Honeywell iGSMHS Installation Manual



Related Products

Honeywell iGSMHS - AlarmNet High Security Dual Path Alarm Monitoring Communicator
Honeywell iGSMHS
AlarmNet High Security Dual Path Alarm Monitoring Communicator

Related Categories


Document Transcript

AlarmNet

!

IGSMHS
Internet Communication Module Installation and Setup Guide

Requires Compass Version 1.5.8.54A (or higher) for IP/GSM Downloading 800-08077 12/10 Rev. B

Table of Contents
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

SECTION 1: General Information ........................................................................................................... 1-1 System Overview...................................................................................................................................... 1-1 Introduction ....................................................................................................................................... 1-1 General Information.......................................................................................................................... 1-1 System Features....................................................................................................................................... 1-2 About AlarmNet-i Internet Application ................................................................................................. 1-2 Encryption ................................................................................................................................................ 1-2 Modes of Operation .................................................................................................................................. 1-2 ECP Mode........................................................................................................................................... 1-2 Zone Trigger Mode............................................................................................................................. 1-3 4204 Mode and Two-4204 Mode ....................................................................................................... 1-3 Module Supervision Features.................................................................................................................. 1-3 Antenna.............................................................................................................................................. 1-4 Specifications............................................................................................................................................ 1-4 Mechanical ......................................................................................................................................... 1-4 Electrical ............................................................................................................................................ 1-4 RF ....................................................................................................................................................... 1-4 Ethernet ............................................................................................................................................. 1-4 Environmental ................................................................................................................................... 1-5 Compatibility............................................................................................................................................ 1-5 SECTION 2: Mounting and Wiring.......................................................................................................... 2-1 Determine the Signal Strength and Select a Location .......................................................................... 2-1 Mounting the IGSMHS............................................................................................................................ 2-2 Standard Mounting Procedure ......................................................................................................... 2-2 Wiring the IGSMHS .......................................................................................................................... 2-3 Wiring a Telco Line Fault Monitor for Zone Mode .......................................................................... 2-3 Wiring for ECP, 4204 and Two-4204 Modes .................................................................................... 2-4 Wiring for Zone Trigger Mode .......................................................................................................... 2-4 Wiring for Module Fault Relay ......................................................................................................... 2-5 Ethernet Connections........................................................................................................................ 2-6 Power Connections and Options ............................................................................................................. 2-6 Powering the Communication Module ............................................................................................. 2-6 Backup Battery Connection .............................................................................................................. 2-7 Initial Power-Up Sequence ............................................................................................................... 2-7 SECTION 3: Programming the IGSMHS ............................................................................................... 3-1 General Information ................................................................................................................................ 3-1 Programming the Control Panel to work with the IGSMHS.......................................................... 3-1 Using the AlarmNet Direct Website ................................................................................................ 3-2 Using a 7720P Programming Tool.................................................................................................... 3-2 Using the Control Panel Programming Mode ................................................................................. 3-3 Programming Conventions ............................................................................................................... 3-3 ECP Mode Programming ......................................................................................................................... 3-3 ECP Status Codes.............................................................................................................................. 3-9 Alternative Modes (Zone Trigger, 4204 and Two-4204) ........................................................................ 3-9 Zone Trigger Mode............................................................................................................................. 3-9 i

IGSMHS Installation and Setup Guide 4204 Emulation Mode ..................................................................................................................... 3-10 4204 Emulation Mode Options ....................................................................................................... 3-10 Alternative Mode Programming ........................................................................................................... 3-11 Exiting Programming Mode .................................................................................................................. 3-20 Setting Factory Defaults........................................................................................................................ 3-21 SECTION 4: Registration .......................................................................................................................... 4-1 Registering the IGSMHS......................................................................................................................... 4-1 Register through the AlarmNet Direct Website .............................................................................. 4-1 Register using the Tamper Switch ................................................................................................... 4-2 Register using the Programming Tool ............................................................................................. 4-2 Replacing an existing module using the programming tool ........................................................... 4-3 Register by Phone .............................................................................................................................. 4-3 SECTION 5: Programmer Keyboard Commands................................................................................. 5-1 Module Identification Displays ............................................................................................................... 5-1 GSM Status Displays............................................................................................................................... 5-2 System Status Displays ........................................................................................................................... 5-3 SECTION 6: Network Diagnostics........................................................................................................... 6-1 Running Network Diagnostics on the IGSMHS..................................................................................... 6-1 Possible Errors Running Network Diagnostics...................................................................................... 6-2 Appendices................................................................................................................................................... A-1 Appendix A : Summary of LED Operation .............................................................................................A-1 Appendix B : Central Station Messages .................................................................................................B-1 Appendix C : IP Downloading .................................................................................................................C-1 Appendix D : Glossary ............................................................................................................................ D-1

Summary of Connections Diagram……………………………………..………………...Inside Back Cover

ii

S E C T I O N

1

General Information
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

System Overview
Introduction Congratulations on your purchase of Honeywell's IGSMHS combination Internet and GSM communication module (henceforth referred to as IGSMHS). It represents the latest and most innovative communication technology for the security industry and uses the most sophisticated encryption to ensure the highest level of security for your customer.
The IGSMHS module requires an AlarmNet–i account. For new installations, please obtain the account information from the central station prior to programming this module. For replacement installations, the AlarmNet-i account is created automatically when the module is registered.

In addition to alarm reporting, the IGSMHS provides upload/downloading capability of Honeywell's control panel data over the Internet (via the AlarmNet-G network), using GSM (Global System for Mobile) technology. General Information Honeywell's IGSMHS Internet communication module communicates via the Internet (when service is available) and switches to GSM service when the Internet is not available. In normal operation (with Internet connectivity), the IGSMHS communicates from your customer's network connection to the Honeywell Network Operations Center, (NOC) via the AlarmNet-i network. The NOC receives data and routes the information to the Central Station of your choice, based on the account number you assign to the module. Note that your Central Station needs to give you the account number. The same account number is used for both Internet and GSM transmissions. If your current Central Station is capable of receiving signals from the Honeywell NOC, they are capable of receiving signals from the IGSMHS module. If, for some reason, Internet connectivity is not available, (for example, your customer's ISP is off line or disconnected), the IGSMHS will transmit signals via the AlarmNet-G (GSM) cellular network, which uses the GPRS (General Packet Radio Service) to complete these transmissions. These transmissions are sent to the Honeywell NOC and then forwarded to your Central Station exactly the same way as if they were received via the Internet. If the Internet and GPRS (part of the GSM cellular network) are both unavailable (fail), the message will not be sent via this communication module.
For maximum reliability, it is recommended the device be operated in dual path mode with Internet and GSM both enabled and connected.

1-1

IGSMHS Installation and Setup Guide

System Features
Basic features include: " " " " " " Supports dynamic or static IP addressing, and installs behind firewalls without compromising network security. Quick connection to compatible Honeywell series control panels Simple programming using a 7720P programming tool Reports fire (Fire has not been evaluated by UL), burg, and status messages via the Internet Reports messages via AlarmNet-G as backup to Internet reporting Allows uploading and downloading of control panel data over the Internet.

About AlarmNet-i Internet Application
AlarmNet-i is a fully encrypted, secure method of delivering alarm messages from a protected premise to an AlarmNet equipped central station. An Internet Communicator Module transmits status, supervisory, and alarm messages to the AlarmNet Control Center using a broadband Internet connection. The AlarmNet Control Center identifies, validates, and forwards the messages to the appropriate AlarmNet central station. AlarmNet-i has an unlimited account capacity.

Encryption
The IGSMHS supports private key encryption. Private Key encryption means that both the sender and the receiver know the KEY used to encrypt the data. Each communication module produced by Honeywell is loaded with a globally unique identifier called a MAC number, and a large random number or KEY. This KEY and MAC number are also stored in the AlarmNet servers. When a communication module contacts AlarmNet, it sends the MAC number in the clear followed by the message that is encrypted using the KEY data. The server looks up its copy of the KEY based on the MAC number and uses that KEY to decrypt the message. The IGSMHS uses 256 bit AES (Rijndael) encryption (which is required for certain government installations). The AlarmNet-i AES Encryption Software Module Version 1.0 contained in the Honeywell products has NIST approval. Listings for this approval can be found at http://csrc.nist.gov/cryptval/aes/aesval.html Certification number 127.

UL
Modes of Operation

The IP and GSM signaling paths are suitable for encrypted line security when programmed for 1 minute IP/GSM Fault Times. The system configurations are not suitable as a Dual Line Signal transmission system.

The IGSMHS provides four modes of operation so it can be used with various types of control panels, as summarized below.

UL

Only ECP Mode and Zone Trigger modes have been approved for UL installations.

ECP Mode " This mode is for use with Honeywell control panels that support ECP communication " The module connects to the control panel’s keypad terminals and provides 2-way communication with the control panel using ECP messaging " The control panel treats the IGSMHS as a communications module (LRR), so program the control panel accordingly, including setting the module’s proper LRR device address " Reports are sent in Contact ID format " The module also supports two hardwire zone trigger inputs (zones 6 and 7) Options include; V+, V–, EOL, inverted, and non-inverted.

1-2

Section 1: General Information UL – For the IGSMHS, only the V+ inverted, V– non-inverted, and EOL options have been evaluated.

UL

Opening and Closing ring back is fully supported.

Zone Trigger Mode " This mode is for use with control panels that do not support ECP communication nor 4204 Relay Modules " The module provides six input zones and each zone can be configured for +V, -V, or EOLR triggering. UL – For the IGSMHS, only the V+ inverted, V– non-inverted, and EOL options have been evaluated. " Each zone can be programmed for inverted operation, delayed reporting, and restoral reporting " Zone 1 input can distinguish between pulsed and steady signals and report fire or burglary alarms respectively " Zone 1 can be programmed to report a LYNX panic (if used with LYNX control panel) UL – This feature has not been evaluated by UL. " Reports are sent in ADEMCO High-Speed format

UL

Opening and Closing ring back is supported by the control panel’s digital dialer.

4204 Mode and Two-4204 Mode " This mode is for use with Honeywell control panels that do not support ECP communication, but do support 4204 Relay Modules " The module connects to the control panel’s keypad terminals " The control panel treats the module as 4204 Relay Module(s), so program the control panel accordingly, including setting the module’s proper 4204 device address " 4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on options programmed " Two-4204 mode provides up to eight zone inputs, depending on options programmed " Each 4204 zone can be programmed for delayed reporting and restoral reporting " Reports are sent in ADEMCO High-Speed format

UL

4204 Mode and Two-4204 Mode has not been evaluated.

Module Supervision Features

The IGSMHS provides the following types of supervision and module fault detection: " Network communication failure: In the event the AlarmNet network does not hear a supervisory message from the module within a specified time AlarmNet notifies the central station of a communication failure. " Communication path failure: In the event the module detects a communication path failure, the control panel can be notified of a trouble condition with the module after a specified time has elapsed. " Fault output: Terminal 11 can serve as a fail-safe trigger for module fault conditions. " If used, the fault relay will trip when the following conditions occur: tamper*, power loss*, low battery*, battery charger fault*, loss of network connectivity*, the communication module is not registered and the communication module is remotely disabled by AlarmNet. * Alarm reporting for the noted conditions must be enabled for it to trigger the fault relay. 1-3

IGSMHS Installation and Setup Guide " " Antenna The IGSMHS comes equipped with an internal antenna. This feature provides additional security to the installation by making the module tamper resistant. Primary power loss and low battery conditions. Cover tamper condition.

UL

External antenna options have not been evaluated by UL.

AMPS antennas, such as the 7825-OC antenna, cannot be used with this product.

