2GIG SMKT3‐345 Install Guide

2GIG
SMKT3
345
WIRELESS SMOKE/HEAT/FREEZE ALARM
INSTALL INSTRUCTIONS
FCC
ID:
ZFH
SMKT3345
Industry
Canada
ID:
9640A
SMKT3345
2GIG’s
Wireless
Smoke/Heat/Freeze
Alarm
is
a
3xAAA
battery
powered
wireless
alarm
intended
for
use
in
a
2GIG
system.
The
alarm
has
a
built
in
wireless
transmitter,
which
communicates
with
the
2GIG
Control
Panel.
When
smoke,
excessive
heat
or
cold
is
detected,
the
alarm
sounds
a
loud
local
alarm
and
the
built
in
t
ransmitter
sends
a
signal
to
the
Control
Panel.
This
alarm
is
designed
to
provide
protection
within
a
35
foot
radius
of
the
unit.
The
2GIG
SMTK3
345
can
send
alarm,
tamper
and
battery
condition
messages
to
the
Control
Panel.
Box Contents
•Wireless
Smoke/Heat
Alarm
•Pack
of
screws
and
fixings
•3
AAA
Energizer
E92
batteries
(1.5
V1100mAh)
or
equivalent
The
Wireless
Smoke/Heat
Alarm
contains
a
sounder
that
generates
the
ASHI
s3.41
temporal
3
pattern
in
an
alarm
condition.
In
alarm,
a
message
is
also
sent
to
the
Control
Panel
and
the
alarm’s
zone
type
and
name
ar
e
displayed
at
the
panel.
During
an
alarm
condition,
pressing
the
alarm’s
hush
button
silences
the
sounder.
Tricolored
LED
(red,
yellow,
green)
and
a
sounder
on
the
alarm
provide
local
visual
and
audible
indication
of
the
alarm’s
status.
After
power
up
has
completed
and
the
alarm
is
functioning
normally,
the
green
LED
blink
s
every
12
seconds.
Alarm
Trouble:
When
the
alarm
has
a
general
fault,
the
yellow
LED
blinks
once
every
four
seconds
and
there
is
a
chirp
every
48
seconds.
After
4
hours
the
2GIG
Control
Panel
displays
a
loss
of
supervision
message.
Alarm
Dirty
Feature:
When
the
alarm
has
been
contaminated,
the
y
ellow
LED
blinks
once
every
8
seconds
and
there
is
a
chirp
every
48
seconds.
After
4
hours
the
2GIG
Control
Panel
displays
a
loss
of
supervision
message.
Low
Battery
Detection:
The
Wireless
Smoke/Heat
Alarm
is
powered
by
3
AAA
batteries.
The
alarm
regularly
checks
for
a
low
battery.
If
a
lo
w
battery
is
detected,
the
transmitter
sends
a
low
battery
message
to
the
2GIG
Control
Panel,
that
displays
the
alarm’s
ID
at
low
battery.
In
addition,
the
yellow
LED
of
the
alarm
blinks
every
12
seconds.
The
alarm’s
sounder
chirps
every
48
seconds
(yellow
LED
continues
to
blink)
until
the
ba
tteries
are
replaced.
Pressing
the
hush
button
silences
the
chirping
for
12
hours
if
no
other
trouble
conditions
exist.
Replace
the
batteries
when
the
chirping
begins.
Replace
the
old
batteries
with
new
ones.
If
you
are
experiencing
low
battery
issues,
check
to
make
sure
that
you
have
the
correct
batteries
installed
(3
AA
A
Energizer
E92).
Inserting and Replacing Batteries
1. Remove
the
alarm
from
its
base
by
twisting
the
it
counter
clockwise.
Remove
and
dispose
of
the
batteries
according
to
your
local
regulations.
2. To
ensure
proper
power
down
sequence,
wait
a
minimum
of
20
seconds
before
inserting
new
batteries.
3. Insert
3
AAA
Energizer
E92
batteries
in
the
battery
compartment.
Follow
the
polarity
diagr
am
inside
the
compartment.
If
the
batteries
are
inserted
incorrectly,
remove
gently
with
a
non
conductive
tool
and
correctly
reinsert.
4. Reinstall
the
alarm
onto
the
mounting
base
by
turning
the
alarm
clockwise
until
the
mating
marks
align.
