Honeywell 5800SS1 Installation Manual

K0011 10/01
5800SS1
Wireless Shock Sensor
INSTALLATION GUIDE
GENERAL INFORMATION
The 5800SS1 is a wireless shock sensor
intended for use in systems that support 5800
series devices. Each transmitter has its own
unique serial number, assigned during
manufacture, which must be “enrolled” in the
control panel before the device can be used
with the system. Refer to the control panel's
Installation and Setup Guide for programming
details.
One 5800SS1 is required for each pane of glass
protected. (Do not use more than one sensor
per pane.)
Types of Glass Protection
Tempered
Ordinary Plate
Laminated Type
Wired
Coated
Sealed Insulated
Note:
It is not necessary to remove the case
cover during installation.
ENROLLING THE 5800SS1
You must enroll the 5800SS1
serial number in
the control panel during zone programming.
The control panel's Installation and Setup
Guide
provides
detailed
programming
procedures. Before programming, perform the
following:
1.
To cause the transmitter to transmit,
remove the “PULL TO CONNECT
BATTERY” tab
(see Figure 1)
.
(For
additional transmissions, lightly tap on
the base of the sensor with a
screwdriver.)
5800SS1-001-V0
PULL
TAB
SENSOR
Figure 1
2.
When programming the shock sensor,
note the following:
Input Type = 3 (Supervised RF)
Loop Number = 1
3.
When prompted for the serial number,
you can transmit by lightly tapping on the
base of the sensor with a screwdriver or
by manually entering the serial and loop
number.
MOUNTING
1.
Determine
the
optimum
mounting
location. For best sensitivity, the sensor
should be mounted one-inch from the
corner edge of the window frame (see
Figure 2).
1in.
1in.
10 FT. RADIUS
MAXIMUM
COVERAGE
STRIKE AT
FURTHEST
OPPOSITE
CORNER WITH
SCREWDRIVER
HANDLE
MOUNT 1 INCH FROM CORNER
OF WINDOW FRAME.
5800SS1-003-V0
Figure 2
2.
Before the transmitter is permanently
mounted, conduct Go/No Go tests (see
control’s instructions) to verify adequate
signal strength from the mounting
location.
3.
Always verify range by holding the sensor
in the approximate mounting location and
tapping at the base. The panel (in test
mode)
should
respond
to
the
transmissions. If not, find a more suitable
mounting location.
4.
Clean the glass, where the sensor will be
mounted, with a mixture of water and
isopropyl alcohol.
5.
Once the glass has dried, remove the tape
backing paper and firmly press the sensor
in the desired mounting location.
6.
Verify operation by striking the furthest
opposite corner of the glass with the
handle of a large screwdriver. Always
check the alarm panel keypad to verify
that the zone has tripped.
7.
Apply optional “WARNING” label to the
outside glass surface opposite the tape side
of the 5800SS1.
REPLACING THE BATTERY
1.
Using a screwdriver, carefully remove the
sensor’s cover.
2.
Check the battery polarity orientation
before installing
(see Figure 3).
3.
Insert the battery securely in the sensor.
4.
Snap the sensor cover back in place.
5800SS1-001-V0
Figure 3
SPECIFICATIONS
Glass Coverage:
Plate, Laminate, Wired, Sealed Insulated,
Coated and Tempered, up to
¼
” (6.35 mm) and
10 ft (3.048 m) distance from mounting
location. One sensor is required for each
separate pane of glass.
Dimensions:
1.6" H x 1.6" W x 0.8" D (40.64 mm x 40.64
mm x 20.32 mm)
Power:
Single
3V
Panasonic
CR2, Sanyo CR2, or
Duracell DLCR2 Lithium Battery
WARNING
Risk of fire, explosion, and burns. Do not
recharge, disassemble, heat above 212º F (100º
C) or incinerate. Dispose of used batteries
properly. Keep away from children.
FCC NOTICE
FCC ID:CFS8DL5800SS1
This device complies with Part 15 of the
FCC Rules. Operation is subject to the
following two conditions:
(1) This device may not cause harmful
interference.
(2) This device must accept any
interference
received,
including
interference
that
may
cause
undesired operation.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing
by the user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular
maintenance program to the user as well as acquainting the user with the proper operation
and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to ensure the system’s
proper operation at all times.
FOR WARRANTY INFORMATION AND DETAILS REGARDING THE LIMITATIONS OF
THE ENTIRE ALARM SYSTEM REFER TO THE INSTALLATION INSTRUCTIONS FOR
THE RECEIVER/CONTROL USED WITH THIS DEVICE.
165 Eileen Way, Syosset, NY 11791
Copyright
©
2001
i.Il
K0011 10/01
of 2


