First Alert Pro VISTAHTKVR-B - Data Sheet - Dated 11/24



Document Transcript

The VISTAHKVR-B takeover module allows for certain legacy VISTA
(ECP) enhanced control protocol devices to be compatible with the
VISTAH3 control panel which saves dealers material and installation
costs when taking over an existing VISTA installation. With millions of
legacy VISTA installations currently active this is a huge opportunity to
take over or increase value to those systems
For 5800 wireless applications the VISTATKVR-B module allows you to
use or re-use the existing 5881 line of 5800 RF receivers, for hardwired
zone installations you can use or re-use the 4219 hardwired zone
expanders and for hardwired relay applications you can use or re-use
the 4204 relay module and/or the 4229 combined hardwired zone
expander plus relay module. Please reference the chart below for all
compatible devices.
The module has a built-in tamper allowing detection and reporting
if the front cover is removed and is supervised so if the wiring is cut
a supervision alarm will result indicating the module may not be
operational. The flexibility to mount the module on a surface wall or to
a gang box depending on the installation environment and the terminal
strips are removeable to give installers easier access to help making
wiring easier.
Specifications

Supports 17 total ECP devices, 64 zone inputs, 32 relays
and (2) 5800 RF Receivers

Electrical Input Voltage: 12VDC nominal (10-14VDC)

Electric Input Current: 45mA (This does not include powered devices

using AUX terminals)

Operating Temperature: 32 to 122 F (0 to 50 C)

Operating Humidity: 0 – 95% Relative Humidiy

Dimensions
: 6.93” W (176mm) X
5.43”H (138mm) X 1,99”D (50.5mm)

ECP addressing is set to 00-31.

Two built-in tampers (front and rear) for removal of cover
or from the wall

Module is supervised for wires being cut and alarm signal will result

Can only be mounted remotely in the included plastic on a wall or

gang box
VISTAHTKVR-B
VISTA
®
H3 Hybrid Series

ECP to IB2 Converter Module ECP Table of Compatible Devices
5800 Sensor Compatibility
Device
Device Type
4219, 4229, 4229EX
Zone Expanders
4204, 4204CF
Relay Modules
RF Receiver *
5800 Wireless Receivers
ECP-ISO / ECP-ISOR
N/A - ECP Short Isolator
Sensor
Description
5800PIR-COM
Commercial PIR Sensor
5-800PIR-OD
Outdoor PIR Sensor
5800PIR-RES
Residential PIR Sensor
5814
Miniature Door Sensor
5815
Door/Window Transmitter
5816
Door/Window Transmitter
5816OD
Outdoor Door Contact
5817CBXT
Three Zone Commercial Fire
5817XT
Three Point Wireless Transmitter
5818MNL
Recessed Door Transmitter
5820L
Slim Line Door/Window Transmitter
5822T
Tilt Sensor
5853
Dual Tec Glass Break Detector
5898
Wireless Motion Sensor
* Consists of the 5881ENH, 5881ENHC, 5881ENL, 5881ENM, 5881ENMLA, and 5883H.
Note:
ECP addressing is set from 00-31 and the address is not specific as long as no two modules may contain the same ECP address.
SUMMARY OF CONNECTIONS
iBus Input
1
Red: Positive (.)
2
Black Negative (-)
3
Yellow: iBus B
4
Green: iBus A
iBus Output
9
Green: iBus A
10
Yellow: iBus B
11
Black Negative (-)
12
Red: Positive (*)
13
LED
14
Tamper
TB4 ECP 2 Burg
5
Red: Positive (+)
6
Black Negative (-)
7
Green: Data In
8
Yellow: Data Out
INPUT
OUTPUT
VIST
AH
TKVR-B
TB4 ECP2 BURG
12
11
56
10
9
1
2
3
4
78
13
14
VIST
AT
KVR-B-001-V0 For more information
resideo.com/pro
VISTAHTKVR-B_DS | AR | 11/24
© 2024 Resideo Technologies, Inc.
All rights reserved
Resideo Technologies, Inc.
2 Corporate Center Dr. Suite 100
P.O. Box 9040
Melville, NY 11747
1-800-645-7492
Ordering Information
Part #
VISTAHTKVR-B
iBus Wiring Limitations
Wire Gauge
Total Current of All Devices Connected to a Single Wire Run
(AWG)
50mA or less
100mA
300mA
500mA
600mA
#22
700ft (213m)
350ft (107m)
120ft (37m)
70ft (21m)
60ft (19m)
#20
1200ft (366m)
600ft (183m)
200ft (61m)
120ft (37m)
100ft (30m)
#18
1900ft (579m)
950ft (290m)
320ft (98m)
190ft (58m)
160ft (49m)
#16
3000ft (914m)
1500ft (457m)
500ft (152m)
300ft (91m)
260ft (76m)
Note:
The length of all wire runs for all partitions combined must not exceed 3000 feet (914m) when unshielded quad conductor cable is used

or 1500 feet (457m) if shielded cable is used.