Installation
Manual & User
Guide

IMPORTANT SAFETY INFORMATION. READ ENCLOSED WARNINGS AND SAFETY INFORMATION


OPERATION

The
FireFighter

sensor
is designed
to listen
to the alarm sounder
of any
UL
smoke
detector.
Once
confirmed
as an alarm,
it will
transmit
a signal
to the
alarm
control
panel
which
if connected to a central monitoring station,
will
dispatch
the
fire
department.


WARNING
:

THIS
AUDIO
DETECTOR
IS INTENDED
ONLY
FOR USE WITH
SMOKE
DETECTORS
BUT
IT DOES
NOT
DETECT
THE
PRESENCE
OF
SMOKE,
HEAT, OR
FIRE
DIRECTLY. THIS DEVICE
IS NOT INTENDED TO REPLACE SMOKE, HEAT OR FIRE DETECTORS IN THE FIRE ALARM SYSTEM,
IT IS A SECONDARY LISTENING DEVICE.


CE DÉTECTEUR AUDIO EST UNIQUEMENT DESTINÉ À UNE UTILISATION AVEC DES DÉTECTEURS DE FUMÉE, MAIS IL NE DÉTECTE PAS LA PRÉSENCE DE FUMÉE, LA CHALEUR OU LE FEU
DIRECTEMENT. CE DISPOSITIF DE SAPEUR
-POMPIER EST PAS DESTINÉ À
REMPLACER LA FUMÉE, LA CHALEUR OU LE DÉTECTEUR D'INCENDIE DANS LE SYSTÈME D'ALARME D'INCENDIE, IL
EST UN DISPOSITIF D'ÉCOUTE SECONDAIRE.



ENROLLING

(See IMAGE
1) To enroll
the
sensor,
set
your
panel
into
sensor learn
mode.
Refer
to your
specific
alarm
panel
instruction
manual for
details
on
these
menus.

To trigger a transmission from the sensor
, press
the
tamper switch on the FireFighter
when
prompted
by the
panel
. For some
panels, you may need to manually
enter the serial number, which is printed on the back of each unit
. With
Simon XT/XTi, Concord, and
Advisor
panels program the zone to use sensor group 26.
With
NetworX and Zerowire
panels program the zone to use sensor group 8.
Ensure the
Fire Verify
reporting option is enabled.


MOUNTING

(See IMAGES
2 & 3)
Included
with
this
device
is a mounting bracket,
hardware
and
double
sided
tape.
To ensure
proper
operation
ensure
the
side
of the
device
with
the
small
holes
is directly
facing the
sounder
holes on the smoke
detector.
Secure
the mounting
bracket
to the wall
or ceiling using the two
mounting screws
or double
sided
tape
provided,
and then
secure
the
audio
detector
to the mounting
bracket
using
the
small
screw
provided.

The

FireFighter
must
be
mounted
within
6 inches
of the
detector.


WARNING
:

NON
-INTERCONNECTED
SMOKE
DETECTORS
REQUIRE
AN
AUDIO
DETECTOR
BY
EACH
SMOKE
DETECTOR
SOUNDER.


DETECTEURS DE FUMÉE NON INTERCONNECTÉS NÉCESSITENT UN DÉTECTEUR AUDIO PAR CHAQUE SONDEUR DÉTECTEUR DE FUMÉE.


TESTING

(See
IMAGE 1
) To test the RF transmission from the mounted position, set the panel in sensor test mode,
and then
press the
test
button within the device.
This wi
ll send a RF transmission
signal to the control panel. To
test the audio detection, press
and hold the smoke detector
TEST
button¹
. If the smoke
detector TEST button does NOT trigger all smoke
detectors
then use
a common can of smoke to simulate a real
fire, which should trigger the entire system.
²

If the Fire Verify reporting option is enabled,
the sensor will need to stay in alarm for at least one minute for the panel to verify it as an alarm and communicate
to the central station.
Ensure the FireFight
er cover is
installed
during this test and that y
ou wear hearing protection.



NOTE
S:


¹For valid audio testing t
he smoke detector test must produce three separate temporal 3 (T3) sound patterns. Verification
of two
complete T3 patterns
with
alarm at the beginning of the third T3 pattern.



²With some smoke detector model types (i.e. combination smoke / carbon mono
xide) using the TEST button
to test audio detection may not
result in an audio output that the FireFighter recognizes
, in this case use a common can of smoke to simulate a real fire.



This system must be checked by a qualified technician at least once every three (3) years.
Please test the unit once per week to ensure proper
functionality.



