Honeywell Home PROSIXCOMBO Installation Instructions - Dated 7/19 Rev. B
Related Products
Document Transcript
PROSiXCOMBO
Combination Smoke/Carbon Monoxide (CO) Detector
w/Built
-in Wireless Transmitter
(features voice and 360
degree viewable LED rin
g)
Installation an
d Setup
Guide
T
his device is intended for use with Honeywell
Home
control panels
that support
PR
O
S
iX series
devices.
Before installing detectors, please thoroughly read these installation instructions and read
the
Limitations of Fire Alarm Systems
Insert (P/N 800
-15144
5/13)
and
System Smoke Detectors
Application Guide
(P/N SPAG9101 7/12)
– www.
resid
eo.com
.
FEATURES
•
Multi
-Criteria Sensing:
uses four sensing elements to react faster
while minimizing false alarms:
-
Photoelectric smoke sensor detects airborne smoke
particles
-
Carbon Monoxide (CO) sensor detects smoldering fires
-
Infrared (
IR) sensor measures ambient light
and flame signatures,
such as flame flicker
-
Heat
detection monitors for dangerous rise in temperature
•
One Go / All Go: all smoke detec
tors in the system
programmed
as one-go-
all -go will sound on alarm.
•
CO Detector End
-of
-Life reporting (detector needs replacing)
•
Smoke detector maintenance reporting (detector needs cleaning)
•
Low Battery Detection
Table 1: Operation Modes
MODE
Status LED
(Top)
LED
Windows
(Side)
Sounder
Speaker
Power Up
Blink Green,
every 2
secs
Dark
Silent
Vo
ice welcome,
instructions after first
time power up or
after default
Normal
(Standby)
Single Blink
Green every
10 secs
Dark
Silent
Silent
Smoke
Alarm
Blink Red
every 10
secs
Blink red
Temp
-3
Voice smoke
warning
Heat
Alarm
Blink Red
every 10 secs
Blink
red
Temp
-3
Voice smoke
warning
CO Alarm
Blink Red
every 10 secs
Blink blue
Temp
-4
Voice CO
warning
Powered
Down
Dark
Dark
Silent
Silent
ENROLLMEN
T
The
PROSiXCO
MBO
has a
unique MAC ID number
. The heat, smoke
, and CO are assi
gned to loops 1
-
3 re
spectively
and
are enrolled in separate
zones.
NOTE:
Once enrolled, the device cannot be used with another system until it is removed from the current con
troller. See the
24-hour Enrollment
Deletion section below or the
controller’s ins
tructions.
Enroll th
e Device Services (Smoke, Heat, CO)
1. Remove the detector from the base plate
.
2. Put the control panel in Programming mode.
3. Pull the battery tab to activate enrollment
process (be sure batteries are seated
properly to avoid a false l
ow battery conditi
on). If the battery tab has already been
removed and the unit is
powered up, press either Test switch for less than 3
seconds to activate the enrollment process.
4. The device attempts enrollment (green LED flashes about 8 seconds). If successful, the green LED lights steady for 3 seconds and the device
announces succe
ssful enrollment.
If the LED does not light steady, enrollment failed. Retry by pressing either Test switc
h for less than 3 seconds.
All services (Smoke, Heat, and CO) are
automatically enr
olled in sequential (or next available) zone numbers with the fol
lowing default attributes:
NOTE
: Maintenance and CO End-
of-Life are automatically enrolled for
the respective smoke and CO zones. Contact ID code E386 “Low Maintenance Smoke” is sent for the
CO zone at End-
of-Life and Contact ID code
E385 “High Maintenanc
e Smoke” is sent for the Smoke Zone when dirty.
Supervision
: Detector supervision is factory set for 1 minute and is not programmable.
Zone
Device Type
Zone Response Type
Smoke Det.
Smoke Detector
Fire No Ver
ificat
ion
Heat Det.
Heat Sensor
Fire No Verification
CO Det.
Carbon Mono. Det.
C
arbon Mo
noxide
24-Hour Enrollment Deletion
Use th
is procedure within 24 hours of initial enrollment to delete this device from the controller. This al
lows reenrollment in a specific controller in case
enrollment in that controller failed.
This resets the device to factory default settings and removes the
communication li
nk data in the controller in which
it is enrolled
.
1.
Press and hold
both the Smoke and
CO test switches simultaneously
until the welcome message announces, then release.
2.
Wait for the green LED to flash rapidly.
3.
Press and hold both
switches
again for one second and release.
4.
LED blinks rapidly after 15 seconds, confirming d
eletion.