Specifications
Mechanical Dimensions: 8.4" x 8.0" x 1.5" Weight: 2.4 lbs., with battery Electrical Input Power: 16.5VAC, 40VA transformer, Honeywell Model No. 1361 Current Drain: 65mA average standby, 500mA peak transmit Or 12VDC from control panel. Current Drain: 80mA average standby, 650mA peak transmit UL: Powering the IGSMHS from a control panel has not been evaluated by UL. Backup Battery: 6V, 3.1AH, Honeywell part number K14139, (included) Expected Battery Life: 5 Years (approx.) Fault Relay Output: Open collector, 12VDC, .25W max. Positive Trigger Level: 6V or greater = positive trigger. (4V or less = restore.) Negative Trigger Level: 4V or less = negative trigger. (6V or greater = restore.) RF Transceiver Type: Quad-Band GSM / GPRS Class 10 Modulation: GMSK Antenna: Internal GSM quad-band antenna 1.3 dBi gain
Band GSM 850 GSM 900 GSM 1800 GSM 1900 Transmission Frequency (MHz) 824-849 890-915 1710-1785 1850-1910 Transmit Power (dBm) 33 33 30 30 Receive Frequency (MHz) 869-894 935-960 1805-1880 1930-1990 Receive Sensitivity (dBm) -107 -107 -106 -105.5 Number of Channels 124 124 374 299 Channel Spacing (MHz) 200 200 200 200 Duplex Separation (kHz) 45 45 95 80

Ethernet Network Standard: IEEE 802.3u compliant Data Rate: 10Base-T / 100Base-T with auto detect Ethernet Cable: Cat. 5 (min), MDI / MDI-X auto crossover

1-4

Section 1: General Information Environmental Operating temperature: –20º to +55ºC (UL evaluated range: 0º to +49ºC) Storage temperature: –40º to +70ºC Humidity: 0 to 85% relative humidity, non-condensing Altitude: to 10,000 ft. operating, to 40,000 ft. storage

Compatibility
For a list of control panels that are compatible with various features of this communication module, go to: http://www.security.honeywell.com/hsc/resources/MyWebTech. After logging on, select the applicable communication product, and then select “Compatibility Chart” under Essential Docs. For UL installations, compatible control panels are: " Vista-128BP " Vista-250BP

For UL installations, compatible receivers are: " MX8000 (UL – can be used for supplemental reporting in ECP mode when connected to model 7810iR-ENT; must be used for opening/closing ring back in Zone Trigger mode when connected to control unit’s DACT.) (UL – must be the primary alarm receiver.) (UL – Ademco 685 has not been evaluated by UL.)

" 7810iR-ENT " Ademco 685

UL

The Automation System must be UL1981 listed. The IGSMHS has been evaluated for connection to police station receivers.

1-5

IGSMHS Installation and Setup Guide

1-6

S E C T I O N

2

Mounting and Wiring
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

Determine the Signal Strength and Select a Location
The IGSMHS must be mounted indoors within the protected premises. When choosing a suitable mounting location, understand that signal strength is very important for proper operation. For most installations using the supplied antenna, mounting the unit as high as practical, and avoiding large metal components provides adequate signal strength for proper operation. You will use the communications module to determine signal strength in order to find a suitable mounting location. NOTE: If the SIM is already activated, the RSSI signal strength indicators will indicate signal strength. If the SIM has not been activated, the firmware in the communications module enables it to communicate with the cellular network towers (without the SIM being activated) so that signal strength measurements can be determined. In this case, you can display the signal strength by simultaneously pressing the MODE and TAMPER switches. RF Exposure Warning – The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter. NOTE: The IGSMHS must be installed in accordance with the National Fire Alarm Code, ANSI / NFPA 70. Unshielded, 22 AWG cable is recommended for IGSMHS power / data wires. 1. Unpack the IGSMHS and detach the case back by pushing up into the two tabs located at the bottom of the IGSMHS with the blade of a screwdriver while pulling the case back and case front apart. 2. Temporarily connect the IGSMHS to the AC transformer, supplied. 3. Choose the installation site with the best signal strength by observing the signal strength (RSSI) bar graph (refer to Appendix A for information about signal strength and status indications). Signal strength should be within 3-5 bars. The best signal strength is usually found at the highest point in the building, near a window. Unplug the transformer.
3 BARS MIN.

R

Y

Y

G

G

G
7845i-GSM-025-V0

4. Mark the location for the IGSMHS.

2-1

IGSMHS Installation and Setup Guide

Mounting the IGSMHS
The communications module can be mounted in two ways depending on the installation requirements.

UL

The cover must be secured with the supplied screw.

Standard Mounting Procedure 1. Locate the case back over selected mounting position such that the opening in the case back is aligned with the wire / cable opening on the mounting surface. 2. Pass the wire / cable through the opening in the case back, or route through the removable knockouts located on the back cover. 3. Secure the case back to the mounting surface using four screws (supplied).
4.

When all wiring is completed, attach the case front. Position the top first, then press the bottom section until it snaps in place. Secure bottom using the supplied cover screw. (This is required for UL installations.)
MOUNTING SCREW (4) (TYP)

CASE BACK

WALL OR MOUNTING SURFACE

INTERNAL ANTENNA

OPTIONAL WIRING KNOCKOUT CASE FRONT
RX TX GSM GPPS WEB MODE 2 MODE 1 RSSI

OPTIONAL WIRING KNOCKOUTS TAB TAB

COVER SECURING SCREW

7845i-GSM-028-V0

Figure 2-1. Standard Mounting

2-2

Section 2: Mounting and Wiring

Wiring the IGSMHS

UL

"

Installation must be in accordance with; the National Electrical Code, UL681 Installation and Classification for Burglary and Hold-Up Alarm Systems, and UL827 for Central-Station Alarm Services. IGSMHS must be connected to a UL Listed dry contact or voltage trigger outputs of a UL Listed compatible control panel. All interconnecting wires between the UL Listed control panel and the IGSMHS must be less than 3 feet in length contained in the same room. All interconnecting wiring must be installed in rigid or EMT (where exposed on interior walls) or in flexible metal tubing if run in the walls or ceiling. A UL listed control panel must monitor the radio fault output of the IGSMHS. Premises openings and closings should be sent via the UL listed control panel. Only ECP mode has been evaluated by UL. 4204 Mode and Two-4204 Mode has not been evaluated.

" "

" " "

Wiring a Telco Line Fault Monitor for Zone Mode When using an Ademco No. 659EN Line Fault Monitor, follow the diagram below for wiring information. (For detailed information, refer to the Ademco No. 659EN Installation Instructions P3516-1V2.)
No. 659EN Line Fault Monitor
6-14VDC STAND BY: 5mA ACTIVE: 35mA 1 2 3 4 5 6 7 8

RED

BLK

CONTROL PANEL
RED AUX POWER BLK TO TELCO LINE (Disregard Polarity)

High Security Communicator
TB1 4 9 OR 10 GND
IGSMHS-002-V0

ZONE 6 ZONE 7

The Telco line fault monitor should utilize either zone 6 or zone 7 on the IGSMHS. When programming the IGSMHS ensure the following programming is accomplished. The example below is for Zone 6.
Programming Prompt Enable Zn6 Zn6 Trigger Type Invert Zn6 Restore Zn6 Delay Zn6 Rpt Zn6 ONLY if Armed Setting [Y] [V+] [Y] [Y] [00] [N]

2-3

IGSMHS Installation and Setup Guide Wiring for ECP, 4204 and Two-4204 Modes Most Honeywell control panels support ECP data communication. Check the Installation and Setup Guide for the control panel you are using to see if it supports ECP communication. Connect the IGSMHS to a compatible Honeywell VISTA control panel's ECP terminals, in parallel with keypads and other peripheral devices such as RF receiver, VIP module, etc. Wire length / gauge limitations are the same for the module as they are for keypads and other peripheral devices. To wire the module for ECP or 4204 modes, see Figure 2-2 and make the following connections:

TRANSFORMER

TB1 1 2 AC INPUT 1 AC INPUT 2 ECP (+) VOLTAGE INPUT GND ECP DATA IN ECP DATA OUT
J1

+12V AUX GND DATA OUT DATA IN

RED BLK YEL GRN

3 4 5 6

BATTERY

VISTA CONTROL PANEL

COMMUNICATIONS MODULE

Figure 2-2. Wiring a VISTA for ECP Mode or 4204 Modes

Wiring for Zone Trigger Mode To trip a zone using a positive trigger, the voltage level must be: 6V or greater = positive trigger. (Levels above +14V may cause damage to the unit.) 4V or less = restore. To trip a zone using a negative trigger, the voltage level must be: 4V or less = negative trigger. 6V or greater = restore. (Levels above +14V may cause damage to the unit.) NOTE: Remember to program the communications module zone for the desired trigger type. Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control panel to the zone input of the module, and connect a common ground between the module and control panel. Examples of zone connections follow:
TRANSFORMER

TB1 1 2 AC INPUT 1 AC INPUT 2

GND + TRIGGER (VOLTAGE: 6 to 13V)

4 5

GND ZONE INPUT Z1/Z2

J1

BATTERY

TRIGGERING DEVICE

COMMUNICATIONS MODULE

GSMV-005-V0

Figure 2-3. Wiring Zone 1 Input for a Positive (+) Trigger

2-4

iGSMBR-005-V0

Section 2: Mounting and Wiring

TRANSFORMER

TB1 1 2 AC INPUT 1 AC INPUT 2

GND (VOLTAGE 4 to 0V)

4 5

GND ZONE INPUT Z1/Z2

-TRIGGER

TRIGGERING DEVICE COMMUNICATIONS MODULE

J1

BATTERY

GSMV-006-V0

Figure 2-4. Wiring Zone 1 Input for a Ground (-V) Trigger

TRANSFORMER

TB1 1 AC AC

UL

" Zones should use EOL resistors, and be programmed as V+ Inverted or V– Inverted operation such that a cut line results in an alarm. " EOL resistors must be UL Listed. " Do not use zones 1 and 2 for UL installations.
2K EOL RESISTOR N.O. N.C.

2

4 5

GND ZONE INPUT Z1/Z2

J1

BATTERY

COMMUNICATIONS MODULE

Figure 2-5. Wiring Zone 1 Input for EOL Supervised N.O. / N.C. Triggers Wiring for Module Fault Relay You may wire and program the module's fault output trigger for fail-safe mode (see the prompt "FLT REL ON Y/N"). To sense a module fault at the control panel, make connections as shown in Figure 2-6, including the proper EOL resistor required by the control panel.

UL

For Commercial Burglary, a 24 hour zone (supervisory) must be assigned on the control panel, with the communication module's fault relay wired to that zone.

TRANSFORMER

TB1 1 2 AC INPUT 1 AC INPUT 2 ECP (+) VOLTAGE INPUT GND

12V AUX GND ZONE IN (+) 2K EOL RESISTOR

3 4

CONTROL PANEL

11 RAD FLT
iGSMBR-011-V0

J1

BATTERY

COMMUNICATIONS MODULE

Figure 2-6. Wiring the Fault Relay to a Control Panel Zone for Normally Closed Fault

2-5

iGSMBR-010-V0

IGSMHS Installation and Setup Guide Ethernet Connections

UL

" For UL installations, the Cat. 5 Ethernet connection between the IGSMHS and the router cannot exceed 12 feet with both the IGSMHS and the router located within the same room.

" Use a Listed cable / DSL router suited for the application.

Connect one end of the Ethernet cable (Category 5) to the IGSMHS’s RJ45 Ethernet connector and the other end to the cable / DSL router as shown in the figure below.
7720P PROGRAM CONNECTOR

IBS GPRS

J1 BATTERY CONNECTOR

TO ROUTER

Figure 2-7. Ethernet Connections

Power Connections and Options
Powering the Communication Module For a standard installation, primary power is provided by the AC plug-in transformer. For ECP communication, you must also connect the +12VDC AUX voltage output of the control panel (9.6V-13.8V typical) (see Figure 2-8). In all installations, TB1-4 GND must be connected to ground (GND) on the control panel.
TRANSFORMER TB1 1 2 12V AUX GND 3 4 AC INPUT 1 AC INPUT 2 ECP (+) VOLTAGE INPUT GND

Standard Installation

iGSMBR-012-V0

J1

BATTERY

CONTROL PANEL

COMMUNICATIONS MODULE

Figure 2-8. Powering the Communications Module NOTE: When calculating the total load on the auxiliary power output of the control panel, budget 10mA
for the IGSMHS when using ECP mode.

2-6

iGSMBR-013-V0

M1 M0 RSSI

RJ45 (FOR INTERNET CONNECTION)

Section 2: Mounting and Wiring Backup Battery Connection The included battery (K14139) is used for backup in the event of power loss to the communications module. It does not provide power to the control panel. " The battery can provide over 24 hours of system life in the event of a power failure. " A programmable power loss message can alert the AlarmNet Control Center when system power is lost (power loss messages are reported within 1-3 hours of actual loss). " The module transmits a low-battery message (programmable) when the battery reaches 5.7V ±5%, indicating subsequent messages may not be transmitted. " The system shuts down when the battery falls below 5.1V, and radio transmissions are no longer possible. " If system power is restored before the module shuts down, a power restore message is sent within 1-3 hours after power is restored, and the battery is recharged using the IGSMHS’s built-in battery charger. If system power is restored after the IGSMHS has shut down, a power-on reset condition exists, the module initializes itself and the battery will recharge. Install the battery as follows, and refer to the Summary of Connections diagram at the end of this document. 1. Place the battery inside the case back. 2. Snap the right side of the battery clip onto the inside of the case back and secure the left side with the screw provided. NOTE: Do not plug the battery in until after you have powered-up the IGSMHS. Initial Power-Up Sequence Before connecting power, check that the following have been completed: " If using ECP, 4204 or 2-4204 Mode, terminal block TB1 V+ and GND terminals are connected to the control panel’s auxiliary power output: 12VDC nominal. " Plug in the transformer. " Connect the red and black battery cables to the battery terminals. Connect battery cable to connector J1. " Power up the control panel. " Initially, all IGSMHS programming options are set to the factory default settings.

