTALL SENSOR TOP
AFTER

ENROLLING
Figure 1
LEARN BUTTON
TAMPER SWITCH
FIREFIGHTER SENSOR
Figure 2
1. HOOK SENSOR
TOP INTO SLOT
2. SNAP CLOSED
3. INSER
T TWO SCREWS
THROUGH BOTTOM
INST
ALLED BA
TTER
Y
SENSOR SIDE VIEW
Figure 3
LINE UP WITH
SMOKE DETECTOR
LINE UP WITH
SMOKE DETECTOR
Smoke Detector This Side
FIREFIGHTER SENSOR
SENSOR
MOUNTING
PLA
TE
MOUNTING
SCREWS
OR
DOUBLE
STICK T
APE
Smoke Detector This Side
SENSOR
MOUNTING
PLA
TE
Figure 4
6” MAXIMUM
FIREFIGHTER
SENSOR
DETECT
OR
LINE UP SPEAKER
HOLES
WITH
SMOKE DETECTO
R
Slide to
Remo
ve
Slide to
Remo
ve
Figure 5 Legacy Smoke Detectors
All Smoke detectors should be replaced after 10 years. If you encounter
a smoke detector that does not support Temporal 3 pattern, that smoke
detector should be replaced as per the manufacturer recommendation. If
replacement is not an option, the FireFighter can be programmed to detect
non-temporal detectors.
In the mode, the FireFighter must not be located near any other audible
device, like a security keypad or sounder. Those can be misconstrued
as a valid smoke alarm.
To enter this change the mode press and hold
the tamper switch while inserting the battery. Release the tamper switch
and note the LED. Repeating this action will switch the FireFighter operating
mode from one to the other.
You can verify the mode FireFighter is in by simply removing the battery and
replacing it. The LED will flash once or twice depending on the mode it is in.
ONE flash:
Only Temporal 3 and 4 signal will trigger an alarm (Default).
TWO flashes:
Generic listening mode. Will trigger after 30 seconds of
continuous sounding.
REPLACING THE BATTERY
When the battery is low a signal will be sent to the control panel. To replace
the battery:
1.
Slide Sensor in direction of arrow to remove from mounting plate.
2.
Remove 2 screws from sensor base. Remove the top cover to reveal the
battery. This will send a tamper signal to the control panel.
3.
Replace with a Panasonic CR123A battery ensuring the + side of the
battery faces as indicated on the device (see Figure 1).
4.
Re-attach the cover, you should hear a click when the cover engages
properly.
5.
Re-install the two screws holding the sensor together.
WARNING:
While the audio detector monitors its own battery, it does not
monitor the battery in the smoke detectors. Batteries should be changed as
per the original smoke detector manufacturer’s instructions. Always test the
audio detector and smoke alarms after battery installation to confirm proper
operation.
Specifications
Transmitter Frequency
345.00 MHz (crystal controlled)
Battery
One 3Vdc lithium CR123A (1550 mAh)
Code Outputs
Alarm; Supervisory; Low Battery
Battery Life
5 Years
Detection distance
6 inches max
Operating Temperature
32° to 120° F (0° to 49° C)
Operating Humidity
5-95% RH non-condensing
Compatibility
2GIG receivers
Supervisory Interval
64 min (approx.)
Maximum current draw
23mA during transmission
Housing Material
ABS Plastic
Color
White
Regulatory Listings
FCC, IC
Equipment Code
2069
Panel Programming
Sensor Loop
Loop 1
Regulatory Information
We, Nice North America LLC of 5919 Sea Otter Place, Ste. 100, Carlsbad, CA 92010, declare under our sole
responsibility that the device, 2GIG-FF1E-345 complies with Part 15 of the FCC rules.
FCC Notice & ICC Notice
This device complies with Part 15 of the FCC’s Rules. Operation is subject to the following two conditions:
1)
This device may not cause harmful interference, and
2)
This device must accept any interference received, including interference that may cause undesired
operation.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de
licence. L’exploitation est autorisée aux deux conditions suivantes:
1)
l’appareil ne doit pas produire de brouillage, et
2)
l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est
susceptible d’en compromettre le fonctionnement.
This Class B digital apparatus complies with Canadian ICES‐003.
Cet appareil numérique de la classe B est conforme à la norme NMB¬003 du Canada.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the
following measures:

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and receiver.

Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.
WARNING
Changes or modifications not expressly approved by the manufacturer could void the user’s authority to
operate the equipment.
* For more warranty and compliance information, visit out website (www.2gig.com)
Limited Warranty
This Nice North America product is warranted against defects in material and workmanship for two (2)
years. This warranty extends only to wholesale customers who buy direct from Nice North America LLC or
through Nice North America LLC’s normal distribution channels. Nice North America LLC does not warrant
this product to consumers. Consumers should inquire from their selling dealer as to the nature of the
dealer’s warranty, if any. There are no obligations or liabilities on the part of Nice North America LLC for
consequential damages arising out of or in connection with use or performance of this product or other
indirect damages with respect to loss of property, revenue, or profit, or cost of removal, installation, or
reinstallation. All implied warranties for functionality, are valid only until the warranty expires. This Nice
North America LLC Warranty is in lieu of all other warranties express or implied.
All products returned for warranty service require a Return Authorization Number (RA#). Contact Returns
at 1‐855‐546‐3351 for an RA# and other important details.
Disclaimer
The Firefighter sensor does not detect the presence of smoke, heat, or fire directly. It relies solely on
the presence of an audio alarm signal generated by an existing smoke or fire detector in proximity
to the Firefighter sensor to make such a determination. The Firefighter™ sensor must be used with
smoke detectors certified according to UL Standards, and in strict accordance with the installation and
operation instructions provided with such detectors. It is the owner’s responsibility to ensure that smoke
or fire detectors used in conjunction with the Firefighter sensor are maintained and tested on a regular
basis in accordance with the manufacturer’s instructions. Nice North America expressly disclaims any
responsibility for the failure of the Firefighter sensor to detect the presence of smoke or fire due to the
failure of any smoke or fire detector used in conjunction with the Firefighter sensor to operate properly
due to any condition, including improper installation, operation, maintenance or testing of such smoke
or fire detector.
Slide to
Remove
SENSOR MOUNTING PLA
TE
MOUNTED TO CEILING
SLIDE SENSOR
IN DIRECTION OF
ARROW TO REMOVE
FROM MOUNTING PLA
TE
Figure 6
10024471 Rev-C
5919 Sea Otter Place, Suite 100
Carlsbad, CA 92010 USA
For technical support in the USA and Canada:
855-2GIG-TECH (855-244-4832)
Email:

2GIG.Linear@niceforyou.com
Visit Niceforyou.com for technical support hours of operation.
For technical support outside of the USA and Canada:
Contact your regional distributor
.
Visit www.2gig.com/dealers for a list of distributors in your region.
Niceforyou.com
©2023 Nice North America LLC. 2GIG is a registered
trademark of Nice North America LLC. All rights reserved.


Uploaded