Honeywell VISTA 15P, 20P: Configurable Zone Types Worksheet
Related Products
Document Transcript
CONFIGURABLE ZONE TYPES WORKSHEET
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-
*185. Configurable zone types 92 and 93 (VISTA-20P only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for
zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields
*183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
(See note 5 for RF zones)
ENTRY 2
(See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
Auto
Restore
Vent Zone
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = yes
0 = no
8 = yes
Entry 1 = EOL + Open
Entry 2 = Short + auto restore + vent zone
ENTRY 3
(See note 5 for RF zones)
ENTRY 4
(See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
Byp. when
disarmed
Byp. when
armed
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = yes
0 = no
8 = yes
Entry 3 = EOL + Open
Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 5
(See note 5 for RF zones)
ENTRY 6
(See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
Open
RF zone N/A
Shorted
RF zn off-normal
Dial Delay
(see field *50)
Fault Delay
(see field *87)
0 = normal
1 = alarm
2 = trouble
3 = fault
0 = normal
4 = alarm
8 = trouble
12 = fault
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
0 = no
4 = use delay
0 = no
8 = use delay
see note 1
Entry 5 = EOL + Open
Entry 6 = Short + dial delay + fault delay
ENTRY 7
ENTRY 8
Display Faults
Power Reset/
Verification
Use Entry
Delay 1/2
Use Exit
Delay
Respond as
Interior Type
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
armed
(show
alarms, trbles,
faults when
disarmed)
3 = never show
any alarms,
trbles, faults
0 = no
4 = power reset
after fault
(by code + OFF)
12 = verification
(see zone
type 16)
0 = no
1 = delay 1
2 = delay 2
0 = no
4 = use exit
delay
0 = no
8 = yes
see note 2
Entry 7 = fault display + power
reset/verification
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
ENTRY 9
ENTRY 10
Alarm Sounds
Use Bell
Timeout
Respond as
Fire Zone
Trouble
Sounds
Chime when
Chime Mode On
0 = none
1 = steady
keypad
2 = steady bell
and keypad
3 = pulsing bell
and keypad
0 = no
4 = yes
see fields *32,
*33
0 = no
8 = yes
see zone type
09; see note 4
0 = none
1 = periodic
beep
2 = trouble
beeps
0 = no
4 = yes
Entry 9 = alarm sounds + bell timeout + fire zone
Entry 10 = trouble sounds + chime
Entries for Fields *182 and *184
Entry Zone Type 90
Zone Type 91
(field *182) (field *184)
1
2
3
4
5
6
7
8
9
10
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
OPEN
SHORTED
INTACT
EOL
ZONE-003-V0
Zone Conditions Represented
in Entries 1-6
NOTES:
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
“respond as interior zone type” (entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
not display unless the [
∗
] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The “open” option in entries 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for off-
normal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled
pair or on a double-balanced zone
causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones,
both
zones
of the doubled pair must be assigned
the same response to a short.
–
18
–
- Uploaded