2-7

S E C T I O N

3

Programming the IGSMHS
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

General Information
The IGSMHS is designed to deliver alarms via the Internet to an AlarmNet central station or via the AlarmNet-G network, using GSM (Global System for Mobile) technology when the Internet is not available. The IGSMHS uses 256 bit AES (Rijndael) encryption which is required for certain government installations.
The IGSMHS module requires an AlarmNet–I account. For new installations, please obtain the account information from the central station prior to programming this module. For replacement installations, the AlarmNet-i account is created automatically when the module is registered.

You can program a IGSMHS by one of the following methods: " Through the AlarmNet Direct website " Through use of a 7720P Programming Tool " Through a programming mode in the control panel, on panels that support this option

UL

Only ECP and Zone Trigger modes have been evaluated by UL.

Programming the Control Panel to work with the IGSMHS For Residential and Commercial control panels, there are certain programming field settings that must be adhered to for using the IGSMHS. (For programming information, please refer to the appropriate control panel guides.) Ensure the following programming fields are set:
RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.) UL: These control panels have not been evaluated by UL. Programming Field !29 Menu Mode for IP/GSM Enable !54 Dynamic Signaling Delay !55 Dynamic Signaling Priority Setting 1 (Enable LRR.) 0 (Dialer and LRR reports go out at the same time.) 0 (Primary dialer reports first.)

COMMERCIAL Control Panels (Such as the VISTA-128 / 250 series.) Programming Field !32 Primary Subscriber's Acct No. !56 Dynamic Signaling Delay !57 Dynamic Signaling Priority !58 Comm Central Station #1 Category Enable !59 Comm Central Station #2 Category Enable #93 Menu Mode Setting nnnn (Required for the communicator to report.) 00 (Dialer and LRR reports go out at the same time.) 1 (Communicator, as first reporting.) 111111 (All events will be reported to the primary Central Station.) 000000 (If Central Station #2 is not used.) 111111 (If Central Station #2 is used.) Zone programming – set Zone 803 for Type 05. Device programming – set Address 03 for Type 06 (LRR).

3-1

IGSMHS Installation and Setup Guide Using the AlarmNet Direct Website To program the module via the website (if you are already signed up for this service), go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx If you are not signed up for this service, click on “Dealer Sign-Up. Log in and follow the on-screen prompts. Please have the following information available when programming the module: 1. Primary City ID (two-digit number) 2. Primary Central Station ID (two-digit hexadecimal number) 3. Primary Subscriber ID (four-digit number) 4. MAC ID and MAC CRC number (located on the outside of box and on label inside module) of the communication module you are installing After programming is complete, you must transfer the data to the module and the module must be registered. Refer to Section 4: Registration, for further instructions. Using a 7720P Programming Tool Connect the 7720P Programming Tool as shown below. The IGSMHS powers the 7720P Programming Tool via the programming jack, and automatically senses the presence of the 7720P when it is plugged in.
7720P PROGRAM CONNECTOR

Xmit Shift

BS / ESC /

A

1
D

2
E

B

3 6 9 #
X Enter F

C

4
N /Y Shift S

5 8 0
T

IBS GPRS

M1 M0 RSSI

7
Space

Figure 3-1. Cable Connections Each key of the 7720P has two possible functions: a normal function and a Shift function. To perform a normal key function, simply press the desired key. To perform a Shift function, press the [shift] key, and then press the appropriate key. The prompts in this document reflect use of the 7720P Programming Tool. The table below lists each normal and shift key function. Table 3-1. 7720P Normal and Shift Key (shift LED lit) Functions
KEY BS / ESC #/$ N/Y SHIFT 1/A 2/B 3/C 4/D 5/E SHIFT KEY FUNCTION [ESC]: Press to quit program mode; also can reset programming defaults* [#]: Scroll down programming [$]: Scroll up programming [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out once a key is pressed. Press again for each SHIFT function desired. [1]: For entering the number 1 [A]: For entering letter A [2]: For entering the number 2 [B]: For entering letter B [3]: For entering the number 3 [C]: For entering letter C [4]: For entering the number 4 [D]: For entering letter D [5]: For entering the number 5 [E]: For entering letter E NORMAL KEY FUNCTION [BS]: Press to delete entry

3-2

iGSMBR-015-V0

Section 3: Programming the IGSMHS
KEY 6/F 7/S 8 /T 9/X SPACE 0 # / ENTER NORMAL KEY FUNCTION [6]: For entering the number 6 [7]: For entering the number 7 [8]: For entering the number 8 [9]: For entering the number 9 [SPACE]: For scrolling option list [0]: For entering the number 0 [#/ENTER]: Starts programming mode; Press to accept entries SHIFT KEY FUNCTION [F]: For entering letter F [S]: For entering letter S [T]: For entering letter T [X]: For entering letter X No SHIFT function No SHIFT function No SHIFT function

* Active only when the "Exit Programming Mode" prompt is displayed. Using the Control Panel Programming Mode Most control panels support programming of the IGSMHS through the control panel programming mode (refer to the control panel’s installation guide). If programming through the control panel, only the ECP Mode programming options are available. The "mode" prompts will not be displayed, and the mode cannot be changed. For a description of key functions on the control panel keypad, and how they map to the 7720P Programming tool, refer to the control panel's Programming Guide. Programming Conventions Programming is accomplished by answering a series of prompts. Most prompts require only a [Y]es or [N]o response, while others require a numerical response (ID numbers, etc.). The current value is displayed on the second line in parentheses ( ). A "?" indicates an invalid entry. Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the entered value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not displayed until a valid answer is entered. Use the up / down arrow keys to scroll through the programming prompts without changing any values. Press the [ESC] key to go to the end of the list of prompts.

ECP Mode Programming
The IGSMHS supports ECP messaging via the control panel’s ECP bus. These messages are in Contact ID format. (Not all control panels support the ECP bus, so be sure to check the control panel’s Installation and Setup Guide to see if it supports this feature.) Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears: Access to Prog Mode Denied

Table 3-2: Programming an IGSMHS for ECP mode only.
PROMPTS 1 2 Strt Prog Mode? (Y/N)_ Enter Password: ENTRY OPTIONS [Y], [N] [0-9, A-F, N, S, T, X, Y] DESCRIPTION Enters programming mode. If a password has been previously assigned, this prompt appears. Enter a 4-digit password (0-9, A-F, N, S, T, X, Y). The next prompt appears.

3-3

IGSMHS Installation and Setup Guide
PROMPTS 3 Program Device? (Y/N)_ ENTRY OPTIONS [Y], [N ] DESCRIPTION To begin programming the module, press [Y] and go to Prompt 10: "Device Mode." To create a password if none has been assigned, press [N] and go to Prompt 4: "Create Password." To change an existing password, press [N] and go to Prompt 5: "Change Password." Passwords can be used to protect account and programming information. If no password has been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt. If a password is desired, press [Y] and go to "Enter Password." If a password has already been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt. Press [Y] if you want to change the password. NOTE: To clear an existing password, without entering a new one, answer [Y] to the "Change Password?" prompt, then press the [Enter] key when prompted for the new password and its confirmation. This prompt is displayed if [Y] was pressed in Prompt 4 or 5. Enter a 4-digit password (0-9, A-F, N, S, T, X, Y). Re-enter the password as confirmation. If the password doesn't match the first entry, the following is displayed followed by the "Exit Prog. Mode?" prompt: Verify Not OK PSWD not created Otherwise, the "Exit Prog. Mode?" prompt is displayed directly. Exits program mode. Press [N] to go back to Prompt 3. Press [ESC] to load factory defaults. Refer to the Exiting Programming Mode paragraph in this section. Press the [space] key to scroll through the communication path choices. Press [ENTER] to select. For maximum reliability, select IP&GSM, and ensure the Internet is connected using the Ethernet cable. NOTE: After going from a “GSM” only com path choice to an “IP” only choice, Prompt 41: “DHCP” will default to No. Press the [space] key to scroll through the modes of operation. Press [ENTER] to select ECP mode.

4

Create Password? (Y/N)_

[Y], [N]

5

Change Password? (Y/N)_

[Y], [N]

6

Enter Password

[0-9, A-F, N, S, T, X, Y] [0-9, A-F, N, S, T, X, Y]

7

Verify Password

8

Exit Prog. Mode? (Y/N)_

[Y], [N] [ESC]

9

Comm Path Choice (IP&GSM)_

" IP&GSM " IP " GSM

10

Device Mode (ECP)_

Account information is provided by the central station administrator. If the control panel supports secondary account reporting, you will need secondary account information. The City ID, CS ID or Subscriber ID of the secondary account must differ from that of the primary account.

" ECP " Zone Triggers " 4204 Emu See Table 3-4 if programming other modes. " Two 4204s Important Information Regarding Primary and Secondary Accounts (Prompts 11-17)

3-4

Section 3: Programming the IGSMHS
PROMPTS
11

ENTRY

OPTIONS [01-99] [01-FE]

DESCRIPTION Enter the 2-digit primary city ID, 01-99 (decimal). Enter the 2-digit primary central station ID number, 01-FE (HEX). Enter the 4-digit subscriber account number, 00019999 (decimal). Applicable only if control panel supports Central Station #1 and #2 Category Enable reporting for the communications device (LRR) (e.g., VISTA-128BP, FA1660C, etc.). Used if reporting to a second central station is desired. If [N], go to Prompt 18: "Device Address." Enter the 2-digit secondary city ID, 01-99 (decimal). Enter the 2-digit second central station's ID number, 01-FE (HEX). Enter the 4-digit subscriber account number for the second central station, 0001-9999. In ECP mode, the IGSMHS communicates with the control panel as a communications device (LRR). Enter the appropriate ECP device address. For VISTA-10 and VISTA-20 series control panels, use address 03. For other controls, see the control panel’s Installation and Setup Guide. NOTES: 1. When programming the control panel, enable the LRR output. 2. The device address must be unique from the "Keypad Address" entered in Prompt 20. Enables Direct Wire Downloading over IP. This applies only to the Vista-32FB and VISTA BP and FBP series control panels with revision 3.x. BP and FBP panels rev 4.x and higher support Downloading via IP over ECP. If [N], skip to Prompt 21: "Supervision." Must be programmed if using Direct Wire downloading. NOTES: 1. This address must also be programmed as an alpha keypad in the control panel or an AUI (advanced user interface) type device, if a full enhanced graphic interface to the system is desired and the control panel supports it. DO NOT connect an actual keypad (or any other device) assigned to this address. 2. This address must be unique from the "Device Address" entered in Prompt 18.

Primary City ID (??)_ Primary CS ID (??) Primary Sub ID (????) En. 2nd CS Y/N (N)_

12

13

[0001-9999] [Y], [N]

14

15 16

2nd City ID (??)_ 2nd CS ID (??)_ 2nd Sub ID (????)_ Device Address (03)_

[01-99] [01-FE] [0001-9999] [01-30]

17

18

19

Direct Wire Y/N (N)_

[Y], [N]

20

Keypad Address (28)_

[01-30]

3-5

IGSMHS Installation and Setup Guide
PROMPTS 21 Supervision (UL Hi Line Sec)_ ENTRY OPTIONS " UL Hi Line Sec " 3 Minutes " 6 Minutes DESCRIPTION The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred. (If the supervision period is changed after registration, you must re-register the module.) Press the [space] key to scroll through choices. NOTE: When “UL Hi Line Sec” is selected, a loss of communications is treated as an alarm condition. UL: Must be set to "UL Hi Line Sec" (200 sec). NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM. 22 GSM 24Hr Tst Y/N (N)_ [Y], [N] If enabled a message is sent every 24 hrs over GSM to verify proper operation. If it fails, a Periodic Comm Test Failure message will be sent over Ethernet. UL: Must be set to "Y". 23 Old Alarm Time 10 Minutes_ "10 Minutes " 15 Minutes " 30 Minutes " 1 Hour " 2 Hours " 4 Hours " 8 Hours " 12 Hours " 24 Hours [00-99] Sets how long an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm time is reached or the message is validated. Press the [space] key to scroll through choices. UL: Must be 10 minutes.

NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or IP. 24 IP Flt Time (01 mins)_ In the event there is a loss of contact with the network over the Ethernet connection, enter the time delay (in minutes) before the IGSMHS notifies the central station. IP failure will always be sent to the central station as Primary Communication Path Failure. UL: Must be one (01) minute. NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or GSM. 25 GSM Flt Time (01 mins)_ [00-99] In the event the module detects a communication path failure, enter the time delay (in minutes) before the IGSMHS notifies the central station. A GSM failure will always be sent to the central station as Secondary Communication Path Failure. UL: Must be one (01) minute. If "Both IP and GSM Faults" is selected, the device will only notify the control panel if both communication paths fail, but will always send notification of either failure to the central station. NOTE: The fault relay output (if programmed) will be triggered only if "Both IP and GSM Faults" is selected. Press the [space] key to scroll through choices. UL: Must be set to "Both IP and GSM Faults".

NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM. 26 Notify Panel Of_ (Both IP&GSM Flts) [Both IP and GSM Faults] [Neither fault]

3-6

Section 3: Programming the IGSMHS
PROMPTS 27 Flt Rel ON Y/N (N)_ ENTRY OPTIONS [Y], [N] DESCRIPTION If enabled, the fault open collector output is normally energized to ground, and de-energizes (open circuit) in the event of a module fault. For conditions that trip the fault relay refer to Module Supervision Features in Section 1. Set to [Y] if fail-safe mode is desired. See Wiring for Module Fault Relay in Section 2. UL: Must be set to "Y." 28 Pwr Loss Rpt Y/N (Y)_ [Y], [N] Sends a primary power loss report to the central station within 1-3 hours after its detection. A restore report is sent within 1-3 hours after power is restored. UL Standard Installations (using transformer and battery): Must be set to "Y". Sends a low-battery report when a low battery condition exists. A low battery restore is automatically sent when the low battery condition clears. UL Standard Installations (using transformer and battery): Must be set to "Y". Sends a tamper report when the module detects a tamper condition. A tamper restore is automatically sent when the tamper condition clears. UL: Must be set to "Y."

29

Low Bat Rpt Y/N (Y)_

[Y], [N]

30

Tamper Rpt Y/N (Y)_

[Y], [N]

Important Information Regarding Zone Input Options ECP mode supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or zone 7 terminals and programming the appropriate zone trigger options below. Each zone input can be programmed to cause an alarm under one of the following conditions: " (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC) " (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC) " (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by open collector, voltage trigger, NO, NC. " UL Installations, V+ is to be set as inverted and V– as non-inverted. In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations. These zone inputs can also be programmed for restore reporting, and for delayed reporting (NOT for UL installations), which allows time for the user to abort false alarms. NOTE: Optional hardwire zones report in ADEMCO High-Speed format. 31 32 Enable Zn6 Y/N (N)_ Zn6 Trigger Type (V+)_ [Y], [N] " (V+) " (V–) " (EOLR) [Y], [N] [Y], [N] [01-15] [00] = no delay [Y], [N] Enables alarm reporting for zone 6. If [N], skip to Prompt 36: "Enable Zn7." Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. Inverts the alarm and normal states of the zone 6 trigger; otherwise uses normal input signal. Enables restore reporting for zone 6. Defines the reporting delay in seconds for zone 6. UL: Must be set to 00. Enables alarm reporting for zone 7. If [N], skip to Prompt 41: "Use DHCP."

33 34 35

Invert Zn6 Y/N (N)_ Restore Zn6 Y/N (Y)_ Delay Zn6 (secs) (00)_ Enable Zn7 Y/N (N)_

36

3-7

IGSMHS Installation and Setup Guide
PROMPTS 37 Zn7 Trigger Type (V)_ ENTRY OPTIONS " (V+) " (V–) " (EOLR) [Y], [N] [Y], [N] [01-15] [00] = no delay DESCRIPTION Selects the triggering method for this zone input. Press the [space] key to scroll choices. UL: V+ must be set as inverted and V– as non-inverted. Inverts the alarm and normal states of the zone 7 trigger; otherwise, uses normal input signal. Enables restore reporting for zone 7. Defines the reporting delay in seconds for zone 7. UL: Must be set to 00.

38 39 40

Invert Zn7 Y/N (N)_ Restore Zn7 Y/N (Y)_ Delay Zn7 (secs) (00)_

NOTE: Prompts 41 through 46 only appear if the Comm Path Choice is IP, or IP&GSM. 41 Use DHCP Y/N (Y)_ NIC IP Address: 255.255.255.255_ Subnet Mask: 255.255.255.255_ [Y], [N] Dynamically allocates the IP addresses (recommended); then skip to Prompt 46: "Enable Pwr Save". If [N], uses fixed IP addresses. Enter the 4-part address for this device. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). Enter the 32-bit address mask used to indicate the portion (bits) of the IP address that is being used for the subnet address. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). Enter the 4-part address assigned to the Gateway. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). Enter the 4-part IP address assigned to the DNS (Domain Name System) server. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). To meet the 24 hour UL battery backup requirement, choose "Y" to enable this feature. If this causes connectivity problems with certain routers or switches, then choose "N" and wire the communications module so it is plugged into a UL listed UPS. UL: Must be set to Y. 47 IP Connection (Present) " Present " Auto Detect Press the [space] key to toggle between the options. Press [ENTER] to select the configuration. If “Present” is chosen, it is assumed that an IP is connected to the device. If it is not detected, a Primary Comm Path Failure message will be delivered after the programmed fault time expires. If “Auto Detect” is chosen, the device will always try to use IP to communicate but it will not generate a Primary Comm Path Failure unless it previously detected the presence of IP. As soon as the presence of IP is detected, a Primary Comm Path Restore message is generated and the value of IP Connectivity programming parameter is changed from “Auto Detect” to “Detected”. From this point on, the software expects connectivity. The auto detect logic will resume only when the parameter is changed back to “Auto Detect”.

42

12 digit: xxx.xxx.xxx.xxx 12 digit: xxx.xxx.xxx.xxx

43

44

Gateway IP Addr: 255.255.255.255_ DNS Serv IP Addr: 255.255.255.255_

12 digit: xxx.xxx.xxx.xxx 12 digit: xxx.xxx.xxx.xxx

45

46

Enable Pwr Save (Y)_

[Y], [N]

3-8

Section 3: Programming the IGSMHS
PROMPTS 48 Review? Y/N ENTRY OPTIONS [Y] = review [N] = exit DESCRIPTION Reviewing Programming Mode Entries To review the programming options (to ensure that the correct entries have been made), press [Y]. The programming prompts are displayed again. Use the up/down arrow keys to scroll through the program fields without changing any of the values. If a value requires change, simply type in the correct value. When the last field is displayed, the “REVIEW?” prompt again appears. To exit the programming mode, press [N] in response to the "REVIEW?" prompt, and refer to Exiting Programming Mode at the end of this section.

ECP Status Codes When the IGSMHS is configured for ECP mode, it sends status messages to the control panels for battery, power, tamper, and network connectivity failures. Some control panels display these on the keypad as “LngRng Radio” followed by a 4-digit code (listed in the table below). In addition, the Contact ID codes (listed in Appendix B) for these conditions are sent to the central station by the module.

UL

The information in the following table is based on the VISTA-20 which has not been evaluated with this communication module.

Table 3-3. Common ECP Keypad Display Status Codes
STATUS CODE 0000 0880 4005 000F 0019 0400 0C80 0C8F 08E0 3000 8000 0060 DESCRIPTION Control panel lost communication with IGSMHS. IGSMHS tamper detected (cover removed). IGSMHS has lost contact with AlarmNet. IGSMHS is not registered; account not activated. IGSMHS shutdown. IGSMHS power on / reset AND the control panel lost communications with IGSMHS. IGSMHS power on / reset AND tamper detected. IGSMHS power on / reset AND tamper detected AND not registered. IGSMHS tamper detected and IGSMHS battery low. Primary power loss (will only be displayed in conjunction with another event). Battery charger failure (will only be displayed in conjunction with another event). Low battery (will only be displayed in conjunction with another event).

Alternative Modes (Zone Trigger, 4204 and Two-4204)

UL

The LYNX controls have not been evaluated with this communication module.

Zone Trigger Mode There are six input zones available on the IGSMHS. Each zone is selectable for +V, -V, or EOLR trigger. The first zone input can detect both pulsed and steady signals if connected to a bell output. Additionally, the first zone input can be programmed to detect a single pulse (characteristic of a Panic indication on the Lynx, LynxR or LynxR-EN control panel by enabling the Lynx Panic option). If the programming option “Lynx Panic” is enabled, the IGSMHS reports an alarm on zone 3. No restores are reported for this zone. If this option is selected, the second physical zone input is ignored. 3-9

IGSMHS Installation and Setup Guide When using Zone Trigger mode, messages are sent in ADEMCO High-Speed format. Zones 3, 4, 5, 6 and 7 are voltage trigger inputs located on TB1 pins 6-10. If the Lynx Panic feature is being used, do not connect zone 3 (the second physical zone input). Refer to Table 3-4 for Zone Trigger Mode programming and follow the prompts that pertain to Zone Trigger Mode. A check mark (!) indicates whether the prompt applies to that mode. 4204 Emulation Mode In 4204 Emulation Mode, the IGSMHS communicates with a compatible Honeywell VISTA series or First Alert control panel as though it were a 4204 Relay Module. If two 4204s are enabled in the module, it acts as two 4204s at consecutive device addresses. The control panel must be configured to recognize one or two 4204 relay modules accordingly. On VISTA-32FB (or higher) control panels and First Alert equivalents, addresses 6 and 13 should not be used when the secondary 4204 is enabled. Messages are sent in ADEMCO High-Speed format. NOTE: See your control panel Installation and Setup Guide for the number of 4204 modules supported. 4204 Emulation Mode Options For control panels that do not support ECP communication, the 4204 Emulation modes provide a means of sending up to eight unique reports based on defined system conditions. In 4204 mode, the IGSMHS functions as a logical 4204 Relay Module, where each relay number, referred to in the module as zone number, can be programmed to send a report based on the output function programmed in the control panel for that relay. Each relayzone can also be programmed to send a restore message of the reported condition, can be set to delay transmission of messages, and can be programmed to send reports only when a conditional zone is triggered (armed), (see Important Information Regarding Zone Input Options later in this section). In single 4204 mode, the IGSMHS supports up to four relay-zones. In Two-4204 mode, the IGSMHS functions as two 4204 modules, supporting up to eight relay-zones.

UL

4204 Mode and Two-4204 Mode has not been evaluated.

4204 Relay Outputs map to IGSMHS zones as follows: First 4204 Zones
(device address entered in Prompt 14):

Second 4204 Zones
(device address entered in Prompt 14, plus 1):

Relay 1 = Zone 1 Relay 2 = Zone 2 Relay 3 = Zone 3 Relay 4 = Zone 4 or conditional zone trigger if “report only if armed” is selected in any zone 1-3 when using single 4204 mode. NOTE: Zone 4 status is not reported when being used as the conditional (armed) trigger zone.

Relay 1 = Zone 5 Relay 2 = Zone 6 Relay 3 = Zone 7 Relay 4 = Zone 8 or conditional zone trigger if “report only if armed” is selected in any zone 1-7 when using Two-4204 mode. NOTE: Zone 8 status is not reported when being used as the conditional (armed) trigger zone or if tamper reporting is enabled.

When using the IGSMHS in 4204 Emulation Mode, DO NOT enable the Long-Range Radio module in control panel programming. Instead, enable 4204 relay module address(es) and program the appropriate relay activation functions for the relay-zones being used. In some control panels, it is called “relay programming” and in others it is called “output device programming.” It is recommended that “close and stay closed” (usually choice 2) action is selected. Selection of momentary activation will cause the IGSMHS to generate an alarm and NOT a restore, even if the IGSMHS is programmed to send a restore for the given zone. In 4204 mode, messages are reported in ADEMCO High-Speed format. Zone alarms (status 7) are reported with “1” (alarm) or “3” (restore) displayed in the zone position for the respective zone (e.g. alarm on zone 2: 5155 5555 7; restore 5355 5555 7). A supervision fault 3-10

Section 3: Programming the IGSMHS trouble message is automatically sent if the module detects no activity on its connection to the control panel. The message is: 5555 5515 5; restore message is: 5555 5535 5. Refer to Table 3-4 for 4204 Emulation Mode programming and follow the prompts that pertain to 4204 or Two-4204 mode. A check mark (!) indicates whether the prompt applies to that mode.

Alternative Mode Programming
Press the [ENTER] key to begin programming and follow the prompts for the mode of operation being programmed.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears: Access to Prog Mode Denied

Table 3-4: Programming a IGSMHS for Zone Trigger, 4204 Emulation, or Two-4204 Emulation modes.
PROMPTS 1 2 Strt Prog Mode? Y/N_ Enter Password ZONE TRIG. ! ! 4204/ 2-4204 ! ! ENTRY OPTIONS [Y], [N] [0-9, A-F, N, S, T, X, Y] [Y], [N] DESCRIPTION Enters programming mode. If a password has been previously assigned, this prompt appears. Enter a 4-digit password (0-9, A-F, N, S, T, X, Y). The next prompt appears. To begin programming the module, press [Y] and go to Prompt 10: "Device Mode." To create a password if none has been assigned, press [N] and go to Prompt 4: Create Password. To change an existing password, press [N] and go to Prompt 5: "Change Password." Passwords can be used to protect account and programming information. If no password has been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt. If a password is desired, press [Y] and go to Prompt 6: "Enter Password." If a password has already been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt. Press [Y] if you want to change the password. NOTE: To clear an existing password, without entering a new one, answer [Y] to the "Change Password?" prompt, then press the [Enter] key when prompted for the new password and its confirmation. This prompt is displayed if [Y] was pressed in Prompt 4 or 5. Enter a 4-digit password (0-9, A-F, N, S, T, X, Y). Re-enter the password as confirmation. If the password doesn't match the first entry, the following is displayed followed by the "Exit Prog. Mode?" prompt: Verify Not OK PSWD not created

3

Program Device? Y/N_

!

