Honeywell 470-12 - Installation Manual

GENERAL
INFORMATION
The
No.
470
Water
Sensor
is
completely electronic
and
its
design
allows
water
to
be
detected
with low
voltage
and
low
current.
Electronic
module
is
designed
to
be
located
in
and
powered
by
a like
voltage alarm control
and
can
monitor
up
to
2
sensor probes.
The
probes
are
normally
placed
by
sump
pumps,
washing
machines,
kitchens,
computer
rooms,
etc. where
flooding
is
a possibility
and
early
warning
is
desirable
to
prevent
damage.
WIRE:
The
control
module
can be
located
up
to
20
feet
when
used
with
22AWG
twisted pair
wire
or
100
feet
using
20AWG
twisted
wire
from
the
detection
probe(s).
PROBE
INSTALLATION:
Mount probe
No.
470-PB
to water
pipe
in the sump pump pit or any location where detection
of
water
is
desired
using
the
two
mounting
holes provided.
A tie
strap
can
also
be used
for
ease
in
attaching
the
probe
to
pipes.
Adjust
the
probe
to
the
point
of
desired detection.
The
detector
will
activate
when
both
pins contact water.
TERMINAL
CONNECTION:
Connect
the
filtered
DC
power
to
terminals
5(+)
and
6(
-
).
Be
sure to observe polarity. Connect one terminal
of
the
probe
to
terminal
6
(
-
)
of
the module and the other terminal to termi
nal
4
of
the module. Terminals l(N.C.),
2(C),
and
terminal
3(N.O.)
will
provide dry
contact
only
(no
voltage
output).
After
installing
the
probe, coat both
its
screw
terminals
with
a
silicone
sealer.
SENSITIVITY
:
The
No.
470
is
provided
with
two
sensitivity
settings. After
installation,
check
the
sensor
by
placing
the
probe
in
the
water
to
be
detected.
If
the
unit
activates when
the
terminals
are
shorted
at
the
module
and
not
at
the
probe,
recheck your
wiring
and
connections.
If
the
wiring
is
correct,
then
you
must
increase
the
detectors
sensitivity.
Rem
ove the module
lid
by unscrewing the f
our small screws. Cut the
loop
wire protruding from the
PC
board
and then spread
apart.
The
high sensitivity
mode
will
alIow
detec
tion
of
moisture betwee
n two probe pins.
Repeat
the
above
testing
procedure.
TESTING:
The
No.
470
Water Sensor
should
be
periodically
tested to ensure proper
operation
(suggested monthly). After
200
hours
of
continuous activation (detection
of
water) the probe should be cleaned. Wipe or scrape
off
any
accumulated substances
to
expose
the
metal
pins.
THE SECOND
PROBE:
If
desired, you may connect
a
second detection
probe
to
the
module
to
protect
another
area.
The
second
probe
is
connected
to
the same
terminals
(6)
and
(4).
Note:
2
probes maximum per unit.
SPECIFICATIONS:
Physical
Module
size:
2 1/2"
inches (63.5 mm) deep by
3
inches
(76.2
mm) wide by
4
inches
(101.6
mm) long.
Probe
size: 1/2"
inch (12.7 mm) deep by 1/2"
inch
(12.7
mm) long by
2
inches
(50.8
mm) wide.
Electrical
470
-
6
470
-
12
Voltage
6VDC
12VDC
Probe Current (activated)
.3
mils 1
.O
mils respectively
Total
Current
Draw
on
alarm
52
mils
40
mils
respectively
Relay
rating
3
amps
5
amps
respectively
Standby
Current
0
0
TO
THE
INSTALLER
Regular
maintenance
by
the
installer
and
frequent
testing
by
the
user
is
vital
for
continuous
satisfactory
operation
of
any alarm system. The installer should assume the responsibility
of
developing and offering
a
regular
maintenance program
to
the
user
as
well
as
acquainting
the
user
with
a
proper
operation
and
limitation
of
the alarm system and its component parts. Recommendations must be included for
a
specific
program
of
frequent testing to ensure the systems proper operation at
all
times.
ALARM
DEVICE
MANUFACTURING
PROGRAM
Division
of
Pittway Corporation
165
Eileen
Way
Syosset,
NY
1
11791
of 2


Related Products

Honeywell 470-12 - Wired Flood Detection Module
Honeywell 470-12
Wired Flood Detection Module

