Honeywell Vista-128BPT/250BPT- Quick User Guide Part 1
Related Products
Related Categories
Document Transcript
Ê800
-
22781EŠ
800-
22781 10/16 Rev A
PART 1
TESTING THE SYSTEM
The TEST key puts your system in Burglary Walk Test mode, which
allows each burglary protection point to be checked for proper
operation.
Testing should be conducted weekly to ensure proper
operation
.
•
The keypad sounds a single beep ab
out every 30 seconds as a
reminder that the system is in the Test mode.
•
Alarm messages are not sent to your Central Station while Test
mode is on.
If a problem is experienced with any detection
point (no confirming
sounds, no display), call for service i
mmediately.
1.
Disarm
the system and close all protected windows, doors, etc.
The READY indicator
light should come on if all zones are intact
.
2.
Enter
test mode:
User Code
Master code
+
5
3.
Listen
. The external sounder
should sound for about 1 second
then turn off. If the sounder does not sound, CALL FOR
SERVICE. The
"Burg Walk Test Reduced RF Sens."
display
appears only on the keypad that started the test.
4.
Fault zones.
Open each protected doo
r and window in turn and
listen for three beeps from the keypad. Each faulted detection
point should appear on the display. The display clears when the
door or window is closed.
5. Walk in front of any interior motion detectors
(if
used) and listen
for three beeps. Each
detector should appear on the display when
it is activated. The display clears when no motion is detected.
Note that if wireless motion detectors
are used, there is a 3
-
minute delay between activations
to
conserve battery life.
6. When all detection
points have been checked and are intact
(closed), there should be no zone numbers displayed.
7.
Exit test mode:
User Code
+
1
SETTING THE DATE AND TIME
NOTE:
All partitions must be disarmed before date/time can be set.
You
can set the time and date by doing the following:
1.
+[#] + [6] [3]
(Master Code)
2. Press [
∗
] when the time
/date is displayed.
A cursor appears under the first digit of the hour.
To move cursor to the right, press [
∗
]. To move the cursor to the
left, press [#].
•
Enter the correct hour setting, then press [
∗
].
•
Enter the correct minute setting, then press
[
∗
].
•
Press
any key [0] –
[9] to change AM to PM, or PM to AM, then
press
[
∗
].
•
Enter the correct month using a 2
-digit setting, then press [
∗
].
•
Enter the correct day using a 2
-digit setting, then press [
∗
].
•
Enter the current year, then press [
∗
].
3. Press [
∗
] to exit the Real Time Clock Edit Mode.
SERVICING INFORMATION
Your local Honeywell dealer is the person best qualified to
service your alarm system. Arranging some kind of regular
service program with him is advisable. Your local Honeywell
dealer is:
Name:
Address:
Phone:
TROUBLE CONDI
TIONS
The word CHECK or TRBL on the keypad's display, accompanied by
a rapid "beeping" at the keypad, indicates a trouble condition in the
system.
To
silence
the beeping for these conditions
:
Press a valid
user
code +
1
To reset the trouble press a valid u
ser code + 1 a second time. In
the event the trouble will not clear
CALL FOR SERVICE
IMMEDIATELY.
Typical Trouble conditions include the following:
“Open Circuit Call for Service"
indicates a problem exists with your
keypad connection to the Control panel
.
“CHECK”
or
“TRBL
"
display accompanied by a display of one or
more zone descriptors indicate that a problem exists with those
zone(s). First, determine if the zone(s) displayed are intact (this
may include Fire and Waterflow type zones) and make them so
if
they are not. If the problem has been corrected, key an OFF
sequence (Code plus OFF) to clear the display. If the display
persists.
“CHECK”
or
“TRBL”
display accompanied by a display of “6XX,”
where XX = 01
-32, indicates a trouble on a supervised relay
(corresponding relay number 01
-32).
“CHECK”
or
“TRBL”
display accompanied by a display of “8XX,”
where XX = 00
-
30, indicates a trouble on a peripheral device
(connected to the panel’s keypad terminals).
“CHECK”
or
“TRBL”
display accompanied by a display o
f “9XX,”
where XX = 00
-
99, indicates a system trouble exists (dialers,
Notification Appliance Circuits, ground fault, etc.). These zones are
as follows:
970:
Bell 1 Output
975:
Dialer 2
971:
Bell 2 Output
988:
2
nd
RF Receiver
–
no
signals
972:
Earth G
round Fault
990:
1
st
RF Receiver
–
no
signals
973:
J2 Trigger Output
997:
Polling Loop Short
974:
Dialer 1
“SUPV”
display accompanied by a display of one or more zone
descriptors indicates a problem on fire supervisory zone(s). This
means that the oper
ation of the fire alarm system may be
compromised. First, determine if the zone(s) displayed are intact
and make them so if they are not. If the problem has been
corrected, key an OFF sequence (Code plus OFF) to clear the
“SUPV”
display. If the display per
sists.