Tampers will not be detected by NX panels unle
ss the option is turned on at the panel
. (Feature 4, Input Option 1)


LED

The
FireF
ighter
is equipped with a multi
-color LED. When
a valid audio signal is hear
d the LED will turn yellow and flash in sequence to the smoke detector
sounder. When the Firefighter
™ has determined the audio signal heard
is a valid alarm, the LED will turn red to indicate it has transmitted to the panel.
It
will also turn red when the c
ase is opened to indicate a tamper transmission to the control panel. On power up the LED will also flash red then green as part
of its power up cycle.

Insert Battery = One RED
flash
, then one GREEN flash

If frequency sound detected = Flash
YELLOW
for the duration of that sound
Fire Alarm detected = Solid RED for 3 seconds, then flash
RED when tone detected

Tamper = Solid RED for three second

Test
button pressed = Solid GREEN for 3 seconds


REPLACING THE BATTERY

When the
battery
is low
a signal
will
be sent
to the
control
panel.
To replace
the
battery:
1. Remove the top cover to
reveal
the
battery.
This
will
send
a tamper
signal
to the
control
panel.

2. Replace
with
a Panasonic
CR123A
battery
ensuring the

+
side
of the battery
faces
as indicated
on the device.

3. Re
-attach the cover
. You
should
hear a click when
the
cover
engages
properly.


WARNING
:

WHILE THE AUDIO
DETECTOR
MONITORS
ITS
OWN
BATTERY,
IT DOES
NOT MONITOR THE BATTERY
IN THE
SMOKE
DETECTORS.
BATTERIES
SHOULD
BE
CHANGED
AS
PER
THE
ORIGINAL
SMOKE
DETECTOR
MANUFACTURER’S
INSTRUCTIONS.
TEST THE AUDIO
DETECTOR
AND
SMOKE
ALARMS
AFTER
BATTERY
INSTALLATION
TO CONFIRM PROPER
OPERATION
.

BIEN QUE LE DÉTECTEUR AUDIO SURVEILLE SA PROPRE BATTERIE, IL NE CONTRÔLE PAS LA BATTERIE DANS LES DÉTECTEURS DE FUMÉE. LES PILES DOIVENT ÊTRE CHANGÉES SELON
LES INSTRUCTIONS DU FABRICANT ORIGINAL DE DÉTECTEUR DE FUMÉE. TOUJOURS TESTER LES DÉTECTEURS DE FUMÉE ET ALARMES AUDIO APRÈS L'INSTALLATION DE LA BATTERIE
POUR CONFIRMER LE BON FONCTIONNEMENT.

SLX
-
AD
-
T3

Audio Detector
P/N 466-
5233
• REV B
• 12SEPT
16 © 2016
UTC Fire & Security Americas Corporation, Inc.
All rights reserved.







TEST
BUTTON


6”
MAX





TAMPER
SWITCH




MARKINGS
TO
LINE

UP
WITH
EXISTING
SMOKE
DETECTOR


BATT



IMAGE
1
: TEST
/ TAMPER
/ BUTTON

IMAGE
2
: INSTALLATION
DISTANCE

IMAGE
3
: SIDE
MARKINGS


INSTALLATION RECOMMENDATIONS

The FireFighter can be mounted within six inches away from any one of a number of hardwired interconnected smoke detectors. Careful
consideration should
be made in identifying whi
ch smoke detector location will
opt
imize performance and/or reduce the risk
of other sound source
s or sound distortion interfering in
the operation of the device.



Install the FireFighter in the most isolated installation areas where an interconnected smoke detector is located
.


To reduce the sound verification challenges that may occur with multiple unsynchronized smoke alarms do
not install the FireFighter next to a
smoke

detector that is within six feet of another inter
connected smoke detector
.


Avoid installing the FireFighter in areas where there may be a lot of sound echoing. (
e.g. tiled flooring, walls, and ceilings)


This equipment should be installed in accordance
to the
National Fire Alarm Code, ANSI/NFPA 72, (National Fire Protection Association, Batterymarch Park, Quincy
, MA 02269).
Printed information describing proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this equipment. Warning:
Owner’s instruction notice: ’Not to be removed by anyone except occup
ant’.


SPECIFIC
ATIONS

Frequency:
319.5 MHz

Operating
Temperature:
32°
-120°F
(0°
-49°C)
Battery:
One
3Vdc

lithium
CR123A
(1550
mAh)

Operating
Humidity:
5-95%
RH non condensing

Battery
life:
4 years

Works with any Interlogix Learn Mode Panel

Detection
distance:
6 in (15 cm)
max

Supervisory
signal
interval:
64 min(approx.)

