L5210 Installation and Setup Guide
Related Products
Related Categories
Document Transcript
LYNX Touch
L5210/L7000 Series
Security Systems
Installation and Setup Guide
800-19974 12/14 Rev. A
LYNX Touch Installation and Setup Guide
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help
Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72
noted below.
• Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be installed outside of
each separate sleeping area, and on each additional floor of a multi-floor family living unit, including
basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.
• For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the
sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room
could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
DINING
BEDROOM BEDROOM
TV ROOM
KITCHEN
DINING
BDRM
LIVING ROOM
BDRM
BEDROOM
BEDROOM
LIVING ROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BEDROOM
BEDROOM
TO
BR
BEDROOM
KTCHN
LVNG RM
.
CLOSED
DOOR
GARAGE
BASEMENT
floor_plan-001-V1
Recommendations For Proper Intrusion Protection
• For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multi-level
building.
• In addition, we recommend that radio backup be used in a security system. This will ensure that alarm
signals can be sent to the alarm monitoring station in the event that the telephone lines are out of order
(alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).
-2-
LYNX Touch Installation and Setup Guide
Table of Contents
System Features .................................................................................................................................................................................5
Installing the Control........................................................................................................................................................................7
Wall Mounting ...............................................................................................................................................................................7
Desktop Mounting..........................................................................................................................................................................7
Wiring Overview ............................................................................................................................................................................8
Wiring Connections ...........................................................................................................................................................................9
AC Power and Backup Battery .......................................................................................................................................................9
General ................................................................................................................................................................................................10
Installing the Rechargeable Backup Battery ..............................................................................................................................10
Replacing the Rechargeable Backup Battery..............................................................................................................................10
Battery Selection..........................................................................................................................................................................10
Installing/Configuring Communications & Home Automation Modules .............................................................................12
General ................................................................................................................................................................................................12
Connecting and Configuring Communications Modules ....................................................................................................................12
Installing the 4GL/4GLC or 3GL/3GLC ......................................................................................................................................12
Installing the ILP5.......................................................................................................................................................................14
Installing the L5100-WiFi Module ..............................................................................................................................................15
Installing the L5100-ZWAVE Module .........................................................................................................................................15
Installing Wireless Zones ...............................................................................................................................................................17
General Information ............................................................................................................................................................................17
Zones.............................................................................................................................................................................................17
Range ............................................................................................................................................................................................17
Transmitters ................................................................................................................................................................................17
House Identification.....................................................................................................................................................................17
Transmitter Supervision .............................................................................................................................................................17
Transmitter Input Types .............................................................................................................................................................17
Transmitter Battery Life .............................................................................................................................................................17
RF Sniffer Test Mode ...................................................................................................................................................................18
Go-No-Go Test Mode ....................................................................................................................................................................18
5800 Series Transmitter Loop Numbers .....................................................................................................................................19
Mechanics of Programming ...........................................................................................................................................................20
Navigating Menus ...............................................................................................................................................................................20
Touchscreen Display ....................................................................................................................................................................20
Navigation Keys ...........................................................................................................................................................................21
Home Screen ................................................................................................................................................................................21
Security Screen ............................................................................................................................................................................22
Security Menus ............................................................................................................................................................................22
Installer Tools Menu ....................................................................................................................................................................22
User Tools Menu ..........................................................................................................................................................................22
General Programming Information ....................................................................................................................................................23
Programming .......................................................................................................................................................................................23
Enter Installer Programming Mode ............................................................................................................................................23
Loading Factory Defaults ....................................................................................................................................................................24
Select a Default Configuration ....................................................................................................................................................24
Exiting Programming Mode ................................................................................................................................................................24
Zone Response Type Definitions ..................................................................................................................................................25
General Information ............................................................................................................................................................................25
Programming the Control ..............................................................................................................................................................27
Enter Installer Programming Mode without using Installer Code ...................................................................................................27
Change Installer Code .........................................................................................................................................................................27
Select a Language................................................................................................................................................................................27
System Type ........................................................................................................................................................................................27
Program Date and Time ......................................................................................................................................................................30
Program the Communications Module ...............................................................................................................................................31
Program the Z-Wave Module ..............................................................................................................................................................34
Program Zones .....................................................................................................................................................................................35
Program Keys ......................................................................................................................................................................................38
Program Reporting ..............................................................................................................................................................................40
Program Sounder.................................................................................................................................................................................47
Program System Settings....................................................................................................................................................................48
Communications Diagnostics ..............................................................................................................................................................51
Communications Status...............................................................................................................................................................51
Ethernet Information...................................................................................................................................................................51
GSM Information .........................................................................................................................................................................51
-3-
LYNX Touch Installation and Setup Guide
Table of Contents (Continued)
Communications ID Numbers .....................................................................................................................................................52
Test Communications ..................................................................................................................................................................52
Setup Communications ................................................................................................................................................................52
Registering the LYNX Touch.......................................................................................................................................................52
Register through AlarmNet Direct Website................................................................................................................................53
Register by Phone ........................................................................................................................................................................53
Register through LYNX Touch Diagnostics ................................................................................................................................53
Register Device with PIN ...........................................................................................................................................................54
Update Server ..............................................................................................................................................................................55
Enroll the L5100-WiFi Module ....................................................................................................................................................55
Enroll Using Scan Access Points .................................................................................................................................................56
Manually Configure Access Points ..............................................................................................................................................56
WiFi Protected Set-up (WPS) ......................................................................................................................................................57
Factory Defaults...........................................................................................................................................................................57
Remote Programming/Control (Downloading)..........................................................................................................................58
General Information ............................................................................................................................................................................58
Remote Programming Information .....................................................................................................................................................58
Remote Programming Advisory Notes ........................................................................................................................................59
System Operation.............................................................................................................................................................................60
Key/Touchscreen Operation ................................................................................................................................................................60
Panic Key/Icons ...................................................................................................................................................................................60
Security Codes .....................................................................................................................................................................................60
Installer Code ...............................................................................................................................................................................60
Master Code .................................................................................................................................................................................60
Enter/Change the Master Code by Installer ...............................................................................................................................60
Secondary User Codes .................................................................................................................................................................61
Reset Master Code .......................................................................................................................................................................61
Security Code Notes .....................................................................................................................................................................61
“Follow Me” System Announcement Feature (L5210/L5210CN only) ...............................................................................................62
“Follow Me” Reminder Feature (L5210/L5210CN only) ....................................................................................................................63
Remote Phone Control Feature (L5210/L5210CN only) ....................................................................................................................63
System Displays ..................................................................................................................................................................................64
Zone Status Displays ...........................................................................................................................................................................64
Audio Alarm Verification (Two-Way Voice Feature) ..........................................................................................................................65
Activation .....................................................................................................................................................................................65
Operator Commands ....................................................................................................................................................................65
Event Log .............................................................................................................................................................................................66
Contact ID & SIA Event Log Codes ....................................................................................................................................................66
Central Station Messages ...................................................................................................................................................................67
Testing the System...........................................................................................................................................................................68
Test Modes ...........................................................................................................................................................................................68
Testing the System ..............................................................................................................................................................................68
Armed System Test .............................................................................................................................................................................68
Dialer Test ...........................................................................................................................................................................................69
Zone Discovery Mode ...........................................................................................................................................................................69
Rebooting the System ..........................................................................................................................................................................69
LYNX Touch (L5210/L7000) Programming Default Values......................................................................................................70
LYNX Touch (L5210CN/L7000CN) Canada Programming Default Values ...........................................................................73
Zone Programming Default Values ..............................................................................................................................................76
Zone Response Type Matrix ..........................................................................................................................................................77
Regulatory Agency Statements .....................................................................................................................................................78
Limitations of this System Statement .........................................................................................................................................79
UL Notices .........................................................................................................................................................................................80
SIA Quick Reference Guide ...........................................................................................................................................................81
Specifications ...................................................................................................................................................................................82
Contacting Technical Support ......................................................................................................................................................83
Glossary .............................................................................................................................................................................................84
Index ...................................................................................................................................................................................................85
Summary of Connections Diagram ..............................................................................................................................................87
Support & Warranty Information ................................................................................................................................. Rear Cover
-4-
LYNX Touch Installation and Setup Guide
System Features
The LYNX Touch L5210 and L7000 series controls are self-contained, rechargeable wireless
control/communicator that features easy installation and usage. A built-in speaker provides voice
annunciation of system status along with voice descriptors of each zone. An internal module (if provided)
allows the LYNX Touch to communicate with the Central Station via the Internet or GSM Cellular Wireless.
UL
LYNX Touch is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N
300-03866/LYNXRCHKIT-SHA) is installed.
System Features
• 4.7-inch color graphic touch screen
• 7.0-inch color graphic touch screen
• Message center (for user recorded messages)
• Voice announcement of system and zone status
• User-selectable voice chimes
• Reminders
• Automatic stay arming
• Night stay arming
• Remote phone control
• Speaker phone operation
• “Follow me” reminder and system announcements
• User Codes (Installer, Master, Guest, Duress)
• Panic Functions (Police, Fire, Medical)
• Programmable reminders
• Video Camera Control (requires installation of a L5100 WiFi Module)
• Supports Mobile Devices (Tablet, iPAD, etc.) that duplicate functions of the LYNX
Touch (i.e.; Security, Web Content Home Automation and Video Control)
Home Automation (requires installation of a L5100 Z-Wave Module)
• Control Z-Wave Home Automation devices
- Thermostats
- Door locks
- Devices (outlets, switches, lamps/appliances)
• Supports Garage Door Feature (5877 Relay Receiver)
• Programmable scheduled events, rules and scenes
• Supports Z-Wave Network Wide Inclusion (NWI) Mode
Zones and Devices
• Hardwire Zone (EOLR, N/C, N/O)
• Wireless Zones (5800 Series transmitters)
• Wireless Button (Keyfob) Zones (5800 Series transmitters)
• Garage Door Zones
• Temperature Zones
• Resident Monitor Zone Types
• Supports Wireless Keypads
• Built-in Case tamper
-5-
L5210
n/a
10
32
16
1
L7000
n/a
10
n/a
n/a
n/a
48
16
4
4
4
3
4
40
3
20
4
6
40
4
20
1
63
16
3
6
2
1
79
24
4
8
2
LYNX Touch Installation and Setup Guide
System Features
Communication
• ADEMCO Contact ID
• SIA (DC-03)
• Internet Central Station communication
• GSM cellular Central Station communication
• WiFi Central station communication
• Two-way voice communication
• Supports AlarmNet remote services
System Power
• Primary Power: Plug-in Power Supply, 110VAC to 9VDC, 2.7A output P/N 30004705V1 or 300-04065V1 (300-04063V1 or 300-04064V1 in Canada)
• Backup battery: Rechargeable nickel-metal hydride battery pack rated at 7.2Vdc.
(P/N 300-03864-1/LYNXRCHKIT-SC or 300-03866/LYNXRCHKIT-SHA)
Alarm Output
• Built-in sounder
• Steady output for burglary/panic
• Temporal (3) pulse output for fire alarms
• Temporal (4) pulse output for carbon monoxide alarms
• Long Range Radio (GSM)/Audio Alarm Verification
• Trigger output
Programming
• Options stored in EEROM
• Can be uploaded, downloaded or controlled via IBM-compatible computer using
Compass downloader software and specified HAYES or Honeywell CIA modem or
via capable GSM, IP or WiFi communications module
* L7000 requires GSM, IP or WiFi communications
• Flash downloading
Other Features
• Exit error feature (detects difference between an actual alarm and exit alarm caused
by leaving a door open after the exit delay expires)
• Event log storage (total events)
• RF jam detection
• Installer programmable user (Follow Me) phone numbers
• Advanced Protection Logic™ (APL) (Minimizes the likelihood of the system being
disabled before notification can be sent to the Central Station indicating that the
premise has been compromised.)
• Displays web content including Local News, Weather and Traffic (requires Total
Connect Service)
• Dealer/Central Station messages (requires Total Connect Service)
-6-
L5210
L7000
*
128
2
256
n/a
LYNX Touch Installation and Setup Guide
Installing the Control
Wall Mounting
For wall mounting follow the steps below and refer to the appropriate figure for the LYNX Touch L5210 OR
L7000 control.
1.
2.
3.
4.
5.
6.
7.
Release the front case assembly from the back case by depressing the two locking tabs at the top of the unit with the
blade of a medium size screwdriver.
Separate the front and back case assemblies by rotating the front case so that it is perpendicular to the back case and
unsnapping (releasing) the two hooks from the back case.
Feed the field wiring through the appropriate openings in the back case. Use tie-wraps to secure the wiring to the built-in
wire loops as needed.
Mount the back case to a sturdy wall.
If required, install an additional mounting screw in the case tamper (see Detail A).
Attach the front and back cases by connecting the hooks on the front case to the attachments on the rear case. Once
attached, the hooks will support the front case and allow you to make the wiring connections.
After all wiring connections have been made, snap the front case and back case closed and ensure that the control is
secured by the locking tabs.
MOUNTING
HOOKS (HINGES)
INSTALL
SCREW
IN CASE
TAMPER
TIE WRAP
POINT (3)
MOUNTING
HOOKS (HINGES)
INSTALL
SCREW
IN CASE
TAMPER
TIE WRAP
POINT (2)
BACK
CASE
BACK
CASE
DETAIL A
DETAIL A
MOUNTING
HOLES (4)
MOUNTING
HOLES (4)
ROTATE
FRONT CASE
UPWARD
TO RELEASE
HOOKS
ROTATE
FRONT CASE
UPWARD
TO RELEASE
HOOKS
TIE WRAP
POINTS (2)
TIE WRAP
POINTS (2)
LOCKING
TABS
FRONT
CASE
FRONT
CASE
5100-100-064-V1
LOCKING
TABS
L5210 Wall Mounting
7000-100-013-V1
L7000 Wall Mounting
Desktop Mounting
For desktop mounting, the optional mounting base (model L5000DM OR L7000DM, purchased separately)
must be used.
1.
2.
3.
4.
Slide the Control Panel onto the mounting base locking tabs.
Bring all wiring through the bottom of the mounting base, using one of the wire entry locations, before making
connections to the Control Panel.
Use tie-wraps to secure the wiring to the built-in wire loops as needed.
Use the supplied screws to secure the Control Panel to the mounting base.
-7-
LYNX Touch Installation and Setup Guide
Installing the Control
5201-100-003-V0
7000-100-017-V0
L7000 Desk Mount
L5210 Desk Mount
Wiring Overview
The following summarizes the electrical connections associated with the L5210/L5210CN and
L7000/L7000CN. Refer to the Wiring Connections paragraph and the Summary of Connections diagram on
the inside back cover when making connections.
STANDARD
CAPACITY BATTERY
CONNECTION
SUPER HIGH
CAPACITY BATTERY
CONNECTION
POWER SUPPLY
RECEPTACLE
TELEPHONE
CONNECTIONS
(L5210 ONLY)
COMMUNICATION
MODULE
RECEPTACLE
TERMINAL
STRIP
EDGE
CONNECTOR
EDGE
CONNECTOR
TAMPER
SWITCH
5201-100-006-V1
-8-
LYNX Touch Installation and Setup Guide
Wiring Connections
INCOMING
PHONE LINE
1. Make Earth Ground Connection - The designated earth ground
terminal EGND must be terminated in a good earth ground for the
lightning transient protective devices in this product to be effective.
The following are examples of good earth grounds available at
most installations:
RING
TIP
RED
4
Metal Cold Water Pipe - Secure a non-corrosive metal strap
(copper is recommended) to the pipe that is electrically connected
and secured to which the ground lead is electrically connected and
secured.
Full Line Seizure: The control must be placed in series with the
incoming phone line. Plugging the Direct Connect Cord directly into
the RJ31X jack, allows the control to seize the phone line when an
alarm occurs and normal phone line usage by the premises
phones if the plug needs to be removed.
c. Cut the incoming RING and TIP phone lines (typically red and
green, respectively) and connect them to RJ31X terminals 4
(red) and 5 (green).
GREY
H/S R
H/S T
RED
INCOMING
PHONE LINE
BROWN
DIRECT
CONNECT
CORD
RING
Local Seizure
a. Connect the incoming phone line to the terminals TIP and RING
on the Control as shown on the Summary of Connections.
b. Connect the handset phone lines to terminals H/S T (TIP) and
H/S R (RING) as shown in the diagram.
GREY
RING
TIP
BROWN
7
8
2
1
GREEN
2. Make Phone Line Connections - For local or full line seizure
follow the appropriate steps below.
TO
PREMISES PHONES
6
RJ31X
TIP
AC Power Outlet Ground - Available from 3-prong, 120VAC power
outlets only. To test the integrity of the ground terminal, use a
three-wire circuit tester with neon lamp indicators, such as the UL
Listed Ideal Model 61-035, or equivalent, available at most
electrical supply stores.
a. Connect terminal EGND to a good earth ground as shown on the
Summary of Connections.
GREEN
5
3
TO
PREMISES
PHONES
FULL LINE SEIZURE CONNECTIONS
d. Connect the premises end of the cut RING and TIP wires to
RJ31X terminals 1 (grey) and 8 (brown) respectively.
e. Wire the flying leads of a Direct Connect Cord to the control's
phone terminals as shown in the diagram.
f. Plug the Direct Connect Cord into the RJ31X jack.
HARDWIRED ZONE: If the EOLR is not at the end of the
loop, the zone will not be properly supervised, and the
system may not respond to an open circuit on the zone.
3. Hardwired Zone Connections - One EOLR supervised zone
supports both open circuit and closed circuit devices and has a
response time of 350msec. Maximum zone resistance: 300 ohms,
plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a. Connect sensors/contacts to the hardwired zone terminals GND
(-) and HWZ1 (+). Refer to the Summary of Connections
diagram.
b. Connect closed circuit devices in series in the high (+) side of
the loop. The EOL resistor must be connected in series with the
devices, following the last device.
c. Connect open circuit devices in parallel across the loop. The
2000-ohm EOLR must be connected across the loop at the last
device.
4. AC Power Connections - Connect the Power Supply to the
receptacle on the Control.
OR
Connect wires from the Power Supply to +9VDC and EGND
terminals as shown on the summary of connections diagram.
