First Alert VISTAHISO - Installation Instructions Dated 1/24



Related Products

Taxons
First Alert VISTAHISO
VISTA H3 iBus Isolator Module
List Price:
Our Price: $40.99

Document Transcript


VISTA
H
ISO


iBus Isolator


INSTALLATION AND SETUP GUIDE

GENERAL INFORMATION

CONNECTIONS (Continued)
The
VISTA
HISO Module separates fire keypads and other devices
from burglary devices on the iBus data circuit. Isolation between
fire and burglary devices is required in a Residential Fire Listed
system. The module is designed to isolate data wir
e and power
(+/
-) shorts or grounds that occur on the burglary side of
the
iBus
circuit from interfering with communications to Fire devices
connected to the iBus.

NOTE:
This module must be installed in accordance with National
Fire alarm and Signal Code ANSI/NFPA 72, Chapter 29.

The iBus Isolator and Control Panel must be wired so that the
Control Panel iBus terminals connect to the harness from the
VISTA
HISO.
Additionally, the Control Panel
's iBus Terminals also
connect to all Fire
Devices
[1]
following the instructions that are
supplied with the devices.
The
output
on the iBus Isolator is then
used to connect to all Burglary Devices
[2]
. Wiring in this manner
isolates the Fire Devices from the Burglary Devices in case of a
short on the Burglary circuit. To connect the
iBus
Isolator, reference
the following illustration and make these connections:

Agency Note:



All power
-limited circuit wiring must remain at least 0.25” (6.35
mm) away from any non
-power
-limited circuit wiring and non
-
power-
limited circuit wiring must enter and exit the cabinet
through a different knockout and/or conduits.



Input & Output CLASS B.

INSTALLATION

The module is designed to be mounted in the control cabinet.
Below the
Control Panel PCB
and to the left of the battery.

NOTE:
Only one (1)
VISTA
HISO can be installed.

IMPORTANT:

Damage to product can occur if incorrectly wired. See summary of
connections for proper wiring.

MOUNTING


Mount using the 2 screws (provided) as shown below:


CONNECTIONS

NOTES:


Connect iBus Burglary Devices, following the directions that
come with these devices,
except
make the connections to iBus
Isolator.



If using a supplementary power supply for burglary or fire
devices, connect the ground from the power supply to the burg
ground on the iBus Isolator, or the control panel ground,
respectively.

Connect to the control’s iBus terminals via
t
he input side of the
module using the supplied harness (P/N R600
-00547)[1]. The
output (isolated Burglar) side [2] is wired as
follows:

[1]

Input Harness

[2]

Output

Description

Red

2a

12VDC Positive (+)

Black

2b

Ground (
-
)

Yellow

2c

iBus B

Green

2d

iBus A


LED OPERATION
[1]

Color

Indication

Function

Red

Fast Blink
(500ms)

Output shorted or iBus
communication
failure.

N/A

Off

Normal Operation



VISTA
HISO-003
-V0
(-)
(+)
B
A
(-)
(+)
B
A
2
1
VIS
TAHISO-005-V0
(+)
B
A
1
AFFIXING THE SUMMARY OF CONNECTIONS LABEL

The provided Summary of Connections label is to be affixed to the control panel door. It is to be placed in the blank panel
to the left
of the Summary of Connections
label.

SPECIFICATIONS

Electrical

Input Voltage

12VDC

Input Current

10mA

Environmental

Operating Temperature

32°
-

122°F (0°
-

50°C)

Operating Humidity

0
-

95% Relative Humidity

Physical

Dimensions

.866 in x 3.15 in


(22 mm x 80 mm)


FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANADA (IC) STATEMENTS

The user
shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Man
ual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.

CLASS B DIGITAL DEVICE STATEMENT

This equipment has been tested and found to comply with the limits for a Class B digital device, as defined by FCC Rules Part
15.105. The Class B
Digital Device statement can be viewed at:

https://customer.resideo.com/en
-US/support/residential/codes
-and
-standards/FCC15105/Pages/default.aspx

FCC / IC STATEMENT

This device complies with Part 15 of the FCC Rules, and Industry Canada’s license
-exempt RSSs. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) This device must accept any interference receiv
ed, including interference that may cause
undesired operation.


Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate Center Drive.,
Melville, NY 11747, Ph: 516
-
577
-
2000


REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED, FOR DETAILS ON LIMITATIONS OF THE
ENTIRE ALARM SYSTEM.

For the latest warranty information, please go to: www.resideo.com

For technical support, call 1
-800
-645
-7492, M
-F 8:30am to 5pm EST.

For documentation, go to:
www.resideo.com


This
equipment should be installed in accordance with National Electrical Code, NFPA 70, Standard for the Installation of Resident
ial Fire Warning Systems,
CAN/ULC-
S540 and Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269).
Printed information describing proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this equipment
.

Canadian Installations

For installation in Canada
, wiring shall be in accordance with CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installation
s; CAN/ULC
S302, Standard for the Installation, Inspection and Testing of Intrusion Alarm Systems; and CAN/ULC S301, Standard for S
ignal Receiving Centre Intrusion
Alarm Systems and Operations.


Warning
: Owner’s instruction notice: ’Not to be removed by anyone except occupant’


This system must be checked by a qualified technician at least once every
three (3) years.


The product should not be disposed of with other household waste. Check for the nearest authorized collection centers or auth
orized recyclers. The correct
disposal of end
-
of
-
life equipment will help prevent potential negative consequences for the environme
nt and human health.


Any attempt to reverse
-engineer this device by decoding proprietary protocols, de
-compiling firmware, or any similar actions is strictly prohibited.


Resideo Technologies, Inc

2 Corporate Center Drive

P.O. Box 9040, Melville, NY 11747

© 2024 Resideo Technologies, Inc. All rights reserved




ÊR800
-
28393AHŠ
R800
-
2839
3
A 1/24 Rev A


Uploaded