LANGUAGE
SELECTION
1. Press and hold both the Smoke and CO test switches simultaneously for 5 seconds until Welcome message is announced, then rele
ase. The green
light flashes rapi
dly.
2. Pre
ss the Test button corresponding to the desired language:
English:
Press the Smoke (•) test button
Spanish: Press the CO (••) test button
MOUNTING
After enrolling, verify adequate signal strength with the device in its intended mounting
location. Adjust the device location and
orientation as necessary.
1. Using two suppli
ed screws and anchors, mount the base.
2. Attach the smoke detector to the mounting base with a clockwise motion.
3.Test each detector as described in the Testing section.
4. Confirm all desired signals have been received by the Central Stati
on.
NOTE:
NFPA
72 recommends the installation of detectors only after completing construction or any other dust producing
activity.
NOTE:
This device should not be located w
ithin 5 ft.
(1.5 m) of any cooking appliance.
TESTING
Test communications between the detector and the control panel.
The detector
mode has two test buttons; one for smoke testing and one for CO testing.
The detector may also be functionally tested u
sing canned s
moke and canned
CO. If the detector fails any of the test methods, the
detector should be replaced.
NOTE:
Testing the detector will activate the alarm and send a signal to the
panel.
Before testing, notify the proper authorities to avoid any
false alarms.
Smoke Test (Alarm Test)
Press and hold
the Smoke Test button for 1 t
o 2 seconds. T
he detector will sound
and illuminate per Table 2 and send a smoke alarm signal to the control panel
(all
programmed smoke detector loops are
signaled)
. Verify
that the smok
e alarm
signal was received at the control panel.
Smoke System Test (Functional Sm
oke Test)
CANNED SMOKE NOTE:
Detector sounds an alarm when using canned smoke
ONLY
when in Functional Test mode (canned smoke does not cause
alarm sounding when in normal m
ode.)
Press and hold the Smoke Test button for 3 to 5 seconds to enter
the functional smoke test mode.
See Functional Smoke Test section below.
Functional Smoke Test
With the detector in smoke system (functional) test mode, spray canned smoke into the detec
tor. The canned smoke that can be used and is approved
for test include: Home Safeguard Industries 25S, SDi CHEK02 and CHEK06, SDi SOLOA4, and SDi SMOKESABRE.
1. The detector will sound and illuminate per Table 2 and a smoke alarm signal will be
sent to the p
anel.
2. Verify the smoke alarm signal was received by the control panel.
CO Test (A
larm Test)
Press and hold the CO Test button for 1 to 2 seconds. The control panel should display and sound a CO alarm
(all programmed CO detector loops are
se nt)
.
CO Syste
m Test (Functional CO Test)
CANNED CO NOTE:
Detector sounds an alarm w
hen using canned CO
ONLY
when in Functional Test mode (canned CO does not cause alarm
sounding when in normal mode.)
Press and hold the CO Test button for 3-
5 seconds to ent
er the functi
onal gas test mode.
See Functional Gas Test section below.
Functiona
l Gas Test
Sol
o C6 brand canned CO may be used to verify the detector’s ability to sense CO by utilizing the RealTest® feature as follows:
1. Press and hold the CO test butt
on for 3 to 5
seconds. The green LED will start blinking once per second
indicating
the detector is in RealTest® mode.
(If the detector will not go into RealTest® mode, the CO sensor may be in fault or at end-
of-life.)
2. While the green LED is blinking on
ce per second
, spray a small amount of canned CO directly into the CO gas entry por
t.
3. Upon successful gas entry and if functioning properly, the detector will go into CO alarm and send an alarm to the control panel.
4. The CO test will automatically c
lear when the
CO clears from the sensor or in 30 seconds if no CO was introduced.
HUSH FEATURE /
ALARM SILENCE
If required, the audible alarm for smoke and CO conditions can be silenced for 5 minutes by pushing the “Test/Hush” button. I
n addition, low
bat
tery
chirping
can be silenced for 12 hours when the Test/Hush button is pressed.
During a Smoke alarm, if an alarm condition still exists after the 5
-minute
hush period, the alarm will sound. The hush feature will not operate at levels
above 4%/
ft. smoke
concentration
.
During a CO alarm, if carbon monoxide is still present after the
5-minute
hush period, the alarm will sound. The hush feature will not operate at levels
above 350 ppm (parts per million) carbon monoxide.
CO SENSOR END-
OF
-LIFE FEATURE
When t
he CO sensor h
as passed end-
of-life, a trouble signal will be sent to the control panel (if progr
ammed). This indicates that the CO sensor inside
the detector must be replaced. If unresolved for 30 days, the detector will chirp every 45 seconds. The typical life of the
CO sensor is ten years from the
date of manufacture. It is recommended to periodica
lly check the “Replace by” date located on the label on the back of the detector head.