5. After
the
power
up
sequence,
the
green
LED
should
blink
about
once
every
12
seconds
to
indic
ate
normal
operation.
If
the
batteries
are
not
inserted
correctly,
the
alarm
will
not
operate
and
the
batteries
may
be
damaged.
If
the
alarm
does
not
power
up,
check
for
correct
battery
insertion
and
for
fully
charged
batteries.
Constant
exposure
to
high
humidity
may
reduce
battery
life.
Programming
The
following
steps
describe
general
guidelines
for
programming
(learning)
the
Wireless
Smoke/Heat
Alarm
(2GIG
SMKT3
345)
into
the
2GIG
Control
Panel.
Scroll
between
options
using
the
and
arrows.
Move
to
the
previous
or
next
prompt
by
pressing
the
and
arrows.
For
more
details
regarding
how
to
program
the
Control
Panel,
refer
to
the
2G
IG
Control
Panel
Install
Guide
.
1. Select
RF
sensor
#(01
to
48).
Assign
the
Wireless
Smoke/Heat
Alarm
to
a
new
zone.
2. Select
RF
sensor
type.
(09)
24
hour
fire
(recommended
for
smoke
and
fire)
(16)
24
hour
fire
with
verification
(optional)
(23)
no
response
type
(optional
with
freeze)
3. Select
RF
equipment
type.
4. Select
RF
sensor
equipment
code.
Enter
1058
for
th
e
SMKT3
345
2GIG
Smoke/Heat
Alarm.
5. Enter
RF
sensor
serial
number
(7
digits).
Manual
Entry:
Type
in
the
last
7
digits
of
the
TX
ID
that
is
found
outside
the
box
or
on
the
bottom
of
the
head
unit
by
removing
the
base.
Auto
Entry:
With
the
panel
in
Learn
in
mode
(p
ress
Shift
then
Learn
)
cause
a
tamper
on
the
alarm
by
twisting
the
base
unit
counter
clockwise
and
removing
it.
The
correct
TX
ID
should
appear.
Accept
the
correct
TX
ID
by
pressing
ok
.
Remember
to
press
the
arrow
to
continue
through
the
system
configuration
prompts.
6. Select
RF
sensor
equipment
age.
(0)
new
(p
roduct
is
new)
(1)
existing
(product
already
exists).
7. Select
RF
sensor
loop
number.
Select
which
loop
you
would
like
to
set
up.
(1)
Smoke
(2)
Heat
(3)
Freeze
NOTE:
Each
loop
must
be
setup
as
a
different
zone.
If
you
want
to
utilize
all
three
features
(smoke,
heat,
freeze)
you
will
need
to
se
tup
three
different
zones
and
use
each
loop.
8. Select
RF
sensor
1
dialer
delay
(0)
disabled
(there
should
never
be
a
dialer
delay
on
this
type
of
alarm)
9. Construct
RF
sensor
descriptor.
Press
Insert
then
press
any
number
between
002
and
255
to
add
a
word.
For
example,
if
you
wanted
to
na
me
this
alarm
as
“smoke
alarm,”
press
Insert
then
press
208
for
SMOKE
.
Press
Insert
then
press
005
for
ALARM
.
10. Select
RF
sensor
reports
(0
to
1).
(0)
disabled
(sensor
does
not
report
to
central
station)
(1)
enabled
(sensor
reports
to
the
central
station)
11. Select
RF
sensor
supervised
(0
to
1)
.
(0)
disabled
(sensor
does
not
report
loss
of
supervision
or
low
battery)
(1)
enabled
(sensor
reports
loss
of
supervision
or
low
battery)
12. Select
RF
sensor
chime
(0
to
13).
(0)
disabled
(panel
will
not
chime
when
sensor
is
activated)
(1)
(13)
(selects
a
voice
and
chime
to
sound
when
sensor
is
activated)
13.
To
program
another
sensor,
click
next
.
14. To
exit
programming,
click
skip
then
end
and
exit
.
Upon
exit,
the
panel
takes
a
few
seconds
to
reset.
Testing
Before
testing,
put
the
panel
into
test
mode
so
the
central
station
is
not
notified
to
prevent
unwanted
alarms.
Testing
the
alarm
activates
an
alarm
sound
and
sends
a
signal
to
the
Control
Panel.
The
test
function
cannot
be
used
if
the
alarm
has
a
trouble
condition.