WIRING TABLE
MAXIMUM DISTANCE BETWEEN
POWER SUPPLY AND CONTROL
Up to 11 feet
Up to 20 feet
Up to 26 feet
-9-
WIRE
GAUGE
# 22
# 20
# 18
5000-100-094-V4
LYNX Touch Installation and Setup Guide
AC Power and Backup Battery
General
The system is powered by a 9 Volt DC, 2.7 Amp Plug-in Power Supply, 300-04705V1, or 300-04065V1 (30004063V1 or 300-04064V1 in Canada). Refer to the wiring table below for wire gauge and length. In the event
of an AC power loss, the system is supported by a long life backup battery that is supervised for connection
and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a “low
battery” message is displayed and a report is sent to the Central Station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping).
Use only the provided 300-04705V1, or 300-04065V1 (300-04063V1 or 300-04064V1 Canada) Power Supply. Do
not plug the power supply into the AC outlet until after all wiring connections have been made. Ensure the
cover is snapped closed prior to applying AC power.
The LYNX Touch is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc.
Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack.
Refer to the appropriate figure for the LYNX Touch L5210 OR L7000 control.
Installing the Rechargeable Backup Battery
1. Remove battery retainer.
2. Insert battery pack into back case.
3. Install battery retainer.
4. Secure battery retainer with the provided screw.
5. Secure battery wiring in the wire routing clips (3).
6. Connect the battery connector to the receptacle on the PC board.
7. After the wiring connection has been made, snap the front and the back case closed.
8. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the system will display “Checking
System Integrity” and then the “System Standby!” screen will be displayed.
Replacing the Rechargeable Backup Battery
1. When battery replacement is required, unplug the power supply from the wall outlet, and open the Control Panel cover.
2. Disconnect the battery pack connector from the receptacle on the PC board.
3. Remove the screw that secures the battery retainer and remove the battery retainer.
4. Remove the battery pack from the back plate.
5. Install a replacement battery pack (P/N 300-0364-1/LYNXRCHKIT-SC OR P/N 300-0366/LYNXRCHKIT-SHA) into the
back case.
6. Route the battery cable through the channel (cutout) on the left side of the compartment.
7. Install the battery retainer.
8. Secure battery retainer with the provided screw.
9. Secure battery wiring in the wire routing clips (3).
10. Connect the battery connector to the receptacle on the PC board.
11. After the wiring connection has been made, snap the front and the back case closed.
12. Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the system will display “Checking
System Integrity” and then the “System Standby!” screen will be displayed.
Ensure the Control Panel assembly is snapped closed prior to applying AC power. Rechargeable batteries
may take up to 48-hours to fully charge. The “Low Battery” message should clear within four hours or by
entering Test Mode.
Battery Selection
The LYNX Touch L5210 and L7000 controls are equipped with an integral, replaceable, rechargeable battery pack
rated at 7.2Vdc. Select the appropriate battery pack, based on the installation’s requirement, and install the battery
pack.
Battery Part Number
300-03864-1/LYNXRCHKIT-SC
300-03866/LYNXRCHKIT-SHA
Battery StandbyTime
4-hours (minimum)
24-hours (minimum)
Low Battery Notification
Approximately 1-hour before battery depletion
At least 1-hour before battery depletion
- 10 -
LYNX Touch Installation and Setup Guide
AC Power and Backup Battery
SCREW
SCREW
RETAINER
RETAINER
BATTERY PACK
(P/N 300-03866/
LYNXRCHKIT-SHA)
BATTERY PACK
(P/N 300-03864-1/
LYNXRCHKIT-SC)
OR
BATTERY
CABLE
CHANNEL
BATTERY
WIRE ROUTING
CLIPS (3)
5000-100-093-V2
L5210 Battery Installation
SCREW
SCREW
RETAINER
RETAINER
BATTERY PACK
(P/N 300-03864-1/
LYNXRCHKIT-SC)
BATTERY PACK
(P/N 300-03866/
LYNXRCHKIT-SHA)
OR
BATTERY
CABLE
CHANNEL
BATTERY
WIRE ROUTING
CLIPS (3)
7000-100-010-V0
L7000 Battery Installation
- 11 -
LYNX Touch Installation and Setup Guide
Installing/Configuring Communication & Home Automation Modules
General
This LYNX Touch controls support Central Station reporting using wireless/cellular (GSM) WiFi and
hardwire (IP) communications modules. They also support upload/download programming capability via the
Internet or a Private local area network (Intranet). This allows site maintenance independent of Central
Station monitoring, and modification to sites globally via the Internet or through a private LAN. Refer to the
instructions provided with the GSM, WiFi or IP Communications Module being installed for additional
information regarding its installation, programming, and registration. Additionally, the installation of a ZWave module allows the control to support Home Automation functions. (refer to the Home Automation
Guide (P/N 800-19979 for additional information.) The controls are compatible with the following AlarmNet
Communications and Home Automation Modules:
• 4GL/4GLC or 3GL/GLC GSM Communication Module
• ILP5 Ethernet Communications Module
• L5100-WiFi WiFi Communications Module
• L5100-ZWAVE Home Automation Module
Refer to the appropriate figure for the LYNX Touch L5210 OR L7000 control when installing the selected
Communication and/or Automation Module(s).
Communications Module 24-Hour Standby Power
If 24-hour standby is required, the Super High Capacity battery (P/N 300-03866/LYNX-RCHB-SHA) must be
installed in the control.
!
RF Exposure
WARNING: The LYNX Touch must be installed to provide a separation distance of at least 7.8 in (20 cm) from
all persons and not co-located or operated in conjunction with any other transmitter except in accordance
with FCC multi-transmitter product procedures.
Connecting and Configuring GSM and IP Communication Modules
Connect and configure the communications GSM or IP module as follows:
Installing the 4GL/4GLC or 3GL/3GLC Communications Module
!
1.
2.
3.
Ensure that SIM card and the connector board are securely installed in the 4GL/4GLC or 3GL/3GLC before
installing the communications module in the LYNX Touch.
Install the communications module into the LYNX Touch control front case. Ensure that the connector board is properly
seated into the receptacle on the control.
Secure the communications module with the three provided screws.
Enable the communications module device, configure alarm reporting and module supervision and register the device.
Refer to the “Program the Communications Module” and “Communications Diagnostics” sections.
The communications module must be registered with AlarmNet before downloading or alarm reporting can
take place.
- 12 -
LYNX Touch Installation and Setup Guide
Installing/Configuring Communication & Home Automation Modules
SCREW
(3)
CONNECTOR
BOARD
CONNECTOR
BOARD
SIM
CARD
ROTATED
180
4GL/4GLC
OR
3GL/3GLC
RECEPTACLE
LYNX TOUCH
L5210
LOCKING TABS
5201-100-009-V1
L5210 GSM Communications Installation
SCREW
(3)
CONNECTOR
BOARD
CONNECTOR
BOARD
SIM
CARD
ROTATED
180
4GL/4GLC
OR
3GL/3GLC
RECEPTACLE
LYNX TOUCH
L7000
LOCKING TABS
L7000 GSM Communications Module Installation
- 13 -
7000-100-015-V2
LYNX Touch Installation and Setup Guide
Installing/Configuring Communication & Home Automation Modules
Installing the ILP5 Ethernet Communications Module
Do not install the ILP5 if the L5100-WiFi communications module is being installed.
!
1.
2.
3.
4.
5.
6.
7.
8.
Ensure that the connector board and cable are securely installed in the ILP5 before installing the
communications module in the LYNX Touch.
Using a wire cutter or knife cut the plastic tabs that secure the ILP5 spacer to the back case of the LYNX Touch.
Remove the ILP5 receptacle knockout from the left side of the LYNX Touch back case.
Install the ILP5 into the LYNX Touch control front case. Ensure that the connector board is properly seated into the
receptacle on the control.
Secure the ILP5 with the three provided screws.
Insert the ILP5 receptacle and spacer into the slot on the back case.
Secure the communications cable to the tie wrap point on the ILP5 with the provided tie wrap.
Connect the Ethernet cable to the RJ45 receptacle.
After closing the panel, enable the ILP5 and configure alarm reporting and module supervision and register the device.
Refer to the “Program the Communications Module” and “Communications Diagnostics” sections.
Alternate Installation (Refer to the Alternate Installation as shown on the figure below)
1. Install the ILP5 into the LYNX Touch control front case. Ensure that the connector board is properly seated into the
receptacle on the control.
2. Secure the ILP5 with the three provided screws.
3. Insert the ILP5 receptacle into the slot on the back case as shown on the figure below.
4. Secure the communications cable to the tie wrap point on the ILP5 with the provided tie wrap.
5. Connect the Ethernet cable to the RJ45 receptacle.
6. After closing the panel, enable the ILP5 and configure alarm reporting and module supervision and register the device.
Refer to the “Program the Communications Module” and “Communications “Diagnostics” sections.
The communications module must be registered with AlarmNet before downloading or alarm reporting can
take place.
ETHERNET CABLE
TO ILP5
RJ45 RECEPTACLE
LYNX TOUCH
REMOVE
ILP5
KNOCKOUT
ALTERNATE INSTALLATION
REMOVE
ILP5
SPACER
ILP5
SPACER
RJ45
RECEPTACLE
CONNECTOR
BOARD
ROTATED
180
TIE
WRAP
(1)
TIE
WRAP
POINT
CONNECTOR BOARD
SCREW
(3)
ILP5
RECEPTACLE
LYNX TOUCH
L5210
5201-100-012-V1
L5210 IP Communications Module Installation
- 14 -
LYNX Touch Installation and Setup Guide
Installing/Configuring Communication & Home Automation Modules
ETHERNET CABLE
TO ILP5
RJ45 RECEPTACLE
LYNX TOUCH
REMOVE ILP5
KNOCKOUT
ALTERNATE INSTALLATION
REMOVE ILP5
SPACER
ILP5 SPACER
RJ45
RECEPTACLE
CONNECTOR
BOARD
ROTATED
180
TIE
WRAP
(1)
TIE
WRAP
POINT
CONNECTOR BOARD
SCREW
(3)
ILP5
RECEPTACLE
LYNX TOUCH
L7000
7000-100-014-V1
L7000 IP Communications Module Installation
Installing the L5100-WiFi module
!
1.
2.
Do not install the L5100-WiFi if the ILP5 Ethernet communications module is being installed.
Install the L5100-WiFi into the LYNX Touch control front case as shown below. Ensure that the receptacle is properly
seated into the edge connector on the right (speaker) side of the control’s circuit board.
After closing the panel, enable the L5100-WiFi module, configure alarm reporting and module supervision and register the
device. Refer to the “Program the Communications Module” and “Communications Diagnostics” sections.
The communications module must be registered with AlarmNet before downloading or alarm reporting can
take place.
Installing the L5100-ZWAVE Home Automation module
1.
2.
Enable the L5100-ZWAVE module. Refer to the “Program the Z-Wave Module”.
Install the L5100-ZWAVE into the LYNX Touch control front case as shown below. Ensure that the receptacle is properly
seated into the edge connector on the left (TELCO terminal) side of the control’s circuit board.
- 15 -
LYNX Touch Installation and Setup Guide
Installing/Configuring Communication & Home Automation Modules
L5100-ZWAVE
RECEPTACLE
RECEPTACLE
EDGE CONNECTOR
L5100-WiFi
EDGE
CONNECTOR
LYNX TOUCH
L5210
5201-100-007-V1
L5210 Z-Wave Automation & WiFi Communications Module Installation
L5100-ZWAVE
RECEPTACLE
RECEPTACLE
EDGE
CONNECTOR
L5100-WiFi
EDGE
CONNECTOR
LYNX TOUCH
L7000
7000-100-016-V1
L7000 Z-Wave Automation & WiFi Communications Module Installation
- 16 -
LYNX Touch Installation and Setup Guide
Installing Wireless Zones
General Information
Zones
The L5210 and L7000 controls respectively support up to 79 and 103 total wireless zones using 5800 Series
transmitters, and wireless buttons.
Range
The built-in RF receiver is capable of detecting signals from wireless transmitters within a nominal range of
200 feet.
Transmitters
5800 Series transmitters have built-in serial numbers that must be entered into the system using the
“Zones” programming section, or input to the control via the downloader. 5800 Series transmitters (except
the 5800RL) do not have DIP switches. Each transmitter's zone number is also programmed into the system
in the “Zones” programming section. Some transmitters, such as the 5816 can support more than one "zone"
(referred to as loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1; the
reed contact is loop 2. Each loop must be assigned a different zone number.
For button transmitters (RF "keys") such as the 5804, a unique zone number must be assigned to each
individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or
input number, which is automatically displayed.
UL
The 5816 Transmitters do not have EOL supervision of their loop wiring, which must not exceed 3 feet.
The 5800PIR-OD, 5800RL, 5800SS1, 5804E, 5804BD, 5804BDV, 5814, 5816TEMP, 5821, 5828/5828V, 5877 and 5878 wireless
transmitters have not been evaluated by UL/ETL.
House Identification
If a 5804BD/5804BDV or 5828/5828V Wireless Keypad is being used in conjunction with the system, a RF
House Code (House ID) Code (01–31) must be programmed, (see the “System Type” programming section) to
establish proper communication, and the keypad must be set to the same code. House ID 00 disables all
wireless keypads. A House ID is not necessary for other 5800 Series transmitters.
Transmitter Supervision
With the exception of some transmitters/keypads that may be carried off-premises (5804BD, 5804BDV and
5804E), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period,
the "missing" transmitter zone number(s) and "Supervision" will be displayed. The supervision for a
particular transmitter in the system that may also be carried off the premises may be turned off by entering
it as an Unsupervised type, as described in the “Program Zones” section. 5800 Series transmitters have
built-in tamper protection and will annunciate as a fault condition if covers are removed. In Canada the RF
supervision period is 3-hours for Fire zones and 12 hours for all other zone types.
Transmitter Input Types
Each of the transmitters has one or more unique factory-assigned input (loop) ID codes. Each of the inputs
requires a programming zone (e.g., a 5804's four inputs require four button zones). Transmitters can be
entered as one of the following types (see transmitter’s instructions for appropriate input type):
Type
Supervised
Unsupervised
(Unsupervised) Button
Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals. The transmitter must
remain within the receiver's range.
Sends periodic check-in signals, as well as fault, restore, and low battery signals, but the control does
not supervise the check-in signals. The transmitter may be carried off-premises.
Sends only fault signals. Transmitters do not send low battery signals until they are activated. The
transmitter may be carried off-premises.
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage,
and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well
as large swings in temperature may all reduce the actual battery life in a given installation. The wireless
system can identify a true low battery situation, thus allowing the dealer or user of the system time to
arrange a change of battery and maintain protection for that point within the system.
• Button-type transmitters should be periodically tested for battery life. The 5804BD, 5804BDV, and
5804E button transmitters have replaceable batteries.
- 17 -
LYNX Touch Installation and Setup Guide
Installing Wireless Zones
RF Sniffer Test Mode
This mode is used after all transmitters have been entered to check that all transmitters have been properly
programmed. Sniffer mode does not automatically expire. Sniffer mode must be manually exited to return to
normal operation.
SCREEN
ACTION
Test
5000-100-096-V0
RF Sniffer
Test
5000-100-102-V0
Notes: (1)
(2)
(3)
(4)
1. At the Tools Screen, select “Test”. The following options are displayed.
Walk Test
RF Sniffer Test
Go-No-Go Test
Dialer Test
2. Select “RF Sniffer Test” from the options.
Note: If the communicator is in the process of sending a report to the Central Station, the
system will not go into the Sniffer mode. If so, wait a few minutes and try again.
3. The system displays all programmed zone numbers and zone descriptors, which have a
non-zero Zone Type. Fault each transmitter in turn, causing each one to send a signal. As
the system receives a signal from each of the transmitters, the zone number of that
transmitter disappears from the display. The transmitters may be checked upon installation,
or in an installed system. The system will beep once every 30-40 seconds while the RF
Sniffer Test mode is active.
4. When all transmitters have been checked, Exit RF Sniffer Test mode by depressing the
Home key and entering the Installer or a User Code.
All button-type units must physically be activated to clear the display, since they do not automatically send check-in signals.
When one button of a button type, supervised or unsupervised RF transmitter is activated, all zones assigned to other buttons
on that transmitter are cleared. This also applies to 5816 transmitters that have multiple loops (zones).
Any transmitter that is not “entered” will not turn off its zone number.
For SIA installations, the following devices may be used as specified for panic (24-hour) alarm response:
• wireless keys which have two-button panic pairs available (e.g., 5804BDV), on which only the two-button panic pairs may be
programmed for any 24-hour alarm response
• wireless keypads (e.g., 5828/5828V) keypads that have a two-second delay on the special function keys, or two-button panic
pairs
• built-in keypad panic key
Go-No-Go Test Mode
Conducting this test with your hand wrapped around the transmitter will cause inaccurate results.
On button type transmitters that have been programmed to set ARM AWAY, ARM STAY, or DISARM, pressing a
button will take the system out of the Go-No-Go Test mode causing the programmed action to occur.
The Go-No-Go tests will verify adequate RF signal strength from the proposed transmitter location, and
allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently.
This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This
will enable you to make sure that the RF signal from each transmitter is received with sufficient signal
amplitude when the system is in the normal operating mode.
SCREEN
ACTION
1. At the Tools Screen, select “Test”. The following options are displayed.
Test
5000-100-096-V0
2.
3.
Go-No-Go
Test
5000-100-103-V0
4.
5.
6.
Walk Test
RF Sniffer Test
Go-No-Go Test
Dialer Test
Select “Go-No-Go Test”.
Once all transmitters have been placed in their desired locations, and the approximate
length of wire to be run to sensors is connected to the transmitter's screw terminals (if
used), fault each transmitter.
a. The keypad beeps three times indicating signal reception, displays the appropriate
zone number and announced the zone description.
b. If the keypad does not beep, reorient or move the transmitter to another location.
Usually a few inches in either direction is all that is required.
If each transmitter produces the proper keypad response when faulted, they can be
permanently mounted according to their respective instructions.
The system will beep once every 30-40 seconds while the Go-No-Go Test mode is active.