Related Products

Honeywell 5800SS1 - Exterior of Wireless Shock Sensor
Honeywell 5800SS1
Wireless Shock Sensor
List Price: $108.00
Our Price: $77.99

Related Categories


Document Transcript

K0011 10/01

5800SS1 Wireless Shock Sensor INSTALLATION GUIDE
GENERAL INFORMATION The 5800SS1 is a wireless shock sensor intended for use in systems that support 5800 series devices. Each transmitter has its own unique serial number, assigned during manufacture, which must be “enrolled” in the control panel before the device can be used with the system. Refer to the control panel's Installation and Setup Guide for programming details. One 5800SS1 is required for each pane of glass protected. (Do not use more than one sensor per pane.) Types of Glass Protection • Tempered • Ordinary Plate • Laminated Type • Wired • Coated • Sealed Insulated
Note: It is not necessary to remove the case cover during installation.

2.

When programming the shock sensor, note the following: • Input Type = 3 (Supervised RF) • Loop Number = 1 When prompted for the serial number, you can transmit by lightly tapping on the base of the sensor with a screwdriver or by manually entering the serial and loop number.

3.

MOUNTING 1. Determine the optimum mounting location. For best sensitivity, the sensor should be mounted one-inch from the corner edge of the window frame (see Figure 2).
STRIKE AT FURTHEST OPPOSITE CORNER WITH SCREWDRIVER HANDLE

10 FT. RADIUS MAXIMUM COVERAGE

1in.
5800SS1-003-V0

ENROLLING THE 5800SS1 You must enroll the 5800SS1 serial number in the control panel during zone programming. The control panel's Installation and Setup Guide provides detailed programming procedures. Before programming, perform the following: 1. To cause the transmitter to transmit, remove the “PULL TO CONNECT BATTERY” tab (see Figure 1). (For additional transmissions, lightly tap on the base of the sensor with a screwdriver.)

1in. MOUNT 1 INCH FROM CORNER OF WINDOW FRAME.

Figure 2 2. Before the transmitter is permanently mounted, conduct Go/No Go tests (see control’s instructions) to verify adequate signal strength from the mounting location. Always verify range by holding the sensor in the approximate mounting location and tapping at the base. The panel (in test mode) should respond to the transmissions. If not, find a more suitable mounting location. Clean the glass, where the sensor will be mounted, with a mixture of water and isopropyl alcohol. Once the glass has dried, remove the tape backing paper and firmly press the sensor in the desired mounting location. Verify operation by striking the furthest opposite corner of the glass with the handle of a large screwdriver. Always check the alarm panel keypad to verify that the zone has tripped.

3.

SENSOR

TAB

4.

5.

PULL
5800SS1-001-V0

6. Figure 1

7.

Apply optional “WARNING” label to the outside glass surface opposite the tape side of the 5800SS1.

SPECIFICATIONS
Glass Coverage: Plate, Laminate, Wired, Sealed Insulated, Coated and Tempered, up to ¼” (6.35 mm) and 10 ft (3.048 m) distance from mounting location. One sensor is required for each separate pane of glass. Dimensions: 1.6" H x 1.6" W x 0.8" D (40.64 mm x 40.64 mm x 20.32 mm) Power: Single 3V Panasonic CR2, Sanyo CR2, or

REPLACING THE BATTERY 1. Using a screwdriver, carefully remove the sensor’s cover. 2. 3. 4. Check the battery polarity orientation before installing (see Figure 3). Insert the battery securely in the sensor. Snap the sensor cover back in place.

Duracell DLCR2 Lithium Battery
WARNING Risk of fire, explosion, and burns. Do not recharge, disassemble, heat above 212º F (100º C) or incinerate. Dispose of used batteries properly. Keep away from children. FCC NOTICE FCC ID:CFS8DL5800SS1 This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.

5800SS1-001-V0

Figure 3

TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system. The installer should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts. Recommendations must be included for a specific program of frequent testing (at least weekly) to ensure the system’s proper operation at all times. FOR WARRANTY INFORMATION AND DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM REFER TO THE INSTALLATION INSTRUCTIONS FOR THE RECEIVER/CONTROL USED WITH THIS DEVICE.

165 Eileen Way, Syosset, NY 11791
Copyright © 2001

i.Il
K0011 10/01


Uploaded