!

4

Create Password? Y/N_

!

!

[Y], [N]

5

Change Password? Y/N_

!

!

[Y], [N]

6

Enter Password

!

!

[0-9, A-F, N, S, T, X, Y] [0-9, A-F, N, S, T, X, Y]

7

Verify Password

!

!

3-11

IGSMHS Installation and Setup Guide
PROMPTS ZONE TRIG. 4204/ 2-4204 ENTRY OPTIONS DESCRIPTION Otherwise, the "Exit Prog. Mode?" prompt is displayed directly. Exits program mode. Press [N] to go back to Prompt 3. Press [ESC] to load factory defaults. Refer to the Exiting Programming Mode paragraph in this section. Press the [space] key to scroll through the communication path choices. Press [ENTER] to select. For maximum reliability, select IP&GSM, and ensure the Internet is connected using the Ethernet cable. NOTE: After going from a “GSM” only com path choice to an “IP” only choice, Prompt 68: “DHCP” will default to No. Press the [space] key to scroll through the modes of operation. Press [ENTER] to select mode.

8

Exit Prog. Mode? Y/N_

!

!

[Y], [N] [ESC]

9

Comm Path Choice (IP&GSM)_

!

!

" IP&GSM " IP " GSM

10

Device Mode (ECP)_

Account information is provided by the central station administrator.
11 12 13 14 Primary City ID (??)_ Primary CS ID (??) Primary Sub ID (????) Device Address (12)_ ! ! ! ! ! ! ! [01-99] [01-FE] [00019999] [01-15]

" ECP " Zone Trig. " 4204 See Table 3-2 for ECP mode programming. Emu " Two 4204s Important Information Regarding Primary Account (Prompts 11-13) ! ! Enter the 2-digit primary city ID, 01-99 (decimal).

Enter the 2-digit primary central station ID number, 01-FE (HEX). Enter the 4-digit subscriber account number, 0001-9999 (decimal). The IGSMHS communicates with the control panel as a 4204 relay module. Enter the appropriate address. For VISTA-10P, and FA130CP Series control panels, this must be address 12. For other controls, see the control panel’s Installation and Setup Guide. NOTES: 1. The 4204 protocol limits address range to 01-15. If using 2-4204 mode, the IGSMHS assigns the second 4204 to the next higher device address (e.g., if entering address 12 for the first 4204, then address 13 is automatically assigned to the second 4204 module). Program the control panel accordingly. 2. The device address(es) must be unique from the "Keypad Address" entered in Prompt 16 and any other address used on the control panel.

3-12

Section 3: Programming the IGSMHS
PROMPTS 15 Direct Wire (N)_ Y/N ZONE TRIG. 4204/ 2-4204 ! ENTRY OPTIONS [Y], [N] DESCRIPTION Enables Direct Wire Downloading over IP. This applies only to the Vista-32FB and VISTA BP and FBP series control panels with revision 3.x. BP and FBP panels rev 4.x and higher support Downloading via IP over ECP. If [N], skip to Prompt 17: "Supervision." Must be programmed if using Direct Wire downloading. Enter the appropriate device address. NOTES: 1. This address must also be programmed as an alpha keypad in the control panel or an AUI (Advanced User Interface) type device, if a full enhanced graphic interface to the system is desired and the control panel supports it. DO NOT connect an actual keypad (or any other device) assigned to this address. 2. This address must be unique from the "Device Address" entered in Prompt 14, and cannot equal that device address plus 1 (one) if using 2-4204 mode. The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred. (If the supervision period is changed after registration, you must re-register the module.) Press the [space] key to scroll through choices. NOTE: When “UL Hi Line Sec” is selected, a loss of communications is treated as an alarm condition. UL: Must be set to "UL Hi Line Sec" (200 sec). NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM. 18 GSM 24Hr Tst Y/N (N)_ ! ! [Y], [N] If enabled a message is sent every 24 hrs over GSM to verify proper operation. If it fails, a Periodic Comm Test Failure message will be sent over Ethernet. UL: Must be set to "Y". Sets how long an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm time is reached or the message is validated. Press the [space] key to scroll through choices. UL: Must be set to 10 minutes.

16

Keypad Address (28)_

!

[01-30]

17

Supervision (UL Hi Line Sec)_

!

!

" UL Hi Line Sec " 3 Minutes " 6 Minutes

19

Old Alarm Time 10 Minutes_

!

!

" 10 Min " 15 Min " 30 Min " 1 Hr " 2 Hrs " 4 Hrs " 8 Hrs " 12 Hrs " 24 Hrs

3-13

IGSMHS Installation and Setup Guide
PROMPTS ZONE TRIG. 4204/ 2-4204 ! ENTRY OPTIONS DESCRIPTION

NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or IP. 20 IP Flt Time (01 mins)_ ! [00-99] In the event there is a loss of contact with the network over the Ethernet connection, enter the time delay (in minutes) before the IGSMHS notifies the central station. IP failure will always be sent to the central station as Primary Communication Path Failure. UL: Must be one (01) minute. NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or GSM. 21 GSM Flt Time (01 mins)_ ! ! [00-99] In the event the module detects a communication path failure, enter the time delay (in minutes) before the IGSMHS notifies the central station. A GSM failure will always be sent to the central station as Secondary Communication Path Failure. UL: Must be one (01) minute. NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM. 22 Notify Panel Of_ (Both IP&GSM Flts)_ ! ! [Both IP and If "Both IP and GSM Faults" is selected, the GSM Faults] device will only notify the control panel if both communication paths fail, but will always send [Neither notification of either failure to the central fault] station. NOTE: The fault relay output (if programmed) will be triggered only if "Both IP and GSM Faults" is selected. Press the [space] key to scroll through choices. UL: Must be set to "Both IP and GSM Faults". [Y], [N] If enabled, the fault open collector output is normally energized to ground, and de-energizes (open circuit) in the event of a module fault. For conditions that trip the fault relay refer to Module Supervision Features in Section 1. Set to [Y] if fail-safe mode is desired. See Wiring for Module Fault Relay in Section 2. UL: Must be set to "Y". 24 Pwr Loss Rpt Y/N (Y)_ ! ! [Y], [N] Sends a primary power loss report to the central station within 1-3 hours after its detection. A restore report is sent within 1-3 hours after power is restored. UL Standard Installations (using transformer and battery): Must be set to "Y". Sends a low-battery report when a low battery condition exists. A low-battery restore is automatically sent when the low battery condition clears. UL Standard Installations (using transformer and battery): Must be set to "Y". Sends a tamper report when the module detects a tamper condition. A tamper restore is automatically sent when the tamper condition clears. UL: Must be set to "Y".

23

Flt Rel ON Y/N (N)_

!

!

25

Low Bat Rpt Y/N (Y)_

!

!

[Y], [N]

26

Tamper Rpt Y/N (Y)_

!

!

[Y], [N]

3-14

Section 3: Programming the IGSMHS
PROMPTS 27 Lynx Panic Y/N (N)_ ZONE TRIG. ! 4204/ 2-4204 ENTRY OPTIONS [Y], [N] DESCRIPTION Applies only if used with a Lynx, LynxR or LynxR-EN control panel LRR trigger connected to the module's zone terminal. Reports a Panic alarm on zone 3 when the module detects a single pulse on zone 1. No restores are generated for a Panic alarm.

Important Information Regarding Zone Input Options If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or zone 7 terminals and programming the appropriate zone trigger options below. NOTE: These triggers are not available when using 2-4204 mode. Zone Trigger Mode provides six hardwire zone input triggers by making connections to the module’s zone terminals and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a reporting zone only (see Bell Output Zone below). Bell Output Zone 1 (and 2): The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell output to the IGSMHS zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The IGSMHS reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when it detects a steady signal. UL: Use of the Bell output is not supported. Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the Telco fault zone and/or an open/close (arm/disarm) reporting zone. When triggered, these zones report a Telco line fault or open/close report respectively, in ADEMCO High-Speed format. Connect the appropriate trigger from the control panel to the selected zone input for each of these options. Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the following conditions: " (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC) " (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC) " (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by open collector, voltage trigger, NO, NC. " UL Installations, V+ is to be set as inverted and V– as non-inverted. Inverted Trigger: Zones can be programmed for inverted trigger, where the alarm and normal states of the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations. Restore and Delayed Reports: Zone inputs can be programmed for restore reporting, and for delayed reporting (NOT for UL installations) which allows time for the user to abort false alarms. UL: Zone restoral must be enabled. Report Only if Armed option: To help eliminate redundant reports, zone alarms can be restricted to report only if a conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the “arming” zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be programmed as necessary in the control panel. The conditional (arming) zone on the module is a different dedicated zone for each programming mode, as follows: Mode Zone Trigger 4204 2-4204 Conditional (Arming) Zone 7 4 8

IMPORTANT: If any zone (zones 1-6 in zone trigger mode, zones 1-3 in 4204 mode, zones 1-7 in 2-4204 mode) is set for Report Only if Armed, the conditional (arming) zone becomes unavailable for reporting (as it is reserved for the “arming” trigger connection). 28 Trip Inputs 1or2 w/Bell Out (N)_ ! [Y], [N] Use if the zone 1 connection to the control's bell output causes a bell fault on the control panel. NOTES: 1. If used, EOLR trigger type is not available for zones 1 and 3. 2. Do not use with Lynx controls.

3-15

IGSMHS Installation and Setup Guide
PROMPTS 29 Telco Zone (0)_ ZONE TRIG. ! 4204/ 2-4204 ! ENTRY OPTIONS Zone Trig: [3-7] 4204: [1-4] 2-4204: [1-8] [0] = not used DESCRIPTION See Important Information above, Regarding Zone Input Options. Enter the zone number to be used for Telco line fault reports. This zone assignment must be unique from the open/close zone selected in Prompt 30. Zone Trigger Mode: If any zone is programmed for "report only if armed," zone 7 cannot be used. If Lynx Panic is enabled, zone 3 cannot be used. 4204 Mode: If any zone is programmed for "report only if armed," zone 4 cannot be used. 2-4204 Mode: If any zone is programmed for "report only if armed," or if tamper is enabled, zone 8 cannot be used. NOTE: Connect the Telco line fault output (or relay output programmed for "Telco line fault") to the Telco zone. Enter the zone number to be used for open/close (arm/disarm) reports. This zone assignment must be unique from the Telco zone selected in Prompt 29. Zone Trigger Mode: If any zone is programmed for "report only if armed," zone 7 cannot be used as an open/close zone. If Lynx Panic is enabled, zone 3 cannot be used. 4204 Mode: If any zone is programmed for "report only if armed," zone 4 cannot be used as an open/close zone. 2-4204 Mode: If any zone is programmed for "report only if armed," or if tamper is enabled, zone 8 cannot be used as an open/close zone. NOTE: Connect an open/close (arm/disarm) trigger (or relay output) from the control panel to the open/close zone. Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. Enables restore reporting for zone 1. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 1. UL: Must be set to 00. Report alarms on zone 1 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; or zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 1. Inverts the alarm and normal states of the zone 2 trigger; otherwise uses normal input signal.

30

Open/Close Zone (0)_

!

!

Zone Trig: [3-7] 4204: [1-4] 2-4204: [1-8] [0] = not used

31

Zn1 Trigger Type (V+)_

!

" (EOLR) " (V+) " (V–)

32 33

Restore Zn1 Y/N (Y)_ Delay Zn1 (secs) (00)_ Rpt Zn1 ONLY if Armed (N)_

! !

! !

[Y], [N] [01-15] [00] = no delay

34

!

!

[Y], [N]

35

Invert Zn2 Y/N (N)_

!

[Y], [N]

3-16

Section 3: Programming the IGSMHS
PROMPTS 36 37 Restore Zn2 Y/N (Y)_ Delay Zn2 (secs) (00)_ Rpt Zn2 ONLY if Armed (N)_ ZONE TRIG. ! ! 4204/ 2-4204 ! ! ENTRY OPTIONS [Y], [N] [01-15] [00] = no delay ! ! [Y], [N] DESCRIPTION Enables restore reporting for zone 2. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 2. UL: Must be set to 00. Reports alarms on zone 2 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 2.