Exit Go-No-Go Test mode by depressing the Home key and entering the Installer or a
User Code.
- 18 -
LYNX Touch Installation and Setup Guide
Installing Wireless Zones
5800 Series Transmitter Loop Numbers
(Refer to this information when programming transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop
designations.
LOOP
1
LOOP 1
LOOP
1
LOOP 1
(LOW
SENSITIVITY
LOOP 1
(LOW
SENSITIVITY
LOOP 2
(HIGH
SENSITIVITY)
LOOP 2
(HIGH
SENSITIVITY)
LOOP 3 (TEMP)
LOOP 3 (TEMP)
LOOP 4 (TAMPER)
LOOP 4 (TAMPER)
5800PIR-RES
ENROLL AS
SUPERVISED
LOOP 3
LOOP 4
OF
F
LOOP 1
LOOP
3
5 8 0 0 WAV E
P RO G R A M
HOUSE ID
5804E
ENROLL AS BUTTON
LOOP 2
(REED)
5 8 0 4 B D / 5 8 0 4 B DV
ENROLL AS BUTTON
PROGRAM HOUSE ID
LOOP 1
5816MN
ENROLL AS
SUPERVISED
5818MNL
ENROLL AS
SUPERVISED
AR
Y
MIC
SERIAL #2
LOOP 4
ME
SSAG
E
SERIAL #1
LOOP 4
SERIAL #2
LOOP 2
5822T
ENROLL AS
SUPERVISED
5828/5828V
P RO G R A M
HOUSE ID
LOOP 1
(HIGH
SECURITY)
5834-2
ENROLL AS BUTTON
SERIAL #1
LOOP 3
AW
AY
SERIAL #1
LOOP 4
LOOP 2
(STANDARD
SECURITY)
SERIAL #1
LOOP 2
1
2
SERIAL #2
LOOP 3
LOOP 3 (TILT MODE)
3
4
SERIAL #1
LOOP 1
5877
5878
ENROLL AS BUTTON
SERIAL #1
LOOP 1
5834-4
ENROLL AS BUTTON
5853
ENROLL AS
SUPERVISED
5869
ENROLL AS
SUPERVISED
LOOP 1
(LOW SENSITIVITY)
LOOP 2
(HIGH SENSITIVITY)
SERIAL #2
LOOP 2
LOOP 4 (TAMPER)
5870API
ENROLL AS
SUPERVISED
ST
AY
5820L
ENROLL AS
SUPERVISED
LOOP 1
SERIAL #2
LOOP 3
D
AD
5821
ENROLL AS
SUPERVISED
5819S (WHS & BRS)
ENROLL AS
SUPERVISED
SERIAL #2
LOOP 1
ME
LOOP 3
LOOP 1
LOOP 1
(INTERNAL
SHOCK
SENSOR
LOOP 1
(TERMINALS)
5819
ENROLL AS
SUPERVISED
SERIAL #1
LOOP 2
RE
LOOPS
1-3
LOOP 3
(TERMINALS)
SERIAL #2
LOOP 1
SERIAL #1
LOOP 3
LOOP 2
(REED)
5811
ENROLL AS
SUPERVISED
LOOP 3
(TERMINALS)
LOOP 1
(TERMINALS)
5816
ENROLL AS
SUPERVISED
5809
ENROLL AS
SUPERVISED
5806/5806W3/5807
5808/5808LST/5808W3
ENROLL AS
SUPERVISED
LOOP 2
(REED)
ALTERNATE
POSITION
FOR LOOP 2
5814
ENROLL AS
SUPERVISED
LOOP 1
LOOP 1
•
•• •••
••• • •
• ••
LOOP 2
(REED)
LOOP 1
(TERMINALS)
LOOP 1
LOOP 1
LOOP 4
LOOP
1
5800SS1
ENROLL AS
SUPERVISED
5800RL
SET HOUSE ID
LOOP 2
LOOP 2
LOOP 1
••
•
••
LOOP
1
ON
5800PIR-OD
ENROLL AS
SUPERVISED
5800PIR/5800PIR-COM
ENROLL AS
SUPERVISED
5898
ENROLL AS
SUPERVISED
5800-002-V3
5800Micra
ENROLL AS
SUPERVISED
5800CO
ENROLL AS
SUPERVISED
Notes: (1) The 5806W3 smoke detector must be used in SIA applications.
(2)
(3)
(4)
(5)
Button type devices send only fault and low battery signals; no restore or check-in signals.
Supervised devices send periodic check-in signals, faults, restore and low battery signals.
Unsupervised devices send periodic check-in signals, faults, restore and low battery signals but the control does not supervise
the check-in signals.
If an external sounder is required, the 5800WAVE should be used.
The 5804E and 5834-4 encrypted (High-Security) devices must be activated while the system is in Go-No-Go Test Mode. Refer
to the transmitter’s Installation Instructions for complete details. The system will confirm the enrollment of the encrypted device
by beeping two times
The 5800PIR-OD, 5800RL, 5800SS1, 5804E, 5804BD, 5804BDV, 5814, 5816TEMP, 5821, 5828/5828V, 5877, and 5878
wireless transmitters have not been evaluated by UL/ETL.
- 19 -
LYNX Touch Installation and Setup Guide
Mechanics of Programming
Navigating Menus
Touchscreen Display
LYNX Touch’s Liquid Crystal Display (LCD) touch-screen displays variable icons and text on “screens”. The
screen displays status icons and associated text, the current time and date, system status information and
menu choices. The Menu area includes a list of commands, or choices that apply to the current selection. The
status area provides information about various system events and a colored bar also provides an indication
of system status. A “Home Screen” is displayed whenever power is applied to the system. In addition, the
“Home” Function key is lit Green when the system is ready or flashes when it is not. When the system is
Armed the “Panic” Function and “Home” Function keys are both lit red.
WiFi
STATUS
SYSTEM
STATUS
Ready To Arm
12:35
Security
Automation
Video
PM
January 12, 2010
Notices
HOME
FUNCTION
KEY
PANIC
FUNCTION
KEY
70000-100-012-V2
L5210/L7000 Home Screen
Key
Description
Panic key - Initiates panic alarm options when depressed for 4 seconds.
Home key - Used to exit from a screen or return to the home screen
- 20 -
LYNX Touch Installation and Setup Guide
Mechanics of Programming
Navigation Keys
Navigating through the screens is accomplished by lightly touching the icons or menu items on the touchscreen. Once activated, the control advances to the next screen. Selecting the “Home” (cancel) key or the “”
Key will return you to the previous screen at any time unless System Programming mode is active. By
touching (selecting) an icon or key the system, depending on the function, advances to another screen,
toggles between options or scrolls through multiple options that can be selected. The system provides a
prompt when a specific input is required.
Note:
You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow
you to clearly hear the feedback announcements or system beeps from the system’s built-in speaker. To
adjust the volume, select “More” on the “Security Screen” and then select “Settings”. Adjust the volume
using the slide displayed on the Settings screen and then select “Save” to accept. Upon exiting the
Program Mode, the system resets the volume to the default value (mid-level).
Home Screen
System Status is displayed at the top of screen. In addition to the system status, the Home Screen displays
the current date and time and Security, Automation, Video and Notices icons. When Total Connect Services
are connected and web content is enabled, Weather, News, Traffic and Notices icons are displayed along
with the current weather forecast and a 5-Day Forecast button.
Ready To Arm
12:35 PM
October 1, 2013
Mostly Sunny
Security
Automation
Video
News
Traffic
Notices
68 F
Feels Like 71
F
5-Day Forecast
5200-100-001-V0
Home Screen with Total Connect Services
Icon or Button
Security
Automation
Video
News
Traffic
Notices
Weather
5-Day Forecast
Function
Provides access to Security Screen
Provides access to Automation Screen
Provides access to Video Screen
Provides access to News Screen
Provides access to Traffic Screen
Provides access to Dealer Notification Message Screen
Provides local forecast and severe weather alerts
Provides access to local 5-Day Weather Forecast Screen
- 21 -
LYNX Touch Installation and Setup Guide
Mechanics of Programming
Navigating Menus
Security Screen
System Status is displayed at the top of each screen and the time and date are displayed at the bottom of the
Security Screen. The Security menu Screens differ between the LYNX Touch L5210 and the L7000 versions.
Refer to the paragraphs below for additional information.
Security Menu
The Security Screen consists of two pages. The first page displays the system status and selection “icons”
and “tabs”. The displayed pages and options may vary slightly depending upon the devices and services that
are installed in or connected to the system.
Selection
Zones
System
Arm Away
Arm Stay
Message
Phone
Delay/Instant
More
Function
Provides access to Zone information and options.
Provides information about system status
Used to Arm the system in Away mode (displayed on both Home Screen pages).
Used to Arm the system in Stay mode (displayed on both Home Screen pages).
Provides access to Message Center.
Provides access to Speaker Phone mode. (if programmed L5210 only)
Used to toggle between exit delay and instant arming options
Advances system to second page of the Home Screen.
The second page also displays the system status and additional selection “icons” and “tabs”.
Selection
Tools
Arm Away
Arm Stay
Settings
Delay/Instant
Back
Function
Provides access to Installer and User Programming Menus (Master Code required for access).
Used to Arm the system in Away mode (displayed on both Home Screen pages).
Used to Arm the system in Stay mode (displayed on both Home Screen pages).
Provides access to various keypad functions (i.e.; Brightness, Contrast, Volume, Voice, Chime & Ringer).
Used to toggle between exit delay and instant arming options (displayed on both Home Screen pages).
Returns system to first page of the Home Screen.
Installer Tools Menu
The Tools/Installer Menu provides access to the
Installer configurable features and displays six
options. Entering the Installer Code is required to
access the Installer Menu.
System Programming...
Note: For information regarding the Rules, Events and
Schedules programming screens, refer to the User
Manual.
Program
Test
Rules
Events
Initiate
Downloads
Schedules
5200-100-092-V0
Installer Tools Menu Page
User Tools Menu
The User Menu provides access to the User
configurable features and displays eight options.
Entering the Master Code is required to access the
User Menu.
Ready To Arm
Users
Events
Test
Keypad
Date Time
Reminders
Slide Show
WiFi Config
Back
5100-100-006-V0
User Tools Menu Page
- 22 -
LYNX Touch Installation and Setup Guide
Mechanics of Programming
General Programming Information
When power cycling the control, remove AC power first and wait approximately 1 minute before
disconnecting battery.
Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The
system can be programmed at any time, even at the installer's premises prior to the actual installation.
Simply apply power temporarily to the Control and then program the unit as desired.
The “Initiate Download” button is used to initiate remote programming using an IBM PC compatible
Personal Computer, and Compass Downloader and modem (L5210 only) or via capable GSM or IP
communications modules (L5210 and L7000). See the Remote Programming/Control (Downloading) section
for additional information.
Programming
If the system is Armed or in Alarm, the Tools icon will not be functional. The system must first
be disarmed.
Enter Installer Programming Mode
SCREEN
ACTION
1.
System Standby!
Security
Automation
Video
10:00
January, 1, 2014
7000-100-011-V1
System Standby Screen
System Programming...
Program
Test
Rules
Events
Initiate
Downloads
Schedules
Power-up the control and allow it to “boot-up”. “System
Standby” is displayed on the touch screen. When the
“boot-up” is complete (approximately 1-2 minutes) “Ready
to Arm” is displayed.
2. Select the “Security” icon.
3. Select the “More” tab on the first page of the Security
Screen.
4. Select “Tools” icon.
5. Enter the Installer Code 4112 on the displayed keypad.
6. The Installer Tools menu screen appears. Select the
“Program” button. “System Programming…” is displayed
and the “Panic” function key is lit red and the “Home”
function key alternately flashes red and green.
7. Select one of the following options:
Installer Code
System Type
Date Time
Communicator
Zones
Comm. Diagnostics
Keys
Reporter
Use the down arrow to scroll to the next page of
options.
Sounder
System Settings
Default Config.
Language*
Reset Master Code
Z-Wave
8. The system advances to the Programming screen of the
selected option.
* This programming field may not be available with the system
being installed.
5200-100-092-V0
Installer Tools Menu Screen
- 23 -
LYNX Touch Installation and Setup Guide
Mechanics of Programming
Loading Factory Defaults
To load the factory defaults, enter the Installer Programming Mode and advance to second page of the
System Programming and refer to following procedure. Refer to the Programming Default Values section of
this manual to view the Default Values.
If a default configuration is loaded, any data that has already been programmed into the system will be
changed according to the default configuration selected!
Select a Default Configuration
SCREEN
ACTION
System Programming...
1. Select “Default Configuration” to display the following options:
Default Config 1
Default Config 2
Default Config 3
Default Config 4
Default Downloader
Note: For a list of the pre-programmed defaults refer to the
Default Values section.
2. Select the desired Default Configuration.
3. A Confirmation screen is displayed.
4. If “Yes” is selected, the System beeps three times and returns
to the Default option screen.
5. If “No” is selected, the System returns to the Default option
screen.
Sounder
System Settings
Default Config.
Language
Reset Master Code
Z-Wave
5100-100-060-V0
Exiting Programming Mode
1. Select the “” key to exit the current screen. The system returns to the previous screen.
2. Select the “” key as required until system displays a Confirmation screen.
3. Select “Yes” to allow the installer to re-enter Programming mode or “No” to prevent re-entry.
4. Select the “” key again to return to the Security Screen OR depress the Home button to return to the
Home Screen.
- 24 -
LYNX Touch Installation and Setup Guide
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type
Not Used
Entry/Exit 1
(Burglary)
Function
Characteristics
Used to program a zone that is not used.
Usually assigned to sensors or contacts on
primary entry and exit doors.
•
•
•
•
•
•
•
•
•
•
Entry/Exit 2
(Burglary)
Usually assigned to sensors or contacts on
secondary entry and exit doors that might be
further from the keypad (typically used for a
garage, loading dock, or basement door).
Perimeter
(Burglary)
Interior, Follower
24-hour Silent
Alarm
Usually assigned to all sensors or contacts on
exterior doors and windows
Usually assigned to a zone covering an entry area
(i.e.: foyer, lobby, or hallway) that one must pass
upon entry (after faulting the entry/exit zone) to
reach the keypad. It provides an instant alarm if
the entry/exit zone is not violated first, and protects
an area in the event an intruder has hidden on the
premises before the system is armed, or gains
access to the premises through an unprotected
area.
Usually assigned to a zone that covers a sensitive
area (i.e.: stock room, drug supply room, etc.) It
can also be used on a sensor or contact in an area
where immediate notification of an entry is desired.
Usually assigned to a zone containing an
Emergency button (silent emergency).
24-hour Audible
Alarm
Usually assigned to a zone containing an
Emergency button (audible emergency).
24-hour
Auxiliary Alarm
Usually assigned to a zone containing a button
for use in personal emergencies or to a zone
containing monitoring devices (i.e.: water or
temperature sensors, etc.).
Provides entry delay (using the programmed entry
time), if tripped when the panel is armed in the
Away mode. Bypassed when the panel is armed in
the STAY or STAY INSTANT mode.
Trouble by Day/
Alarm by Night
Interior with Delay
Fire No Verification
Fire with
Verification
24-hour Carbon
Monoxide Monitor
Can be assigned to any wireless zone used as a
fire zone. This zone type is always active and
cannot be bypassed.
Can be assigned to any wireless zone used as a
fire zone. Fire with verification is available with
smoke detector device type. It can not be used
with heat detectors, combination heat/smoke
detectors, wireless sensors or fire pull stations.
This zone type is always active and cannot be
bypassed.
•
•
•
•
•
•
None
Entry delay #1 is programmable.
Exit delay is independently programmable.
Exit and entry delays when armed in AWAY, STAY or NIGHT STAY
mode.
No entry delay when armed in STAY INSTANT or AWAY INSTANT
mode.
Exit delay regardless of the arming mode selected.
Entry delay #2 is programmable.
Exit delay is independently programmable.
Secondary entry delay, if armed in the AWAY or STAY mode.
No entry delay when armed in the STAY INSTANT or AWAY
INSTANT mode.
Exit delay begins regardless of the arming mode selected.
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY,
NIGHT STAY or AWAY INSTANT mode.
Delayed alarm (using the programmed entry/exit time) if entry/exit
(types 01 or 02) or interior-with-delay (type 10) zone is faulted first.
Instant alarm in all other situations.
Active when armed in AWAY or AWAY INSTANT mode.
Bypassed automatically when armed in STAY, NIGHT STAY or
STAY INSTANT mode.
• Instant alarm, when armed in AWAY, STAY, NIGHT STAY , STAY
INSTANT, or AWAY INSTANT (night) mode.
• Provides a latched trouble sounding from the keypad and, if desired,
a Central Station report when disarmed (day).
• Sends a report to the Central Station but provides no keypad display
or sounding.
• In disarmed state sends a report to the Central Station displays "Not
Ready to Arm" on the keypad and “AWAY”, “STAY” and “TOOLS”
buttons are disabled.
• Follows sounder timeout
• Sends a report to the Central Station, and provides alarm sounds at
the keypad.
• Sends a report to the Central Station and provides an alarm sound at
the keypad. (There is no keypad timeout.)
• Entry delay #1 (with programmed entry time) when armed in the
AWAY mode.
• Entry delay begins whenever sensors in this zone are violated,
regardless of whether an entry/exit delay zone was tripped first.
• No entry delay when armed in the AWAY INSTANT mode.
• Exit delay regardless of the arming mode selected.
• Alarm sound will pulse (Temporal Fire) when this zone type is
alarmed.
• Alarm sound will pulse (Temporal Fire) when this zone type is
alarmed. Only after the alarm has been verified.
• System verifies alarm by delaying reporting and Control Panel alarm
sounding for 30 seconds after alarm is detected. If the zone remains
faulted after 30 seconds a fire alarm is provided. If any other fire
zone is faulted during the 30 second delay window a fire alarm is
immediately provided for that zone. An alarm for original fire zone will
also be provided if that zone is still faulted afterward. If there are no
fire alarms after the 30 second delay expires, the system will open a
60 second window. If any fire zone is faulted during that window a
fire alarm will immediately be provided for that zone.
