Honeywell Vista 15P, 15PSIA, 20P and 20PSIA Installation Manual


Love this board!

Related Products

Honeywell VISTA-15P - Alarm Control Panel
Honeywell VISTA-15P
Alarm Control Panel
List Price: $196.00
Our Price: $121.99
Honeywell VISTA-15PSIA - Alarm Control Panel
Honeywell VISTA-15PSIA
Alarm Control Panel
List Price: $196.00
Our Price: $121.99
Honeywell VISTA-20P - Wired Alarm Control Panel
Honeywell VISTA-20P
Wired Alarm Control Panel
List Price: $244.00
Our Price: $150.99
Honeywell Tuxedo Touch - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch
Talking Color Graphic Wired Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI - Talking Color Graphic Touchscreen Alarm Keypad
Honeywell Tuxedo Touch WIFI
Talking Color Graphic Touchscreen Alarm Keypad

Related Categories


Document Transcript

VISTA-20P / VISTA-20PSIA VISTA-15P / VISTA-15PSIA
Security Systems

ADEMCO VISTA SERIES

Installation and Operation Guide

K5305-1V9 2/11 Rev. B

RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below. Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended. For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages. In addition, we recommend the following: • Install a smoke detector inside every bedroom where a smoker sleeps. • Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed. • Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners or KITCHEN KITCHEN DINING BDRM BEDROOM BEDROOM TV ROOM DINING humidifiers) are used.
LIVING ROOM BDRM BEDROOM

LIVING ROOM

BEDROOM

• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long. • Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.

Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection BEDROOM TO BR Heat-Activated Detectors

BEDROOM

BEDROOM KTCHN GARAGE

LVNG RM BASEMENT

.

CLOSED DOOR

floor_plan-001-V1

Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building. In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station). ii

Table Of Contents
Features and Installation Highlights............................................................................................................1-1
Capabilities and Functions................................................................................................................................................1-1 Compatible Devices ...........................................................................................................................................................1-2 Important Installation Highlights (Installer Please Read) .............................................................................................1-2

Mounting and Wiring the Control .................................................................................................................2-1
Installing the Control Cabinet and PC Board ..................................................................................................................2-1 Cabinet and Lock .........................................................................................................................................................2-1 Mounting the PC Board Alone (no RF Receiver) ........................................................................................................2-1 Mounting Board with RF Receiver..............................................................................................................................2-1 Auxiliary Device Current Draw Worksheet................................................................................................................2-2 AC Power, Battery, and Ground Connections ..................................................................................................................2-3 1321 Transformer.........................................................................................................................................................2-3 1361X10 Transformer ..................................................................................................................................................2-3 Battery Connections.....................................................................................................................................................2-3 Battery Saver Feature .................................................................................................................................................2-3 Earth Ground ...............................................................................................................................................................2-3 Sounder (Bell) Connections ...............................................................................................................................................2-4 Basic Connections ........................................................................................................................................................2-4 Supervised output ........................................................................................................................................................2-4 Connecting the Keypads and Other Addressable Devices ...............................................................................................2-4 Connections ..................................................................................................................................................................2-4 Supplementary Power (optional).................................................................................................................................2-4 Keypad Notes ...............................................................................................................................................................2-5 Communication Device ................................................................................................................................................2-5 (Long Range Radio) Connections.................................................................................................................................2-5 Table of Device Addresses .................................................................................................................................................2-5 Hardwire Zones and Zone Expansion ...............................................................................................................................2-6 Hardwire Zones ............................................................................................................................................................2-6 Double-Balanced Zones................................................................................................................................................2-6 Zone Doubling ..............................................................................................................................................................2-6 Smoke Detectors...........................................................................................................................................................2-6 Smoke Detector Notes..................................................................................................................................................2-7 4219/4229 Expansion Zones ........................................................................................................................................2-7 Installing the RF Receiver and Wireless Transmitter Zones ..........................................................................................2-8 Compatible Receivers...................................................................................................................................................2-8 Receiver Connections ...................................................................................................................................................2-8 RF Receiver Notes........................................................................................................................................................2-8 Installing a 5800TM Module .......................................................................................................................................2-9 Installing the Transmitters .........................................................................................................................................2-9 Transmitter Battery Life .............................................................................................................................................2-9 Installing a Keyswitch.....................................................................................................................................................2-10 Keyswitch Connections ..............................................................................................................................................2-10 Keyswitch Notes.........................................................................................................................................................2-10 Connecting Relay Modules, Powerline Carrier Devices and Output Triggers..............................................................2-11 4204/4229 Relay Modules ..........................................................................................................................................2-11 Powerline Carrier Devices .........................................................................................................................................2-11 On-Board Triggers .....................................................................................................................................................2-12 Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections............................................................2-13 Phone Line..................................................................................................................................................................2-13 4286 Phone Module....................................................................................................................................................2-13 Phone Module Problems ............................................................................................................................................2-13 Audio Alarm Verification Connections......................................................................................................................2-14 Audio Alarm Verification Connections......................................................................................................................2-15