38

If Lynx Panic is enabled, then skip to Prompt 43: "Rpt Zn3 ONLY if Armed." 39 Zn3 Trigger Type (V+)_ ! " (EOLR) " (V+) " (V–) Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. Inverts the alarm and normal states of the zone 3 trigger; otherwise uses normal input signal. Enables restore reporting for zone 3. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 3. UL: Must be set to 00. Reports alarms on zone 3 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 3. 4204 mode: If any zone is programmed to "Report Only if Armed," skip to Prompt 54: "Enable Zn6." Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. 45 46 47 Invert Zn4 Y/N (N)_ Restore Zn4 Y/N (Y)_ Delay Zn4 (secs) (00) Rpt Zn4 ONLY if Armed (N)_ ! [Y], [N] [Y], [N] [01-15] [00] = no delay ! 24204 only [Y], [N] Inverts the alarm and normal states of the zone 4 trigger; otherwise uses normal input signal. Enables restore reporting for zone 4. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 4. UL: Must be set to 00. Reports alarms on zone 4 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 4.

40 41 42

Invert Zn3 Y/N (N)_ Restore Zn3 Y/N (Y)_ Delay Zn3 (secs) (00) Rpt Zn3 ONLY if Armed (N)_

! ! ! ! !

[Y], [N] [Y], [N] [01-15] [00] = no delay

43

!

!

[Y], [N]

44

Zn4 Trigger Type (V+)_

!

" (EOLR) " (V+) " (V–)

!

!

!

!

48

3-17

IGSMHS Installation and Setup Guide
PROMPTS 49 Zn5 Trigger Type (V+)_ ZONE TRIG. ! 4204/ 2-4204 ENTRY OPTIONS " (EOLR) " (V+) " (V–) DESCRIPTION Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. Inverts the alarm and normal states of the zone 5 trigger; otherwise uses normal input signal. Enables restore reporting for zone 5. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 5. UL: Must be set to 00. Reports alarms on zone 5 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 5. Enables alarm reporting for zone 6. If [N], skip to Prompt 60: "Enable Zn7." Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. Inverts the alarm and normal states of the zone 6 trigger; otherwise uses normal input signal. Enables restore reporting for zone 6. UL: Must be set to “Y.” ! ! [01-15] [00] = no delay ! ! [Y], [N] Defines the reporting delay in seconds for zone 6. UL: Must be set to 00. Reports alarms on zone 6 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 6. Enables alarm reporting for zone 7. If [N], skip to Prompt 68: "Use DHCP." Selects the triggering method for this zone input. Press the [space] key to scroll through choices. UL: V+ must be set as inverted and V– as non-inverted. Inverts the alarm and normal states of the zone 7 trigger; otherwise uses normal input signal.

50 51

Invert Zn5 Y/N (N)_ Restore Zn5 Y/N (Y)_ Delay Zn5 (secs) (00)_ Rpt Zn5 ONLY if Armed (N)_

! ! 24204 only 24204 only 24204 only 4204 only ! 4204 only

[Y], [N] [Y], [N] [01-15] [00] = no delay [Y], [N]

52

!

53

!

54 55

Enable Zn6 Y/N (N)_ Zn6 Trigger Type (V+)_

[Y], [N] " (EOLR) " (V+) " (V–)

56 57 58

Invert Zn6 Y/N (N)_ Restore Zn6 Y/N (Y)_ Delay Zn6 (secs) (00)_ Rpt Zn6 ONLY if Armed (N)_

! !

4204 only !

[Y], [N] [Y], [N]

59

60 61

Enable Zn7 Y/N (N)_ Zn7 Trigger Type (V+)_ !

4204 only 4204 only

[Y], [N] " (EOLR) " (V+) " (V–)

62

Invert Zn7 Y/N (N)_

!

4204 only

[Y], [N]

3-18

Section 3: Programming the IGSMHS
PROMPTS 63 Restore Zn7 Y/N (Y)_ ZONE TRIG. ! 4204/ 2-4204 ! ENTRY OPTIONS [Y], [N] DESCRIPTION Enables restore reporting for zone 7. Zone Trigger mode: This prompt will only be displayed if zone 7 is not used as the conditional (arming) trigger zone. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 7. Zone Trigger mode: This prompt will only be displayed if zone 7 is not used as the conditional (arming) trigger zone. UL: Must be set to 00. Reports alarms on zone 7 ONLY if the conditional zone (zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed). If [N], always reports alarms on zone 7. 2-4204 mode: If any zone is programmed to "Report Only if Armed," or if tamper is enabled, skip to Prompt 68: "Use DHCP." Enables restore reporting for zone 8. UL: Must be set to “Y.” Defines the reporting delay in seconds for zone 8. UL: Must be set to 00.

64

Delay Zn7 (secs) (00)_

!

!

[01-15] [00] = no delay

65

Rpt Zn7 ONLY if Armed (N)_

!

[Y], [N]

66

Restore Zn8 Y/N (Y)_ Delay Zn8 (secs) (00)_

24204 only 24204 only

[Y], [N]

67

[01-15] [00] = no delay

NOTE: Prompts 68 through 73 only appear if the Comm Path Choice is IP, or IP&GSM. 68 Use DHCP Y/N (Y)_ NIC IP Address: 255.255.255.255_ Subnet Mask: 255.255.255.255_ ! ! [Y], [N] Dynamically allocates the IP addresses (recommended); then skip to Prompt 73: "Enable Pwr Save". If [N], uses fixed IP addresses. Enter the 4-part address for this device. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). Enter the 32-bit address mask used to indicate the portion (bits) of the IP address that is being used for the subnet address. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). Enter the 4-part address assigned to the Gateway. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). Enter the 4-part IP address assigned to the DNS (Domain Name System) server. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode). To meet the 24 hour UL battery backup requirement, choose "Y" to enable this feature. If this causes connectivity problems with certain routers or switches, then choose "N" and wire the communications module so it is plugged into a UL listed UPS. UL: Must be set to Y.

69

!

!

12 digit: xxx.xxx.xxx. xxx 12 digit: xxx.xxx.xxx. xxx

70

!

!

71

Gateway IP Addr: 255.255.255.255_

!

!

12 digit: xxx.xxx.xxx. xxx 12 digit: xxx.xxx.xxx. xxx [Y], [N]

72

DNS Serv IP Addr: 255.255.255.255_ Enable Pwr Save (Y)_

!

!

73

!

!

3-19

IGSMHS Installation and Setup Guide
PROMPTS 74 IP Connection (Present) ZONE TRIG. ! 4204/ 2-4204 ! ENTRY OPTIONS " Present " Auto Detect DESCRIPTION Press the [space] key to toggle between the options. Press [ENTER] to select the configuration. If “Present” is chosen, it is assumed that an IP is connected to the device. If it is not detected, a Primary Comm Path Failure message will be delivered after the programmed fault time expires. If “Auto Detect” is chosen, the device will always try to use IP to communicate but it will not generate a Primary Comm Path Failure unless it previously detected the presence of IP. As soon as the presence of IP is detected, a Primary Comm Path Restore message is generated and the value of IP Connectivity programming parameter is changed from “Auto Detect” to “Detected”. From this point on, the software expects connectivity. The auto detect logic will resume only when the parameter is changed back to “Auto Detect”. 75 Review? Y/N ! ! [Y] = review [N] = exit Reviewing Programming Mode Entries To review the programming options (to ensure that the correct entries have been made), press [Y]. The programming prompts are displayed again. Use the up/down arrow keys to scroll through the program fields without changing any of the values. If a value requires change, simply type in the correct value. When the last field is displayed, the “REVIEW?” prompt again appears. To exit the programming mode, press [N] in response to the "REVIEW?" prompt, and refer to Exiting Programming Mode below.

Exiting Programming Mode
To exit the programming mode, press [N] in response to the "REVIEW?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded. If critical configuration changes were made, such as the mode of operation, the IGSMHS will reset to ensure that the programming features are enabled. If the file is not successfully uploaded, one of the following prompts will be displayed. Follow the steps shown below until the upload is successful. Display
Cannot Upload Try Again? Y/N_ Failed to Update Root File!

Description
IGSMHS module is not yet initialized. Network problem, or you answered "N" to "Cannot Upload Try Again?" prompt.

What to do
Wait for RSSI LEDs to be lit. Press [Y]. Initiate the Force Server Update Command by pressing the [0] key; refer to Section 5: Programmer Keyboard Commands.

3-20

Section 3: Programming the IGSMHS

Setting Factory Defaults
To reset the programming options to factory-default values, press [ESC] at the "Exit Prog Mode?" prompt.
Set Default? Y/N_ Press [Y] to reset factory default values. Press [N] to cancel this function.

If you press [Y], all programmed values are reset to the original factory settings. PLEASE NOTE THAT THIS WILL ERASE ANY PASSWORD THAT MAY HAVE BEEN ENTERED. After pressing [Y], the Create Password prompt appears (see Prompt 4).

3-21

IGSMHS Installation and Setup Guide

3-22

.

S E C T I O N

4

Registration
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

Registering the IGSMHS
Once you have initialized and programmed the IGSMHS, it must be registered to enable the account. The registration status is indicated below:

LED STATUS (green) MESSAGE (yellow)

DESCRIPTION ON – Is NOT registered with AlarmNet. OFF – Is registered with AlarmNet. ON – Message transmission pending. QUICK PERIODIC BLINK - Normal SLOW BLINK – In unison with green LED, Registration in progress. OFF – No fault present.

STATUS MESSAGE FAULT

FAULT (red)

Upon completion of the registration process, the IGSMHS transmits a registration message and receives a registration validation indicating that the account is now enabled. Wait for the "Registration Success" message to appear, regardless of which registration method used. You can register the IGSMHS by one of the following methods: " " " " Through the AlarmNet Direct website Through use of the Tamper Switch Through use of a 7720P Programming Tool By phone

Register through the AlarmNet Direct Website The IGSMHS can be registered through the AlarmNet Direct Website. To program the module via the website (if you are already signed up for this service), go to: https://services.alarmnet.com/AlarmNetDirect/ Log in and follow the on-screen prompts. If you are not signed up for this service, click on “Dealer Signup” from the login screen to gain access to the Honeywell web-based programming. Dealer Sign-Up Direct Link: https://services.alarmnet.com/AlarmnetDirectP_SignUp/ You will be instructed how to proceed upon completing the sign-up form. Only one sign-up per dealer is required. Once an initial user is established, additional logins may be created by that user. NOTE: Central Stations sign up by contacting AlarmNet Administration at 800-222-6525 option3. Please have the following information available when programming the device: " Primary City ID (two-digit number) 4-1

IGSMHS Installation and Setup Guide " Primary Central Station ID (two-digit hexadecimal number) " Primary Subscriber ID (four-digit number) " MAC ID and MAC CRC number (located on outside of box and on label inside module) of the device you are installing. Once module is registered, you may log out of the AlarmNet Direct website. Register using the Tamper Switch Initiate the registration sequence by clicking the Tamper Switch three times. You can monitor the registration process by viewing the Status Display. The Message (yellow) LED and the Status (green) LED will blink slowly in unison while registration is in progress. Once the registration has been completed successfully, the IGSMHS enters normal operating mode; the Status (green) LED goes out and the Message (yellow) LED is lit to indicate that the Power On / Reset message is waiting to be sent. This message will appear at the receiving station as “E339 C08xx”, where “xx” is the ECP device address. The description may read “Trouble – Exp. Mod. Reset”. If registration is not validated within 90 seconds, the IGSMHS times out, and the (green) LED will be lit (solid). The Power On / Reset message will be sent in ADEMCO High-Speed format if the module is programmed for zone trigger, 4204 or 2x4204 modes. If repeated registration attempts time out, check your Internet connection and RSSI level, and verify that IGSMHS account information has been entered correctly. Register using the Programming Tool The interactive registration feature allows the installer to register the IGSMHS through a series of keyboard commands on the 7720P Programming Tool. This method of registration lets the installer monitor the registration process. Registering … Once the installation is complete, press the [Shift] and the up arrow [$] key on the 7720P. The registration message is sent and the unit waits for the acknowledgment. If this is a new installation and the city, central station, and customer numbers have been correctly entered, the IGSMHS is registered and this message is displayed. The IGSMHS is now in full service and available for alarm reporting to the central station.

Registration SUCCESS

Possible Errors Registration BAD Timed Out Registration BAD Pri Sub ID BAD Displayed if no response to the registration request is received. Indicates the city, central station, or customer number for the labeled account(s) is not accepted. The ID information was either entered incorrectly, or the central station failed to pre-authorize programmed ID numbers with AlarmNet customer service. Indicates the city, central station, or customer number for the Secondary account is not accepted. The ID information was either entered incorrectly, or the central station failed to pre-authorize programmed ID numbers with AlarmNet customer service.