Test
alarm
sounder,
LEDs
and
transmitter
1.Hold
the
Test
button
for
4
beeps
(approximately
6
seconds).
2.Release
the
Test
button.
3.Once
released,
the
product
will
continue
to
beep
5
more
times.
Before
the
beeps
stop,
a
signal
will
be
sent
triggering
the
alarm.
Smoke
Test
Hold
a
cotton
wick
at
the
side
of
the
alarm
and
gently
blow
smoke
through
the
alarm
until
the
smoke
triggers
the
alarm.
You
can
also
use
smoke
aerosol.
Direct
Heat
Test
(Use
Hair
Dryer
1000
1500
Watts)
Direct
heat
toward
the
alarm.
Hold
the
heat
source
about
12
inches
from
the
alarm
to
avoid
damage
to
the
plastic.
The
alarm
resets
only
after
it
has
time
to
cool.
If
an
alarm
fails
any
of
these
tests,
see
Maintenance
for
how
to
clean
the
alarm.
Mounting the Alarm
1. See
the
diagram
to
install
the
mounting
base
on
the
ceiling
or
on
the
wall.
Use
the
2
screws
and
anchors
provided.
Maneuver
the
base
so
the
screws
are
at
the
elbow
of
the
screw
slots
and
secure.
2. Fit
the
alarm
inside
the
base
by
aligning
it
over
the
base
as
shown
(a
larm’s
alignment
notch
should
be
slightly
offset
from
the
mounting
base
tamper
release
tab),
then
turn
the
alarm
clockwise
until
the
alarm
clicks
into
the
base.
of 2


Related Products

2GIG SMKT3-345 - Wireless Smoke, Heat and Freeze Detector
2GIG SMKT3-345
Wireless 2GIG Smoke, Heat, & Freeze Detector

Related Categories


Document Transcript

2GIG‐SMKT3‐345
WIRELESS SMOKE/HEAT/FREEZE ALARM
INSTALL INSTRUCTIONS
FCC ID: ZFH‐SMKT3345
Industry Canada ID: 9640A‐SMKT3345 
2GIG’s Wireless Smoke/Heat/Freeze Alarm is a 3xAAA battery‐powered wireless alarm intended 
for use in a 2GIG system. The alarm has a built‐in wireless transmitter, which communicates 
with the 2GIG Control Panel. When smoke, excessive heat or cold is detected, the alarm sounds 
a loud local alarm and the built‐in transmitter sends a signal to the Control Panel. This alarm is 
designed to provide protection within a 35‐foot radius of the unit. The 2GIG‐SMTK3‐345 can 
send alarm, tamper and battery condition messages to the Control Panel.
Box Contents
• Wireless Smoke/Heat Alarm
• Pack of screws and fixings
• 3 AAA Energizer E92 batteries (1.5 V1100mAh) or equivalent
The Wireless Smoke/Heat Alarm contains a sounder that generates the ASHI s3.41 temporal 3
pattern in an alarm condition. 
In alarm, a message is also sent to the Control Panel and the alarm’s zone type and name are
displayed at the panel. During an alarm condition, pressing the alarm’s hush button silences the 
sounder. Tricolored LED (red, yellow, green) and a sounder on the alarm provide local visual and 
audible indication of the alarm’s status.
After power‐up has completed and the alarm is functioning normally, the green LED blinks every 12 
seconds.
Alarm Trouble: When the alarm has a general fault, the yellow LED blinks once every four seconds 
and there is a chirp every 48 seconds. After 4 hours the 2GIG Control Panel displays a loss of
supervision message.
Alarm Dirty Feature: When the alarm has been contaminated, the yellow LED blinks once every 8 
seconds and there is a chirp every 48 seconds. After 4 hours the 2GIG Control Panel displays a loss 
of supervision message.
Low Battery Detection: The Wireless Smoke/Heat Alarm is powered by 3 AAA batteries. The alarm 
regularly checks for a low battery. If a low battery is detected, the transmitter sends a low battery 
message to the 2GIG Control Panel, that displays the alarm’s ID at low battery. In addition, the
yellow LED of the alarm blinks every 12 seconds. The alarm’s sounder chirps every 48 seconds
(yellow LED continues to blink) until the batteries are replaced. Pressing the hush button silences 
the chirping for 12 hours if no other trouble conditions exist. Replace the batteries when the
chirping begins. Replace the old batteries with new ones.