Table
3: Carbon Monoxide Detector: Events &
Contact
ID Codes
Event
Panel Display
CS
Repor
t
A
larms
CO Alarm
CO alarm (CID 162)
T
est
CO Alarm
CO alarm (CID 162)
Low
B
attery
Lo Bat
RF low
-
battery
(CID 384)
Detector
S
upervisio
n
C
O
Supervision
Loss
of RF Superv
i
sion
(CID 381)
Detector end
-
of
-
life/trouble
Low Maintenance
Sensor trouble
-
(CID
386
)
Low Maintenance
Tamper
Disarmed or Armed = Tamper
RF sensor tamper
(CID 383)
Table 4: Smoke
and Heat
Detector: Events &
Contact ID Codes
Event
Pan
el Display
CS
Report
Alarms
Fire Alarm
Fire Alarm (CID 110
)
Test
Fire Alarm
Fire Alarm (CID 1
10
)
Low Battery
Lo Bat
RF low
-
battery
(CID 384)
Detector
Supervision
S
moke or Heat Supervision
Loss of RF Supervision
(CID 381)
Detector Maintenance (Needs c
leaning)
Main
t
enance Smoke
Smoke Detector
High Sensitivity
(CID 385
)
Tamper
Disarmed or Armed =
Tamper
RF sensor tamper
(CID 383)
Table 2: LED Indication & Sounder during Test and Trouble
MODE
Status LED (T
op)
Side LED Windows
Sounder
Speaker
Smoke Test
Blink Green
once every second
Dark
Temp-3
Warning of alarm signal transmission.
Voice smoke warning
Functional SMOKE Test
–
Waiting for canned
smoke entry
Blink Green once a sec
Dark
Silen
t
Voice instr
u
ctions and warning of
alarm signal
Functional SMOKE Test
-
Successful smoke
entry
Blink Red every 10 secs
Blink Red every 10 secs
Temp-3
No voice announcment
RealTest™
Functional CO gas entry test –
Waiting for gas
entry
Blink Green once per second
Dark
Silent
No voice announcment
RealTest™
Functional CO gas entry test -
Upon succ
essful
gas entry
Blink Red once every
10 secs
Blink blue every
10 secs
Modified Temp
-4
Voice carbon monoxide warning
Low Battery
Blink Amber every 10 secs
Dark
Chirp eve
r
y 45 secs
after 7 days
Voice instruc
-
tions when chirp is
silenced by pressing
eithe
r test button
Smoke Maintenance
Blink Amber every 5 secs
Dark
Silent
Voice smoke maintenance instructions
if either test button is pressed
CO Trouble
Double
Blink Amber
every 5 secs
Dark
Silent
Silent
CO End of Life –
First 29 days
Double Blink Amber every 3 secs
Dark
Silent
Voice end
-
of
-
life instructions when
either test button is pressed
CO End of Life –
after 30 days
Double Blink Amber every 3 secs
Dark
Chirp ever
y 45 secs
Voice end
-
of
-
life instructions when
either test button is pressed
Power U
p
Blink Green, for 30 secs
Dark
Silent
Language set instructions only on first
time power
-
up
Normal (Standby)
Single Blink Green every 10 secs
Dark
Silent
Si
lent
LED INDICATORS
The
PROSiXCOMBO
has a multi
-color top LED:
Green =
Supervisory indication; blinks during power on,
reset, and
during normal operation
Amber =
Signal maintenance and trouble events
Red =
Alar
m conditi
on (either Smoke,
CO
, or Heat
)
Side LED windows indicate alarms:
Red =
Smoke
Blue =
CO
CLEANING
IMPORTANT:
This detector must be tested and maintained regularl
y following NFPA
-72 requirements. The detector should be cleaned at least once a
ye ar.
1. Remo
ve the detector from the base plate by turning counterclockwise.
2. Clean the outside casing with a cloth. Ensure that the holes on the front of the alarm are not bl
ocked with dirt and dust. Canned air can be used to
remove any dust or debris.
3. Reat
tach the detector to the base plate by rotating clockwise.
4. Test the detector to insure it is fully functional. (See Testing section).
5. Notify the proper authorities and C
entral Station when the system is back in service
REPLACING THE BATTERIES
CAUTION
:
The batteries used in this device may present a fire or chemical burn hazard if mistreated. Do not recharge, disassemble, heat above 100°C
(212°F) or dispo
se of in fire.