Can be assigned to any wireless zone with a carbon • Local keypad and detector will sound when this zone type is alarmed.
monoxide detector. This zone type is always active
(Pulse Temporal 4)
and cannot be bypassed.
- 25 -
LYNX Touch Installation and Setup Guide
Zone Response Type Definitions
Type
Arm–Stay
Arm–Away
Disarm
No Alarm Response
Function
Characteristics
Special-purpose zone type used with 5800 Series
wireless button units.
Special-purpose zone type used with 5800
Series wireless button units.
Special-purpose zone type used with 5800
Series wireless button units.
Assigned when no-alarm response is required
Silent Burglary
Usually assigned to sensors or contacts on
exterior doors and windows where sirens are NOT
desired.
Monitor
Can be assigned to any wireless zone used for
asset protection. Works as a dynamic monitor of a
zone fault/trouble (not alarm).
General Monitor
Assigned sensors or contacts on doors and
windows or asset protection within the premises.
Used to track activity of the occupant and alert
occupant of the activity of others.
General Response
Assigned sensors or contacts on doors and
windows or asset protection within the premises.
Used to track activity of the occupant and alert
occupant of the activity of others.
• Exit delay regardless of the arming mode selected.
• System is armed in the STAY mode when the zone is activated.
• System is armed in the AWAY mode when the zone is activated.
• Disarms the system when the zone is activated.
No reports to the Central Station.
No keypad sounding or chime
System can still be armed
No display on the screen
Instant alarm, with NO audible indication when armed in the AWAY,
STAY, STAY NO DELAY, NIGHT STAY, or AWAY INSTANT mode.
• Report sent to the Central Station.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Resident Monitor
Resident Response
Used to monitor a resident in an area deemed to
be dangerous by a caregiver.
Used to monitor a resident in an area deemed to
be dangerous by a caregiver. Requires
acknowledgement by caregiver.
•
•
•
•
•
•
•
•
•
Trouble
Used with Other response type
Garage (Burglary)
Assigned to Automatic Garage Door applications.
Provides a status of the garage door close/open
real time state
Garage Monitor
Assigned to Automatic Garage Door applications.
Provides a status of the garage door close/open
real time state
Reports to the Central Station, if enabled.
Fault/restore events are logged by the system.
Activity Zone No. and Zone Descriptor displayed on LCD.
Restore will be stored in event log.
No keypad sounding or chime
System can still be armed
No reports to the Central Station.
Fault/restore events are logged by the system.
Monitors entry into a monitored area. Activates a one-time
announcement when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
No reports to the Central Station.
Fault/restore events are logged by the system.
Monitors entry into a monitored area. Activates a zone announcement
when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
System re-triggers audible sounding every ten seconds until
acknowledged (Off sequence or wireless button).
No reports to the Central Station.
Monitors entry into a monitored area. Activates a zone announcement
when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
Fault/Restore events are not logged by the system.
No reports to the Central Station.
Monitors entry into a monitored area. Activates a zone announcement
when faulted.
Activity Zone No. and Zone Descriptor displayed on LCD.
System re-triggers audible sounding every ten seconds until
acknowledged (Off sequence or wireless button).
Fault/Restore events are not logged by the system
• The system will provide a trouble sounding from the keypad (and a
Central Station report, if desired).
• Associated With Entry Delay #2 Programmed Time.
• Exit delays when armed in AWAY, STAY or NIGHT STAY mode.
• No Entry Delay when armed in Away or Stay Instant modes.
• System can be armed with zone in the faulted state. When the zone is
closed it will automatically be inclusive within protection points. If the
point is subsequently violated, it will initiate an alarm.
• Can be assigned to any wireless zone used for automatic “Garage
Door” Open/Close status.
• Will not initiate an alarm condition on the control.
• When zone is in the open state will display “FAULT.”
• Does not report alarms to Central Station.
• Zone will chime if enabled to do so
• System can be armed if this zone type is in fault
- 26 -
LYNX Touch Installation and Setup Guide
Programming the Control
After entering the System Programming mode select from the options provided on the First and Second
Installer Programming tools screens as shown in the accompanying figure.
System Programming...
System Programming...
Installer Code
System Type
Sounder
System Settings
Date Time
Communicator
Default Config.
Language
Zones
Comm. Diagnostics
Reset Master Code
Z-Wave
Keys
Reporter
5100-100-060-V0
5000-100-013-V1
Page 1
Page 2
Enter Installer Programming Mode without using Installer Code
SCREEN
ACTION
1.
System Standby!
Security
Automation
Video
10:00
January, 1, 2014
2.
3.
4.
5.
During the initial system power-up initialization delay
(while "SYSTEM STANDBY!" is displayed), depress the
Home key. Wait for system to terminate the system
initialization delay.
Select the “Security” icon.
Select the “Arm Stay” icon.
Press the “Clear” key on the displayed keypad. A blue
vertical bar is displayed below the “Enter Code”.
Enter “00” on the keypad. The system will enter Installer
Programming mode and the Installer Tools Menu will be
displayed.
7000-100-011-V1
Change Installer Code
The factory default Installer Code for the LYNX Touch Control is set to 4-1-1-2.
SCREEN
ACTION
1.
Installer Code
2.
5000-100-129-V0
3.
4.
Select “Installer Code”. The current four-digit Installer Code is displayed on the left side
of the screen.
Select the “Clear” button, then enter a new four-digit Installer Code on the displayed
keypad. The system will display the new code on the left side of the screen.
Select “Done” when you are finished.
The system returns to the “System Programming” Screen.
Select a Language
Note: This programming field may not be available with the system being installed.
SCREEN
ACTION
System Programming...
Sounder
System Settings
Default Config.
Language
Reset Master Code
Z-Wave
5100-100-060-V0
1. If applicable, select “Language” to display the following
options:
Installer Language
User Language
2. Select “Installer Language. The system toggles between
“English” and “French”.
3. Select the desired language.
4. Select “User Language. The system toggles between
“English” and “French”.
5. Select the desired language.
6. Select “Save” when you are finished.
7. A confirmation screen appears. If “Yes” is selected, the
System returns to the second page of the Programming
screen, which will be displayed in the selected language.
- 27 -
LYNX Touch Installation and Setup Guide
Programming the Control
System Type
The following system options are programmed in this section:
Option
RF Jam
Speaker Phone
Two Way Voice
RF House Code
Remote Phone
Function
Enable or disable RF Jam Log and Reporting
Enable or disable Speaker Phone mode. (Only available on the LYNX Touch L5210/L5210CN)
Enable or disable Two Way Voice communication with the Central Station.
Set RF House Code. (Bi-directional RF Devices)
Enable or disable Remote Phone Control mode. (Only available on the LYNX Touch L5210/
L5210CN)
Enable or disable Phone Notification mode. (Phone Line-cut) (Only available on the LYNX Touch
L5210/ L5210CN)
Select a delay period between phone line-cut & system response (allows phone to restore) (Only
available on the LYNX Touch L5210/ L5210CN)
Phone Notification
Phone Detect Time
Note: This field is displayed if Phone Notification is enabled.
Events
Non-Security
Remote Access
Serial
Multi Mode Serial
Enable or disable multiple options for event logging (i.e.; alarms, troubles, open/close, bypass, all)
Enable or disable non-security event logging
Enable or disable end user to access their system via a website
Enable or disable transmission of panel status events via email (Active only when Remote Access
Serial is enabled)
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless
otherwise noted.
Screen
ACTION
System Type
5000-100-130-V0
RF Jam
Disabled
Speaker Phone
Disabled
Two Way Voice
Disabled
RF House Code
0
Remote Phone
Enabled
System Type
Note: If applicable, the pre-programmed default will be displayed beneath the option.
1. Select “System Type” from the following options:
RF Jam
Speaker Phone
Two Way Voice
RF House Code
Phone Notification
Remote Phone
Phone Detect Time
Use the down arrow to scroll to the next page of options.
Events – Log All
Events – Log Alarm
Events – Log Bypass
Events – Log Open/Close
Events – Log Trouble
Non Security
Remote Access Serial
Multi Mode Serial
2. Select “RF Jam”. The System scrolls between the following:
Disabled
RF Jam Log
RF Jam Log & Report
Note: The Speaker Phone field is not available on the LYNX Touch L7000/L7000CN.
3. Select “Speaker Phone”. The System toggles between the following:
Disabled
Enabled
4. Select “Two-Way Voice” .The System toggles between the following:
Disabled
Enabled
5. Select “RF House Code”.
6. After entering a code (00-31) on the displayed keypad, select “Done”.
Note: The Remote Phone field is not available on the LYNX Touch L7000/L7000CN.
7. Select “Remote Phone”. The System toggles between the following options:
Disabled
Enabled
- 28 -
LYNX Touch Installation and Setup Guide
Programming the Control
System Type (Continued)
Screen
ACTION
Phone Notification
Note: The Phone Notification field is not available on the LYNX Touch L7000/L7000CN.
8. Select “Phone Notification” (phone line cut). The System scrolls between the following
options:
Disabled
Keypad
Trouble
If “Keypad” or “Trouble is selected proceed to Step 8.
Note: The Phone Detect Time field is not available on the LYNX Touch L7000/L7000CN.
9. If Keypad or Trouble was selected in Step 7, the “Phone Detect Time” option is displayed.
Select “Phone Detect Time”. The system scrolls between the following options:
1 Minute
2 Minutes
3 Minutes
4 Minutes
Disabled
Phone Detect Time
2 Minutes
Events - Log All
Log All Set
Events – Log Alarm
Enabled
Use the down arrow to scroll to the next page of options.
10. Select “Events - Log All”. The system displays “Press To Log All”. Selecting this option
programs the system to log all events and “Log All Set” is displayed. Additionally all of the
options listed below are enabled.
Events – Log Alarm
Events – Log Bypass
Events – Log Open/Close
Events – Log Trouble
Non-Security
OR
Proceed to step 11 and select the options individually.
11. Select “Events – Log Alarm”. The System toggles between “Enabled” and “Disabled.
12. Select “Events – Log Bypass”. The System toggles between “Enabled” and “Disabled”.
13. Select “Events – Log Open/Close”. The System toggles between “Enabled” and
“Disabled”.
14. Select “Events – Log Trouble”. The System toggles between “Enabled” and “Disabled”.
Non Security
15. Select “Non Security”. The System toggles between “Enabled” and “Disabled”.
Enabled
Remote Access Serial
Disabled
Multi Mode Serial
Disabled
16. Select “Remote Access Serial”. The System toggles between “Enabled” and “Disabled”.
If the Remote Access Serial” option is enabled, the “Multi Mode Serial” option is
displayed.
Note: The Multi Mode Serial field is “Disabled” unless the Remote Access Serial field has
been set to “Enabled”.
17. Select “Multi Mode Serial”. The System toggles between “Enhanced Reports” and
“Disabled”.
18. Select “Save” when complete.
- 29 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Date and Time
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
SCREEN
ACTION
Note: If you are installing a 4GL/4GLC or 3GL/3GLC, L5100-WiFi or ILP5
Communication Module, the time and date will be programmed and
updated automatically via Central Station. You must still program the
correct Time Zone below.
1. Select “Date Time”.
Date Time
5000-100-131-V0
System Programming...
June
SUN
MON
2.
Using the left ⊳ and right arrows select the Month and Year then
select the date. Select the key to advance to the next screen.
3.
To set the correct time, touch the “Clear” button.
4.
Enter the correct time and then select AM or PM. Select the key to
advance to the next screen or select “Save” to return to the System
Programming Screen.
2010
TUE
1
WED
THU
FRI
SAT
2
3
4
5
12
6
7
8
9
10
11
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Save
5000-100-016-V0
System Programming ...
Enter Time
10:21
AM
1
2
3
4
5
6
7
8
9
Clear
0
AM / PM
Save
5000-100-010-V0
Time Zone
Eastern (EST)
Day Light Savings Time
Yes
Start Month
March
Start Week
Second
End Month
November
End Week
First
6. Select “Time Zone”. The system scrolls between the following options:
Eastern (EST)
Pacific (PST)
Atlantic (AST)
Central (CST)
Alaska (AKST)
Newfoundland (NT)
Hawaii (HAST)
Brasilia (BRT)
Mountain (MST) Mid-Atlantic (MAT)
7. Select “Day Light Savings Time”. The system toggles between “Yes” and
“No”. If “Yes” is selected the following options will become active.
8. Select “Start Month”. The system displays the following options.
January
February
March
April
May
June
July
August
Use the down arrow to scroll to the next page of options.
September
October
November
December
9. Select “Start Week”. The system scrolls between the following options.
First
Fourth
3rd from Last
Second
Last
Third
Next to Last
10. Select “End Month”. The system displays the following options.
January
February
March
April
May
June
July
August
Use the down arrow to scroll to the next page of options.
September
October
November
December
11. Select “End Week”. The system will scrolls through the available weeks.
First
Fourth
3rd from Last
Second
Last
Third
Next to Last
12. After programming these options, select the “Save” key.
- 30 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program the Communications Module
A router is required if you are installing the L5100-WiFi module. The router must be powered on and
connected for WiFi operation (alarm reporting) to occur.
The following system options are programmed in this section:
Option
Communications Path
APL
City ID
CS ID
Sub ID
Supervision
Old Alarm Time
Remote Acc. Comm.
Multi Mode Comm.
IP Fault Time
Function
Selects type of Communications Module
Enables Advanced Protection Logic
Enter Central Station Primary City ID
Enter Primary Central Station ID
Enter Central Station Primary Subscriber ID
Selects how often the Communications Module sends supervisory messages to the Central Sta.
Selects how long an undeliverable alarm delivery is retried to the Central Station.
Enables or disables user remote access via internet and/or GSM.
(appears only if Remote Access IP or GSM is enabled.) Enables or disables multi mode feature.
(Appears only if IP or WiFi is enabled in Communications Path field.) Selects time delay before
the Communications Module notifies the Control Panel of a loss of contact with the internet.
Dynamically selects the IP addresses
(Appears only if “No” is selected in Use DHCP field.) Enter NIC IP Address.
(Appears only if “No” is selected in Use DHCP field.) Enter Subnet Address.
(Appears only if “No” is selected in Use DHCP field.) Enter Gateway IP Address
(Appears only if “No” is selected in Use DHCP field.) Enter Domain Name Server IP Address.
(Appears only if GSM is enabled in Communications Path field.) Selects time delay before the
Communications Module notifies the Control Panel of a loss of contact with the network.
Allows messages to be sent over GSM in the event that contact with the internet is lost.
(Appears only if “WiFi & GSM” is selected as the Communications Path.)
Enables daily test of GSM module operation. (Appears only if “WiFi & GSM” is selected as the
Communications Path.)
Use DHCP
NIC IP Address
Subnet Mask
Gateway IP Address
DNS Server IP Address
GSM Fault Time
GSM Rollover
GSM 24 Hour Test
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
Remote Access (Total Connect) and Multi Mode (PSD) over WiFi, IP or GSM cannot be enabled in the panel alone.
Availability of this service is controlled via the web-based programming tool on the AlarmNet Direct website. These
features must to be enabled through the AlarmNet Direct website first and transferred to the device.
SCREEN
ACTION
Communicator
5000-100-132-V0
Communicator
1. Select “Communicator”. The System displays several pages of options that vary
depending upon the selections that are made. Use the down arrow to scroll
through the pages of options.
Communications Path
City ID
CS ID
Supervision
APL
Sub ID
Old Alarm Time
Remote Acc. Comm.
Multi Mode Comm.
IP Fault Time
Use DHCP
GSM Fault Time
Communications Path
None
APL
Disabled
2. Select “Communications Path”. The system scrolls between the following options.
Notes: The available options are dependent upon which communications module(s)
has been installed. If Communication Path is set to GSM, the control will report
to AlarmNet over GSM/GPRS not WiFi.
None
WiFi
IP
WiFi & GSM
GSM
3. Select “APL”. The system scrolls between “Enabled” and “Disabled”.
Note: If APL is used, GSM or IP must be selected as the Primary Communicator Type in
the Reporter programming.
- 31 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program the Communications Module (Continued)
SCREEN
ACTION
City ID
4.
Select “City ID”. Enter the 2-digit Primary City ID (Decimal).
Options
01-99
CS ID
5.
Select “CS ID”. Enter the 2-digit Primary Central Station ID (HEX).
Options
01-FE
Sub ID
6.
Select “Sub ID”. Enter the 4-digit Subscriber Account Number (Decimal).
Options
0001-9999
Supervision
7.
Select “Supervision”. The system scrolls between the following options:
24 Hours
None
30 Days
8.
Select “Old Alarm Time”. The system scrolls between the following options. Use the
down arrow to scroll to the next page of options.
10 Minutes
15 Minutes
30 Minutes
1 Hour
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
24 Hours
Old Alarm Time
10 Minutes
Remote Acc. Comm.
Disabled
Multi Mode Comm.
Disabled
IP Fault Time (min)
00
Use DHCP
Yes
NIC IP Address
9.
Select “Remote Acc. Comm”. The system toggles between “Disabled” and
“Enabled”.
Note: This field will not be programmable unless it is enabled when creating the
Communications Module account in AlarmNet.
10. If “Remote Acc. Comm.” was enabled in the previous step, the “Multi Mode Comm.”
option is displayed. The system scrolls between the following options.
Disabled
Relay Reports
Enhanced Reports
Note: This field will not be programmable unless it is enabled when creating the
Communications Module account in AlarmNet. The Relay Reports option should
not be selected when using TotalConnect 2.1 Service.
11. Use the down arrow to scroll to the next page of options. If IP was selected in
step 2, proceed to step 12. If GSM was selected in step 2, proceed to step 19.
12. Select “IP Fault Time (min)”. Enter the time delay (in minutes) on the keypad.
Options
00-99
13. Select “Use DHCP”. The system toggles between “Yes” and “No”. If “No” is selected
the system displays four additional options. If “Yes” is selected, skip to step 18.
