Honeywell SixSMOKE Install Guide
Related Products
Related Categories
Document Transcript
SiXTM Series
SiXSMOKE / SiXSMOKE-CN
Installation Instructions
This wireless smoke/heat detector
is intended for use with Honeywell
controls that support SiX™ series
devices.
PULL
TO T
NEC
CON
To remove the mounting bracket,
turn the top of the detector 15
degrees counterclockwise and
separate the mounting bracket and
top cover.
PULL
TO
NEC
CON
T
SiXSMOKE /
SiXSMOKE-CN
Open
Programming Mode > Zones >
Add New > Serial Number
Enroll
This device can be enrolled and programmed either
before or after installation.
1. Set the Lyric Controller in Programming Mode and go
to Zone Programming. Select Add New and then
Serial Number.
2. Remove the battery tabs to activate the device and
begin the enrollment process.
3. The Green LED flashes rapidly during enrollment (up
to about 20 seconds*).
1
Serial Number
Loop Number
Zone Description 1
Zone Description 2
Device Type
Response Type
Alarm Report
Chime
Panic
PULL
TO T
NEC
CON
Supervision
Home
10
20
30
ON for 3 seconds
5
Trigger the device
again to complete
enrollment
6
Press SAVE
Enroll
After enrolling, update the detector firmware (via the
Controller) to ensure the latest version is used. See the
Controller’s instructions.
NOTE: Once enrolled in a system, the detector cannot be used
with another controller until it is removed from the current
controller. See the Controller’s instructions for details.
Fault device features to learn the device Services in the controller:
-
The LED
Flashes for
up to about
20 seconds
4 The Green LED is
Consult the Controller’s instructions to program the device in the system.
-
PULL
TO T
NEC
CON
0
Program
-
2
45
• The detector sends its unique MAC ID (Serial
Number) and Services information to the controller.
• The controller registers the device and displays the
transmitter data on screen.
4. Enrollment is confirmed when the Green LED is ON
for 3 seconds and the device chirps.
5. Repeat the process, pressing the Test Switch to start
enrollment, and select Heat Sensor Device type to
enroll the heat sensor. The device will enroll the
same MAC ID in another Zone.
6. Press SAVE.
The device can also be manually enrolled. See the
Controller’s Programming Guide for details.
PULL
TO T
NEC
CON
3
*NOTE: Enrollment time varies depending on the signal
strength between the device and the controller.
If the detector is not successfully enrolled during the
enrollment period, the LED turns off and the device
powers down. Activate the tamper or press the Test
switch to restart the enrollment process.
PULL
TO CT
NE
CON
Smoke and Heat detector - Reports to panel:
• Smoke Alarm when smoke is detected
• Temperature Alarm when temperature of 135° F (57° C) or greater OR when there is a
temperature increase of 15° F (8.33° C) or greater within one minute
Percentage of obscuration (smoke or dirt in the detector)
Cover tamper: The 10 minute tamper timer is reset every time the tamper switch is closed and
opened or the detector cover is opened.
Supervision – 200 second check-in compatible
NOTE: If programmed in
the panel to operate in
one-go-all-go mode, all
smoke detectors
programmed as one-goall-go in the system will
sound on alarm.
Mount
Refer to the System Smoke Detectors Application Guide (P/N
SPAG9101) and the Limitations of Fire Alarm Systems (P/N
800-15144) for detailed information on detector spacing,
placement zoning and special applications. Copies of this
document are available on https://mywebtech.honeywell.com/.
NOTE: Before mounting the detector permanently, conduct
Go/No Go tests (see control’s instructions) to verify adequate
signal strength and adjust the device location and orientation as
necessary.
The detector can be mounted on the ceiling or on the wall (if
local ordinances permit). Select a location and mount using the
included mounting hardware.
Mount
Test
The detector should be tested immediately after installation
and at least once a year.
Recommended: To prevent unwanted alarms, notify the
Central Station that the smoke detector system is undergoing
maintenance before testing begins.
Press for 3 seconds
Test Mode can be activated remotely from the Controller (see
the Controller’s manual), or on-site by pressing the test switch.
Tests and testing methods:
- Test Switch –
• press and release to check circuitry functionality;
• press and hold for 3 seconds to test the sounder (the
device will emit a temporal tone).
- Direct Heat Test (hair dryer)
- Smoke Entry Test (canned smoke*)
- Signal Strength (signal strength information is sent with
every communication to the panel.)
- Programmed Services [Loops].
≥ 12” (30.48 cm)
AT
HE
Follow
instructions
on the can
*Use UL/ANSI
Approved
canned smoke.
E
OK
SM
Test
LED
LEDs and Sounder
The SIXSMOKE / SiXSMOKE-CN has one bi-colored LED and an 85dB
sounder. Refer to the following table for operation of these features.
LED and Sounder Indication Table
R = Red
= Slow Flash
= ON
G = Green
R
R
= Rapid Flash
G
G
~20 sec,
G
3 sec
G
3 sec
= Chirp
= Temporal Tone
Sounder
Status
Power Up – Enrollment
R
G
1 x every 10 sec
G
Alternate
every 10 sec
Power Up – Device enrolled
Normal mode
1 x every 5 sec
Maintenance1
R
1 x every 1 sec
Test Alarm2a, 2b
R
1 x every 4 sec
Heat Alarm3
R
1 x every 1 sec
Smoke Alarm
R
1 x every 45 sec
Low Battery4y
10 min
Test mode is activated by the test switch or from
the panel. The detector is functioning properly
(within proper sensitivity).
