Honeywell FG1625RFM Installation Manual



Related Products

Honeywell FG1625RFM - Round Flush Mount Glass Break Detector
Honeywell FG1625RFM
Round Flush Mount Glass Break Detector
List Price: $104.00
Our Price: $73.99

Related Categories


Document Transcript

IntelliSense® FG-1625RFM Glassbreak Detector Installation Instructions
Refer to Supplemental Information (page 2) for complete descriptions of these installation steps
FG-1625RFM Glassbreak Detector Set Sensitivity & LED Configuration

SENS1 & SENS2 configure sensitivity

FG-1625RFM with Small Front Cover

FG-1625RFM with Large Front Cover

SENSITIVITY MAX MEDIUM LOW LOWEST

APPROXIMATE RANGE 7.6m (25 ft) 4.6m (15 ft) 3m (10 ft) 1.5m (5 ft)

SENS1 OFF ON OFF ON

SENS2 OFF OFF ON ON

Wiring and Installing the Detector • Select either the small or large front cover and attach it to the detector: insert the front cover installation posts into the mounting holes and snap the front cover into place. Note: Both the small and large covers provide the same excellent detection. Select the front cover size to best fit the application.

NOTE: Ranges are approximate and vary with each room’s acoustic properties. Always verify range with an IntelliSense FG-701 Glassbreak Simulator. The LATCH and LED DIP switches configure LED indicator behavior.
SWITCH LATCH LED OFF Red LED lights for 5 seconds during alarm LEDs disabled (except for power up and test mode3 ) ON Red LED latches ON when 1, 2 detector goes into alarm LEDs always enabled

Test Detector Installation
Enter Test Mode using an FG-701 Glassbreak Simulator (see Testing the Detector on the next page) or manually by shorting Test Mode pads. Note: Testing with the FG-701 is highly recommended. To use the test mode pads, first remove the front cover of the detector. Carefully slide the tip of a flat blade screwdriver under the edge of the front cover and gently pry upward. Next, remove the detector from the wall sleeve. Insert a 3mm screwdriver into the detector latch (see Components illustration in first column). Gently press outward, and then pull the detector toward you with the screwdriver.

FG-1625RFM Components
1 2

The timing of the alarm relay is not affected by the latched Alarm LED. Reset the Alarm LED by removing/restoring power, or by toggling the detector in and out of Test Mode. 3 LEDs can be enabled/disabled using FG-701.

Connect Detector
Connect detector using 18 to 22 AWG wire, with ends stripped approximately 5mm (3/16 in.) Use the appropriate wiring method as shown in these diagrams:

FG-1625RFM Glassbreak Detector, Terminal Block and Sensitivity / LED Switch

Select Mounting Location
IMPORTANT: Before drilling the mounting hole, make sure you do NOT exceed the maximum distance (25’/7.6 m) from the glass.

Normally Closed Loop/No EOL Resistor Removing detector from the Wall Sleeve

Normally Closed Loop/With EOL Resistor Note: Be sure to pass the wire through the wall sleeve before wiring the detector.

Install Detector
• • Test location and set Sensitivity as needed. Drill a mounting hole 1” diameter by 2.75” deep (minimum) in the wall or ceiling. (The hole diameter may need to be increased for best installation in some solid materials.) Run the wire through the wall or ceiling and slide the wire through the hole at the bottom of the wall sleeve. Insert the wall sleeve into the wall or ceiling. Position the “TOP” marking to ensure the front cover center design has either a horizontal or vertical alignment when attached. (See following illustration.) Wire the detector. Align the “TOP” markings on the detector and wall sleeve, and insert the detector into the wall sleeve.

Shorting the Test Mode Pads (if the FG-701 is unavailable) Short the test mode pads with the screwdriver, and check to make sure the detector is in test mode. Once in test mode, replace the detector in the wall sleeve, and replace front cover before testing the detector.

• •

5-051-789-40C

Page 1

IntelliSense® FG-1625RFM Glassbreak Detector Supplemental Information
Refer to Installation Instructions and diagrams (page 1) when installing this product
1. General Information
The FG-1625RFM flush mount glassbreak detector senses the sound of breaking plate, tempered, laminated, wired, coated and sealed insulating glass.

9. Installing the Detector Cover
Select the appropriate cover from the two sizes provided. Align the two cover mounting posts with the two marked holes in the detector and snap the cover into place. See Components illustration on page 1. Note: The cover must be in place for correct operation.

12. Remote LED Enable/Disable Mode
The detector’s Remote LED Enable/Disable Mode allows you to enable or disable the detector’s LEDs with the FG-701 Glassbreak Simulator. To enable or disable the LEDs with the FG-701: 1. LED switch, S4 position 4, must be off. 2. Enter Test Mode, and then exit Test Mode. 3. Within two (2) seconds, enter Test Mode again; this changes LED enable/disable status. 4. Exit Test Mode again. 5. Clap your hands to test the LEDs. If enabled, the green LED will flicker. If disabled, the green LED will remain off.