iii

Table Of Contents
System Communication and Operation .......................................................................................................3-1
Panel Communication with Central Station ....................................................................................................................3-1 Report Code Formats.........................................................................................................................................................3-1 Ademco Contact ID® .........................................................................................................................................................3-3 Uploading/Downloading via the Internet .........................................................................................................................3-4 System Security Codes ......................................................................................................................................................3-5 Panic Keys..........................................................................................................................................................................3-7 Setting the Real-Time Clock .............................................................................................................................................3-7 Various System Trouble Displays .....................................................................................................................................3-8

Testing the System.............................................................................................................................................4-1
About Test Procedures.......................................................................................................................................................4-1 System Test........................................................................................................................................................................4-1 Checking Transmitter Enrollment (Sniffer Mode)...........................................................................................................4-1 Go/No Go Test Mode ..........................................................................................................................................................4-2 Dialer Communication Test and Periodic Test Reports...................................................................................................4-2 Automatic Standby Battery Tests.....................................................................................................................................4-2 Security Control.................................................................................................................................................................5-1 Compatible Devices ...........................................................................................................................................................5-1

Specifications & Accessories...........................................................................................................................5-1 Regulatory Agency Statements ......................................................................................................................6-1 Limitations and Warranty ...............................................................................................................................7-3

iv

Features and Installation Highlights

S E C T I O N

1

This manual applies to the following Honeywell security systems: ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred to as VISTA-15P series) Features and procedures apply to all, except where differences are noted. SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications for False Alarm Reduction. The other controls described in this manual are not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.

Capabilities and Functions
Feature/Function Partitions VISTA-20P Series VISTA-15P Series VISTA-15P is not a partitioned system. • 2 partitions, can protect two independent areas • Common zone option allows either partition to arm, while leaving a common area (ex. lobby or foyer) disarmed for access into the other partition. Up to 32 zones plus 8 keyfob zones (zones Zones Up to 48 protection zones plus 16 keyfob 49-56) for total of 40 zones: zones (zones 49-64) for total of 64 zones: • 6 basic hardwired zones (zone 1-6) • 8 basic hardwired zones (zones 1-8) with optional zone-doubling feature • Up to 16 additional wired zones (zones 924) using up to 2 4219/4229 modules • Up to 40 additional wired zones (zones 948) using up to 5 4219/4229 modules • Up to 26 wireless transmitter zones (5800 series; zones 9-34) • Up to 40 wireless transmitter zones (5800 series; zones 9-48) • Up to 2 configurable zone types • Up to 4 configurable zone types Security Codes Up to 48 Security Codes, with separate Up to 32 Security Codes, with separate authority levels and partition access authority levels One-button arming Dedicated keys can arm the system. Dedicated keys can arm the system. Schedules Up to 32; can control devices and/or autoUp to 8; can control devices and/or autoarm/disarm arm/disarm Keypad macros Up to 4; activated by wired keypads Up to 2; activated by wired keypads Paging Up to 4 pagers; certain system conditions Up to 2 pagers; certain system conditions can report to pagers; can use a dedicated can report to pagers; can use a dedicated key on keypads to send a signal to a pager key on keypads to send a signal to a pager Event Logging 100 events; display via Compass Downloader 50 events; display via Compass Downloader software or installer/master code at Keypad software or installer/master code at Keypad Zone descriptors Can assign for all zones (for alpha display keypads and/or 4286 Phone Module). Bell supervision Optional, detects external sounder wiring short (when in alarm) or open (when bell is off); causes a trouble condition, keypad display, and sends a report to the central monitoring station, if enabled (field ∗91, option 1). RF jam detection Optional, for wireless systems detects a condition that may impede proper RF reception (i.e., jamming or other RF interference); causes keypad display, and sends a report to the central monitoring station (if trouble reporting is enabled). Telephone Line Built-in option can monitor the telephone line voltage and can cause a local display, or a Monitoring display and trouble/alarm sound. Downloading via • Via Standard Phone Line: Use an IBM compatible computer, Compass downloading Phone Line or software, and a compatible HAYES or CIA modem specified by Honeywell. Internet • Via Internet: supports Upload/Download via the Internet/Intranet when used with an appropriate communications device (ex. 7845i-GSM) and Compass downloading software. This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet. UL NOTE: Uploading/Downloading via the Internet has not been evaluated by UL.