2b
If Test mode is activated and the LED and
Sounder do not function, check for maintenance
or trouble conditions.
3
4
The Heat alarm triggers when the device senses
heat of 135° F (57° C) or greater, or the
temperature rises 15° F (8.33° C) or more within 1
minute.
Recommended: Replace Battery before the
device starts chirping. The device starts chirping
after 7 days and continues until the batteries are
replaced or die. To quiet the sounder for 5
minutes, press the Test Switch (does not work
when set in one-go-all-go mode). See Battery
Replacement section.
To silence the detector:
Press the test switch or disarm the
system at the controller. The detector
sounds again after 5 minutes if the
alarm condition continues. When
programmed in one-go-all-go mode, the
detector can only be silenced from the
controller.
Tamper Activated
Maintenance
The Maintenance type is reported by the
controller. See the Maintenance Section below for
details.
2a
Processing Controller queries
R
G
1
1
When testing, if the sensitivity is outside the proper range,
the detector will send a Trouble signal to the controller
through the Honeywell Interface module and the detector’s
red LED will flash every five seconds. The controller will
report a Low or High Maintenance message:
2
Low = Smoke head is dead and needs to be replaced.
High = Smoke head is dirty and needs to be cleaned.
Recommended: To prevent unwanted alarms, notify the
Central Station that the smoke detector system is
undergoing maintenance before cleaning the detector.
1. Twist the top cover clockwise to remove it from the
mounting plate.
2. Remove the batteries.
3. Wait at least 10 seconds to ensure the detector powers
down properly.
4. Turn the detector cover counterclockwise to remove it
and vacuum the cover.
5. Pull the screen sensing chamber out and vacuum to
clean it.
0
3
10
45
20
30
4
5
Maintenance
Wait for about
10 seconds
6. Reinsert the screen/sensing chamber and press
firmly to set it in place.
7. Reinsert the detector cover back over the
screen/sensing chamber and turn it clockwise until
it locks in place.
8. Reinsert the batteries.
9. Reattach the device to the mounting plate.
7
6
8
Maintenance (continued)
Battery Replacement
•
•
Reattach to the detector to the mounting plate.
5
Honeywell 466, Panasonic CR123A
Duracell DL123, Duracell DL123A
Twist the front cover counterclockwise
15 degrees and separate it from the mounting
bracket.
Remove both batteries and wait 10 seconds,
then insert two new batteries.
Recommended batteries:
- Honeywell 466
- Panasonic CR123A
- Duracell DL123 or DL123A
NOTE: Do not mix old and new batteries, battery
types or manufacturers.
•
1
2
3
0
10
45
~ 10
sec
30
4
Replace Batteries
BATTERY CAUTION: Risk of fire, explosion and burns. Do not recharge,
disassemble, heat above 212° F (100° C) or incinerate. Dispose of used batteries
properly. Keep away from children.
Specifications:
Approval Listings:
Batteries: Two 3V Lithium; Honeywell 466, Panasonic CR123A, Duracell DL 123 or DL 123A
RF Frequency: 2.4GHz
Tamper: Cover tamper
Operating Temperature: 0° to 35° C / 32° to 95° F
Relative Humidity: 95% max. (Agency Compliance – 93% max.), non-condensing
Maximum Spacing: 50ft x 50ft (refer to National Fire Alarm Code Standard NFPA 72 for
application requirements)
Dimensions: 13.46 cm Diameter x 4.19 cm Thick / 5.3 in. Diameter x 1.65 in. Thick
FCC / IC
ETL Listed – Conforms to UL 268 & UL 521
cETL Listed – Certified to ULC-S529 & ULC-S530
Other Standards:
NFPA 72
ANSI / SIA-CP-01
CSFM
RoHS
NOTE: Smoke detectors are not to be used
with detector guards unless the combination is
evaluated and found suitable for that purpose.
FEDERAL COMMUNICATIONS COMMISSION & INDUSTRY CANADA STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or
modifications could void the user's authority to operate the equipment.
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and RSS-210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS-210 des Industries Canada. Son fonctionnement est soumis aux conditions suivantes: (1) Cet
appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les interférences causant une reception indésirable.
RF EXPOSURE WARNING – The antenna(s) used for this device must be installed to provide a separation distance of at least 7.8 inches (20 cm)
from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter except in accordance with FCC multitransmitter product procedures.
MISE EN GARDE EXPOSITION AUX FREQUENCES RADIO: L'antenne (s) utilisée pour cet émetteur doit être installée à une distance de
séparation d'au moins 7,8 pouces (20 cm) de toutes les personnes.
For the latest documentation and online support information, please go to:
https://mywebtech.honeywell.com/
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa.
For patent information, see www.honeywell.com/patents
MyWebTech
Warranty
Patents
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED, FOR DETAILS REGARDING
LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
2014 Honeywell International Inc. Honeywell and is a registered trademark of Honeywell International Inc.
All other trademarks are the properties of their respective owners. All rights reserved.
www.honeywell.com/security
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Ê800-15961PŠ
800-21343 11/15 Rev A
- Uploaded