2. Choosing Mounting Location
The preferred mounting location for the device is on a wall or ceiling, opposite the protected glass. For the best detector performance, select a mounting location that is: • within 7.6 m (25 feet) of the protected glass; • within clear view of the protected glass; • at least 2 m (6.5 feet) from the floor; • at least 1 m (3.3 feet) from forced air ducts; • at least 1 m (3.3 feet) from sirens or bells greater than 5 cm (2 inches) in diameter. • between the protected glass and any heavy window coverings that may be present. Alternatively, when heavy window coverings are present, the detector can be mounted on the frame of the window. Avoid mounting the detector on the same wall as the protected glass, on free-standing posts or pillars, or in rooms with noisy equipment (air compressors, bells, power tools, etc.), if this equipment is operated when the detector is armed.

10. Testing the Detector
The detector should be tested at least once each year. Test the detector with the FG-701 Glassbreak Simulator. Note: The FG-701 uses calibrated signal output for true range verification, and provides reliable, convenient remote test-mode activation. Testing each installation with the FG-701 is highly recommended Other simulators will not give accurate indication of range. Always test detector with cover in place. To enter the Test Mode with the FG-701: 1. Stand within 4.6 m (15 feet) of the detector. 2. Switch the FG-701 to ACTIVATE and MANual modes. 3. Point the front of the glassbreak simulator towards the detector. Press the red START button to send a short activation code. To enter Test Mode manually: 1. Remove the front cover. 2. Use a screwdriver to remove the detector from the wall sleeve (see illustration on page 1). 3. Short the Test Mode pads on the PC board (located next to the DIP switch). 4. Replace the detector in the wall sleeve, and then replace the front cover. The detector’s green LED blinks approximately once per second to indicate that it has entered Test Mode. When the detector enters Test Mode, the green LED on the detector flashes about once per second. If the green LED does not flash, move closer to the detector and repeat the procedure. Testing the Detector (flex and audio signals): To test the detector using the FG-701: 1. Place the detector in Test Mode. 2. Set the FG-701 switches to the TEST and FLEX positions. 3. Position the FG-701 near the farthest point of the protected glass, and point it directly at the detector. If window coverings are present, close them fully and hold the FG-701 between the coverings and the protected glass. 4. Press the red START button. The simulator clicks on and starts an 8-second armed period. 5. Generate a flex signal by carefully striking the glass with a cushioned tool. The FG-701 responds with a burst of glassbreak audio. If the detector receives both the flex and audio signals properly, its red Alarm LED lights for five (5) seconds. (Red Alarm LED does not latch in Test Mode). Testing the Detector (audio signals only): The FG-701 can also be used to test the detector’s ability to receive audio signals only. See the FG-701 Operating Instructions for additional information. When it receives the audio signal, the detector flickers its green Event LED. Exiting Test Mode: When you have finished testing, exit Test Mode by following the same procedure used to enter Test Mode. The FG-1625RFM automatically exits Test Mode after five minutes if no events are detected.

13. Specifications
Range: 7.6 m (25 ft.) maximum, omnidirectional No minimum range Operating Temperature: -10° to 55° C (14° to 131° F) Storage: -20° to 60° C (-4° to 140° F) Alarm Duration: 5 seconds (unaffected by alarm LED latching) Alarm Relay: Form A 90 mA maximum 16 VDC maximum Rated for direct panel connection only Power Requirements: 8 - 16 VDC; 5.5 mA typical at 12 VDC, 12 mA max at 12 VDC, LED Latched AC Ripple: 4 Volts peak-topeak at Nominal 12 VDC RFI Immunity: 30 V/m, 10 MHz - 1000 MHz ESD Immunity: 10 kV discharges of either polarity to exposed surfaces Dimensions:
Small Front Cover: 45.0mm (1.8 in.) Diameter Large Front Cover: 63.5mm (2.5 in.) Diameter Wall Sleeve: For installation in 1” (25mm) hole. Maximum depth, without wire 66mm (2.6 in.)

3. Configuring Sensitivity (Range)
DIP switches SENS1 and SENS2 set detector sensitivity (range), as shown:
SENSITIVITY MAX MEDIUM LOW LOWEST RANGE * 7.6m (25 ft) 4.6m (15 ft) 3m (10 ft) 1.5M (5 ft) SENS1 OFF ON OFF ON SENS2 OFF OFF ON ON

* Sensitivity must be set to match the distance between the detector and the protected glass, as verified using the FG-701 Glassbreak Simulator. 4. Configuring LED Switch
The LATCH and LED DIP switches determine LED indicator operation.
SWITCH LATCH LED
1 2