FCC, IC, and ETL listed in US and Canada to UL985

Maximum current draw: 23mA during transmission


CONTACT INFORMATION

www.interlogix.com

For customer support, see www.interlogix.com/support


PRODUCT ORDERING

Model

SLX
-AD
-T3

FireFighter Wireless Alarm Monitoring & Relay Device

Accessories
SM
200-
12PKG

Smoke! In A Can (canned smoke) for functional testing of smoke alarms


FCC COMPLIANCE STATEMENT
: FCC ID
: XQC
-WST601 IC:9863B
-WST601

This
equipment
has
been
tested
and
found to comply with the
limits
for
Class
B digital devices, pursuant
to Part 15
of the FCC Rules. These
limits
are
designed to provide
reasonable protection against
harmful interference
in a residential installation.
This
equipment
generates
uses
and
can radiate
radio
frequency
energy
and,
if not
installed
and
used
in accordance
with the
instruction
manual, may cause harmful interference to radio
communication
s. However,
there
is no guarantee
that interference will not
occur
in a particular

installation.
If this equipment
does cause harmful
interference to radio
or television
reception,
which can
be
determined
by turning the equipment
off
and
on, the user
is encouraged
to try to
correct
the interference by
one or more
of the following measures:



Re
-orient or
relocate
the
receiving
antenna
.


Increase
the separation between the equipment and receiver
.


Connect the equipment to an outlet on a
different
circuit
from
the
receiver
.


Consult the dealer or an experienced radio/TV contractor for
help.

This device complies with Industry Canada license
-exempt RSS standard(s).
Operation is subject to the
following two conditions: (1) this device may not cause interference, and (2)
this device must accept any
interference,
including
interference that may cause undesired
operation
of the device.

C’et
appareil
est conforme la norme d'Industrie Canada exempts de licence
RSS. Son fonctionnement est soumis aux deux conditions suiv
antes:
(1)
c’et
appareil
ne
peut
pas

provoquer
d'interférences,
et (2)
c’et
appareil
doit
accepter
toute
interférence,
y compris
les
interférences
qui
peuvent
causer un mauvais fonctionnement de la
dispositif.


ADDITIONAL WARRANTY AND DISCLAIMER INFORMATION

THE
FIREFIGHTER™
DETECTOR
DOES
NOT
DETECT
THE
PRESENCE
OF
SMOKE,
HEAT,
OR
FIRE
DIRECTLY.
IT RELIES
SOLELY
ON
THE
PRESENCE
OF
AN
AUDIO
ALARM
SIGNAL
GENERATED
BY
AN
EXISTING
SMOKE
OR
FIRE
DETECTOR
IN PROXIMITY
TO
THE
FIREFIGHTER™
DETECTOR
TO
MAKE
SUCH
A DETERMINATION.
THE

FIREFIGHTER™
DETECTOR
MUST
BE
USED
WITH
SMOKE
DETECTORS
CERTIFIED
ACCORDING
TO
UL
STANDARDS,
AND
IN STRICT
ACCORDANCE
WITH
THE
INSTALLATION
AND
OPERATION
INSTRUCTIONS
PROVIDED
WITH
SUCH
DETECTORS.
IT IS THE
OWNER’S
RESPONSIBILITY
TO
ENSURE
THAT
SMOKE
OR
FIRE

DETECTORS
USED
IN CONJUNCTION
WITH
THE
FIREFIGHTER™
DETECTOR
ARE
MAINTAINED AND
TESTED
ON
A REGULAR
BASIS
IN ACCORDANCE
WITH
THE

MANUFACTURER’S
INSTRUCTIONS.
INTERLOGIX
EXPRESSLY
DISCLAIMS
ANY
RESPONSIBILITY
FOR
THE
FAILURE
OF
THE
FIREFIGHTER™
DETECTOR
TO
DETECT
THE

PRESENCE
OF SMOKE
OR
FIRE
DUE
TO
THE
FAILURE
OF
ANY
SMOKE
OR
FIRE
DETECTOR
USED
IN CONJUNCTION
WITH
THE
FIREFIGHTER™
DETECTOR
TO
OPERATE
PROPERLY
DUE
TO
ANY
CONDITION,
INCLUDING
IMPROPER
INSTALLATION,
OPERATION,
MAINTENANCE
OR
TESTING
OF
SUCH
SMOKE
OR
FIRE
DETECTOR.


MANUFACTURER HEREBY DISCLAIMS ALL WARRANTIES AND REPRESENTATIONS, WHETHER EXPRESS, IMPLIED, STATUTORY OR OTHERWISE INCLUDING (BUT NOT LIMITED TO) ANY
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO ITS FIREFIGHTER PRODUCTS
AND RELATED SOFTWARE. MANUFACTURER FURTHER
DISCLAIMS ANY OTHER IMPLIED WARRANTY UNDER THE UNIFORM COMPUTER INFORMATION TRANSACTIONS ACT OR SIMILAR LAW AS ENACTED BY ANY
STATE.

(USA only) SOME STATES DO NOT ALLOW THE EXCLUSION OF IMPLIED WARRANTIES, SO T
HE ABOVE EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS
AND YOU MAY ALSO HAVE OTHER LEGAL RIGHTS THAT VARY FROM STATE TO STATE.