A display of
"COMM. FAILURE
"
at the Keypad indicates that a
failure has occurred in the telephone communication portion of
your system.
A display of
"MODEM COMM"
indicates that the control is on-
line
with the central station's remote computer. The control will not
operate while on-
line.
A display of
“HSENS”
and a zone number indicates a smoke
detector wit
h a high sensitivity level, which may cause false alarms.
A display of
“LSENS”
and a zone number indicates a smoke
detector with a low sensitivity level. Detectors with a low sensitivity
might not detect a smoke condition.
Power Failure
If the message
"AC LOSS"
is displayed, the Keypad is operating on
battery power only. If only some lights are out on the premises,
check circuit breakers and fuses and reset or replace as necessary.
CALL FOR SERVICE IMM
EDIATELY
if AC power cannot be restored.
A display of
"SYSTEM LO BAT
"
, accompanied by a rapid "beeping"
at the Keypad indicates that a low system battery condition exists.
A display of
"LO BAT
"
and a zone descriptor, accompanied by a
once per
minute "beeping" at the Keypad indicates that a low
battery condition exists in the wireless transmitter displayed.
VISTA
TURBO
BURGLAR
SERIES
VISTA-
128BPT/VISTA
-128
BPT
SIA
/VISTA-
250BPT
Quick Guide
to User Functions
Full User Guide Available Online:
This Quick Guide describes the most frequently used features and functions of your system. For full
details of all user functions, please see the system’s User Guide located online at:
http://
www.security.honeywell.com/hsc/products
.
The
full version User Guide is also available from your installer upon request.
Congratulations on your ownership of a Honeywell Security System. This system provides:
•
Three forms of detection: burglary, fire and
emergency (see your installer for
which forms of detection are installed)
•
At least one keypad
which provides control of system and displays system status
•
Your system may also be programmed to automatically send alarm and status
mess
ages to a Central Monitoring Station
•
Various sensors for perimeter and interior
burglary detection
•
Smoke and/or combustion detectors designed
to provide early warning in case of fire.
SYSTEM BASICS
The following is a list of some of th
e most common features and
functions of your system:
•
Several modes of burglary detection
: Away
, Stay
, Instant, Maximum
.
•
Bypass feature lets authorized persons to
bypass
selected zones
while leaving the rest of the system armed.
•
Chime
mode alerts you to the opening of protected doors and
windows while the system is disarmed, if enabled.
•
Fire and carbon monoxide detection
are always active (if installed)
and an alarm sounds if a fire or carbon monoxide condition is
detected.
•
Panic keys (if programmed) let you manually initiate a fire and
personal alarms using the keypad.
•
User Code
security codes are used in conjunction with keypad
command to per
form system functions
.
•
Each user can be assigned a different security code, each with
different authority levels
.
•
The system sensing devices have been assigned to various “zones,”
which are specific areas of detection
(e.g., fro
nt door, storage room
window, etc.).
•
Zone numbers (points of detection) are displayed at the keypad
when an alarm or trouble condition occurs.
•
Partitions provide 8
independent areas of
detection
with each
partition containing a
group of zones that can be armed and
disarmed without affecting other zones.
•
Function keys may have been programmed to perform various
functions. Ask your installer if these keys are active.
•
A Scheduling feature can be programmed to automatically perf
orm
certain functions (e.g., arm the system) at a predetermined time
each day. See the full User Guide for details
.
ENTRY/EXIT DELAYS
•
Entry Delays
give you time to disarm the system when you enter
through the designated entrance door
.
•
You must disarm the system before the entry delay period ends, or
an alarm will occur (keypad beeps during the entry delay period,
reminding you to disarm the system).
•
Exit delay
gives you time after arming the system to leave through
the designated exit door(s) without setting off an alarm. If
programmed, a slow beeping
will sound during the exit delay period
until the last 10 seconds, which then changes to fast beeping
(alerting you to the end of exit delay). If
you cannot leave within this
delay time period, you should stop, disarm the system, and start
over to avoid a false alarm.
•
See your installer for your delay times
. See the full User Guide for
details on Exit Error alarms.
NOTES on BURGLARY
DETECTION
•
The system must be armed before the burglary detection
can
sense intrusions.
•
To arm your system, enter your security code followed by the
desired arming key.
•
To disarm the system, enter your security code then press the
OFF
key.
•
When an alarm
occurs, the keypad sounds
and displays the
zone(s) causing the alarm. The external sounder may also
sound.
•
If your system is connected to a Central Monitoring Station,
an alarm message is also sent (
may be delayed 30 seconds
to reduce false alarms).