1-1

Installation and Setup Guide

Compatible Devices
Device Addressable Keypads Touch Screen (AUI) Devices 4219, 4229 Zone Expander Modules 5800 Series Wireless Output relays and/or Powerline Carrier Devices (X-10 type) On-Board Triggers Output functions 4286 Phone Module Audio Alarm Verification VISTA-20P 8 4 Up to 5 for up to 40 exp. zones Up to 40 RF zones Up to 16 2 Up to 48 Partition 1 only Using AAV module VISTA-15P 8 2 Up to 2 for up to 16 exp. zones Up to 26 RF zones Up to 8 2 Up to 24 yes Using AAV module Notes 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V Fixed-Word Display Voice Keypad, 6160V Alpha Display Voice Keypad, 6150RF Keypad/Transceiver Touch Screen (AUI) devices are in addition to the 8 addressable keypads. E.g., Symphony, 6270 Zone numbers are predefined according to the device addresses used. See Expander Module Addresses table in Wiring section and set addresses accordingly. Uses 5881/5883 Series Receivers/Transceivers. Use any combination of 4204, 4229 and or Powerline Carrier Devices. Map output devices via *79 Menu mode. Can be used to reset 4-wire smoke detectors. Program output functions via *80 Menu mode. Provides access to the system via on premises or offpremises phones for arming, disarming, etc., plus control of relay outputs and Powerline Carrier devices. Use Honeywell AVS or Eagle Model 1250 in conjunction with an output trigger to permit voice dialog between an operator at the central station and a person at the premises. The AVS system can be used to provide AAV via phone line or AlarmNet IP/GSM (using a GSMV module). Can drive the compatible sounders; steady output for burglary/panic, or temporal pulse (3 pulses – pause – 3 pulses – pause – 3 pulses. . .) for fire. Uses current limiting circuitry for protection. 12VDC, 600 mA maximum; uses circuit protection. Rechargeable (sealed lead-acid type) 12VDC, 4AH minimum. Primary telephone number messages can be reported via ECP connection to various communication devices (check compatibility/availability of specific models) Plug-in 120VAC transformer, 1321 (1321CN in Canada) or, if using Powerline Carrier devices, 1361X10 Transformer Module

Alarm output

12VDC, 2 AMP output See note. See note. See note. See note.

12VDC, 2 AMP output See note See note. See note. See note.

Auxiliary Power Output Backup Battery Communication Device (Long Range Radio) AC Power Supply

NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.