If you are experiencing low battery issues, check to make sure that you have the correct batteries 
installed (3 AAA Energizer E92).
Inserting and Replacing Batteries
1. Remove the alarm from its base by twisting the it counter‐clockwise. Remove and dispose of 
the batteries according to your local regulations.
2. To ensure proper power‐down sequence, wait a minimum of 20 seconds before                           
inserting new batteries.
3. Insert 3 AAA Energizer E92 batteries in the battery compartment. Follow the polarity diagram 
inside the compartment. If the batteries are inserted incorrectly, remove gently with a non‐
conductive tool and correctly reinsert.
4. Reinstall the alarm onto the mounting base by turning the alarm clockwise until the mating 
marks align.
5. After the power‐up sequence, the green LED should blink about once every 12 seconds to
indicate normal operation. If the batteries are not inserted correctly, the alarm will not operate 
and the batteries may be damaged. If the alarm does not power‐up, check for correct battery 
insertion and for fully charged batteries.
Constant exposure to high humidity may reduce battery life.
Programming
The following steps describe general guidelines for programming (learning) the Wireless 
Smoke/Heat Alarm (2GIG‐SMKT3‐345) into the 2GIG Control Panel. Scroll between options 
using the ← and → arrows. Move to the previous or next prompt by pressing the ↑ and ↓ 
arrows. For more details regarding how to program the Control Panel, refer to the 2GIG
Control Panel Install Guide.
1. Select RF sensor #(01 to 48). Assign the Wireless Smoke/Heat Alarm to a new zone.
2. Select RF sensor type. 
(09) 24‐hour fire (recommended for smoke and fire)
(16) 24‐hour fire with verification (optional)
(23) no response type (optional with freeze)
3. Select RF equipment type.
4. Select RF sensor equipment code. Enter 1058 for the SMKT3‐345 2GIG Smoke/Heat Alarm.
5. Enter RF sensor serial number (7 digits).
Manual Entry: Type in the last 7 digits of the TX ID that is found outside the box or on the
bottom of the head unit by removing the base.
Auto Entry: With the panel in Learn‐in mode (press Shift then Learn) cause a tamper on the 
alarm by twisting the base unit counter‐clockwise and removing it. The correct TX ID should 
appear. Accept the correct TX ID by pressing ok.
Remember to press the ↓ arrow to continue through the system configuration prompts.
6. Select RF sensor equipment age.
(0) new (product is new)
(1) existing (product already exists).
7. Select RF sensor loop number. Select which loop you would like to set up.
(1) Smoke
(2) Heat
(3) Freeze
NOTE: Each loop must be setup as a different zone. If you want to utilize all three features 
(smoke, heat, freeze) you will need to setup three different zones and use each loop.
8. Select RF sensor 1 dialer delay
(0) disabled (there should never be a dialer delay on this type of alarm)
9. Construct RF sensor descriptor. Press Insert then press any number between 002 and 255 to 
add a word. For example, if you wanted to name this alarm as “smoke alarm,” press Insert then 
press 208 for SMOKE. Press Insert then press 005 for ALARM. 
10. Select RF sensor reports (0 to 1).
(0) disabled (sensor does not report to central station)
(1) enabled (sensor reports to the central station)
11. Select RF sensor supervised (0 to 1).
(0) disabled (sensor does not report loss of supervision or low battery)
(1) enabled (sensor reports loss of supervision or low battery)
12. Select RF sensor chime (0 to 13).
(0) disabled (panel will not chime when sensor is activated)
(1)‐(13) (selects a voice and chime to sound when sensor is activated)
13. To program another sensor, click next. 
14. To exit programming, click skip then end and exit. Upon exit, the panel takes a few seconds to 
reset.
Testing
Before testing, put the panel into test mode so the central station is not notified to prevent 
unwanted alarms. Testing the alarm activates an alarm sound and sends a signal to the Control 
Panel. The test function cannot be used if the alarm has a trouble condition.
Test alarm sounder, LEDs and transmitter
1.Hold the Test button for 4 beeps (approximately 6 seconds).
2.Release the Test button.
3.Once released, the product will continue to beep 5 more times. Before the beeps stop, a
signal will be sent triggering the alarm.