Use only Panasonic CR123A Lithium batteries. Use of other batteries may present a
risk of
fire or explosion. Keep used
batteries away from children. Dispose of used batteries properly.
Remove old batteries. Wait 10 seconds and then replace with four
new batteries. To avoid a low battery indication when installing new batteries, all
4
batteri
es must be installed within 15 seconds of installing the first one. Any low battery condition that may have occurred should c
lear when the base plate
is installed.
NOTE:
Constant exposure to high or low temperature or high humidity may reduce ba
ttery life.
LIMITED
LIFE
OF
CO
SENSOR
This detector is manufactured with a long-
life electrochemical carbon monoxide sensor. Over time the sensor will lose sensitivity and
will need to be
replaced. The life span of the CO sensor is approximately ten years
from the
date of manufacture.
Periodically check the detector’s replacement date. Remove the detector head and refer to the ‘replace by’ sticker placed on
the
underneath s
ide of the
detector. The sticker will indicate the date the detector should be replaced.
Remi
nder:
This detector is also equipped with a feature that will signal the panel once the CO sensor has passed the end of its’ useful
life. If this occu
rs,
it is tim
e to replace the detector.
What to do if the detector goes into CO alarm:
If the det
ector goes into CO alarm (4 beeps), immediately move to a spot where fresh air is available, preferably outdoors, where the air is saf
e and call
your security service provi
der. Tell your provider the detector alarm status, and that you require professional assista
nce in ridding your home of the
carbon monoxide.
This detector is NOT:
•
A substitute for the proper servicing of fuel
-burning
appliances or the sweeping of chim
neys.
•
To be used on an intermittent basis or as a portable alarm for the spillage of combust
ion products from fuel
-burning appliances or
chimneys.
Carbon monoxide gas is a highly poisonous gas which is released when fuels are burnt. It is inv
isible, has no
smell and is therefore is impossible to
detect with the human senses. Under normal
conditions in a room where fuel burning appliances are well maintained and correctly ventilated, the
amount of carbon monoxide released into the room by appl
iances should
not be dangerous.
CAUTIONS
:
•
This device will only indicate the presence of car
bon monoxide gas at the sensor. Carbon monoxide gas may be present in other areas.
•
This device is designed to protect individuals from the acute effects of carbon monoxide
exposure. It will not fully s
afeguard individuals with specific
medical conditions
. If in doubt consult a medical practitioner.
•
Installation of the device should not be used as a substitute for proper installation, use, and maintenance of f
uel
-burning
appliances, including
appropriate ventilation and exhaust systems.
MAINTENANCE
Do not paint, an
d do not use cleaning agents, bleach or polish the detector.
NOTE:
Before performing any maintenance on the detector, notify the proper authorities and Central S
tation that maintenance is being performed
and the system will be temporarily out of
service. D
isable the zone or system undergoing maintenance to prevent any unwanted alarms. Power
must be removed from the detector before performing maintenanc
e of any kind
.
The
PROSiXCOMBO
detector reports maintenance issues to the control panel and com
municates t
hem visually and audibly per Table 2.
Trouble feature:
When the sensor (supervision) is in a trouble condition (such as a detector that is dirty or C
O sensor non-
functioning), the detector will
send a trouble signal to the control panel. Dependi
ng on the i
ssue, the detector must then be serviced or replaced.
NOTE:
Smoke detectors are not to be used with detector guards unless the combination is evaluat
ed and found
suitable for that purpose.
SYMPTOMS OF CARBON MONOXIDE POISONING
Carbon monoxide bonds to the hemoglobin in the blood and reduces the
amount of oxygen being circulated in the body. The following symptoms
are examples taken from NFPA 720; they represent app
roximate values
for healthy adults.
Concentration
(ppm CO)
Symptoms
200
Mild Head
ache after 2
-
3 hours of exposure
400
Headache and nausea after 1
-
2 hours of exposure
800
Headache, nausea, and dizziness after 45 minutes
of expo-
sure; collapse and uncon
sciousness after 2
hours of exposure
Many cases of reported carbon monoxide poisoning indicate
that while
victims are aware that they do not feel well, they become so disoriented
that they are unable to save themselves by either exiting the building or
calling for assistance. Also,
young children, elderly and pets may be the
first to be
affected.
CO ALARM ACTIVATION
Per UL standard 2075, the
PROSiXCOMBO
detector has been tested to
the sensitivity limits defined in UL standard 2034.
CO Alarm Th
resholds
Pa
r
t
s per Million (ppm)
Detector Response Time (Min.)