Weight: 24.0 g (0.85 oz.) with small front cover 25.5 g (0.90 oz.) with large front cover Packaged: 54.0 g (1.90 oz.) Approvals / Listings: FCC/IC Verified CE C-Tick UL listed ULC listed EN 50131-1 Security Grade 1, Environmental Class II For Connection to an EN 60950 Class II Limited Power Source

OFF Red LED lights for 5 seconds during alarm LEDs disabled (except for 3 power up and test mode )

ON Red LED latches ON when detector goes into alarm 1, 2 LEDs always enabled

14. Nominal Glass Thickness Chart
Glass Type* Plate Tempered Laminated Wired Coated 2 Sealed Insulating1 Nominal Thickness Minimum Maximum
2mm (3/32 in.) 3mm (1/8 in.) 3mm (1/8 in.) 6mm (1/4 in.) 3mm (1/8 in.) 3mm (1/8 in.) [13mm (1/2 in.) overall] 10mm (3/8 in.) 10mm (3/8 in.) 14mm (9/16 in.) 6mm (1/4 in.) 6mm (1/4 in.) 6mm (1/4 in.) [19mm (3/4 in.) overall]

Alarm relay timing is not affected by the latched Alarm LED. Reset the Alarm LED by removing/restoring power, or by toggling the detector in and out of Test Mode. 3 LEDs can be enabled/disabled using FG-701.

5. Preparing Mounting Location
CAUTION: Make sure the mounting location DOES NOT exceed the maximum distance (25’/7.6m) from the glass. The FG-1625RFM is designed for flush mounting in a 1” diameter hole. Once you have selected the appropriate mounting location, drill a 1” diameter hole. NOTE: In hardwood or other solid material the hole diameter must be increased for best installation. The hole must be a minimum of 2.75” deep.

* Minimum size for all types is 28cm (11 in.) square; glass must be
framed in the wall or mounted in a barrier at least 0.9m (36 in.) wide. Protected only if both plates in the unit are broken 2 Coated glass with security films up to 0.35mm (14 mils) thick (including films for solar protection) may be used. Evaluated with these ® ® products: 3M SCOTCHSHIELD SH14CLARL – 0.35mm (14 mils), 4 ® ply film; Film Technologies International, Inc.'s GLASS-GARD GGLL 1200 – 0.3mm (12 mils), 3 ply film.
1

6. Installing the Wall Sleeve
After selecting the location and drilling the mounting hole, pull the hook-up wires through the slot in the bottom of the wall sleeve. Caution: Make sure to orient the wall sleeve so the indentation on the detector’s front cover is either horizontal or vertical when installed. (See Wiring and Installing the Detector illustration on page 1.) Insert the wall sleeve into the installation hole until firmly seated.

Canada: Wiring methods shall be in accordance with CSA C22.1 Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations.
NOTICES FCC Notice: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. The installer can also consult an experienced radio/television technician for additional suggestions, if necessary. IC Notice: This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
To obtain applicable EU compliance Declaration of Conformities for this product, please refer to our Website, http://www.security.honeywell.com/hsce/international/index.html. For any additional information regarding the compliance of this product to any EU specific requirements, please contact: Quality Assurance Department, Honeywell Security & Custom Electronics, Newhouse Industrial Estate Motherwell, Lanarkshire ML1 5SB, Scotland, United Kingdom. Tel:+44(0)1698738200 Email: UK64Sales@Honeywell.com

11. LED Indicators
The detector is equipped with two LEDs: a green Event LED and a red Alarm LED. When the LEDs are enabled, they light in a variety of patterns to indicate the detector's status. The following table summarizes the LED messages.
CONDITION
Normal Normal, event detected Normal, break detected Normal, alarm latched Power up Low Voltage Test Mode Test Mode, event detected Test Mode, alarm

7. Wiring the Detector
Refer to the wiring diagrams (page 1) to select the appropriate wiring configuration. NOTE: US and Canada- This sensor must be connected to a UL/ULC**/or CUL** Listed power supply or control panel supplying a minimum of four hours of standby time. **Listing per Canadian standards S318 or S304. Resetting the FG-1625RFM is accomplished by momentarily disconnecting the V+ line. (Disconnection of only the V- line will not reset the unit).

GREEN LED
OFF Flicker OFF OFF ON 1 second Flash ON/OFF Flash once per sec Flicker Flash once per sec

RED LED
OFF OFF ON 5 seconds ON ON 1 second Flash ON/OFF OFF OFF ON 5 seconds

8. Installing the Detector
Align the “TOP” marking on the detector with the “TOP” marking on the wall sleeve. Insert the detector into the wall sleeve until the latch engages.

Page 2

©2004 Honeywell International Inc. All rights reserved.
Honeywell, IntelliSense and FlexGuard are registered trademarks of Honeywell International Inc. - All other brands mentioned are the trademarks or registered trademarks of their respective owners. Specifications subject to change without prior notice.

Ê5-051-789-40CŠ
5-051-789-40C 7/07


Uploaded