14. Select “NIC IP Address”. Enter the 4-part address on the displayed keypad.
255.255.255.255
Subnet Mask
15. Select “Subnet Mask”. Enter the 4-part address on the displayed keypad.
255.255.255.255
Gateway IP Address
16. Select “Gateway IP Address”. Enter the 4-part address on the displayed keypad.
255.255.255.255
DNS Server IP Address
255.255.255.255
17. Select “DNS Server IP Address”. Enter the 4-part address on the displayed keypad.
18. If “IP” was selected in step 2, select “Save” and then select “OK” when the
“Programming Done” screen appears. Proceed to “Diagnostics” section in order to
register the device.
- 32 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program the Communications Module (Continued)
GSM Fault Time (min)
00
GSM Rollover
No
GSM 24 Hour Test
No
19. Select “GSM Fault Time (min)”. Enter the time delay (in minutes) on the keypad.
Options
00-99
20. If “WiFi and GSM” was selected in step 2, two additional programming fields are
displayed. Select “GSM Rollover”, the system toggles between “Yes” and “No”.
21. Select “GSM 24 Hour Test”, the system toggles between “Yes” and “No”.
22. If “GSM” was selected in step 2, select “Save” and then select “OK” when the
“Programming Done” screen appears. Proceed to “Diagnostics” section in order to
register the device.
- 33 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program the Z-Wave Module
The following system options are programmed in this section:
Option
Z-Wave
Temperature Display
Function
Enables or disables the Z-Wave Module
Toggles between Fahrenheit and Celsius (for Z-Wave compatible Thermostats)
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
SCREEN
ACTION
Z - Wave
1.
2.
Enter Program Mode and default the panel (Refer to “Loading Factory Defaults”).
Select “Z-Wave”
The System displays the following options:
Z-Wave
Temperature Display
3.
Select “Z-Wave”. The system toggles between the following options:
Enabled – Installed Telephone Side
Disabled
Select “Enabled – Installed Telephone Side”.
4.
If you wish to change the temperature format, select “Temperature Display”. The
system toggles between the following options:
Fahrenheit
Celsius
Select “Save”.
Select the “” key to return to the previous screen or the Home button to return to
the Home screen.
Include Z-Wave devices. (Refer to Including/Excluding Z-Wave Devices in the Home
Automation Guide P/N 800-19979 or higher.)
5100-100-067-V0
Z-Wave
Enabled-Installed Telephone
Temperature Display
Fahrenheit
5.
6.
7.
- 34 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Zones
The following system options are programmed in this section:
Option
Serial Number
Loop Number
Zone Description 1/2
Device Type
Response Type
Alarm Report
Chime
Supervision
Arm Night
Function
Manually enter device serial number or enroll via RF transmission
Manually enter device loop number or enroll via RF transmission
Enter Zone Descriptors for the device being enrolled
Select the type of device being enrolled
Select the alarm response for the device being enrolled (refer to Zone Response Type Table)
Activate reporting option for the device being enrolled
Enable/disable chime mode for specific device being enrolled (applies to Entry/ Exit, Perimeter,
and Interior Response types only)
Select supervision for device being enrolled
Allows specific programmed motion sensors to be active when Arm Night mode is enabled and
the system is Armed in Stay mode by the User.
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
SCREEN
ACTION
Zones
5000-100-133-V0
1. Select “Zones”
The System displays the following options:
1. New
2. Front Door
3. Back Door
4.Window
5. Motion Sensor
6.New
2. Use the down arrow to scroll to the next page of options. Use the arrow to return to
the previous page.
7. – 45. New
46. – 48. New (Main) (reserved for Garage Door Zones)
49. – 64. New
140. – 147. 4 Button
148. – 155. New (Button Zones)
180. – 185. Temperature (Z-Wave Thermostat zones) (L5210 only)
180. – 187. Temperature (Z-Wave Thermostat zones) (L7000 only)
95. Fire
96. Medical
99. Police
3. Select a zone and then select “Edit” or “Add New” to program the next available zone. The
following options are displayed (dependant upon Zone Type):
* This field does not apply to
Serial Number *
Loop Number *
Hardwire Zone 1 or
Zone Description 1
Zone Description 2
Temperature Zones 80-85.
Device Type
Response Type
Alarm Report
Chime
Supervision
4. Select an option to display the next programming field.
Serial Number
Loop Number
1
Serial Number (This field does not apply to Temperature Zones 80-85)
When “Serial Number” has been selected “Enter Serial Number or Activate” is displayed. The
transmitter serial number and loop number can be enrolled via RF transmission OR manually.
Enroll via RF Learning To enroll the device using RF Learning mode three transmissions
(open/close) of the device will be required. The initial transmission activates the RF Learning
mode and the system will emit a single beep. A second transmission enrolls the serial number
and the system beeps two times and displays “Activate Sensor Again To Confirm”. A third
transmission will confirm the serial number. The system beeps two times and returns to the
Zone programming Screen.
Enroll Manually
Enter the 7-digit serial number printed on the transmitter using the displayed keypad and
select “Done”. The system beeps one time and returns to the Zone programming Screen.
Loop Number (This field does not apply to Temperature Zones 80-85)
Select “Loop Number” to toggle between 1, 2, 3 and 4. Enter Save.
- 35 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Zones (Continued)
SCREEN
ACTION
Zone Description 1
Zone Description 1/Zone Description 2
When programming the Zone Description, after entering the first letter of the description on the
keypad you can use the up and down arrows to scroll through the available
preprogrammed zone descriptions. For a list of the pre-programmed Zone Descriptors, please
visit http://www.security.honeywell.com/hsc/resources/MyWebTech
Select “Zone Description 1 or Zone Description 2”. Using the displayed keypad enter Zone
Description 1 or Zone Description 2. The system announces the Zone Description. Enter
“Done”, when you are finished. The system returns to the Zone Programming page.
Device Type
Select “Device Type”. The system displays the following options:
New
Door
Window
Motion Sensor
Glass Break
Smoke Detector
Heat Sensor
Carbon Mono. Det.
Use the down arrow to scroll to the next page of options:
Temperature
Flood
Environmental
Medical
Fire
Police
Garage Door
Other
Device Type
Response Type
Not Used
Alarm Report
Yes
Chime
Disabled
Response Type
1. Select “Response Type”. The system displays the specific options, which are dependant
upon the Device Type that was selected for the zone. Use the down arrow to scroll to the
next page of options. Use the arrow to return to the previous page.
Not Used
Entry Exit 1
Entry Exit 2
Perimeter
Interior Follower
Trouble
24 Hour Silent
24 Hour Audible
24 Hour Auxiliary
Fire No Verification
Interior With Delay
Monitor
Carbon Monoxide
Garage
Arm Stay
Arm Away
Disarm
No Response
Silent Burglary
Resident Monitor
Resident Response
General Monitor
General Response
Fire With Verification
Day/Night
Garage Monitor
2. Select the desired Response Type and select “Save”. The system will return to the Zone
screen.
Note: For threshold monitoring to be configurable on the LYNX Touch Z-wave thermostat
screen, the respective zones will first need to be assigned with a response type in zone
programming. The recommended response type is Trouble.
Alarm Report
Note: This field is for Alarms. If Response Type “Trouble” is set up and Alarm Report is set to
“No” the system will still report if Report Alarms was enabled in the Reporter
programming.
Select “Report” to toggle between “No” or “Yes”. Select “Save”.
Chime
Note: Chime only applies to entry/exit, perimeter and interior zone types.
Select “Chime” to scroll through the selections that include “Disabled” and ten optional chimes.
Select “Save”.
- 36 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Zones (Continued)
Supervision
Supervised
Arm Night
No
Supervision
The system displays the applicable Supervision options based upon the Device Type that was
selected. Select “Supervision” to scroll between the following options:
Hardwire Zone
Normal Open
Normal Closed
End of Line
RF Zone
Supervised
Unsupervised
Temperature (Defaulted for Zones 180-187)
Note: Zone 186 and 187 are only available on the L7000)
High Temp (Default selection for Zones 180, 182, 184 and 186)
Low Temp (Default selection for Zones 181, 183, 185 and 187)
After making a Supervision selection, select “Save”.
Arm Night
If “Motion Sensor” is selected in the Response Type Field, the Arm Night option will be
available. Use the down arrow to scroll to the next page of options.
Select “Arm Night” to toggle between “No” or “Yes”. Select “Save”.
- 37 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Keys
The following system options are programmed in this section
Option
Key Type
User
Serial Number
Zone
Button Key * - Zn *
Function
Select the specific type of key being entered or enrolled
Associates the Key with a specific User
Manually enter key serial number or enroll via RF transmission
Manually enter key zone number (between 140 and 155) or enroll via RF transmission
Associate the selected button with a specific function
* Key number and Zn number are dependent upon the Key Type selected.
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
SCREEN
Keys
Key Type
4 Button key
User
ACTION
1. Select “Keys”
The System displays the following options:
Edit
Add New
Delete
2. Select “Add New”.
3. The following options are displayed (dependent upon the “Key Type” selected):
Key Type
User
Serial Number
Zone
Button Key 1 – Zn 140
Button Key 2 – Zn 141
Button Key 3 – Zn 142
Button Key 4 – Zn 143
Button Key 5 – Zn 144
Button Key 6 – Zn 145
Button Key 7 – Zn 146
Button Key 8 – Zn 147
Select an option to display the next programming field.
Key Type
Select “Key Type”. The system scrolls between the following:
1 Button key
6 Button key
2 Button key
8 Button key
4 Button key
User
Select “User” then select from the following options (or the list of Users that have been
programmed):
Master
Guest
Duress
User 3
User 4
User 5
User 6
User 7
Use the down arrow to scroll to the next page. The system displays options for User 8
through 30 (L5210) or 8 though 46 (L7000).
Note: The Key must be associated with a specific User/User Code in order for it to operate.
Refer to the LYNX Touch User Guide for additional Information regarding User Codes.
Serial Number
0
Serial Number
When “Serial Number” has been selected “Enter Serial Number or Activate” is displayed. The
transmitter serial number and loop number can be enrolled via RF transmission OR manually.
Enroll via RF Learning To enroll the device using RF Learning mode three transmissions
(open/close) of the device will be required. The initial transmission activates the RF Learning
mode. A second transmission enrolls the serial number and the system beeps two times and
displays “Activate Sensor Again To Confirm”. A third transmission will confirm the serial
number. The system beeps three times and returns to the Zone programming Screen.
Enroll Manually
Enter the 7-digit serial number printed on the transmitter using the displayed keypad and
select “Done”. The system beeps one time and returns to the Zone programming Screen.
Zone
140
Zone
The system displays the next available key Zone number. Select “Zone” to manually enter a
specific Zone Number on the displayed keypad (140-155 L5210 OR 140-163 L7000). If the
desired Zone Number is not available, the system returns to the previous screen.
Select ”Done”. The system returns to the previous screen. Repeat the previous step to enter
another Zone Number.
- 38 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Keys (Continued)
SCREEN
Button Key * - Zn *
ACTION
Button Key * Zn *
Select the desired Button Key and enter a function for each button key. The system
displays the following options:
Arm Away
Disarm
Arm Stay
No Response
24 Hour Silent
24 Hour Audible
24 Hour Auxiliary
Silent Burglary
Fire No Verification
* Options are the same for each Button/Zone combination.
- 39 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting
!
When Compass service is required and GSM or IP are the only reporting channels: As part of Primary Central Station
programming; the “Phone Type” must be set to any selection other than “None”, the “Communicator Type” must be set to
GSM or IP, as applicable, and must match the compass value; “Phone number” field must be left blank and an “Account
number” must be programmed.
The following system options are programmed in this section:
Option
Primary or Secondary CS Info
Phone Type
Phone Number
Communicator Type
Account Number
Dynamic Priority
Dynamic Delay
Report All
Report Alarms
Report Troubles
Report Open/Close
Report Tests
Follow Me Phone 1 or Phone 2
Phone Type
Phone Number
Report All
Report Alarms
Report Troubles
Report Open/Close
Report Tests
Report Selection
Options
PBX
Call Wait Cancel
Number of Reports
Alarm Report Delay
Swinger Shutdown
Abort Window
First Offset Report
Report Frequency
Downloader
Phone Answer
Modem Speed
Ans. Machine Defeat
Ring Counter
Callback Number
Flexible Callback
Number
Function
Enroll information pertaining to the Primary and/or Secondary Central Station.
Select the Report Format that will be used to send reports to the Primary or Secondary
Central Station, as applicable.
Enter the Phone Number for the Primary or Secondary Central Station, as applicable.
Select the type of Communications Module that will be used to communicate with the Primary
or Secondary Central Station, as applicable.
Enter the account number for the Primary or Secondary Central Station, as applicable.
Select the primary method for sending Reports to the Primary or Secondary Central Station,
as applicable.
Selects delay between switching between reporting methods. Active if Dynamic Delay feature
has been set to Preferred Telco or Preferred Radio.
Enable All Reports to be sent to the Primary or Secondary Central Station, as applicable.
Enable Alarm Reporting to the Primary or Secondary Central Station, as applicable.
Enable Trouble Reporting to the Primary or Secondary Central Station, as applicable.
Enable Open/Close Reporting to the Primary or Secondary Central Station, as applicable.
Enable Test Reporting to the Primary or Secondary Central Station, as applicable.
Enroll information Primary and/or Secondary telephone numbers for “Follow Me”
Announcements and/or Reminders. (This feature is only available on the LYNX Touch
L5210/L5210CN)
Enter Number for Follow Me Phone 1 or Phone 2, as applicable.
Enter Primary and/or Secondary telephone numbers for “Follow Me” Announcements and/or
Reminders.
Enable All Reports to be sent to the Follow Me Phone 1 or Phone 2, as applicable.
Enable Alarm Reporting to the Follow Me Phone 1 or Phone 2, as applicable.
Enable Trouble Reporting to the Follow Me Phone 1 or Phone 2, as applicable.
Enable Open/Close Reporting to the Follow Me Phone 1 or Phone 2, as applicable.
Enable Test Reporting to the Follow Me Phone 1 or Phone 2, as applicable.
Enable Reporting of Specific Events
Enter the digits required to access telephone service. (Not applicable to the L7000/L7000CN)
Enter the digits required to cancel call waiting, if applicable (Not applicable to the L7000/
L7000CN)
Limit the number of messages sent to the Central Station during an armed period.
Disable or select the time delay for alarm reporting (applies to L5210CN/L7000CN only)
Select the number of times reports are sent and sounder sounds for non-fire alarms before
the system ignores subsequent alarms (applies to L5210/L7000 and only)
Select the time delay for alarm reporting (applies to L5210/L7000 only)
Select the time for the first test report following power-up/programming or downloading
Select the test report frequency
Enable to allow control to answer incoming phone line. (Not applicable to the L7000/
L7000CN)
(Future Use)
Enable to defeat answering machine mode. (Active if Phone Answer feature is enabled.)
(Not applicable to the L7000/L7000CN)
Enter the number of rings before control picks up phone line. (Active if Ans. Machine Defeat is
not enabled.)
Enter the phone number the control will use to call back the downloading computer. (Active if
Phone Answer is enabled.)
Allows Download operator to temporarily change the callback number by the number of digits
selected. Active if Phone Answer is enabled
Enter the number of flexible callback numbers that will be used. Available if Flexible Callback
is enabled.
- 40 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting (Continued)
Notes: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
When GSM is used as the Primary Communications channel for any Total Connect service, the GSM Radio must be
selected as the Primary Reporting Path (Preferred Radio).
SCREEN
Reporter
Primary CS Info
Phone Type
Contact Id: 4 Digit
Communicator Type
None
ACTION
Select “Reporter”
The System displays the following options:
Primary CS Info
Secondary CS Info
Follow Me Phone 1*
Follow Me Phone 2*
Report Selection
Options
Downloader
Note: The Follow Me feature is not available on the LYNX Touch L7000 Series controls.
Select “Primary CS Info”. The System displays the following options:
Phone Type
Communicator Type
Select “Phone Type”. The System scrolls though the following options:
None
Contact Id: 4 Digit
Contact Id: 10 Digit
SIA
Select “Communicator Type”. The System scrolls though the following options:
None
GSM
WiFi
WiFi & GSM
IP
Note: The system will display the communications (GSM, WiFi or IP) paths based on the selection
made in Communicator Programming. The Communication Path selection can be enabled for
either Primary Central Station or Secondary Central Station but not both. If it is enabled in one it
will not be available for the other Central Station. If APL is used, GSM, WiFi or IP must be
selected as the Primary Communicator Type.
Phone Number
Account Number
FFFF
Dynamic Priority
Redundant Reports
Dynamic Delay
30 Seconds
If any option other than “None” is selected in “Phone Type” The “Phone Number” option will
be displayed. Select “Phone Number”. Enter the Primary Central Station Phone Number on
the displayed keypad. (Up to 20 digits)
If any option other than “None” is selected in “Phone Type” The “Account Number” option
will be displayed. Select “Account Number”. Enter the Primary Central Station Account
Number on the displayed keypad.
If any option other than “None” is selected in “Communicator Type” The “Dynamic Priority”
option will be displayed. “Select “Dynamic Priority”. The system scrolls between “Redundant
Reports”, “Preferred Telco” and Preferred Radio”.
If any option other than “Redundant Reports” is selected in “Dynamic Priority” The “Dynamic
Delay” option will be displayed. “Select “Dynamic Delay”. The system scrolls between “15
Seconds”, “30 Seconds”, “60 Seconds” and “90 Seconds”.
Note: If GSM is selected as the primary reporting channel Dynamic Delay should be set to minimum
of 60 seconds.
Report All
Press to Report All
Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”.
If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to
return to the Reporter options screen.
Report Alarms
Enabled
Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 Touch default is “Enabled”.
Report Troubles
Enabled
Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled”.
Report Open/Close
Disabled
Select “Open/Close”. The System toggles between “Disabled” and “Enabled”.
Report Tests
Enabled
Select “Report Tests”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled” and is not selectable.
- 41 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting (Continued)
SCREEN
Secondary CS Info
Phone Type
None
Communicator Type
None
ACTION
Select “Secondary CS Info”. The System displays the following options:
Phone Type
Communicator Type
Select “Phone Type”. The System displays the following options:
None
Contact Id: 4 Digit
Contact Id: 10 Digit
SIA
Select “Communicator Type”. The System displays the following options:
None
GSM
WiFi
WiFi & GSM
IP
Note: The system will display the communications path (GSM, WiFi or IP) selected in Communications
Programming. The path can be enabled for either primary Central Station or Secondary Central
Station but not both. If it is enabled in one it will not be available for the other Central Station.