Related Categories


Document Transcript

GENERAL INFORMATION
The No. 470 Water Sensor is completely electronic and its design allows water to be detected with low voltage
and low current. Electronic module is designed to be located in and powered by a like voltage alarm control and
can monitor up to 2 sensor probes. The probes are normally placed by sump pumps, washing machines,
kitchens, computer rooms, etc. where flooding is a possibility and early warning is desirable to prevent damage.
WIRE:
The control module can be located up to 20 feet when used with 22AWG twisted pair wire or 100
feet using 20AWG twisted wire from the detection probe(s).
PROBE INSTALLATION:
Mount probe No. 470-PB to water pipe in the sump pump pit or any location where detection of water
is desired using the two mounting holes provided. A tie strap can also be used for ease in attaching the
probe to pipes. Adjust the probe to the point of desired detection. The detector will activate when both
pins contact water.
TERMINAL CONNECTION:
Connect the filtered DC power to terminals 5(+) and 6(-). Be sure to observe polarity. Connect one terminal of the
probe to terminal 6 (-) of the module and the other terminal to terminal 4 of the module. Terminals l(N.C.), 2(C),
and terminal 3(N.O.) will provide dry contact only (no voltage output). After installing the probe, coat both its
screw terminals with a silicone sealer.
SENSITIVITY :
The No. 470 is provided with two sensitivity settings. After installation, check the sensor by placing the probe in
the water to be detected. If the unit activates when the terminals are shorted at the module and not at the probe,
recheck your wiring and connections. If the wiring is correct, then you must increase the detectors sensitivity.
Remove the module lid by unscrewing the four small screws. Cut the loop wire protruding from the PC board
and then spread apart. The high sensitivity mode will alIow detection of moisture between two probe pins.
Repeat the above testing procedure.
TESTING:
The No. 470 Water Sensor should be periodically tested to ensure proper operation (suggested monthly). After
200 hours of continuous activation (detection of water) the probe should be cleaned. Wipe or scrape off any
accumulated substances to expose the metal pins.
THE SECOND PROBE:
If desired, you may connect a second detection probe to the module to protect another area. The second probe is
connected to the same terminals (6) and (4). Note: 2 probes maximum per unit.
SPECIFICATIONS:
Physical
Module size: 2 1/2" inches (63.5 mm) deep by 3 inches (76.2 mm) wide by 4 inches (101.6 mm) long.
Probe size: 1/2" inch (12.7 mm) deep by 1/2" inch (12.7 mm) long by 2 inches (50.8 mm) wide.
Electrical 470-6 470- 12
Voltage 6VDC 12VDC
Probe Current (activated) .3 mils 1 .O mils respectively
Total Current Draw on alarm 52 mils 40 mils respectively
Relay rating 3 amps 5 amps respectively
Standby Current 0 0
TO THE INSTALLER
Regular maintenance by the installer and frequent testing by the user is vital for continuous satisfactory
operation of any alarm system. The installer should assume the responsibility of developing and offering a
regular maintenance program to the user as well as acquainting the user with a proper operation and
limitation of the alarm system and its component parts. Recommendations must be included for a specific
program of frequent testing to ensure the systems proper operation at all times.
ALARM DEVICE MANUFACTURING PROGRAM
Division of Pittway Corporation
165 Eileen Way Syosset, NY 1 11791
INSTALLATION:
The control module can be
detection probe(s) when
22AWG twisted pair wire is
used. The distance can be
increased to 100 feet when
20AWG twisted pair wire is
used.
The sensor shoutd be
mounted so that the probe
pins are at the point of
desired contact with water
using the two mounting
holes provided. A tie strap
can also be used for ease
in attaching the probe to a
pipe. It's that simple.
SENSITIVITY:
The No. 470 is provided with
two sensitivity settings for
greater fIexibility,
All units are set at the least
sensitive mode. An actual
bridge of water is required
to activate the detector at
this sensitivity setting. This
eliminates falsing due to
condensation.
If higher sensitivity is desired,
this can be accomplished by
removing the cover and clip-
ping the looped resistor on the
PC board. Once the looped
end is clipped, the detector
becomes highly sensitive and
will activate with moisture.
located up to 20 feet from the
SPECIFICATlONS
Physical
Module size: 2 1/2" (63.5mm) deep by 3" (76.2rnm) wide
by 4" (101.6mm) long
Probe size: 1/2" (12.7mrn) deep by 1 1/4" (31.75mrn) long
by 2" (50mrn) wide
Eletrical 470-6
Voltage 6VDC
Probe Current (activated) 6 mils
Total Current Draw
On Alarm 18 mils
Alarm Output: SPDT Relay
Contacts
Relay Rating 2 amps
Standby Current 0
HOW TO ORDER
No. 470-6 Water Sensor, 6VDC
(1 probe included)
No. 470-12 Water Sensor, 12VDC
(1 probe inchded)
NO. 470PB Probe for
No. 470 Water Sensor
I
A DIVISlON of PITWAY CORPORAflON
470-12
12VDC
12 mils
40 mils
SPDT Relay
Contacts
5 amps
0


Uploaded