30+
-
3ppm
No alarm within 30 day
s
70+
-
5ppm
60
-
240
150+
-
5ppm
10
-
50
400+
-
10ppm
4
-
15
SPECIFICATIONS
Electrical Specifications
Voltage:
................................
................................................
3 volts DC
Battery Type:
.................................................................
CR123A lithium
Battery Manufacturer:
......................................
Pa
nasonic CR123A only
Number of Batteries:
................................
...........................................
4
Sensitivity:
.................UL
limits .9 to 3.50%/ft / ULC limit
s .9 to 3.08 %/ft
Thermal alarm:
................................................................
135° F
(57° C)
Audible Signal:
................................
................................
............
85dBA
Physical Specifications
Diameter:
.............................................
6.3 in. Diameter x 1.65 in. Thick
(16.002 cm
x 4.19 cm T
hick)
Weight:
................................
................................
..........
14.3 oz (406 g)
Operating Temperature Range:
.......................
32°
- 100° F (0° -
38° C
)
Storage
Temperature Range:
..........................
14
- 158° F (
-10
- 70° C
)
Operating Humidity Range:
20-
95% R
H
APPROVAL LISTINGS
FCC
Listed to UL 268 & UL 2075.
Listed
to CSA 6.19.
Other Standards: RoHS
FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANAD
A (IC) ST
ATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or U
ser's Manual. Una
uthorized ch
anges or
modifications could void the user's authority to operate the equipment.
CLA
SS B DIGI
TAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following stat
ement
for your in
formation:
This equipment generates and uses radio frequency energy and if not installed and
used properly, that is, in strict accordance with the manufacturer's instructions, may cause
interference to radio and television reception. It has bee
n type tested
and found to comply with the limits for a Class B computing device in accordance w
ith the s
pecifications
in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. How
ever, there i
s no guarantee that
interference will not occur in a particular installation. If this equipm
ent does cause interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to tr
y to correct
the interference by one or more of the following measures:
• If using an indoor antenna, replace it with a quality outdoor antenna.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television
receiver aw
ay from the receiver/control.
• Move the antenna leads away from any wire runs to t
he receiv
er/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch cir
cuits.
• Consult the de
aler or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEM
ENT
This
Class B digital apparatus complies with Canadian ICES
-003.
Cet appareil numérique de la classe B est conforme à la norme NMB
-003 du Canada.
FCC / IC ST
ATEMENT
This
device complies with Part 15 of the FCC Rules, and Industry Canada’s license-
exempt
RSSs. Op
eration is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) This device must accept any interferenc
e received,
including interference that may cause undesired operation.
Cet appareil est conforme
à la par
tie 15 des règles de la FCC et exempt de licence RSS d’Industrie Canada. Son fonctionnement est soumis aux conditions suivant
es: (1) Cet
appareil ne doit pas cause
r d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue
y compri
s les interférences causant une réception indésirable.
RF EXPOSURE
Warning
–
The antenna(s) used for this device must be installed to provide a separ
ation distanc
e of at least 7.8 inches (20 cm) from all persons and must not be co-
located
or ope
rating in c
onjunction with any other antenna or transmitter except in accordance with FCC multi
-transmitter product procedures.
Mise en Garde
Exposition aux Fre
quences Radi
o:
L'antenne (s) utilisée pour cet émetteur doit être installée à une distance de sé
paration d'
au moins
7,8 pouces (20 cm) de toutes les personnes
.
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL
WITH WHICH THIS DEVICE IS USED FOR DETA
ILS
REG
ARDING
THE LIMITATIONS OF THE ENT
IRE ALARM SYSTEM.
Responsible Party / Issuer of Supplier’s
Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate Center Drive.,
Melville, NY 11747, Ph: 516-
577-
2000
The product
should not be disposed of with other household waste. Check for the nearest authorized collecti
on centers or authorized recyclers. The
correct disposal of end-
of-life equipment will help prevent potential negative consequences for the environment and human
health.
Any attempt to reverse-
engineer this device by decoding proprietary protocols, de-
comp
iling firmware, or any similar actions is strictly prohibited.
SUPPOR
T & WARRANTY INFORMATION
For the latest documentation
and
support, please go to:
www.resideo.com
For the latest warranty information, please go t
o:
www.security.honeywellhome.com/warranty
The Honeywell Home Trademark is us
ed under licen
se from
Honeywell International Inc.
This product is manufactured by Resideo
Technologies
, Inc.
and its affiliates.
2 Corporate Center Drive
P.O. Box 9040, Melville, NY 11747
© 2020
Resideo Technologies, Inc.
www.
resideo.
com
Ê800
-
2
5250B2Š
800-
25250B
7/19 Rev
B
- Uploaded