Phone Number
Account Number
FFFF
Dynamic Priority
Redundant Reports
Dynamic Delay
30 Seconds
Report All
Press to Report All
If any option other than “None” is selected in “Phone Type”, the “Phone Number” option will
be displayed. Select “Phone Number”. Enter the Secondary Central Station Phone Number
on the displayed keypad. (Up to 20 digits)
If any option other than “None” is selected in “Phone Type” The “Account Number” option will
be displayed. Select “Account Number”. Enter the Secondary Central Station Account
Number on the displayed keypad.
If any option other than “None” is selected in “Communicator Type” The “Dynamic Priority”
option will be displayed. “Select “Dynamic Priority”. The system scrolls between “Redundant
Reports”, “Preferred Telco” and Preferred Radio”.
If any option other than “Redundant Reports” is selected in “Dynamic Priority” The “Dynamic
Delay” option will be displayed. “Select “Dynamic Delay”. The system scrolls between “15
Seconds”, “30 Seconds”, “60 Seconds” and “90 Seconds”.
Note: If GSM is selected as the primary reporting channel Dynamic Delay should be set to
minimum of 60 seconds.
Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”. If
“Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to return
to the Reporter options screen.
Report Alarms
Enabled
Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”.
Report Troubles
Enabled
Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”.
Report Open/Close
Disabled
Select “Open/Close”. The System toggles between “Disabled” and “Enabled”.
Report Tests
Enabled
Select “Report Tests”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled” and is not selectable.
Follow Me Phone 1
Note:
The Follow Me feature is not available on the LYNX Touch L7000/L7000CN.
Select “Follow Me Phone 1” to program the “Follow Me” Reminder telephone number 1
Phone Type
None
Note:
Phone Number
Note:
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Phone Type”. The System toggles between “None” and “Follow Me”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Phone Number”. Enter the “Follow Me” Phone Number 1 on the displayed keypad.
- 42 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting (Continued)
SCREEN
ACTION
Report All
Press to Report All
Note:
Report Alarms
Disabled
Note:
Report Troubles
Disabled
Note:
Report Open/Close
Disabled
Note:
Report Tests
Disabled
Note:
Follow Me Phone 2
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”.
If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to
return to the Reporter options screen.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Open/Close”. The System toggles between “Disabled” and “Enabled”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report Tests”. The System toggles between “Disabled” and “Enabled”.
Note:
The Follow Me feature is not available on the LYNX Touch L7000/L7000CN.
Select “Follow Me Phone 2” to program the “Follow Me” Reminder telephone number 2.
Phone Type
None
Note:
Phone Number
Note:
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Phone Type”. The System toggles between “None” and “Follow Me”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Phone Number”. Enter the “Follow Me” Phone Number 2 on the displayed keypad.
Report All
Press to Report All
Note:
Report Alarms
Enabled
Note:
Report Troubles
Enabled
Note:
Report Open/Close
Disabled
Note:
Report Tests
Enabled
Note:
Report Selection
Arm Away
Enabled
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report All”. The System toggles between “Press to Report All” and “Report All Set”.
If “Report All” is selected all reporting options will be “Enabled”. Select the “Save” key to
return to the Reporter options screen.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report Alarms”. The System toggles between “Disabled” and “Enabled”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report Troubles”. The System toggles between “Disabled” and “Enabled”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Open/Close”. The System toggles between “Disabled” and “Enabled”.
This field is not available on the LYNX Touch L7000/L7000CN.
Select “Report Tests”. The System toggles between “Disabled” and “Enabled”.
Select “Report Selection”. The System displays the following options:
Arm Away
Arm Stay
Disarm
Exit Error
Recent Closing
Event Log Full
Trouble
Trouble Restore
Use the down arrow to scroll to the next page of options.
Alarm Restore
Alarm Cancel
Test
Test Restore
Bypass
Bypass Restore
AC Loss
AC Loss Restore
Use the down arrow to scroll to the next page of options.
Low Battery
Low Battery Restore
RF Low Battery
RF Low Battery Restore
Select “Arm Away”. The System toggles between “Disabled” and “Enabled”.
- 43 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting (Continued)
SCREEN
ACTION
Arm Stay
Enabled
Select “Arm Stay”. The System toggles between “Disabled” and “Enabled”.
Disarm
Enabled
Select “Disarm”. The System toggles between “Disabled” and “Enabled”.
Exit Error
Enabled
Select “Exit Error”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled” and is not selectable.
Recent Closing
Enabled
Select “Recent Closing”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled” and is not selectable.
Event Log Full
Enabled
Select “Event Log Full”. The System toggles between “Disabled” and “Enabled”.
Trouble
Enabled
Trouble Restore
Enabled
Select “Trouble”. The System toggles between “Disabled” and “Enabled”.
Select “Trouble Restore”. The System toggles between “Disabled” and “Enabled”.
Alarm Restore
Enabled
Select “Alarm Restore”. The System toggles between “Disabled” and “Enabled”.
Alarm Cancel
Enabled
Select “Alarm Cancel”. The System toggles between “Disabled” and “Enabled”.
Test
Enabled
Test Restore
Enabled
Bypass
Enabled
Bypass Restore
Enabled
AC Loss
Enabled
AC Loss Restore
Enabled
Low Battery
Enabled
Low Battery Restore
Enabled
RF Low Battery
Enabled
RF Low Battery Restore
Enabled
Select “Test”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled” and is not selectable.
Select “Test Restore”. The System toggles between “Disabled” and “Enabled”.
SIA: The L5210/L7000 default is “Enabled” and is not selectable.
Select “Bypass”. The System toggles between “Disabled” and “Enabled”.
Select “Bypass Restore”. The System toggles between “Disabled” and “Enabled”.
Select “AC Loss”. The System toggles between “Disabled” and “Enabled”.
Select “AC Loss Restore”. The System toggles between “Disabled” and “Enabled”.
Select “Low Battery”. The System toggles between “Disabled” and “Enabled”.
Select “Low Battery Restore”. The System toggles between “Disabled” and “Enabled”.
Select “RF Low Battery”. The System toggles between “Disabled” and “Enabled”.
Select “RF Low Battery Restore”. The System toggles between “Disabled” and “Enabled”.
- 44 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting (Continued)
SCREEN
Options
PBX
ACTION
Select “Options”. The System displays the following options:
PBX
Number of Reports
First Report Offset
Call Wait Cancel
Alarm Report Delay
Report Frequency
Note: This field is not available on the LYNX Touch L7000/L7000CN.
Select “PBX”, and enter PBX Prefix on the displayed keypad.
Call Wait Cancel
Note: This field is not available on the LYNX Touch L7000/L7000CN.
Select “Call Wait Cancel”, and enter Call Wait Cancel Prefix on the displayed keypad
Number of Reports
2 Reports
Alarm Report Delay
30 Sec.
First Report Offset
6 Hrs
Report Frequency
Never
Downloader
Select “Number of Reports”
LYNX Touch (L5210/L7000)
The system scrolls between the following options:
1, 2, 3, 4, 5 and 6 Reports
LYNX Touch (L5210CN/L7000CN) Canada
The system toggles between “Unlimited” and “10 Reports”.
Select “Alarm Report Delays”. The System scrolls between the following options:
15 Sec.
30 Sec.
45 Sec.
No delay
SIA The Alarm Report Delay (burglary abort window) must be set to a minimum of 15
seconds. The sum of the Alarm Report Delay (burglary abort window) and the entry
delays should not exceed 1 minute.
Note: The L5210/L7000 control validates the data entered in this field. If the selection is not
valid the control will emit a single long beep indicating that the selection has been rejected.
The control replaces the selection with the default value “30 Sec”.
Select “First Report Offset” for the Test Report. The System scrolls between the following
options:
6 Hrs
12 Hrs
18 Hrs
24 Hrs
Select “Report Frequency” for the Test Report. The System scrolls between the following
options:
Never
Every Day
Every 7 Days
Every 30 Days
Select “Downloader”. The System displays the following options:
Phone Answer
Modem Speed
Ans.Machine Defeat
Callback Number
Ring Counter
Flexible Callback
Number
Phone Answer
Note: This field is not available on the LYNX Touch L7000/L7000CN.
Yes
Select “Phone Answer”, the system toggles between “Yes” and “No”.
Modem Speed
(Future Use)
Slow
Ans. Machine Defeat
Yes
Callback Number
Note: This field is not available on the LYNX Touch L7000/L7000CN.
Select “Ans. Machine Defeat”, the system toggles between “Yes” and “No”.
Select “Callback Number” and enter callback number on the displayed keypad.
- 45 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Reporting (Continued)
Ring Counter
2
Flexible Callback
This option only appears if Answering Machine defeat is set to “No”. Enter ring counter (1 –
14 rings) on the displayed keypad.
Select “Flexible Callback”, the system toggles between “Yes” and “No”.
No
Number
1
This option only appears if “Flexible Callback” is set to “Yes”. The system scrolls between
options 1, 2 and 3.
- 46 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program Sounder
The following system options are programmed in this section:
Option
Burglary Alarm Sound
Burglary Bell Timeout
Fire Bell Timeout
Arm Confirm
Alarm Options
Function
Reduces the full 85 dB burglary alarm sound for testing.
Select the time for timeout of the Burglary Alarm sounder.
Select the time for timeout of the Fire Alarm sounder.
Enable sounder “ding” when system is armed via the selected RF device.
Select a limit for the number of times an alarm can sound for a specific zone.
Note: This option does not apply to the L5210/L7000 controls.
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
SCREEN
Sounder
Burglary Alarm Sound
Yes
Burglary Bell Timeout
4 Minutes
Fire Bell Timeout
4 Minutes
Arm Confirm
RF Keyfob
Alarm Options
Unlimited
ACTION
Select “Sounder”
The System displays the following options:
Burglary Alarm Sound
Burglary Bell Timeout
Fire Bell Timeout
Arm Confirm
Alarm Options
Select “Burglary Alarm Sound”. The System toggles between the following options:
Yes (Full volume)
No (Test volume – installer mode)
Select “Burglary Bell Timeout”. The System scrolls between the following options:
No
4 Minutes
8 Minutes
12 Minutes
16 Minutes
Select “Fire Bell Timeout”. The System scrolls between the following options:
No
4 Minutes
8 Minutes
12 Minutes
16 Minutes
Select “Arm Confirm”. The System scrolls between the following options:
None
All RF
RF Key Fob
RF Keypad
Note: This option does not apply to the L5210/L7000 Control.
Select “Alarm Options”. The System scrolls between the following options:
Unlimited
1
2
10
Select “Save”.
- 47 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program System Settings
The following system options are programmed in this section:
Option
Function
Entry Delay1/Entry Delay 2
Selects an Entry Delay time in seconds. The system will wait the time entered before
sounding alarm upon entering if system is not disarmed.
Note: The Default values differ for the L5210/L7000 and L5210CN/L7000CN controls.
Exit Delay
Selects an Exit Delay time in seconds for both Entry Delay 1 and 2 Zone Types. The
system will wait the time entered before sounding an alarm if the exit door is left open after
the system has been armed.
Note: The Default values differ for the L5210/L7000 and L5210CN/L7000CN controls.
Backlight Timeout
Enable or disable display backlight turnoff after 30 seconds.
Quick Arm
Enables or disables Quick Arm Mode. If enabled, security code is not required to arm the
system. The user simply presses the AWAY button (ICON) and then selects the “Quick
Arm” button on the displayed keypad to arm the system.
Quick Exit
Enables or disables Quick Exit Mode. If enabled allows the user restart the exit delay to
allow entry or exit when the system is armed
Restart Exit Time
Enables or disables Restart Exit Time Mode. This option allows the control to restart the
exit delay time (one time) after arming in STAY or AWAY mode by selecting the Restart
key (if quick arming is enabled) or by selecting the Restart key and entering the User Code
(if quick arming is disabled). This option also enables automatic exit delay reset, which
resets exit delay if the entry/exit door is re-opened and closed before exit delay time
expires after arming.
Force Bypass
Enables or disables Force Bypass Mode. All zones bypassed by this function will be
displayed after the bypass is initiated. The Fire and CO Zones are not bypassed in the
L5210/L7000.
Exit Warning
Enables or disables Exit Warning sound. Audible Exit Warning sound consists of slow
continuous beeps until last 10 seconds, when it changes to fast beeps. The warning sound
will end at the termination of exit delay.
Note: This field is not programmable in the L5210/L7000 and is always enabled.
Auto Stay Arming
Enables or disables Auto Stay Arming Mode. If this feature is enabled and the Control
Panel has been armed “Armed Away” at the LYNX Touch keypad or RF keypad, the
system will switch to the “Armed Stay” mode if the Exit Time has expired and no exit has
been made.
Lack of Usage Notify
Enables or disables Lack of Usage Notification feature. If enabled, notifies the Central
Station if an end user is not operating their security system by sending a System Inactivity
report 654. The report will be sent only to the Primary phone number and only if Contact
ID® format was selected.
Power-Up in Previous
Enables or disables Power-Up in Previous Mode feature. When the system powers up
armed, an alarm will occur 1 minute after arming if a zone is faulted. For the
L5210CN/L7000CN control any bypassed zones will be unbypassed. For the L5210/L7000
any bypassed zones will remain bypassed.
Display Alarm Cancel
Enables or disables display of Cancelled Alarm.
Display Exit Time
Enables or disables display of Exit Time.
Cross Zone Delay
Sets the maximum amount of time in which two zones must be tripped in an armed system
to send an alarm message to the Central Station. If only one cross zone is tripped during
this time, a trouble message (CID code 380) for that zone is sent to the Central Station.
Cross Zone 1/Cross Zone 2
Select the zones that will be used for Cross Zoning
- 48 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program System Settings
Note: If applicable, preprogrammed defaults for the L5210/L7000 Control are shown on the screen unless otherwise noted.
SCREEN
System Settings
Entry Delay 1
30 Seconds
ACTION
Select “System Settings”
The System displays the following options:
Entry Delay 1
Entry Delay 2
Exit Delay
Backlight Timeout
Quick Arm
Quick Exit
Restart Exit Time
Force Bypass
Exit Warning
Auto Stay Arming
Use the down arrow to scroll to the next page of options. Use the arrow to return to
the previous page:
Lack of Usage Notify
Power-Up In Previous
Display Alarm Cancel
Display Exit Time
Cross Zone Delay
Cross Zone 1
Cross Zone 2
Select “Entry Delay 1”. The System scrolls between the following options:
LYNX Touch Canada
LYNX Touch
(L5210CN/L7000CN)
(L5210/L7000)
None
None
15 Seconds
15 Seconds
30 Seconds
30 Seconds
45 Seconds
45 Seconds
60 Seconds
60 Seconds
90 Seconds
90 Seconds
2 Minutes
2 Minutes
3 Minutes
4 Minutes
UL installations: The Entry Delay must be set for a maximum of 45 seconds.
SIA: The Entry delay must be set to a minimum of 30 seconds. The sum of entry delay 1 and
the Alarm Report Delay (burglary abort window) should not exceed 1 minute. “None” is
only allowed for use in Commercial High-Security applications.
Entry Delay 2
30 Seconds
Select “Entry Delay 2”. The System scrolls between the following options:
LYNX Touch
LYNX Touch Canada
(L5210/L7000)
(L5210CN/L7000CN)
None
None
15 Seconds
15 Seconds
30 Seconds
30 Seconds
45 Seconds
45 Seconds
60 Seconds
60 Seconds
90 Seconds
90 Seconds
2 Minutes
2 Minutes
3 Minutes
4 Minutes
UL installations: The Entry Delay must be set for a maximum of 45 seconds.
SIA: The Entry delay must be set to a minimum of 30 seconds. The sum of entry delay 1 and
the Alarm Report Delay (burglary abort window) should not exceed 1 minute. “None” is
only allowed for use in Commercial High-Security applications.
Exit Delay
60 Seconds
Select “Exit Delay”. The System toggles between the following options:
LYNX Touch
LYNX Touch Canada
(L5210/L7000)
(L5210CN/L7000CN)
45 Seconds
None
60 Seconds
15 Seconds
90 Seconds
30 Seconds
2 Minutes
45 Seconds
60 Seconds
90 Seconds
2 Minutes
UL installations: Exit Delay must be set for a maximum of 60 seconds
SIA: The Exit Delay must be set to a minimum of 45 seconds.
- 49 -
LYNX Touch Installation and Setup Guide
Programming the Control
Program System Settings (Continued)
SCREEN
Backlight Timeout
ACTION
Select “Backlight Timeout”. The System toggles between No and 30 Seconds.
No
Quick Arm
Select “Quick Arm”. The System toggles between Yes and No.
Yes
Quick Exit
Select “Quick Exit”. The System toggles between Yes and No.
Yes
Restart Exit Time
Yes
Force Bypass
No
Exit Warning
Yes
Auto Stay Arming
Yes
Lack of Usage Notify
Disabled
Power-Up In Previous
Yes
Select “Restart Exit Time”. The System toggles between Yes and No.
SIA: The L5210/L7000 default is “Yes”.
Select “Force Bypass”. The System toggles between Yes and No.
UL installations: must be NO (no forced bypass)
Select “Exit Warning”. The System toggles between Yes and No.
SIA: The L5210/L7000 default is “Yes” and is not selectable.
Select “Auto Stay Arming”. The System toggles between Yes and No.
SIA: The L5210/L7000 default is “Yes”.
Select “Lack of Usage Notify”. The System scrolls between the following options:
Disabled
1 Day
90 Days
7 Days
180 Days
27 Days
365 Days
Select “Power-Up In Previous”. The System toggles between Yes and No.
Note: If the previous state was Armed Away or Stay, the system will not respond to sensor changes for
1 minute. This allows time for sensors such as PIRs to stabilize.
UL installations: must be Yes (power up in previous state)
SIA: The L5210/L7000 default is “Yes” and is not selectable.
Display Alarm Cancel
Select “Display Alarm Cancel”. The System toggles between Yes and No.
