Honeywell 5800 Wireless Smoke, Heat and CO Detector - Installation Instructions
Related Products
Related Categories
Document Transcript
FEATURES
•
Multi
-Criteria Sensing: uses four
sensing elements to react faster
while minimizing false alarms:
-
Photoelectric smoke sensor
detects airborne smoke particles
-
Carbon Monoxide (
CO) sensor
detects smoldering fires
-
Infrared (IR) sensor measures
ambient light and flame
signatures, such as flame flicker
-
Thermal detection monitors for
dangerous rise in temperature
•
Low Temperature sensing:
senses ambient temperature
and reports
if temperature goes
below 41°F (5°C).
•
CO Detector End-of
-Life
reporting (detector needs
replacing)
•
Smoke detector maintenance
reporting (detector needs
cleaning)
•
Low Battery Detection
Table 1: Operation Modes
MODE
Status LED
(Top)
LED Windows
(Side)
Sounder
Speaker
Power Up
Blink Green,
every 2 secs
Dark
Silent
Voice welcome,
instructions
after first
time power up or
after default
Normal
(Standby)
Single Blink
Green every
10 secs
Dark
Silent
Silent
Smoke
Alarm
Blink Red
every 10 secs
Blink red
Temp-
3
Voice smoke
warning
Thermal
Alarm
Blink Red
every 10 secs
Blink red
Temp-
3
Voice smoke
warning
CO Alarm
Blink Red
every 10 secs
Blink blue
Temp-
4
Voice CO
warning
Powered
Down
Dark
Dark
Silent
Silent
POWER UP and LANGUAGE SELECTION
•
Remove battery pull tabs
. Be sure batteries are seated
properly to avoid a low battery condition after 15 seconds
.
•
Upon
power up
,
Green LED Blinks every 2 secs / Sounder
is Silent.
After power up, the detector prompts for
language selection.
•
Select the desired language.
English:
Press the Smoke (•) test button
Spanish: Press the CO (••) test button
RESET
TING
THE LANGUAGE
1. Press and hold both the Smoke and CO test
switches simultaneously for 10 seconds, then
release. The green light flashes
rapi
dly.
2. Press and hold both buttons again for one
second and release. The sensor begins
speaking a Welcome message.
3. Select the desired language by pressing the
corresponding Smoke (English) or CO
(Spanish) test button
.
ENROLLMENT
IMPORTANT:
The Sm
oke and Carbon Monoxide (CO) sensors each have unique serial numbers and must be enrolled in separate zones.
Enroll the Smoke Sensor
1.
Remove the detector from the base plate (tamper switch must be faulted
when enrolling)
.
2.
Put the control panel in Zone Programming mode.
3.
Assign a zone number for the smoke detector zone.
Loop = 1; Zone Type = 09 (Fire) or 16 (Fire with Verification)
Input Type = 03 (Supervised RF)
When prompted for the serial number, press and release the Smoke Test
button for 1 second. The sensor sends two transmissions for enrollment.
Alternatively, you can manually enter the smoke sensor serial number
found on the unit’s label.
4.
If Maintenance monitoring is desired:
VISTA-15P/20P/21iP,
LYNX Touch,
& Lyric: A
ssign a separate zone number
using the Smoke Detector serial number.
Loop = 2 (maintenance); Zone Type = choose a zone type based on
desired operation (ex.24 hr
Trouble, Monitor, or Auxiliary
)
Input Type = 03
(Supervised RF)
VISTA-
128/250 Series: Enable “Smart Contact” option in zone
programming menu for the
assigned smoke detector zone.
5.
If Low Temperature reporting is desired, program a separate zone for this
smoke detector serial number
Loop = 3; Zone Type = choose a zone type based on desired
operation (ex.2
4 hr Trouble, Monitor, or Auxiliary
);
Input Type = 03
(Supervised RF).
WARNING
:The fire protection zone must always be enrolled as Loop 1.
Otherwise, fire alarms will not be reported by the control.
Enroll the CO Sensor
1. Remove the detector from the
base plate.