Important Installation Highlights (Installer Please Read)
• This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in Section 2. Mounting and Wiring – Connecting the Keypads and Other Addressable Devices). • Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196. • Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used. • 4204 Relay Modules must be set for specific addresses (12-15). • This control will not power-up unless AC power is connected (will not power-up on battery alone). However, once the system is powered up, it will operate on battery power in the event of AC loss. • Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions. • This system supports programmable function keys. Use *57 Menu mode to define the function keys.

1-2

S E C T I O N

2

Mounting and Wiring the Control
Installing the Control Cabinet and PC Board
Cabinet and Lock 1. Remove the cabinet door. Remove the cabinet knockouts needed for wiring entry. 2. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet mounting holes. 3. When installation and wiring is completed, install the cabinet door and secure by using 2 screws (supplied) through the door's edge. OPTIONAL KEY LOCK: If desired, a key lock can be installed (K4445, not supplied). Remove the lock knockout from the door. Insert the key into the lock. Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until the snap tabs hold it securely. Mounting the PC Board Alone (no RF Receiver)
CHECK POSITION
LOCKED PUSH
ADEMCO ADEMCO

SECURE WITH SCREWS (2)

cab_6-V0

SNAP TAB

PUSH ON LOCK UNTIL IT IS SEATED SECURELY

UNLOCKED

CABINET DOOR BOTTOM

STEP 1

STEP 2

Figure 1. Installing the Door and Cabinet Lock

Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring entry. Do not remove the knockouts after the circuit board has been installed. 1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B). 2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A). b. Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws (see Detail B).
CIRCUIT BOARD CIRCUIT BOARD CABINET DETAIL A SIDE VIEW OF BOARD SUPPORTING SLOTS
+ +

CABINET

DETAIL B SIDE VIEW OF MOUNTING CLIPS

MOUNTING-001-V0

Mounting Board with RF Receiver

Figure 2. Mounting the PC Board • Do not mount the cabinet on or near metal objects. This will decrease RF range and/or block RF transmissions from wireless transmitters. • Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged lighting of the LED in the receiver (random flicker is OK) 1. a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3 on the next page. Make sure that the board rests on the correct row of tabs. b. Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws. c. Insert the top of the control's board into the slot in the clips and position two clips at the lower edge of the board. d. Swing this board into place and secure it with two additional screws.

cab_lock_snap-001-V0

SNAP TAB

2-1

Installation and Setup Guide
Mounting Board with RF Receiver (continued) 2. 3. Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the left-hand terminals of the antenna blocks (at the upper edge of the receiver board) and secure them to the cabinet top with the screws provided (see Detail B). Insert the receiver's antennas through the top of the cabinet, into the blocks' righthand terminals, and tighten the screws.
CABINET

A

B

RECEIVER CIRCUIT BOARD

BOARD SUPPORTING SLOTS
CIRCUIT BOARD

CABINET

+

+

MOUNTING CLIP
CONTROL CIRCUIT BOARD

DETAIL A
MOUNTING CLIP
SIDE VIEW OF BOARD SUPPORTING SLOTS

INSTALLATION WITH RECEIVER CIRCUIT BOARD
ANTENNA (2) SCREW (2) GROUNDING LUG (2)

WHITE MOUNTING CLIP

BLACK MOUNTING CLIP

RED MOUNTING CLIP
ANTENNA MOUNT (2 PLACES)

NOTE A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN INCLUDED IN YOUR INSTALLATION KIT. USE THE APPROPRIATE CLIPS FOR MOUNTING. IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.

DETAIL B
ANTENNA AND GROUNDING LUG INSTALLATION
pc_mount-001-V1

Figure 3. Mounting the PC Board and RF Receiver

Auxiliary Device Current Draw Worksheet
DEVICE 6150 Fixed-Word Keypad 6160 Alpha Keypad 6150V Fixed-Word Display Voice Keypad 6160V Alpha Display Voice Keypad 8132/8142 Series AUI (Symphony) 6270 Touch Screen Keypad 5881/5882 RF Receiver 5883 Transceiver 4219 Zone Expander 4204 Relay Unit 4229 Zone Expander/Relay Unit 4286 Phone Module

CURRENT 40mA/70mA** 40mA/150mA** 60mA/160mA** 60mA/190mA** 150mA/400mA** 180mA/280mA** 60mA 80mA 30mA 15/180mA‡ 30/100mA‡ 300mA

No. UNITS

TOTAL CURRENT

(Current available from Aux. terminals = 600 mA max.)†

TOTAL =

*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw. ** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on †In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output). ‡Values are for relays OFF/relays ON.