Yes
Display Exit Time
Select “Display Exit Time”. The System toggles between Yes and No.
Yes
Cross Zone Delay
None
Cross Zone 1
Disabled
Cross Zone 2
Disabled
Select “Cross Zone Delay”. The System toggles between the following:
None
30 Seconds
1 Minute
90 Seconds
2 Minutes
3 Minutes
4 Minutes
Note: Cross zoning cannot be used in conjunction with APL.
Select “Cross Zone 1”. The System toggles between the following:
Disabled
Note: If Cross Zone Delay is enabled the system will display the zones that are programmed
with the following Zone Types: Day/Night, Interior Follower and perimeter.
Select “Cross Zone 2”. The System toggles between the following:
Disabled
Note: If Cross Zone Delay is enabled the system will display the zones that are programmed
with the following Zone Types: Day/Night, Interior Follower and perimeter.
- 50 -
LYNX Touch Installation and Setup Guide
Programming the Control
Communications Diagnostics
Communications Status – The system provides a status of the IP or GSM communications paths and
performs a self-test of the AES encryption algorithm as follows:
Message
GSM:
OR
IP:
Encryption:
AlarmNet Registration:
Meaning
OK
Fault Reported!
Not Connected
Not Registered!
No Physical Link
AES Passed!
AES Failed!
No Encryption!
Registered
Not Registered
Normal; No fault. (IP or GSM)
No network connectivity and fault time has expired. (IP or GSM)
No network connectivity over IP and fault time has NOT yet expired.
No network connectivity over GSM and fault time has NOT yet expired.
No network connectivity over IP and fault time is set to 0.
Test successful.
Test failed.
No encryption algorithm set.
Communication Device is Registered with AlarmNet.
Communication Device is not Registered with AlarmNet.
Ethernet Information – Displays IP information, if the IP communication path is enabled.
Physical Link:
DHCP:
NIC IP Address:
Subnet Mask:
Confirms the physical link connection to the internet and the connections speed.
DHCP (Dynamic Host Configuration Protocol) indicates server is performing satisfactorily.
Displays the IP address assigned to this device
Displays the 32-bit address mask used to indicate the portion (bits) of the IP address that is being
used for the subnet address.
Displays the IP address assigned to the Gateway.
Displays the IP address assigned to the DNS (Domain Name System) server.
Gateway IP Address:
DNS Server IP Address:
Message
Physical Link
DHCP
Meaning
10 Mbps or 100 Mbps
Bad
OK
Bad
Off
Link speed of physical connection
No physical connection
DHCP address resolved
DHCP address not resolved
DHCP disabled
GSM Information – Displays GSM information if GSM communication path is enabled.
Status
GSM Registered
Message
Cell Registration:
Primary RSSI:
GPRS: (2G Only)
(Always available in 3G/4G)
Country:
Network:
LAC
Cell: (2G only)
Cell: (3G/4G only)
Base Station: (2G Only)
Pri Sync Code (3G/4G Only)
Channel:
Second Site RSSI:
GSM Not Registered
RSSI Note:
Meaning
Home 2G
Home 3G
Roaming
(See RSSI
Note below)
Yes
No
xxx
xxx
xxxxx
xxxx
xxxxxx
xx
xxx
xxxx
(See RSSI
Note below)
Searching For Coverage!
SIM Error!
Cell Registration: SIM Not Active
Cell Registration: Not Registered
Registered Home with 2G Service
Registered Home with 3G/4G Service
Registered Roaming
Primary Site RSSI level signal strength
(1 to 5 stars or “Not Present” will be displayed)
GPRS Service availability
GPRS is not available
Country Code
Network Code
Local Area Code
Base Station ID
Base Station ID
Base Station Antenna Sector
Primary Sync Code
Control Channel in use
Secondary Site RSSI level availability
(“Present” OR “Not Present” will be displayed)
Searching for cell network.
No SIM card present or SIM card faulty
SIM is not activated
Not registered with cell network
Primary Site Signal strength is displayed by a series of 1 to 5 stars (* weak to ***** strong) or “Not Present” if there is no
signal. To ensure a reliable installation at least 2 (**) stars should consistently be present. Secondary site presence is
indicated by “Present” or “Not Present”.
- 51 -
LYNX Touch Installation and Setup Guide
Programming the Control
Communications ID Numbers – Displays programmed SIM card information
MAC:
MAC CRC:
WiFi:*
WiFi Ver:
SCID:**
IMEI:**
Message
xxxxxxxxxxxx
xxxx
xxxxxxxxxxxx
x.x.x
xxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxx
Meaning
MAC Address indicates the unique identification number for installed
communications module(s)
MAC CRC number for installed communications module(s)
Physical MAC Address of the WiFi module
WiFi module software version
Displays the ID number assigned to the installed SIM card (SCID)
Displays the ID number assigned to the installed GSM module.
* This is the system MAC that should be referenced whenever speaking with technical support.
** Displayed if GSM communication path is enabled.
Test Communications – Performs network diagnostics and sends test alarms to AlarmNet. The following
tests are available depending on the type of communications module installed.
Test Ethernet
This test is available if IP communication path is enabled. The network diagnostic process tests the integrity of the links
between the LYNX Touch and the various connection points of AlarmNet Control that are known as “Redirectors”. If a physical
link is detected and is ready, the following diagnostics are performed.
Testing Gateway…
Traces the connection to the Gateway and displays the following:
Testing Gateway – Successful!
A successful trace to Gateway. OR
Testing Gateway – Failed!
Failed to reach Gateway.
Testing Redirector * Sequentially traces the connection to Redirector 1, 2 and 3 at AlarmNet Control. The following will be
displayed.
Redirector * – Service OK
Service at AlarmNet Control on Redirector 1, 2 or 3 is functioning. OR
Redirector * – Failed
Error occurred on Redirector 1, 2 or 3.
* = Number of the director being tested is displayed
A summary of the tests is displayed after Redirector 3 is tested. The example shows that the tests of all three
connection points, or Redirectors, were successful. If an error occurred at any point, the summary will display “Failed”
next to the faulty Redirector.
Redirector 1 – Service OK
Redirector 2 – Service OK
Redirector 3 – Service OK
If no physical link is detected, the test is aborted and one of the following is displayed:
No Physical Link
No physical link is detected.
Link Not Ready
There is a link but it is not ready (address not resolved).
Send Any
If both IP and GSM communication paths are enabled and the LYNX Touch is registered, a Test alarm is sent over IP path. If
that is not successful, it sends the alarm over GSM path and the following message is displayed: Test Message Sent
If the device is not registered, the following is displayed: Test Message Failed – Not Registered
Send GSM Message
If GSM communication path is enabled and the LYNX Touch is registered, a Test alarm to AlarmNet over the GSM path. The
following message is displayed: Test Message Sent
If the device is not registered, the following message is displayed: Test Message Failed – Not Registered
Send Ethernet Message
If IP communication path is enabled and the LYNX Touch is registered, a Test alarm to AlarmNet over the IP path. The
following message is displayed: Test Message Sent
If the device is not registered, the following message is displayed: Test Message Failed – Not Registered
Setup Communication – Performs registration of the LYNX Touch and its associated communication
module with AlarmNet updates configuration files or reset factory defaults.
Registering the LYNX Touch
Once the LYNX Touch is initialized and a communications module is programmed, it must be registered to
enable the account. Upon completion of the registration process, the LYNX Touch transmits a registration
message and receives a registration validation indicating that the account is now enabled. Wait for the
“Registration Success” message to appear, regardless of which registration method is used.
You can register the communications module by one of the following methods:
• Through the AlarmNet Direct website
• By Phone
• Through the LYNX Touch Diagnostics
- 52 -
LYNX Touch Installation and Setup Guide
Programming the Control
Register through AlarmNet Direct Website
If the communications module has been programmed through AlarmNet Direct, the data must be
transferred to the module, and the module must be registered by visiting:
https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
Log in and follow the on-screen prompts.
If required, click on “Dealer Signup” from the login screen to gain access to the Honeywell web-based
programming.
Dealer Sign-Up Direct Link: https://services.alarmnet.com/AlarmNetDirectP_Sign-Up.
Complete the sign-up form then follow the instructions. Only one sign-up per dealer is required. Once an
initial user is established, additional logins may be created by that user.
Please have the following information available when programming the device:
1. Primary City ID (two-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on outside of box and on label inside module. Once the module
is registered, log out of the AlarmNet Direct website.
Register by Phone
To register the module by telephone, call the AlarmNet Technical Assistance Center (TAC) at 1-800-2226525.
Please have the following information available:
• MAC number (found on the label).
• Subscriber information (provided by the Central Station), including a city code, CSID, and a subscriber ID.
• When instructed to do so, select Register Device in the LYNX Touch Diagnostics to complete the
registration.
Register through LYNX Touch Diagnostics
Register the module using the LYNX Touch Diagnostics and the following procedure.
SCREEN
Comm. Diagnostics
ACTION
1. Select “Comm. Diagnostics” The System displays the following options depending upon
the communication device that is installed:
Ethernet
Configure
WiFi Location
WiFi
Information
None
GSM
Information
Use the down arrow to scroll to the next page of options. Use the arrow to return to
the previous page:
Communication
Test
Setup
Status
Communication
Communication
Communication
ID Numbers
Setup
Communication
2. Select “Setup Communication”. The System advances to the Registration screen and
the following options are displayed:
Register
Register Device
Device
With PIN
Update
Factory
Server
Defaults
3. Select “Register Device”. The registration message is sent and the unit waits
for the acknowledgement. (Refer to the table below for applicable
registration messages.)
Note: Register Device can be cancelled by selecting “Cancel”. The registration process is
aborted and the message Registration Cancelled! is displayed.
- 53 -
LYNX Touch Installation and Setup Guide
Programming the Control
During the registration process the following messages may be displayed:
Message
Getting Configuration File…
Registering…
Registration Successful!
Registering – Try Later!
Registration Failed!
Invalid Configuration!
Timed Out.
Central Station Database Full.
Primary Sub ID Bad.
Primary ID – Need PIN.
Account Disabled.
Meaning
The configuration file is obtained from AlarmNet if the module was programmed through
AlarmNet Direct or a previously programmed module was defaulted.
The registration message is sent and the unit is waiting for the acknowledgement.
The module is registered and is now in full service and available for alarm reporting to the
Central Station.
Error Message indicates the module is busy.
Error message followed by one of the messages below:
Indicates the configuration is invalid.
Displayed if no response to the registration request is received.
Indicates CS database has more than 1000 subscribers.
Indicates the city, Central Station, or customer number for the labeled account is not
accepted. The ID information was either entered incorrectly, or the Central Station failed
to pre-authorize programmed ID numbers with AlarmNet customer service.
Indicates the city, Central Station, or customer number for the labeled account is not
accepted. The ID information was either entered incorrectly, or the Central Station failed
to pre-authorize programmed ID numbers with AlarmNet customer service. See the
Register Device With PIN section.
Displayed if the account is disabled in AlarmNet.
Register Device with PIN
This procedure is used to replace one LYNX Touch module with another.
SCREEN
Comm. Diagnostics
Setup
Communication
ACTION
1. Select “Comm. Diagnostics” The System displays the following options depending upon
the communication device that is installed:
Ethernet
GSM
Communication
Information
Information
Status
Communication
Test
Setup
ID Numbers
Communication
Communication
2. Select “Setup Communication”. The System advances to the Registration screen and
the following options are displayed:
Register
Register Device
Device
With PIN
Update
Factory
Server
Defaults
3. Select “Register Device With PIN”. Enter a 4-digit alphanumeric PIN number
(provided by your Central Station, your dealer or an authorized AlarmNet
representative) on the displayed keypad then select “Done”. (Refer to the
table below for applicable registration messages.)
Note: Register Device With PIN can be cancelled by selecting “Cancel”. The registration
process is aborted and the message Registration Cancelled! is displayed.
During the registration process the following messages may be displayed:
Message
Registering…
Registration Successful!
Registering – Try Later!
Registration Failed!
Invalid Configuration!
Timed Out.
Primary ID – Need PIN.
Meaning
The registration message is sent and the unit is waiting for the acknowledgement.
The PIN number is valid and module is registered and is now in full service and available
for alarm reporting to the Central Station. The old module is unregistered. Additionally,
AlarmNet sends a substitution alarm to the Central Station.
Error Message indicates the module is busy.
Error message followed by one of the messages below:
Indicates the configuration is invalid.
Displayed if no response to the registration request is received.
Indicates PIN that was entered is invalid.
- 54 -
LYNX Touch Installation and Setup Guide
Programming the Control
Update Server
This procedure is used to upload the Configuration File to the Server.
SCREEN
Comm. Diagnostics
ACTION
1. Select “Comm. Diagnostics” The System displays the following options depending upon
the communication device that is installed:
Ethernet
WiFi Location
Configure
WiFi
Information
None
GSM
Information
Use the down arrow to scroll to the next page of options. Use the arrow to return to
the previous page:
Test
Setup
Communication
Communication
Communication
Status
Communication
ID Numbers
Setup
Communication
2. Select “Setup Communication”. The System advances to the Registration screen and
the following options are displayed:
Register
Register Device
Device
With PIN
Update
Factory
Server
Defaults
3. Select “Update Server” and select “Yes” when the confirmation screen appears. The
device uploads its entire configuration file to the server. Selecting “No” will cancel the
operation. (Refer to the table below for applicable registration messages.)
During the upload process the following messages may be displayed:
Message
Meaning
Updating Root File…
Programming Done
Updating Configuration – Try Later!
Cannot Upload – Try Later!
Update Root File – Failed!
The root file is being uploaded.
Indicates the root file has been successfully uploaded.
Error message indicates the module is busy
Error message indicates the communication path(s) is not available.
Error message indicates an error while uploading root file.
Enroll the L5100-WiFi Module
The module can be enrolled using one of the following procedures:
• Scan Access Points
• Manual Configure Access Points
• WPS
SCREEN
Comm. Diagnostics
ACTION
1. Select “Comm. Diagnostics” The System displays the following options depending upon
the communication device that is installed:
Ethernet
WiFi Location
Configure
WiFi
Information
None
GSM
Information
Use the down arrow to scroll to the next page of options. Use the arrow to return to
the previous page:
Communication
Test
Setup
Status
Communication
Communication
Communication
ID Numbers
- 55 -
LYNX Touch Installation and Setup Guide
Programming the Control
SCREEN
ACTION
WiFi Location
2. Select “WiFi Location”. The System will scroll between “None” and “Speaker Side”. After
selecting “Speaker Side”, the “Configure WiFi” option will be displayed.
3. Select “Configure WiFi”. The following options will be displayed”:
None
Scan Access Points
Manually Configure AP
WPS
Enroll using Scan Access Points
Note: If the preferred access point is not available after scanning, manually select the network via the “Manually Configure
Access Points” procedure.
1. Select “Scan Access Points”. The available networks and signal strength are displayed. Use the down
arrow to scroll to the next page of options. Use the arrow to return to the previous page.
Ready To Arm
SSID = Vtek, RSSI = -62dbm
SSID = JimC, RSSI = -66dbm
SSID = Toms_net, RSSI = -86dbm
Edit
Scan
5200-100-074-V0
2. Select the desired Network and then press the “Edit” button.
3. Select “Key” and enter the network password on the displayed keypad. The network information is displayed.
Select Done.
4. Select the “Join” button. A confirmation screen will be displayed.
5. Select “OK”, then select “Save” to confirm the selection.
6. Select the “” button two times. The Ethernet information will be displayed. Signal strength will be indicated
by a series of colored bars along with the RSSI level (in dBM).
Bars
4 White
1 Yellow, 3 White
2 Yellow, 2 White
3 Yellow, 1 White
4 Yellow
Meaning
No connection
Weak
Fair
Good
Excellent
RSSI range (dBM)
-255 (used internally)
-81 or higher
-71 to -80
-51 to -70
-50 or less
Manually Configure Access Points
Note: For WEP Security type, the LYNX Touch supports the Key Index 1 in open system authentication mode.
1.
Select “Manually Configure AP”, the following screen is displayed.
Ready To Arm
Name SSID
Toms_net
Security
Network Type
WPA1
Infrastructure
Key
****
Join
Static
5200-100-076-V0
2. Select “SSID Name” and then enter a name (not to exceed 31 characters) on the displayed keyboard.
3. Select “Security”. The system scrolls between the following options:
Open
WPA1
WPA2
WEP
When configuring for WEP encryption key on the access point, always use hexa-decimal type as the input method.
4. Select “Network Type”. The system scrolls between “Infrastructure” and “Ad-Hoc”.
- 56 -
LYNX Touch Installation and Setup Guide
Programming the Control
5. Select “DHCP”. The system scrolls between “Yes” and “No”. If “No” is selected the “Static” button is displayed.
Note: When entering a password, up to 31 characters can be entered. The system will only display the first 22 characters but
will accept up to 31.
6. If a password is required, select “Key” and enter the password.
7. Select the “Static” button and go to step 8.
8. Select each of the following and enter the required information on the displayed keyboard:
IP Address (Enter the 4-part address)
Subnet Mask (Enter the 4-part address)
Gateway IP Address (Enter the 4-part address)
DNS Server IP Address (Enter the 4-part address)
9. Select “Save” when complete. Pressing “Save” will cause the panel to automatically attempt to join the
configured access point every time the system is powered up.
10. Select “Join” when ready to connect with the access point. If the panel joins the access point successfully, it
will automatically attempt to join this access point again on power up.
WiFi Protected Set-up (WPS)
Note: For WPS operation, press the WPS button on the access point first. Then press the WPS button within 2 minutes
1. Select “WPS”, the system displays “Please Stand-by for WPS Operation…”.
2. If the operation is successful the system displays “Device has been successfully added to the network.”
Select “OK”.
3. If the operation is unsuccessful the system displays “Failed Operation. Device not added to the network.”
Select “OK”.
Factory Defaults
This procedure resets the programming options to factory-default values.