2.
With the control panel in Zone Programming mode, assign a zone
number for the CO detector zone.
Loop = 1; Zone Type =
14 (CO alarm)
;
Input Type = 3 (Supervised RF)
When prompted for the serial number, press and release the CO Test
button for 1 second. The sensor sends two transmissions for
enrollment. Alternatively, you can manually enter the CO sensor serial
number, which is the smoke serial number plus 1 (ex. if smoke s/n is
0000781, the CO s/n is 0000782)
.
3.
If End-
of-
Life monitoring i
s desired:
VISTA-
15P/20P/21iP
, LYNX Touch, & Lyric: automatically sent
VISTA-
128/250 Series: program a separate zone for the CO
serial
no.
Loop = 2; Zone Type = choose a zone type based on desired
operation (
ex.24 hr
Trouble or Auxiliary
); Input Type = 0
3 (
Supervised RF
)
5800COMBO
- Combination Smoke/Carbon Monoxide (CO) Detector w/Built
-in Wireless Transmitter
(features voice and 360 degree viewable LED ring)
INSTALLATION AND SETUP GUIDE
Thi
s device
is intended for use with Honeywell control panels that support 5800 series devices.
Before installing detectors, please
thoroughly read these installation instructions and read the
Limitations of Fire Alarm Systems
Insert (P/N 800-
15144 5/13)
and
System
Smoke Detectors Application Guide
(P/N SPAG9101 7/12).
MOUNTING
After enrolling
and before mounting permanently, conduct Go/No Go test (see controller’s
instructions) to verify adequate signal strength. Adjust the device location as necessary.
1. Using two supplied screws and anchors, mount the base.
2. Attach the smoke detector to the mounting base with a clockwise motion.
3. Test each detector as described in the Testing section.
4. Confirm all desired signals have been received by the Central Station.
NOTE:
NFPA 72 recommends the instal
lation of detectors only after completing
construction or any other dust producing activity.
TESTING
Test communications between the detector and the control panel.
The detector mode has two test buttons; one for smoke testing and
one for CO testing.
The detector may also be functionally tested using canned smoke
and canned CO. If the detector fails any of the test methods, the
detector should be replaced.
NOTE:
Testing the detector will activate the alarm and send a signal to
the panel.
Before testi
ng, notify the proper authorities to avoid any
false alarms.
Smoke Test
(Alarm Test)
Press
and hold
the Smoke Test button for 1 to 2 seconds. The
detector will sound and illuminate per Table 2 and send a smoke
alarm signal to the control panel
(all progr
ammed smoke detector
loops are signaled). Verify that the smoke alarm signal was
received at the control panel.
Smoke System Test (Functional Smoke Test)
Press and hold the Smoke Test button for 3 to 5 seconds
to enter
the functional smoke test mode.
See
Functional Smoke Test section.
NOTE
: Detector sounds an alarm when using canned smoke
only
when in
Functional
Test mode (canned smoke does not cause alarm
sounding when in normal mode).
Functional Smoke Test
With the detector in smoke system (functional) test mode, spray
canned smoke into the detector. The canned smoke that can be
used and is approved for test include: Home Safeguard Industries
25S, SD
i CHEK02 and CHEK06, SDi SOLOA4, and SDi
SMOKESABRE.
1.
The detector will sound and illuminate per Table 2 and a smoke
alarm signal will be sent to the panel.
2.
Verify the smoke alarm signal was received by the control panel.
CO Test (Alarm Test)
Press and hold the CO Test button for 1 to 2 seconds. The control
panel should display and sound a CO alarm
(all programmed CO
detector loops are sent)
.
CO System Test (Functional
CO
Test)
Press and hold the CO Test button for 3-5 seconds t
o enter the
functional gas t
est mode.
See Functional Gas Test section below.
Functional Gas Test
Solo C6 brand canned CO may be used to verify the detector’s
ability to sense CO by utilizing the RealTest® feature as follows:
1. Press and hold the CO test button for 3 to 5 seconds. The green
LED will start blinking once per second
indicating the detector is
in RealTest® mode. (If the detector will not go into RealTest®
mode, the CO sensor may be in fault or at end-of
-life.)