The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below. OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION Output Current Total Maximum Auxiliary Current Battery Capacity Recommended Battery To Use (Amp/Hrs) (Yuasa Model No.) 600mA maximum total of 45mA 4AH NP4-12 (or ADEMCO 467) auxiliary power plus bell 160mA 7AH NP7-12 output currents 200mA 8AH NP4-12 (two) ‡ 425mA 14AH NP7-12 (two) ‡ 500mA 17.2AH NPG18-12 ‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)

CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE 24-HOUR BATTERY BACKUP REQUIREMENTS

2-2

Mounting and Wiring the Control

AC Power, Battery, and Ground Connections
1321 Transformer Connect the 1321 Transformer (1321CN in Canada) to terminals 1 and 2 on the control board. See Wire Run Chart for wire size to use. • Use caution when wiring the transformer to the control to guard against blowing the transformer fuse (the fuse is non-replaceable).

Wire Run Chart
Distance from control Up to 50 feet 50–100 feet 100-250 feet Wire Size # 20 # 18 # 16

1 TO TERMINALS 1 AND 2

1321X10-001-V0

2

1361X10 Transformer (required if using Powerline Carrier devices)

Sy Outnc put Sign Com al mon X1 0 Dat a

TO 8-PIN CONNECTOR

1

2
1361X10-001-V0

TO TERMINALS 1 AND 2

Battery Connections

BLACK RED

UL For UL installations and Residential fire installations, refer to the chart on page 2-2
at left for the correct battery size required to meet the mandatory standby time.
batt_conn-001-V0

CONNECT FLYING LEADS AFTER AC POWER IS APPLIED

Battery Saver Feature

Earth Ground

CO

B OL NTR

R OA

D

25

CONNECT PROPER EARTH GROUND IF DESIRED

The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored. IMPORTANT: The panel will not power up initially on battery power only. You must plug the transformer in first, and then connect the battery. • This product has been designed and laboratory-tested to ensure its resistance to damage from generally expected levels of lightning and electrical discharge, and does not normally require an earth ground. • If an earth ground is desired for additional protection in areas of severe electrical activity, terminal 25 on the control board, or the cabinet, may be used as the ground connection point. The following are examples of good earth grounds available at most installations.
earth_gnd-001-V0

Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured. AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.

DATA COM

AC

SYNC

AC

• Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message will be displayed. • Do not plug the transformer into the AC outlet until all wiring connections to the control are complete. As a safety precaution, always power down the control when making such connections. 8-PIN TRIGGER CONNECTOR 1. Splice one end of a 3-conductor cable 1 3 4 5 6 7 8 to the wire ends of the SA4120XM-1 Cable. 1361X10 TRANSFORMER 2. Connect the SA4120XM-1 cable plug to the 8-pin connector on the control SYNC COM DATA AC AC (see the Summary of Connections 2 5 3 4 1 diagram for location of the 8-pin connector). SA412OXM CABLE 3. Connect the other end of the 2 1 3-conductor cable to the 1361X10 CONTROL Transformer, as shown in Figure 4. BOARD TERMS. Canadian Installations: See Powerline Carrier Device section for Figure 4. 1361X10 Transformer Connections connections to the PSC04 X-10 Interface and trigger pins. 1. Place the 12-volt backup battery in the cabinet. 2. After all connections to the control are completed and AC power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed.
KEY (YELLOW) OUTPUT 18 (GREEN) (ORANGE) (BLUE) (PURPLE) OUTPUT 17 +12 AUX. GND (-) (BLACK) (RED)