Registration BAD 2nd Sub ID BAD

4-2

Section 4: Registration Registration BAD Pri&Sec – IDs BAD Registration BAD Pri ID – Need PIN Displayed when both primary and secondary subscriber IDs are invalid. Displayed if this is a repair / replacement, or an error was made in programming the Primary account information of IGSMHS for an existing account. This prompt appears for 2 seconds. See the Replacing an existing module section below for further displays. This prompt is displayed if this is a repair / replacement, or an error was made in programming the Secondary account information of IGSMHS for an existing account. This prompt appears for 2 seconds. See the Replacing an existing module section below for further displays. This prompt is displayed if this is a repair / replacement, or an error was made in programming BOTH the Primary and Secondary account information of IGSMHS for an existing account. This prompt appears for 2 seconds. See the Replacing an existing module section below for further displays.

Registration BAD 2nd ID – Need PIN

Registration BAD Pri&2nd – Need PIN

Replacing an existing module using the programming tool Enter PIN# This prompt appears after pressing the [Shift} and down arrow [#] on the 7720P. NOTE: If it is necessary to exit registration mode, press ESC from the 7720P programming tool. Enter a 4-digit alphanumeric PIN number provided by your central station, your dealer or an authorized AlarmNet representative. Press the [Enter] key. Registering … Registration SUCCESS Registration BAD The registration message is sent and the unit waits for acknowledgement. If the PIN is valid, the new IGSMHS is registered and the old unit unregistered. Additionally, AlarmNet sends a substitution alarm to the central station. If you entered an invalid PIN, the appropriate message is displayed depending on which account number is being replaced (see above for exact wording). The registration process is repeated. NOTE: Each attempt causes a substitution alarm to be sent to the central station.

Register by Phone You can register the module by calling the AlarmNet Technical Assistance Center (TAC) at 1-800-222-6525. You will need the following information: " MAC number (found on the label). " Subscriber information (provided by the central station), including a city code, CSID, and a subscriber ID. " When instructed to do so, triple-click the tamper switch to complete the registration. 4-3

IGSMHS Installation and Setup Guide

4-4

S E C T I O N

5

Programmer Keyboard Commands
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

Programmer keyboard commands can be used to quickly view your connectivity settings and options. Most commands require you to press the [Shift] key and then the designated command key. (See the keys designated in red on the 7720P Programming Tool.) [A] 7845iGSMHS x.x.xx mm/dd/yy
Software Revision "x.x.xx" indicates the installed software Revision. Mm/dd/yy indicates month, day and year of the revision. " If the IP & GSM comm path is selected, the sign-on will be “7845iGSMHS” " If the IP comm path is selected, the sign-on will be “7845iHS” " If the GSM comm path is selected, the sign-on will be “7845GSMHS”

Module Identification Displays
[B] MAC xxxxxxxxxxxx MAC CRC yyyy
MAC Address “xxxxxxxxxxxx” indicates the IGSMHS's unique identification number. "yyyy" indicates the MAC CRC number. This number is found on the label on the module, and a label on the box. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. SCID Display Displays the identification number assigned to the SIM card (SCID) in this device. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. IMEI Display Displays the identification number assigned to the IGSMHS module in this device. Press the [Space] key to get the MAC Address. Press the backspace [BS] key to go to the previous field. Time Retrieves the current date and time from the AlarmNet network in Greenwich Mean Time (GMT). This display confirms that the module is in sync with network. Network Diagnostics Display Indicates whether the device has detected a physical connection to the internet. Press the [Space] key to go to the next field. IP Information Display Displays the IP address assigned to this device. Press the [Space] key to go to the next field.

NOTE: The SCID and IMEI are only displayed if the Comm Path Choice is “IP&GSM” or “GSM”.

SCID xxxxx xxxxx xxxxx xxxxx

IMEI

xxxxxxxx xxxxxx x

[C]

Mon 01 Jan 2011 05:48:39 am

NOTE: The Physical Link and NIC IP Address is only displayed if the Comm Path Choice is “IP&GSM” or “IP”.

[D]

Physical Link Good/Bad

NIC IP Address xxx.xxx.xxx.xxx

5-1

IGSMHS Installation and Setup Guide
NOTE: The Subnet Mask, Gateway IP Addr, DSN Serv IP and DHCP are only displayed if the Comm Path Choice is “IP&GSM” or “IP”.

Subnet Mask xxx.xxx.xxx.xxx

Displays the 32-bit address mask used to indicate the portion (bits) of the IP address that is being used for the subnet address. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Displays the IP address assigned to the Gateway. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Displays the IP address assigned to the DNS (Domain Name System) server. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Performs a self-test of the AES encryption algorithm. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. DHCP (Dynamic Host Configuration Protocol) indicates server is performing satisfactorily. Press the [Space] key to go to the Physical Link display.

Gateway IP Addr xxx.xxx.xxx.xxx DNS Serv IP xxx.xxx.xxx.xxx

Encryption Test AES Passed! DHCP OK

GSM Status Displays
NOTE: The Status Displays are available only if the Comm Path Choice is “IP&GSM” or “GSM”.

[E]

PriRSSI GPRS REG -xxxdbm x x

GSM Status Display Screen 1 PriRSSI – Primary Site RSSI level in dBm. GPRS – GPRS Service availability where “x” can be: “Y” if GPRS is available “N” if GPRS is Not available REG – Registration status from radio module where “x” can be: N – Not Registered H – Registered Home S – Searching D – Registration Denied R – Registered Roaming ? – Unknown Registration State Press the [Space] key to go to the next screen. Press the backspace [BS] key to go to the last screen. GSM Status Display Screen 2 Cntry – Country Code Netw – Network Code LAC – Local area code Press the [Space] key to get to the next screen. Press the backspace [BS] key to go to the previous field. GSM Status Display Screen 3 Cell – Base Station ID BaseSt – Base Station Antenna Sector Chan – Control Channel in use Press the [Space] key to go to the next screen. Press the backspace [BS] key to go to the previous field.

Cntry Netw LAC xxx xxx xxxxx

Cell BaseSt Chan xxxxx x xxx

5-2

Section 5: Programmer Keyboard Commands Second Site RSSI -xxxdbm
GSM Status Display Screen 4 Secondary GSM Site RSSI level in dBm. Press the [Space] key to go to the GSM Status Display Screen 1. Press the backspace [BS] key to go to the previous field. Run Network Diagnostic Test Performs a set of network diagnostics that tests the integrity of the links between the IGSMHS and the various connection points (Redirs) to AlarmNet. Refer to Section 6: Network Diagnostics.

NOTE: The Network Diagnostic Test is available only if the Comm Path Choice is “IP&GSM” or “IP”.

[F]

Testing Gateway Redir 1

System Status Displays
[S] ECP 67 TmPB Flt xx 5 ++ OK
ECP Mode Displays the zone and system fault status. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. 4204 Emulation Mode Displays the zone and system fault status. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Two-4204 Emulation Mode Displays the zone and system fault status. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Zone Trigger Mode The status of the IGSMHS can be viewed on the 7720P. The status display includes: " Zone input status (1234567) - the numbers 1-7 represent the 7 mappings of the zone input, and follow Honeywell's ADEMCO highspeed format codes: 1 = New Event 5 = Normal X = Not Enabled " Tm – Tamper status follows high-speed format codes above. " P – Represents line voltage as follows: + = Power line voltage OK – = Power line voltage bad and reported V = Power line voltage bad, not reported (reporting window not expired) ^ = Power voltage restored, not yet reported " B – Represents battery condition as follows: + = Battery voltage acceptable – = Battery voltage below 5.7V ±5% " Flt – Represents radio faults: OK = Normal ; No fault I – No network connectivity over IP and fault time has expired i – No network connectivity over IP and fault time has NOT yet expired. G = No network connectivity over GSM and fault time has expired. g = No network connectivity over GSM and fault time has NOT yet expired. NOTE: The 7720P will not operate if the power line voltage is removed.

1234 67 TmPB Flt 5555 xx 5 ++ OK

12345678 TmPB Flt 5555555x 5 ++ OK

1234567 TmPB Flt 5555555 5 ++ OK

5-3

IGSMHS Installation and Setup Guide Bat NLd: x.xxV Bat Ld: x.xxV
Battery Voltage Display The voltage levels of the battery connected to the IGSMHS can be viewed on the 7720P. The first line of the display shows the voltage level of the battery with no load. The second line of the display shows loaded battery voltage. An asterisk (*) next to the voltage indicates that this is below the accepted level. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Battery Charger Status Display The status of the battery charger circuit of the IGSMHS can be viewed on the 7720P. The status is either OK or NOT OK. Press the [Space] key to go to the next field. Press the backspace [BS] key to go to the previous field. Line Voltage Display The line voltage of the IGSMHS can be viewed on the 7720P. An asterisk (*) next to the voltage indicates that this is below the accepted level. Press the [Space] key to go back to the System Status Display. Press the backspace [BS] key to go to the previous field. Test Alarm Sends a Test alarm to AlarmNet. Functional for a registered IGSMHS only. If the device is not registered, a message is displayed indicating that the command cannot be executed. Reset the IGSMHS. Pressing [N] returns to diagnostic mode (blank screen = enter next command or escape). Pressing [Y] resets the module (blank screen = reset complete). Registration Registers a programmed IGSMHS with AlarmNet. Registration with PIN for Replacement Module Registers a replacement IGSMHS with AlarmNet, once programmed, using the existing PIN #. Force Upload of Configuration File to Server Pressing [Y] will force the device to upload its entire configuration file to the server. Pressing [N] cancels the operation. NOTE: If the internet is not available, and the IGSMHS module is not initialized when you enter this command, the following screen will be displayed: Cannot Upload Try Later! _ Wait for the RSSI LEDs to light, indicating the IGSMHS module has completed its initialization, and try again.

Battery Charger OK

Line Voltage xx.xxV

[T]

Test Msg Sent

[X]

Reset CPU Y/N

[$]
(UP arrow)

Registering …

[#]
(DN arrow)

Enter PIN#

[0]

Force Server Update? Y/N

[ENT ER]

Strt Prog Mode? Y/N_

Enter Program Mode Press [Y] to enter program mode; otherwise, press [N].

5-4

S E C T I O N

6

Network Diagnostics
" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

Running Network Diagnostics on the IGSMHS
The network diagnostic process tests the integrity of the links between the IGSMHS and the various connection points of AlarmNet Control that are known as "Redirects" (Redirs or RDR). To initiate the network diagnostics, press the [F] key on the 7720P Programming Tool. NOTES: " The Network Diagnostics is available only if the Comm Path Choice is “IP&GSM” or “IP”. " The test is performed ONLY if a physical link is detected. If no physical link is detected, the test is aborted and the following is displayed: NO PHYSICAL LINK

If a physical link is detected, the diagnostics are performed. The following shows the progression of the test: Testing Redir 1 The first step of the test traces the connection to Redir 1 at AlarmNet Control. A successful trace to Redir 1 is indicated here. See below for possible errors that may occur at this stage of testing. The service at AlarmNet Control on Redir 1 is functioning. See below for possible errors that may occur at this stage of testing. The first step of the test traces the connection to Redir 2 at AlarmNet Control. The service at AlarmNet Control on Redir 2 is functioning. See below for possible errors that may occur at this stage of testing. The first step of the test traces the connection to Redir 3 at AlarmNet Control. The service at AlarmNet Control on Redir 3 is functioning. See below for possible errors that may occur at this stage of testing. A summary of the tests is displayed after Redir 3 is tested. The example shows that the tests of all three connection points, or Redirs, were successful. If an error occurred at any point, the summary will display "FAIL" under the faulty Redir.

Testing Redir 2 Reached Gateway Redir 1 Service OK Testing Redir 2

Redir 2 Service OK Testing Redir 3

Redir 3 Service OK RDR1 RDR2 RDR3 OK OK OK

6-1

IGSMHS Installation and Setup Guide

Possible Errors Running Network Diagnostics
Errors may occur either while tracing the connection to a given Redir or while testing the service at a given Redir. The following list highlights the most common errors. Please contact the AlarmNet Technical Assistance Center (TAC) for help regarding any errors NOT listed below: Possible Errors Testing Redir x FAIL before Gtwy Testing Redir x FAIL at Gtwy Testing Redir x FAIL at Pvt IP Testing Redir x FAIL on IP Addr Redir x ERR:Proxy 18 While tracing the connection to Redir x, the trace fails before ever reaching the local gateway (router). While tracing the connection to Redir x, the trace fails after reaching the local gateway (router). While tracing the connection to Redir x, the trace fails after reaching the private IP. While tracing the connection to Redir x, the trace fails after reaching the public IP. After a successful trace to Redir x, the test of the network service timed out without a response.