Smoke Test
Hold a cotton wick at the side of the alarm and gently blow smoke through the alarm until the 
smoke triggers the alarm. You can also use smoke aerosol. 
Direct Heat Test (Use Hair Dryer 1000‐1500 Watts)
Direct heat toward the alarm. Hold the heat source about 12 inches from the alarm to avoid 
damage to the plastic. The alarm resets only after it has time to cool. 
If an alarm fails any of these tests, see Maintenance for how to clean the alarm.
Mounting the Alarm
1. See the diagram to install the mounting base on the ceiling or on the wall. Use the 2 screws and 
anchors provided. Maneuver the base so the screws are at the elbow of the screw slots and 
secure.
2. Fit the alarm inside the base by aligning it over the base as shown (alarm’s alignment notch 
should be slightly offset from the mounting base tamper release tab), then turn the alarm 
clockwise until the alarm clicks into the base.
NFPA Recommended Locations for Alarm
According to the National Fire Protection Association (NFPA) the major threat from fire in a
dwelling unit occurs at night when everyone is asleep. The principal threat to persons in 
sleeping areas comes from fires in the remainder of the house; therefore smoke alarms are 
best located between the bedroom areas and the rest of the house.
Where NOT to install the Alarm
• Directly above a sink, cooker, stove or oven
• Do not locate alarm within 5 feet (1.5 m) of any cooking appliance
• Next to a door or window that would be affected by drafts (extractor fan or air vent)
• Outside
• In or below a cupboard
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
Do NOT INSTALL this alarm in a location where the normal ambient temperature is 
below 40 F (4.4 C) or where it exceeds 100 F (37.8 C)
INSTALL this equipment in accordance with the National Fire Protection Association (NFPA) 72.
Maintenance
Clean the alarm once a year. To clean the alarm, remove it from the mounting base. You can 
clean the interior using compressed air or a vacuum cleaner. Blow or vacuum through the 
openings around the perimeter of the alarm. The outside of the alarm can be wiped with a 
damp cloth. After cleaning, test the alarm by pushing the Test button. If cleaning does not 
restore the alarm to normal operation you need to replace the alarm.
WARNING: READ THE FOLLOWING CAREFULLY
• NFPA 72 states: Fire‐warning equipment for residential occupancies are capable of
protecting about 50% of the occupants in potentially fatal fires. Victims include the 
elderly, children, and the physically or mentally impaired. Victims include any person 
that cannot escape even when warned early enough that escape should be possible. For 
these people, other strategies such as protection‐in‐place or assisted rescue or escape 
would be necessary.
• Studies show that Smoke/Heat Alarms may not awaken all sleeping individuals. It is the
responsibility of individuals in the household that are capable of assisting others to
provide assistance to those who may not be awakened by the audible alarm or those 
who may be incapable of safely evacuating the area unassisted.
• A battery‐powered alarm must have the specific battery type installed, be in good
condition, and be mounted properly.
• The use of alcohol or drugs may also impair one’s ability to hear the audible alarm. For
maximum protection, ensure that an audible alarm is installed on every floor of the 
home.
• Smoke/Heat Alarms only provide protection to the residence if smoke actually reaches 
the alarm. The Smoke/Heat Alarm is not a substitute for an insurance policy.
Home owners and renters should have adequate insurance to protect their properties.
Safety Tips
• Make a Family Escape Plan. Draw a map of your home showing all doors and windows. 
Discuss the plan with everyone in the home.
• Know at least 2 ways out of every room, if possible. Make sure all doors that lead to the 
outside of home open easily.
• Have an outside meeting place, like a light pole, mailbox, or tree a safe distance from the
residence where everyone meets.
• Practice your Family Escape Plan or “Fire Drill” at night and during the day at least twice a 
year. Only practice when every member of the house can attend.
• Practice using different ways out, if possible.
• Teach your children how to escape on their own in case you cannot help them.
• Close doors behind you as you leave.
Family Escape Plan
According to the National Fire Protection Association (NFPA) there often is very little 
time between the detection of a fire and the time it becomes deadly. This interval can be 
as little as 1 minute. Planning and practicing for fire conditions with a focus on rapid exit 
from the residence are important! Fire drills should be held so that all family members 
know the action to be taken.
If the Alarm Sounds
• Get out and stay out. Never go back inside for people or pets.
• If you have to escape through smoke, get low and go under the smoke.