2-3

Installation and Setup Guide

Sounder (Bell) Connections
Basic Connections
3 4

Make sounder connections to alarm output terminals 3 (+) and 4 (–). • The 12VDC sounder output activates when an alarm occurs. • Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip). • You must install a battery, since the battery supplies this current. Supervised output 1. Connect the supplied 820 ohm Bell Supervision EOL resistor across the terminals of the last sounder. See Figure 5. NOTE: The value of the Bell Supervision EOL Resistor is 820 ohms. This resistor is required ONLY if Bell Supervision is enabled. 2. Set field ∗91 Option Selection for Bell Supervision (option 1).
This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc.
spkr_conn-001-V0

ALARM OUTPUT 10.5 - 13.5 VDC 2A MAX.

UL

TERMINALS ON CONTROL BOARD

EXTERNAL ALARM SOUNDER

DO NOT CONNECT THE RESISTOR DIRECTLY TO THE ALARM OUTPUT TERMINALS!

Figure 5. Sounder Wiring (Supervised)

Connecting the Keypads and Other Addressable Devices
Connections
4_ 5+ 6 IN 7 OUT

BLACK

Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, GSMV, etc.) to the control’s keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program fields *190-*196). Use the Table of Device Addresses to determine the appropriate address for each device. Determine wire size using the Wire Run Chart on the following page. For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size. Use supplementary power if the control’s aux. power load for all devices exceeds 600mA (suggested power supply: AD12612). Connect as shown in Figure 6. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control. IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.

RED GREEN

AR MED RE AD Y

YELLOW

Supplementary Power (optional)

conn-001-V0

SUPPLEMENTARY POWER SUPPLY

CONTROL TERMINAL STRIP
AUX. AUX. DATA DATA – + IN OUT

+

UL

TO KEYPAD BLK WIRE TO KEYPAD GRN WIRE TO KEYPAD YEL WIRE

TO KEYPAD RED WIRE

TO KEYPAD BLK WIRE

TO KEYPAD YEL WIRE

Figure 6. Using a Supplementary Power Supply

2-4

supp_pwr_supply-V0

IMPORTANT: MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN.

TO KEYPAD GRN WIRE

TO KEYPAD RED WIRE

Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss. The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.

4

5

6

7

sounder-001-V2

• Use only UL Listed sounding devices for UL installations. • Bell supervision is required for fire alarm installations. • The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8VDC voltage range, and must be mounted indoors.

4 ALARM OUTPUT TERMINALS 3 OBSERVE POLARITY 820 OHM EOL RESISTOR

+

2

IF BELL SUPERVISION IS ENABLED ( 91 ENABLED) CONNECT AN 820 OHM RESISTOR ACROSS THE EXTERNAL SOUNDER AS SHOWN BY THE DOTTED LINE.

Mounting and Wiring the Control
Keypad Notes Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Device Addresses. See data fields *190-*196 in the Programming Guide for details on enabling keypad addresses, assigning keypad partitions, and selecting keypad sounding options. IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to 23. The first keypad is address 16 (default = partition 1, all sounds enabled). TOUCH SCREEN KEYPAD (AUI) NOTES: • Use of AUI devices (e.g., 6270, Symphony) is independent from standard keypads and does not affect the number of standard keypads the system can support. • AUI devices must be set for address 1, 2, 5**, or 6** depending on which unit is enabled in field *189. ** VISTA-20P series • To ensure proper AUI device operation, use AUI devices with the following rev levels: 6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version 1.1.175 or higher. Connect the data in/data out terminals and voltage input terminals of the communication device to the control's keypad connection points. Set the device’s address to “03” following the instructions provided with the device. • Use a compatible communication device (e.g., 7845GSM, 7845i-GSM).
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