•
To stop the alarm sounding, simply disarm the system.
•
Memory of Alarm:
When an alarm condition occurs, the
keypad displays the number(s) of the zone(s) that caused the
problem, and displays the type of alarm. Clear the Memory of
Alarm display by entering another “off” sequence.
IMPORTANT:
If you return to the premises and the main
burglary sounder is on, or the keypad beeps rapidly upon
entering the premises, it indicates that an alarm has oc
-
curred during your absence and an intruder may still be
on the premises.
LEAVE IMMEDIATELY and CONTACT THE
POLICE
from a nearby safe location.
NOTES on FIRE
and CO
DETECTION
•
Your fire alarm
system (if installed) is on 24 hours a day, for
cont
inuous
detection
. In the event of an emergency, the
smoke and heat detectors
sound their alarms, triggering a
loud, interrupted pulsed sound
from the Keypad(s) and any
external sounders.
•
You can silence the alarm at any time by pressing a valid
code +
OFF
.
•
Carbon monoxide (CO)
detectors, if installed, provide
continuous
detection
. If a high level of carbon monoxide is
detected, an interrupted pulsed alarm sound
occurs at the
keypads and the detector(s)
. Immediately move to a spot
where fresh air is available, preferably outdoors. From a safe
area, call your security service provider for further
instructions.
To silence the keypad sounding, press
a valid
code +
OFF. To silence the detector, see its instructions.
CHECKING
OPEN
ZONES
Checking Zones:
Before arming your system, all protected doors, windows and other
detection
zones must be closed or bypassed; otherwise the keypad display
s "Not Ready."
GOTO:
If the user is authorized, a keypad in one partition can be used to perform system
functions in the other partition by using the GOTO command
.
Mode
Press the
se keys...
W
hat happens
CHECK
ZONES
∗
•
Displays all faulted zones.
GOTO
User
code +
∗
+ partition
no.
:
1 through 8 = go to partition;
0 = return to home part
•
The keypad beeps to confirm the
partition change.
•
Keypads automatically return to thei
r
original partition after 2 minutes
with no
keypad activity.
ARMING THE SYSTEM
, CHIME MODE, and CONTROLLING DEVICES
Before arming, close all perimeter doors and windows and make sure the Ready to Arm
message is shown
. After arming, leave the premises through an entry/exit door
during the
exit delay period
and be sure the door is re
closed to avoid causing an alarm.
Mode
Press these keys...
When to use
an arming mode
and what happens
STAY
STAY Mode 1
User
code
+
3
+
1
STAY Mode 2
User
+
3
+
2
STAY Mode 3
User
code
+
3
+
3
for
3
Three beeps confirm.
•
Used when staying on premises, but someone
might use the entrance door later.
•
Arms the perimeter
(doors, doors, windows,
etc., no interior zone such as s motion
detectors)
.
•
An alarm sounds if a protected window or any
door is opened
.
When armed in STAY mode, the system wil
l
sound an alarm if a protected door or window is
opened, but you may otherwise move freely
throughout the premises.
Arrivals can enter through the entrance door
without causing an alarm, but must disarm the
system within the entry delay period or an alar
m
will occur.
The s
ystem provides three STAY modes STAY
mode 1, 2, and 3.
•
When activated, STAY modes 1 and 2
automatically bypass specific zones assigned
by your installer to each of the STAY modes.
•
STAY mode 3, when activated, automatically
bypasses a
ll zones assigned to STAY modes 1
AND
2.
NOTE:
If none of the zones in a partition are
assigned to Stay mode 2, then when the user
enters
[User Code]
+
[3]
(STAY), all zones
assigned to Stay mode 1 are automatically
bypassed.
The keypad beeps three times,
displays the
armed message, and indicates which STAY mode
(1, 2 or 3).
AWAY
User
code +
2
two beeps confirm
•
Used when nobody is
staying inside.
•
Arms the entire system (
interior and perimeter)
.
•
An alarm sounds if a protected window or any
door i
s opened, or if any movement is detected
inside.
MAXIMUM
User
code +
4
two beeps confirm
•
Used when leaving the premises for extended
periods (e.g., close of business for a holiday)
.
•
Same as Away mode,
except entry d
elay is off.
•
An alarm sounds
same as Away mode, and
sounds upon opening entry/exit doors.
QUICK
ARMING
#
+ arming key
If programmed, you can press the [#] key in place
of your security code when arming the system
CHIME
MODE
User Code
+
9
(enter again to
turn Chime mode
off)
•
Alerts you to the opening of a perimeter door or
window while the system is disarmed.
•
Three tones sound at the keypad whenever a
perimeter door or window is opened (interior
zones do not produce a tone
).