• Call the fire department from outside your home.
FOR MORE SAFETY INFORMATION SEE: www.nfpa.org/education
Specifications
Regulatory Information
This device complies with Part 15 of the FCC's Rules. Operation is subject to the following 
two conditions:
1 This device may not cause harmful interference, and
2 This device must accept any interference received, including interference that may 
cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital 
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable 
protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed 
and used in accordance with the instructions, may cause harmful interference to radio 
communications. However, there is no guarantee that interference will not occur in a 
particular installation. If this equipment does cause harmful interference to radio or 
television reception, which can be determined by turning the equipment off and on, the 
user is encouraged to try to correct the interference by one or more of the following 
measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the 
receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
This product complies with FCC radiation exposure limits for an uncontrolled environment. 
Avoid operating this product at a distance less than 20 cm from the user.
Caution: Any changed or modifications not expressly approved by the party responsible for 
compliance could void the user's authority to operate this equipment.
IC approval
This device complies with Industry Canada license‐exempt RSS standard(s). Operation is 
subject to the following two conditions: (1) this device may not cause interference, and (2) 
this device must accept any interference, including interference that may cause undesired 
operation of the device.
RÉGLEMENTATION IC: Cet appareil est conforme avec Industrie Canada exempts de license 
standard RSS (s). L'opération est soumise aux deux conditions suivantes: (1) cet appareil ne 
peut causer d'interférences, et (2) cet appareil doit accepter toute interférence, y compris 
les interférences qui peuvent causer un mauvais fonctionnement du l'appareil.
Cet équipement est conforme aux limites IC exposition au rayonnement pour un 
environnement non contrôlé. Cet équipement doit être installé et utilisé avec distance 
minimum de 20cm entre l'utilisateur et l'élément rayonnant de l'appareil.
Remarque: le fabricant n'est pas responsable des interférences radio ou télévision causé par 
des modifications non autorisées de cet équipement. Une telle modification pourrait 
annuler l'autorité de l'utilisateur d'exploiter cet équipement.
This Class B digital apparatus complies with Canadian ICES‐003
Cet appareil numérique de classe B est conforme Ia á norme NMB‐003 du Canada.
LIMITED WARRANTY
This 2GIG Technologies product is warranted against defects in material and workmanship 
for 1 year. This warranty extends only to wholesale customers who buy direct from 2GIG 
Technologies or through 2GIG Technologies’ normal distribution channels. 2GIG 
Technologies does not warrant this product to consumers. Consumers should inquire from 
their selling dealer as to the nature of the dealer’s warranty, if any.
There are no obligations or liabilities on the part of 2GIG Technologies for consequential 
damages arising out of or in connection with use or performance of this product or other 
indirect damages with respect to loss of property, revenue, or profit, or cost of removal, 
installation, or reinstallation. All implied warranties for functionality, are valid only until the 
warranty expires. This 2GIG Technologies Warranty is in lieu of all other warranties expressed 
or implied.
For technical support in the USA and Canada
855-2GIG-TECH (855-244-4832)
For technical support outside of the USA and Canada
Contact your regional distributor
Visit 2gig.com for a list of distributors in your region
PN: 77‐000012‐001 Rev. D
2GIG Copyright © 2013. All rights reserved.
Transmitter Frequency 345.00 MHz (crystal controlled)
Transmitter Frequency Tolerance + ‐15 kHz
Transmitter Bandwidth 24 kHz
Modulation Type Amplitude Shift Keying‐On/Off Keying (ASK‐OOK)
Unique ID Codes Over 1 billion different code combinations
Supervisory Interval 70 minutes
Dimensions .5” x 2.5” high (125 mm x 63 mm high)
Weight (including batteries) 8.57 oz (243 g)
Color White
Spacing Rating 70 ft
Audible Signal (ANSI Temporal 3) 85dBA min. in alarm
Sensitivity .5 ‐ 3.5%/foot
Max Current 50mA
Alarm Current 20mA
Supervisory Current 25uA
Operating Temperature  40°‐100 F° (4.4°‐37.8° C)
Relative Humidity 15‐90% Non‐Condensing
Batteries (included) 3 AAA Energizer E92 or equivalent
Regulatory Listing UL 217
Warranty 2 years
Included Accessories Mounting Hardware Package


Uploaded