AR

ME

D

RE

AD

Y

1 4 7

OF F

2 5 8 0

MA X

AW AY

3 6 9 #

INST ANT

TES T

STA Y

BYP

REA

CO DE

ASS

DY

CH IME

Communication Device (Long Range Radio) Connections

Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–) Wire Size #22 #20 #18 #16 50 mA or less 900 ft (274m) 1400 ft (427m) 1500 ft (457m) 1500 ft (457m) 100 mA 450 ft (137m) 700 ft (213m) 1100 ft (335m) 1500 ft (457m) 300 mA 150 ft (46m) 240 ft (73m) 350 ft (107m) 550 ft (168m) 500 mA 90 ft (27m) 140 ft (43m) 220 ft (67m) 350 ft (107m) 600 mA 75 ft (23m) 120 ft (37m) 170 ft (52m) 270 ft (82m)

* Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4286 Phone Module, and Communication Device. Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device alone. The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

Table of Device Addresses
This Device RF Receiver AUI 1 AUI 2 AUI 3 (VISTA-20P series) AUI 4 (VISTA-20P series) Communication Device (LRR) 4286 Voice Module Zone Expanders (4219/4229): module 1 (for zones 09 - 16) module 2 (for zones 17 - 24) module 3 (for zones 25 - 32) module 4 zones 33 - 40 module 5 zones 41 - 48 Relay Modules (4204): module 1 module 2 module 3 module 4 Keypads: keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8 RIS Communication 5800TM Module

Uses Address Reports as†† 00 100 01 02 05 06 03 103 04 104 07** 08 09† 10† 11† 12 13 14† 15† 16 17 18 19 20 21 22 23 25 28 107 108 109 110 111 112 113 114 115 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a

Enabled By… *56 zone programming: input device type entry automatic if AUI enable field *189 enabled for AUI 1 automatic if AUI enable field *189 enabled for AUI 2 automatic if AUI enable field *189 enabled for AUI 3 automatic if AUI enable field *189 enabled for AUI 4 automatic if communication device is enabled in field *29 automatic if phone module access code field *28 enabled *56 zone programming: input device type, entry 2, then: automatic if zone no. 9-16 set as AW type or relay assigned automatic if zone no. 17-24 set as AW type or relay assigned automatic if zone no. 25-32 set as AW type or relay assigned automatic if zone no. 33-40 set as AW type or relay assigned automatic if zone no. 41-48 set as AW type or relay assigned *79 output device programming: device address prompt: entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt data field programming as listed below: always enabled for partition 1, all sounds enabled. data field *190 data field *191 data field *192 data field *193 data field *194 data field *195 data field *196 automatic automatic

** address 07 not available if zone-doubling enabled † 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P. †† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199 for addressable device 3-digit/2-digit identification keypad display options.

2-5

Installation and Setup Guide

Hardwire Zones and Zone Expansion
Hardwire Zones Normally Open Zones/ N.O. EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. Normally Closed Zones/ N.C. EOLR Zones 1. Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device. 2. Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. End of Line Resistor (EOLR) Notes • If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone. • Zone 1 is intended for EOLR only.

HI

LO
zones-001-V0

UL For UL commercial burglar alarm installations, use EOLR zones.
Double-Balanced Zones (V20P only) Connect as shown below (resistor provided for one device). IMPORTANT: Double-balanced zones provide zone tamper protection, and should be used as burglary zones only. Do not use double-balanced zones as fire zones.
12 13 14

2k

TAMPER CONTACTS

2k

2k

TAMPER CONTACTS

2k

Zone Doubling (V20P only)

Fig. 7. Typical Double Balanced Zones This feature provides two hardwired normally closed zones for each standard hardwired zone connected to the control’s terminals (but does not increase the total number of zones supported by the control). If enabled (Zone Programming mode, “Hardwire Type” prompt, option “3”), hardwire zones are automatically paired as shown in the table. Connect as shown (resistors not supplied; use 3k and 6.2k 5%, 1/4W or bigger resistors). • Do not use zone doubling for fire zones. NOTE: A short across the EOL (i.e., at terminal) on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition (displayed as CHECK plus zone numbers).
10 ZONE 2 3k
zone-004-V0