2. While the green LED is blinking once per second, spray a small
amount of canned CO directly into the CO gas entry port.
3. Upon successful gas entry and if functioning properly, the
detector will go into CO alarm and send an alarm to the control
panel.
4. The CO test will automatically clear when the CO clears
from the
sensor or in 30 seconds if no CO was introduced.
Table 2:
LED Indication & Sounder during Test and Trouble
MODE
Status LED
(Top)
Side LED
Windows
Sounder
Speaker
Smoke Test
Blink Red
once every
second
Dark
Temp
-3
Warning of alarm
sig
nal transmission.
Voice smoke
warning
Smoke System
(functional) Test
Blink Red
once every 10
secs
Blink once
every
10 secs
CO Test
Blink Red
once every
second
Dark
Temp
-3
Warning of alarm
signal transmission.
Voice smoke
warning
RealTest™
F
unctional CO gas entry
test –
Waiting for gas
entry
Blink Green
once per
second
Dark
Silent
Voice instructions for
testing; warning of
alarm signal
RealTest™
Functional CO gas entry
test -
Upon successful
gas entry
Blink Red
once every
10 secs
Blink
blue
every
10 secs
Modified
Temp
-4
Voice carbon
monoxide warning
Low Battery
Blink Amber
every
10 secs
Dark
Chirp every 45
secs after
7 days
Voice instructions
when chirp is
hushed by pressing
either test button
Smoke Maintenance
Blink Amber
every 5 secs
Dark
Silent
Voice smoke
maintenance
instructions if either
test button is pressed
CO Trouble
Double
Blink Amber
every 5 secs
Dark
Silent
CO End of Life –
First
29 days
Double
Blink Amber
every 3 secs
Dark
Silent
Voice end
-
of
-
life
instructions
whe
n either test
button
is pressed
CO End of Life –
after
30 days
Double
Blink Amber
every 3 secs
Dark
Chirp every
45 secs
Voice end
-
of
-
life
instructions
when
either test button
is pressed
Power Up
Blink Green, for
30 secs
Dark
Silent
Language set
instr
uctions only on
first time power
-
up
Normal (Standby)
Single Blink
Green every 10
secs
Dark
Silent
Silent
Freeze Warning (low
temp)
Blink Red
every
10 secs
HUSH FEATURE / ALARM SILENCE
If required, the audible alarm for smoke and CO conditions c
an be
silenced for 5 minutes by pushing the “Test/Hush” button. In addition, low
chirping can be silenced
for 12 hours when the Test/Hush button is
pressed.
During a Smoke alarm, if an alarm condition still exists after the 5 minute
hush period, the alarm
will sound. The hush feature will not operate at
levels above 4%/ft smoke concentration.
During a CO alarm, if carbon monoxide is still present after the 5 minute
hush period, the alarm will sound. The hush feature will not operate at
levels above 350 ppm (parts per million) carbon monoxide.
CO SENSOR END
-of-LIFE FEATURE
When the CO sensor has passed end-of
-
life, a trouble signal will be sent to
the control panel (if programmed). This indicates that the CO sensor inside
the detector must be replaced. If unresolved for 30 days, the detector will
chirp every 45 seconds. The typical life of the CO sensor is ten years from
the date of manufacture. It is recommended to periodically check the
“Replace by” date located on the label on the back of the detector hea
d.
TESTING SIGNAL STRENGTH
Perform this test in accordance with NFPA 72 inspection, testing and
maintenance requirements to determine a strong communication path with
the control panel.
1. Activate the wireless system’s GO/NO GO TEST mode.
2. Press the de
tector’s Smoke TEST button (•) for 1
-2 seconds. The
detector should immediately transmit an alarm signal to the control
panel. The built
-in horn will start to sound about 2.5 seconds after
pressing the button.
3. The wireless system’s keypad should emit at least three beeps when
the alarm transmission is received and display the transmitting
detector’s zone number.