6-2

Note: If all LEDs FAST BLINK in unison with the RSSI LEDs this indicates a Hardware Error.
MODULE'S RECEIVED SIGNAL STRENGTH (RSSI) When the Mode Switch is NOT depressed, LED 1 will illuminate red. The remaining LEDs indicate RSSI (Received Signal Strength). MODULE'S OPERATION MODE When the Mode Switch IS depressed, LED 1 will be OFF. LEDs 2 and 3 indicate the module's communication mode with the control panel. Mode ECP Zone 4204 2 - 4204 MODULE'S STATUS ON OFF ON OFF LED 2 (yellow) LED 3 (yellow) OFF OFF ON ON

GRN

ON – NOT registered with AlarmNet. OFF – Registered with AlarmNet. FAST BLINK – Download session with Compass in progress. SLOW BLINK – In unison with yellow LED, registration in progress.

YEL

ON – Message transmission pending. QUICK PERIODIC BLINK – Normal. FAST BLINK – Message waiting for network ACK. SLOW BLINK – Idle power abnormal. SLOW BLINK – In unison with green LED, registratration in progress.

RED

ON – No contact with network. OFF – Normal. SLOW BLINK – Loss of communication with the panel (ECP fault). FAST BLINK – No network contact AND loss of communication with the panel.

RSSI / MODE AND STATUS LEDs
LED 4 (green) ON - Connected to Internet. OFF - Not connected to Internet.

When the Mode Switch IS depressed, LED 1 will be OFF. LEDs 4, 5, and 6 indicate the module's Status. LED 5 (green) ON - GPRS service available. OFF - No GPRS service available FAST BLINK - GPRS in use. LED 6 (green) ON - Module registered, no second site available. OFF - Module not registered with network carrier. SLOW BLINK - Module registered, second site available, and low signal strength.

Appendix A: Summary of LED Operation

PRIMARY POWER: 9 - 16.5 VAC CURRENT: BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX

IC: YYYYYYYYYY

+ BLACK MODE SWITCH RED
IBS GPRS

RSSI

M1 M0

NORMAL BLINK - Module registered, second site available, acceptable signal strength. FAST BLINK - Module registered, second site available, excellent signal strength.

TB 1 1 2 3 4 5 6 7 8 9 10 11

TAMPER SWITCH

1

Ethernet Link/Activity GREEN Link Speed GREEN Network Collision YELLOW

ON – Ethernet Link detected. OFF – No link detected. FAST BLINK – Transmitting/Receiving Data. ON – 100 MB/S link to Internet. OFF – 10 MB/S link to Internet. BLINKING – Network collision detected. OFF – Normal.

" " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " " "

Appendices

A-1

IGSMHS Installation and Setup Guide

A-2

Appendix B: Central Station Messages
Alarm Condition
Power On / Reset Tamper (Compromise Indication) Power Loss Low Battery Battery Charger Failure ECP Supervision (Compromise Indication) Communication Path Supervision Telco (Compromise Indication) Open / Close Test 5555 5555 9

ECP Mode Alarm Code
E339 C08xx* E341 C08xx* E337 C08xx* E338 C08xx* E314 C08xx* E355 C0000 R341 C08xx* R337 C08xx* R338 C08xx* R314 C08xx* R355 C0000 R350 C0951

Zone and 4204 Modes Alarm Code
5551 5555 6 5555 5551 7 1555 5555 6 5155 5555 6 5155 5555 1 5555 5515 5 5555 5553 7 3555 5555 6 5355 5555 6 5355 5555 1 5555 5535 5 5555 5553 5 5555 5155 6 2 sent in selected zone 5555 5555 9 5555 5355 6 4 sent in selected zone

Restore Code

Restore Code

Specific to RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.)

UL
xxxxxx

The information provided in this section for the VISTA-10P, 15P, and 20P series control panels has not been evaluated with this communications module. E353 C08xx* ! R353 C08xx* ‡

Communicator Trouble (low battery, ECP buss, network) (Possible Compromise Indication) Radio Fault

E353 0 1xx* ‡

R353 0 1xx* ‡

Specific to COMMERCIAL Control Panels (Such as the VISTA-128 / 250 series.) Communicator Trouble (low battery, ECP buss, network) (Possible Compromise Indication) Radio Loss of Signal (Possible Compromise Indication) Radio Fault (low battery, tamper, ECP Buss) AlarmNet Messages Communication failure. (Possible Compromise Indication) Authorized Radio Substitution Unauthorized Radio Substitution Attempt Service Termination 5555 1555 6 00D0 010C 0 00D0 010E 0 00D0 020E 0 5555 3555 6 E333 C08xx* ‡ R333 C08xx* ‡

E357 0 8xx* † E333 0 8xx* ‡

R357 0 8xx* ‡ or R380 0 8xx* ‡ R333 0 8xx* ‡

* xx = IGSMHS Device Address
† = Message is sent by dialer only. ‡ = Message is sent by dialer and radio. ! = Message is sent by dialer only, or dialer and radio, depending on failure.

B-1

IGSMHS Installation and Setup Guide

B-2

IGSMHS Installation and Setup Guide

Appendix C: IP Downloading
General Information
The communications module can be used to upload or download data to Honeywell's VISTA and LYNXR-I control panels. This enables local site maintenance that is independent of the central station. In addition, it enables modification to sites globally via the internet. Some control panels support uploading/downloading of data using the ECP bus, and some must use the Direct Wire method. For control panels that support uploading/downloading of data (such as; VISTA-20P, LYNXR-I) via the ECP bus, no further connections to the communications module is necessary. For control panels that do not support uploading/downloading of data via the ECP bus(such as; VISTA-128BP and FBP), a Direct Wire connection using a trigger cable is used.

UL
Direct Wire Setup

Downloading may only be performed if a technician is at the site.

To utilize a Direct Wire connection, this option must be enabled (Direct Wire Y/N) in the control panel's programming, and the ECP device address for the communications module must be entered as a keypad. Additionally, the communications module must be connected to the control panel by a cable as shown below. NOTES: " For Direct Wire downloading on Commercial Fire panels (such as; VISTA-128FBP, FA1700C), set program field 3"19 to [1]. This enables J2 for RS-232 serial data. " This feature is not available if the communications device is set for zone trigger mode.
VISTA-128BP/250BP FA1660C J8 CONNECTOR
1 2 3 4
NU

5

6

7

8

9

COMMUNICATIONS MODULE
PROGRAMMER PORT WHITE BLUE K4668WH RJ 11 CABLE
TB 1
1 2 3 4 5 6 7 8 9 10 11
GSM GPPS WEB MODE 2 MODE 1 RSSI

OUT 5 (GREEN)

OUT 6 (BROWN)

(BLUE)

(RED)

PRINTER DTR

GROUND

GROUND

GROUND (BLACK)

IN 3 (YELLOW)

IN 2 (VIOLET)

(GREY)

4142 TR CABLE

PARTS SUPPLIED WITH DOWNLOADER KIT P/N VBPCOMKIT

iGSMBR-017-V1

C-1

IGSMHS Installation and Setup Guide
VISTA-128FBP/250FBP FA1670C/FA1700C J2 CONNECTOR
1 2 3 4 5 6 7 8 9 PROGRAMMER PORT
4100SM
TO AUX PWR 1 OUTPUT + (TO TERM 11) - (TO TERM 12)
8 7 6 5 4

COMMUNICATIONS MODULE

(BROWN)

(GREEN)

(WHITE)

(GRAY)

OUT 1 (YELLOW)

(VIOLET)

(BLACK)

(BLUE)

(RED)

+ PWR - (GND) RXD not used not used TXD not used not used
TB 1
1 2 3 4 5 6 7 8 9 10 11
GSM GPPS WEB MODE 2 MODE 1 RSSI

GROUND

INPUT 1

OUT 6

OUT 4

OUT 7

OUT 3

OUT 2

OUT 5

4142 TR CABLE

3 2 1

RED BLUE WHITE

PARTS SUPPLIED WITH DOWNLOADER KIT P/N VFBPCOMKIT K14394LF 25-PIN TO RJ11 CABLE

Figure C-1. Cable Connections for IP Downloading

C-2

iGSMBR-018-V1

Appendix D: Glossary
AES DACT DHCP Advanced Encryption Standard Digital Automated Communications Terminal Dynamic Host Configuration Protocol, which provides a mechanism for allocating IP addresses dynamically so that addresses can be reused when hosts no longer need them. Domain Name System, which is a distributed hierarchical naming system used to resolve domain names (e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1.). Digital Subscriber Line. Enhanced Console Protocol, which is a proprietary bus used in Honeywell control panels to communicate with keypads and peripheral devices. It uses four wires; power, ground, data in, data out. A gateway (sometimes called a router) is a computer and / or software used to connect two or more networks (including incompatible networks) and translates information from one network to the other. The Gateway IP address is the IP address for the gateway. General Packet Radio Service. Global System for Mobile communications, which is an international standard for digital mobile phone systems used for cellular communication. International Mobile Equipment Identity number. Internet Protocol. A unique number consisting of four parts separated by periods (for example: 204.17.29.11). An IP Address can be fixed or "static", or "dynamic," where the IP Address is assigned via DHCP at every startup. Integrated Services Digital Network. Internet Service Provider. Local Area Network. Media Access Code, this is a unique address assigned to every network communications device. For the communications module it is located on the module label, and on the box. A Subnet is a portion of a network that shares a network address with other portions of the network, and is distinguished by a subnet number. The Subnet Mask is a 32-bit address mask used in IP to indicate the bits of an IP address that are being used for the subnet address. Transmission Control Protocol / Internet protocol.

DNS

DSL ECP

Gateway IP Address

GPRS GSM

IMEI IP IP Address

ISDN ISP LAN MAC ID

Subnet Mask

TCP / IP

D-1

IGSMHS Installation and Setup Guide

D-2

NOTES:

NOTES:

NOTES:

NOTES:

IGSMHS Summary of Connections
INTERNAL ANTENNA

STATUS LED MESSAGE LED FAULT LED
FOR EXTERNAL ANTENNA 50 OHM MMCX ONLY

7720P PROGRAMMER PORT/ PANEL DOWNLOAD PORT TB 1 1 2 3 4 5 6 7 8 9 10 11 1

PRIMARY POWER: 9 - 16.5 VAC CURRENT: 900mA PEAK, 70mA STANDBY BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX

IC: YYYYYYYYYY

AC 1 AC 2 NOT USED or 12V DC IN GND ZONE INPUT Z1/Z2 or ECP INPUT ZONE INPUT Z3 or ECP OUTPUT ZONE INPUT Z4 or NOT USED ZONE INPUT Z5 or NOT USED ZONE INPUT Z6 or NOT USED ZONE INPUT Z7 or NOT USED OPEN COLLECTOR FAULT OUTPUT MOUNTING HOLE CONNECTOR FOR USE WITH DCID ONLY

BLACK

RED

RSSI / MODE AND STATUS LEDs MOUNTING HOLE (UNDER BATTERY) BATTERY CLIP

GPRS

RSSI

IBS

M1 M0

BLK RED

BATTERY

SCREW J1 BATTERY CONNECTOR RJ45 ETHERNET PORT NETWORK CONNECTIVITY LED DISPLAY MODE AND STATUS INDICATOR SWITCH

TAMPER SWITCH

7845i-GSM-015-V0

NOTE: All circuits are supervised and all circuits are power limited except the battery.

TB1 Wiring for IGSMHS Cellular Communicator
TB1 1 2 3 4 5 6 7 8 9 10 11 ECP Mode AC 1 AC 2 ECP V+ (RED) GND (BLK) ECP IN (YEL) ECP OUT (GRN) NOT USED NOT USED Z6 Z7 FLT OUT Zone Trigger Mode AC 1 AC 2 NOT USED GND (BLK) Z1 / Z2 Z3 Z4 Z5 Z6 Z7 FLT OUT 4204 Mode AC 1 AC 2 ECP V+ (RED) GND (BLK) ECP IN (YEL) ECP OUT (GRN) NOT USED NOT USED Z6 Z7 FLT OUT 2 x 4204 Mode AC 1 AC 2 ECP V (RED)+ GND (BLK) ECP IN (YEL) ECP OUT (GRN) NOT USED NOT USED NOT USED NOT USED FLT OUT

FEDERAL COMMUNICATIONS COMMISSION (FCC) STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment. CLASS B DIGITAL DEVICE STATEMENT NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: " Reorient or relocate the receiving antenna. " Increase the separation between the equipment and receiver. " Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. " Consult the dealer or an experienced radio/TV technician for help.

DOCUMENTATION AND ONLINE SUPPORT For the latest documentation and online support information, please go to: http://www.security.honeywell.com/hsc/resources/MyWebTech/ WARRANTY For the latest warranty information, please go to: http://www.security.honeywell.com/hsc/resources/wa/

2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright % 2010 Honeywell International Inc. www.security.honeywell.com

Ê800-08077\Š
800-08077 12//10 Rev. B


Uploaded