2k ZONE 3

2k ZONE 4

11

ZONE 10 6.2k

Fig. 8. Typical Zone Doubling Wiring
Zone Doubling Table Zone Paired with zone 2 10 3 11 4 12 5 13 6 14 7 15 8 16 NOTE: Zone numbers used for zone doubling cannot be used for anything else (ex. cannot be used for 4219 zones)

Smoke Detectors
TO ZONE 1 TERMINALS

LO ZONE 1

HI

2-6

5806-001-V0

2-WIRE SMOKE DETECTOR

8 9

1. Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the back this manual. Observe proper polarity when connecting the detectors. 2. Connect an EOL resistor across the loop wires at the last detector. 3. Connect 4-wire smoke detectors (number of detectors depend on detector current draw) to any zone from 2-8 as shown in Figures 9a and 9b (on next page). Power Reset: This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information. NOTE: Maximum current on trigger 17 is 100mA.

zone-002-V0

Mounting and Wiring the Control
Smoke Detector Notes • Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the first alarm trigger, and then waiting up to 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control will disregard the first trigger, and no alarm signal will occur. This feature eliminates false alarms due to electrical or physical transients. SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm Listed relay accessories must be used to reset power as described in the Power Reset paragraph above. • The zone 1 alarm current supports only one smoke detector in the alarmed state. • Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the clean-me option. • Do not use 4-wire smoke detectors on zone 1.
+ AUX PWR OUTPUT TERMINALS 5 RELAY PROGRAM RELAY AS ZONE TYPE 54 (FIRE ZONE RESET) 4 BLK + RED EOL POWER SUPERVISION RELAY MODULE EOLR-1. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.

N.O. N.C.
+
4-WIRE SMOKE OR COMBUSTION DETECTOR

CONTACT OPENS MOMENTARILY UPON FIRE ALARM RESET

VIOLET

2000 OHMS EOLR
4_wiresmk-007-V1

TO ZONE TERM. (+) HEAT DETECTOR TO ZONE TERM. ( )

Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset
AUX PWR (+) 5 BLK TO OUTPUT 17 ( ) PROGRAM OUTPUT 17 FOR "OUT NORM LOW" = YES IN 79 MENU MODE AND AS ZONE TYPE 54 IN 80 MENU MODE + RED EOL POWER SUPERVISION RELAY MODULE EOLR-1. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED.

+
4-WIRE SMOKE OR COMBUSTION DETECTOR

N.O.
VIOLET 2000 OHMS EOLR

TO ZONE TERM. (+) HEAT DETECTOR TO ZONE TERM. ( )

Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset 4219/4229 Expansion Zones 1. Connect each module to the control’s keypad terminals and set the device addresses. See the Table of Device Addresses to select an appropriate address for each module. • VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules. • VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules. 2. Connect sensors to the module’s loops. See Figure 10 on the following page. • Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229 modules. (EOLRs used on the control terminals are 2000 ohms.) • Expansion zones have normal response time (300–500 msec), except zone connected to each module’s loop “A,” which can be set for fast response (10–15 msec). 3. If using relays with the 4229, connect the desired field wiring to the unit's relay contact terminals.

4_wiresmk-008-V1

©
©

©

2-7

Installation and Setup Guide
RELAY CONNECTOR RELAY 2

4229
DIP SWITCH FOR SETTING ADDRESS AND ZONE "A" RESPONSE EITHER OR BOTH CAN BE USED

TERMINALS ON CONTROL PANEL

RELAY 1
NO C NC TAMPER JUMPER POSITION 4229 IN CABINET (NOT TAMPER) 4-PIN CONSOLE PLUG

TB2 4 4 3 2 12 1 3 2 1 GRN DATA OUT (>) TO CONTROL BLK RED (–) GROUND (TERM 6) (TERM 4) (TERM 5) (TERM 7)

WHT

GRY VIO BLK YEL ORG BRN

4229 REMOTE (TAMPER PROTECTED)

TB1 6 7 8 9 10 11

NO NC C GND NO NC C

1

2

3

4

5

(+) 12VDC YEL DATA IN (


Uploaded