4. When the console has received the test signal, the horn will stop and a
few seconds later the detector’s zone number will clear from the co
nsole
display.
5. If the console does not respond as noted, and if this is an initial
installation, try moving the detector to another location that provides
proper reception. Also be sure that the detector has been “enrolled” by
the control panel (see Enrollment section). Then, repeat the test.
6. Turn off the system’s TEST mode (typically security code + OFF).
REPLACING THE BATTERIES
CAUTION
:
The batteries used in this device may present a fire or
chemical burn hazard if mistreated. Do not recharge, disassemble, heat
above 100°C (212°F) or dispose of in fire. Use only Panasonic CR123A
Lithium batteries. Use of other batteries may present a risk of fire or
explosion. Keep used batteries away from children. Dispose of used
batteries properly.
Remov
e old batteries. Wait 10 seconds and then replace with four new
batteries
. To avoid a low battery indication w
hen installing new batteries,
all 4 batteries must be installed within 15 seconds
of installing the first one
.
Any low battery condition that may
have occurred should clear when the
base
plate
is installed.
CLEANING
NOTE
:
Notify the proper authorities when the system
will be temporarily out of service.
IMPORTANT:
This detector must be tested and
maintained regularly following NFPA
-72 requirements.
The detector should be cleaned at least once a year.
1.
Remove the detector
from the base
plate
by turning
counterclockwise.
2.
Clean the outside casing with a cloth. Ensure that
the holes on the front of the alarm are not blocked
with dirt and dust. Canned air can be used to
remove any dust or debris.
3.
Reattach the detector to the b
ase
plate
by
rotating
clockwise.
4.
Test the detector to insure it is fully functional. (See
Testing section).
5.
Notify the proper authorities and Central Station
when the system is back in service.
MAINTENANCE
Do not paint, and do not use cleaning agents, bl
each
or polish the detector.
NOTE:
Before performing any maintenance on the detector,
notify the proper authorities and Central Station that
maintenance is being performed and the system will be
temporarily out of service. Disable the zone or system
undergoing maintenance to prevent any unwanted alarms.
Power must be removed from the detector before performing
maintenance of any kind.
The 5800COMBO detector reports maintenance issues
to the control panel and communicates them visually
and audibly per Table
2.
Trouble feature:
When the sensor (supervision) is in a
trouble condition (such as a detector that is dirty or CO
sensor non-functioning), the detector will send a trouble
signal to the control panel. Depending on the issue, the
detector must then be serviced or replaced.
NOTE:
Smoke detectors are not to be used with detector
guards unless the combination is evaluated and found
suitable for that purpose.
LED INDICATORS
The 5800COMBO has a multi
-color top LED:
Green = Supervisory indication; blinks dur
ing power on,
reset, and during normal operation
Amber = Signal maintenance and trouble events
Red =
Alarm condition (either Smoke or CO)
Side LED windows indicate alarms:
red = smoke
blue = CO
Table 3: Carbon Monoxide Detector: Events and Their ID Codes
Event
Alpha Keypad
CS Report
CO alarms
CO Alarm
CO alarm (CID 162)
CO test
CO Alarm
CO alarm (CID 162)
Low battery
Lo Bat
RF low
-
battery (CID 384)
detector
CO Trouble
RF sensor supervision
(CID 381)
detector end-
of-
life/trouble
CO Trouble
sensor trouble -
end-
of life
(CID 380)
tamper
disarmed = CO Trouble
armed = CO Alarm
RF sensor tamper
(CID 383)
LIM
ITED
LIFE
OF
CO
SENSOR
This detector is manufactured with a long-life electrochemical carbon
monoxide sensor. Over time the sensor will lose sensitivity and will
need to be replaced. The life span of the CO sensor is approximately
ten years from the date of manufacture.
Periodically check the detector’s replacement date. Remove the
detector head and refer to the ‘replace by’ sticker placed on the
underneath side of the detector. The sticker will indicate the date the
detector should be replaced.