•
Pressing the READY key displays the open
zones.
CONTROL
OUTPUT
DEVICE
User Code
+
#
Enter 71 or 72.
Activate output device as programmed.
User Code
+
#
Enter 70.
Activate output device manually
User Code
+
#
Enter 77.
Activate output device or system event instantly
RANDOMIZE
OUTPUT
DEVICE
User Code
+
#
Enter 41
Randomize output devices set for random
schedules
User Code
+
#
Enter 42.
Randomize output devices set for random
schedules with activation times between 6 PM and
5 AM
Enter the
sequence used to
activate
random.
De
-
activate randomization
DISARMING THE SYSTEM and SILENCING ALARMS
The
1
OFF key is used to disarm
the system, silence alarm
and trouble sounds, and clear
memory of alarm displays
.
Mode
Press these keys...
What happens
DISARM
and
SILENCE
ALARMS
User Code
+
1
•
System is disarmed and alarm sounding silence
s
.
•
To clear the memory of alarm display (if present),
enter your
User Code
+
1
again.
BYPASSING ZONES
Use the
6
BYPASS
key when you want to arm your system with one or more zones
intentionally unprotected
.
Mode
Press these keys...
What happens
BYPASS
ZONES
User Code
+
6
+
3-digit
zone
numbers to be
bypassed
•
When finished, the key
pad will momentarily display a
"Bypass" message
for each bypassed zone number.
Wait for all bypassed zones to be displayed.
•
Arm the system as usual. When armed, the arming
message is displayed with “ZONE BYPASSED.”
•
Bypassed zon
es are unprotected and will not cause
an alarm if violated.
•
The system does
not allow fire zones to be bypassed.
•
Zones
may be
automatically unbypassed when the
system is disarmed.
PANIC KEYS
Your system may have been programmed to use special keys
or
key pairs
to manually
activate
emergency (panic) functions as follows:
This Function
Key(s)
∗
Sends This Signal
∗
∗
With This Sounding...
Silent Alarm
S
ilent alarm
N
o change to the keypad
(no sound).
Audible Alarm
Audible alarm
A loud, steady alarm at keypa
d(s) and
at any external sounders
.
Personal Alarm
Auxiliary alarm
Steady alarm sound at keypad(s), but
not at external bells or sirens.
Fire Alarm
Fire alarm
Temporal (pulsing) sound at external
bells and sirens.
∗
Enter the appropriate
keys programme
d by your installer for each function (see installer).
∗∗
All panic functions send signals to the Central Monitoring Station, if connected.
To activate a Panic Function:
Press and hold down the programmed or
pair
ed
keys
for at least 2 seconds for the desired
emergency function (or press both keys of the
assigned key pair at the same time).
Keys
Pairs
Displayed as Zone
[A]
(
∗
/1)
9
95
[B]
(
∗
/#)
9
99
[C]
(3/#)
9
96
•
When entering codes and commands, sequential key depressions
must be made within
4-5 seconds of one another. If 4
-5 seconds elapse without a key depression, the entry will
be aborted and must be repeated from its beginning.
• If you make a mistake while entering a security code, stop, press the
∗
key, and then start
over.
If you stop in the middle while entering a code, and then immediately start the entry
over, an erroneous code
might be entered.
SECURITY CODES
Your installer assigned a master code that is used to perform
all system functions.
In addition, other security codes can be assigned for use by other users.
•
Only the Master and Manager Codes
can assign security codes to users.
•
Users are identified by
a 3-digit user number.
•
In addition to a security code, each user is assigned an authority level and
various system
attributes.
See the full User Guide for definitions of each Authority Level.
•
Security codes can be used interchangeably within a partition when performing system
functions (a system armed with one
security code can be disarmed by a different security
code), with the exception of the Guest
codes
.
•
Security code programming involves these steps:
1. Choose a user number from the set of users assigned to the partition in whi
ch the user
will be operating, and assign a 4
-digit security code.
2. Assign an authority level to that user.
3. Assign other attributes as necessary.
Assigning Security Codes and User Attributes
The following lists the various command strings for adding
security codes and attributes.
Function
Commands
Add Security
Code
Master
or Manager co
de +
8
+ [user no.
] + new user’s security
code
Follow the screen prompts to add the authority
level and other
attributes for this user. The Keypad beeps once to co
nfirm that
new user was added.
Delete Security
Code
Master
or Manager code
+
8
+ [user no.] + Master or Manager
code first entered.
When prompted, press 1 (
YES).
The security code s
et for this user number is
erased from the
system.
Change a User
Security Code
Master code + 8
+ [user no.]
. Enter the new code for that user.
When prompted, press 0 (NO).
The security code set for this user number is changed to the new
code.
- Uploaded