Reminder:
This detector is also equipped with a feature that will
signal the panel once the CO sensor has passed the end of its’ useful
life. If this occurs,
it is time to replace the detector.
What to do if the detector goes into CO alarm:
If the detector goes into CO alarm (4 beeps), immediately move to a
spot where fresh air is available, preferably outdoors, where the air is
safe and call your security service provider. Tell your provider the
detector alarm status, and that you require professional assistance in
ridding your home of the carbon monoxide.
This detector is NOT:
•
A substitute for the proper servicing of fuel
-burning appliances or
the sweeping of chimneys.
•
To be used on an intermittent basis or as a portable alarm for the
spillage of combustion produc
ts from fuel
-burning appliances or
chimneys.
Carbon monoxide gas is a highly poisonous gas which is released
when fuels are burnt. It is invisible, has no smell and is therefore is
impossible to detect with the human senses. Under normal conditions
in a room where fuel burning appliances are well maintained and
correctly ventilated, the amount of carbon monoxide released into the
room by appliances should not be dangerous.
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or m
odifications to the equipment unless
authorized by the Installation Instructions or User's Manual. Unauthorized changes or
modifications could void the user's authority to operate the equipment.
FCC STATEMENT
This device complies with Part 15 of the FCC Ru
les,. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
This device must accept any interference received, including interference that may
cause undesired operation.
SUPPORT & WARRANTY
Fo
r the latest documentation and online support information, please go to:
https://mywebtech.honeywell.com/
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
.
For patent information, see
www.honeywell.com/patents
MyWebTech
Warranty
Patents
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL
WITH WHICH THIS DEVICE IS USED FOR
DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
Agile ref. #800
-22142 1/17
Rev E
I
56
-6250-
00
5 1/1
7
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2016 Honeywell International Inc.
www.honeywell.com/security
S
YMPTOMS OF CARBON MONOXIDE POISONING
Carbon monoxide bonds to the hemoglobin in the blood and
reduces the amount of oxygen being circulated in the body.
The following symptoms are examples taken from NFPA 720;
they represent approximate values for healthy adults.
Concentration
(ppm CO)
Symptoms
200
Mild He
adache after 2
-3 hours of exposure
400
Headache and nausea after 1
-2 hours of exposure
800
Headache, nausea, and dizziness after 45 minutes of expo-
sure; collapse and unconsciousness after 2 hours of exposure
Many cases of reported carbon monoxide pois
oning indicate that
while victims are aware that they do not feel well, they become
so disoriented that they are unable to save themselves by either
exiting the building or calling for assistance. Also young children,
elderly and pets may be the first to be affected.
CO A
LARM ACTIVATION
Per UL standard 2075, the 5800COMBO
detector has been
tested to the sensitivity limits defined in UL standard 2034.
CO Alarm Thresholds
Parts per Million
Detector Response Time (Min.)
30+
-
3ppm
No alarm within 30 days
70+
-
5ppm
60
-
240
150+
-
5ppm
10
-
50
400+
-
10ppm
4
-
15
SPECIFICATIONS
Electrical Specifications
Voltage: 3 volts DC
Battery Type: CR123A
lithium
Battery Manufacturer: Panasonic CR123A
only
Number of Batteries:
4
Sensitivity
: UL
limits .9 to 3
.50
%/
ft / ULC limits .9 to 3
.08
%/ft
Thermal
alarm
: 135°
F (57°
C)
Freeze trouble:
41°
F typical (5
° C)
Audible Signal:
85dBA
Physical Specifications
Diameter:
1
6.002
cm x 4.19 cm Thick / 6
.3 in. Diameter x
1.65 in. Thick
Weight:
: 14.
3 oz; 406
g
Oper
ating Temperature Range: 32°
– 1 00° F / 0° –
38° C
Storage Temperature Range: -10
- 70° C (14 -
158° F)
Operating Humidity Range: 20
-
95% RH
Approval Listings:
FCC
Listed to UL 268 & UL 2075.
Listed to CSA 6.19.
Other Standards: RoHS
- Uploaded