SCREEN
Comm. Diagnostics
ACTION
1. Select “Comm. Diagnostics” The System displays the following options depending upon
the communication device that is installed:
Ethernet
Configure
WiFi Location
Information
WiFi
None
GSM
Information
Use the down arrow to scroll to the next page of options. Use the arrow to return to
the previous page:
Test
Setup
Communication
Communication
Communication
Status
Communication
ID Numbers
Setup
Communication
2. Select “Setup Communication”. The System advances to the Registration screen and
the following options are displayed:
Register
Register Device
Device
With PIN
Update
Factory
Server
Defaults
3. Select “Factory Defaults” and select “Yes” when the confirmation screen appears. The
device is reset to factory default values. Selecting “No” will cancel the operation. (Refer
to the table below for applicable registration messages.)
The following messages may be displayed:
Message
Default Configuration – Successful!
Default Configuration Failed –
Access Denied
Default Configuration – Try Later!
Meaning
Indicates all programmed values are reset to the original factory settings.
Error message indicates the device does not have local programming access.
Error message indicates the module is busy.
- 57 -
LYNX Touch Installation and Setup Guide
Remote Programming/Control (Downloading)
General Information
The Control Panel can be remotely programmed from an IBM-compatible Personal Computer (PC), Compass
Downloader, a HAYES compatible Modem (L5210/L5210CN only) or via a capable GSM or IP
Communications Module. When connected to the COMPASS Downloader – “SERVICE UPDATE” appears on
touch screen.
Downloading may only be performed if a technician is at the site.
UL
Multiple security levels protect remote programming against compromise by attempts to defeat the system.
1. Security Code Handshake: A download ID code is verified for authenticity before connection is
established.
2. Site-Initiated Remote Programming: The installer initiates downloading by selecting the “Initiate
Download” button on the Installer programming screen.
3. Station-Initiated Remote Programming: The operator calls the site from your office to initiate the
download call. The Control hangs up and then calls back the PC via the preprogrammed telephone
number. The unit can then be uploaded, downloaded, or controlled from your office.
4. Data Encryption: Data passed between the PC and the Control is encrypted for security so that it is
very difficult for a foreign device tapped into the phone line to take over communication and substitute
system-compromising information.
Equipment required to download to a system at the premises
• Compass Downloader for Windows (at revision level supporting LYNX Touch).
Flexible Callback: If enabled in Installer Programming, the download operator can temporarily change the
last 1, 2, or 3 digits (depending on selection) of the call back number. This allows the control to call back a
computer other than the one programmed, which may be helpful at times of high computer traffic.
Remote Programming Information
If using Remote Programming, the LYNX Touch must be connected to the telephone line, GSM Cellular or to
the Internet, as applicable.
The downloading system can perform many functions when in communication with the Control. Besides
uploading and downloading, the status of the system can be observed and various commands can be
initiated, as follows:
• Arm the system in the away mode; disarm the system.
• Bypass a zone.
• Force the system to accept a new program download.
• Shut down communication functions (for nonpayment of monitoring fees in an owned system).
• Shut down all security system functions (for nonpayment for a leased system).
• Inhibit local keypad programming (prevents account takeover).
• Command the system to upload a copy of its resident program to the office.
• Set the time
• View/Modify
• Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm,
zones currently in trouble, and RF sensors with low battery conditions; read control’s time.
Notes: (1)
(2)
After the control and the PC have established valid communication, “Service Update” will be displayed on the
LCD.
The detailed operation of the download functions is covered in the installation instructions for the Compass
Downloader for Windows.
- 58 -
LYNX Touch Installation and Setup Guide
Remote Programming/Control (Downloading)
Remote Programming Advisory Notes
• A copy of the program downloaded may be printed using the IBM PC-compatible computer’s internal
report generator, when an optional printer is connected (consult your PC manual for proper printer and
connections).
• The approximate time for program upload or download for a complete program is shown below:
Communication Method
PSTN*
GSM
IP or WiFi
Approximate Time
380 secs.
75 secs.
30 secs.
* Not applicable to the LYNX Touch L7000/L7000CN
- 59 -
LYNX Touch Installation and Setup Guide
System Operation
Key/Touchscreen Operation
The keys and touchscreen allows the user to arm and disarm the system, and perform other system
functions, such as bypassing zones. Zone and system conditions (ALARM, trouble, bypass) are displayed on
the display. When an alarm occurs, console sounding and external sounding will occur, and the zone(s) in
alarm will be displayed on the display. Pressing any key will silence the keypad sounder for 10 seconds (only
once). Disarming the system will silence both console and external sounders. When the system is disarmed,
any zones that were in an alarm condition during the armed period will be displayed (memory of alarm). To
clear this display, simply repeat the disarm sequence by pressing the OFF key and entering the Security
Code. The console also features chime annunciation, and three panic key icons for silent, audible, fire or
personal emergency alarms. These keys can notify the Central Station of an alarm condition, if that service
is connected.
Panic Key/Icons
There are three panic key icons that, if programmed, are displayed on the virtual keypad when the “PANIC”
key is depressed for four seconds. The panic key screen will timeout if a selection is not made within ten
seconds. The keys can be used to manually initiate alarms and send a report to the Central Station. Each
can be individually programmed for 24-hour silent, audible, personal or fire emergency responses. The panic
function is activated when the respective keys is pressed. The panic functions are identified by the system as
follows:
Zone
95
96
99
Function
Fire Emergency
Medical Emergency
Police Emergency
Important: For the silent panic functions to be of practical value, the system must be connected to a Central Station.
Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The
factory default Installer Code is 4-1-1-2, but may be changed in the Installer Code programming
field. The Installer Code is the only code that allows entry into Installer Programming mode.
Master Code
In normal operation mode, the Master Code is used to enter the 4-digit User Security Codes.
Enter/Change the Master Code by installer.
The factory default Master Code for the LYNX Touch Control is set to 1-2-3-4. The Master Code is used to
enter the 4-digit User Security Codes.
SCREEN
ACTION
1.
Ready To Arm
Users
Events
Test
Keypad
Date Time
Reminders
Slide Show
WiFi Config
After entering the User Tools/Programming Menu, select the “Users” icon
on the User Menu screen. The system displays the User Code
Programming screen
Back
5200-100-036-V0
Master ****
3.
Select “Master”, then select “Edit”.
4.
Enter a new four-digit Master Code on the displayed keypad The system
will display the new code on the left side of the screen.
Select “Done” when you are finished.
The system returns to the User Code Programming screen.
5.
6.
- 60 -
LYNX Touch Installation and Setup Guide
System Operation
Secondary User Codes
In normal operation mode, the Master Code can be used to assign up to 30 (L5210/L5210CN) or 46
(L7000/L7000CN) secondary 4-digit security codes, including a Guest Code and a Duress Code. The Master
Code can also be used to remove secondary codes from the system (individually). Refer to the LYNX Touch
User Manual for additional information.
Reset Master Code
1. After Entering the Installer Programming Mode, select “Reset Master Code” from the second page of the
Installer Programming Tools menu.
2. The system displays a confirmation screen. Select the “Yes” key to reset the Master Code to “1234”.
3. If confirmed, the Master Code will be reset back to “1-2-3-4”. This will be logged in the System Event Log
as “Reset Master Code User 2 E655”. The system returns to the second page of the Installer
Programming Tools menu. OR
If the reset failed, the system will display: “Command Failed. Unable to Reset Master Code”.
•
•
•
•
•
Security Code Notes
The Master and Secondary security codes permit access to the system for arming, disarming, etc.
The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code
cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
The Babysitter Code can disarm the system only if it was used to arm it. In addition, the Babysitter
Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
Duress code sends a special code to the Central Station when used to perform any system operation.
Instruct users to be careful not to use this code for normal usage.
Opening/closing reports are sent for the Installer Code, with the appropriate subscriber number.
Master Code and secondary User 2 and 3-32 (L5210/L5210CN) or 3-48 (L7000/L7000CN), respectively,
in Contact ID® format (with the appropriate User Code number).
- 61 -
LYNX Touch Installation and Setup Guide
System Operation
“Follow Me” System Announcement Feature (L5210/L5210CN Only)
This feature allows the LYNX Touch to deliver a voice system message to the Follow Me Phone numbers
programmed by the installer. The LYNX Touch will first transmit reports to the Central Station and after
receiving its kiss-off, the system will dial the user phone numbers and begin transmitting the welcome
message “System Message, Press Star to Play”. The system will dial the user phone numbers a maximum of
eight times.
The “Follow Me” System announcements feature is only supported if a PSTN line is available. The
announcements are individually sent to the phone numbers, which are programmed as Follow Me Phone 1
and Follow Me Phone 2 respectively in the Reporter Programming section. System Follow Me
announcements are triggered by a system event that belongs to one of the Event Groups enabled by Installer
individually for the programmed phone number(s). The groups are listed below.
• All Bypassing actions by a user
• Any Open/Close (arming/disarming status changes)
• Any Alarms
• Any Alarm Restores
• Alarm Cancel by the user
• Any System Troubles
• Any Test
• Non-security Events
If the “*” key is not pressed, LYNX Touch will announce “System message Press * to Play” for 45 seconds
before hanging up and redialing the programmed number. The control will make eight attempts before
unsuccessfully ending the System “Follow Me” session and erasing all the events in the queue. The next call
will be triggered by a new event from the Event Group enabled for the programmed number(s).
If the “*” key is pressed, LYNX Touch will play back a sequence of System “Follow Me” announcements from
the queue in chronological order starting with the oldest one. The announcements will include “End of
Message” at the end of the “Follow Me” announcements.
If the “*” key is pressed again during playback or within 15 seconds following the end of the playback, the
control will repeat the sequence. Otherwise the system will hang up, successfully ending the System “Follow
Me” session. Because the “*” key was pressed LYNX Touch will not redial the number again. The next call
will be triggered by a new event from the Event Group enabled for the programmed number(s).
Note: The follow me system announcement will be terminated if any other event requires the system to send a report to the
Central Station. Once the PSTN line is available the session will be resumed and the control will again make up to 8
delivery attempts.
Follow Me Event Triggers
AC Loss
Audible Panic
Automatic Disarmed
Battery Failed Under Load
Burglary Zone Bypass
Carbon Monoxide Detected
Disarmed From AWAY or STAY
Emergency Alarm
Entry/Exit Alarm
Exit Error Alarm (zone)
Expansion Module Tamper
Expansion Module Failure
Expansion Module Tamper Alarm
Expansion Module Tamper Trouble
Fire Alarm
Fire Trouble
Follow Me
Announcement
AC Loss
Panic Alarm
Disarmed
System Low Battery
Zone ** Bypassed
Carbon Monoxide Alarm
Disarmed
Emergency Alarm
Perimeter Alarm
Perimeter Alarm
Tamper Alarm
System Trouble
Tamper Alarm
Tamper Alarm
Fire Alarm
System Trouble
Follow Me Event Triggers
Interior Alarm
Keypad Panic
Manual Test
Medical Alarm
Perimeter Alarm
Remote Disarm
RF Sensor Lost
Sensor Low Battery or Tamper
Silent Burglary
Siren Tamper
System Inactivity
System Low Battery
Water Leakage Alarm
Zone Bypass
Zone Tamper (Alarm)
Zone Trouble
** = Zone Number
- 62 -
Follow Me
Announcement
Interior Alarm
Panic Alarm
System Test
Emergency Alarm
Perimeter Alarm
Disarmed
System Trouble
Sensor Trouble
Silent Burglary
Tamper Alarm
No Check In
System Low Battery
Auxiliary Alarm
Zone ** Bypassed
Tamper Alarm
System Trouble
LYNX Touch Installation and Setup Guide
System Operation
“Follow Me” Reminder Feature (L5210/L5210CN Only)
The “Follow Me” feature allows the user to schedule a time driven message. When activated, the system will
dial the Follow Me Phone 1 and/or the Follow Me Phone 2 telephone numbers, which are programmed by the
installer (in the Reporter Programming section), and deliver a recorded message. The LYNX Touch will
immediately begin transmitting the voice message and will repeat the message for 45 seconds. If the
message has timed out, the system will redial the programmed number a maximum of seven additional
times or until it is acknowledged. Selecting “OK” when the confirmation screen is displayed on the LYNX
Touch will terminate both the “Follow Me” reminder and the local reminder announcements.
Notes: (1) This feature is only supported if it has been programmed.
(2) The follow me reminder will be terminated if any other event requires the system to dial out, however, delivery of
the local schedule reminder message will continue.
(3) If a Central Station report must be sent, the “Follow Me” Reminder message will be suspended. Once the PSTN
line is available the session will be resumed and the control will again make up to 8 delivery attempts.
Remote Phone Control Feature (L5210/L5210CN Only)
The remote phone control feature, which must be enabled, allows the user to access the security system from
any off-site touch-tone telephone. The control will pick up the incoming call, based on the specified ring
count, and will announce “SYSTEM ENTER CODE” every three seconds for the next nine seconds. During
this period the panel will wait for a valid User Code to be entered. If a valid User Code is not entered or the
nine second period expires a modem tone will be generated for remote programming (Compass
Downloading). If a valid User Code has been entered, the control will announce the current system status
and/or beeping sounds. Refer to the User Guide for additional information regarding this feature.
- 63 -
LYNX Touch Installation and Setup Guide
System Operation
System Displays
The following icons will be displayed on the Home screen along with specific zone status information
(if applicable) to indicate system status.
DISPLAY
DEFINITION
DISPLAY
DEFINITION
DISPLAY
DEFINITION
AC Loss
Door Open
Fault *
Garage Door
Alarm
(intrusion)
Window Open
WiFi source
present and
signal strength
Armed Away
Exit Active
No WiFi source
Armed Stay
Battery Low
Fire
OR
Heat Sensor
Flood
Check Zones
Glass Break
CO Alarm
Medical Alarm
Disarmed Not
Ready to Arm
Motion
Disarmed
Ready to Arm
Temperature
90 RF Jam
Cover
Tamper
94 Phone
Line Cut
Reporter
Failure
103 Comm.
Trouble
Automation
(Z-Wave Node
Failure)
Zone Status Displays
The following icons will be displayed on the Zone Status screen along with specific zone status information
when a zone has been Faulted, Bypassed or in Alarm.
DISPLAY
DEFINITION
Alarm
Fault (Yellow)
DISPLAY
DEFINITION
Ready
Trouble (red)
- 64 -
DISPLAY
DEFINITION
Bypass
LYNX Touch Installation and Setup Guide
System Operation
UL
Audio alarm verification has not been evaluated by UL.
Audio Alarm Verification (Two-Way Voice Feature)
This feature allows the Central Station operator to listen, talk to or conduct a two-way conversation with an
individual(s) at the premises. It also assists the operator in gathering information about the nature and
location of the alarm that may be helpful in responding to police and fire departments. All LYNX Touch
Control Panels are capable of supporting the Two-Way Voice feature. The LYNX Touch does not make
system announcements when the Two-Way Voice feature is active.
If a WiFi connection is being used for Two-Way Voice (AAV), sufficient bandwidth must be available.
• AAV requires a continuous WiFi upload/download bandwidth of 90kbps for proper operation.
• WiFi bandwidth less than 90kbps may result in degraded performance.
Activation
Fire and CO alarms will prevent the LYNX Touch from starting an AAV session. A new Fire or CO alarm will
end an AAV session that is in progress.
The LYNX Touch sends the “alarm message” followed by a “Listen-in-to-Follow message” (Contact ID® code
606) to the Central Station. The Listen-in-to-Follow message causes the Central Station’s digital receiver to
temporarily hold the phone line for approximately 1 minute. When the LYNX Touch receives the “kissoff”
from the Central Station, indicating that the alarm message has been received, the Two-Way Voice (AAV)
feature is activated in the (default) “Listen Mode” and sirens and keypad sounds are discontinued. The
LYNX Touch transmits a beep acknowledgment to the Central Station, once per second. The beep alternates
between two tones and indicates that the LYNX Touch is waiting for a session command from the Central
Station operator. Once a command is issued the beep acknowledgement is discontinued. If a command is not
issued within two minutes the system will “time out” and the call will be terminated.
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV
commands shown in the table below. The session may be extended 5 minutes, without changing the
operating mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also
resets the session an additional 5 minutes. During the last minute of the 5 minute, session, the LYNX
Touch generates two beeps every 30 seconds to alert the Central Station operator that the session is about to
time out. The Central Station operator may then extend the session by pressing the [7] key on the touch-tone
phone. If the session is not extended, the phone line is disconnected and the session is ended. Sessions may
be ended at any time by pressing the [9] key on the touch-tone phone. The AAV modes are described as
follows:
Note: When entering AAV commands make sure the Central Station receiver has been disconnected from the phone
line, otherwise AAV commands may not go through.
Key
1
Function
Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication from the
Central Station to the violated premises, and allows the operator to communicate through the built-in speaker on
the LYNX Touch. In this mode the “Panic” function key is lit Red and the “Home” function key is alternately lit
Red and Green.
2
VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice communications between
the Central Station and the violated premises via the built-in speaker and microphone on the LYNX Touch. In this
mode the “Panic” function key is lit Red and the “Home” function key is alternately lit Red and Green.
3
Listen Mode: Pressing the [3] key on the touch-tone phone, Enables one-way audio from the violated premises to
the Central Station. The Listen Mode is the start up default mode of the voice feature and allows the operator to
listen through the LYNX Touch microphone. In this mode the “Panic” function key is lit Red and the “Home” function
key is alternately blinks Green and off.
7
Extends the session 5 minutes without changing its operating mode.
9
Ends the session and disconnects the phone line.
- 65 -
LYNX Touch Installation and Setup Guide
System Operation
Event Log
The LYNX Touch Series event log is capable of recording and displaying up to 128 (L5210/L5210CN) or 256
(L7000/L7000CN) system events. The type of events that can be recorded is selectable and is programmed in
the System Type programming field. The event log can be reviewed by entering the Installer Programming
or Master User Programming mode and selecting “Events”. Refer to the LYNX Touch L5210 or L7000 Series
User Manual for additional information. The Events and CID or SIA Codes that are displayed in the Event
Log vary between the LYNX Touch L5210/L5210CN and L7000/L7000CN controls, according to the options
that are programmed. The table below provides definitions of the events/codes that may be displayed by the
panel.
Note: In the unlikely condition that the backup battery becomes fully discharged when AC power is lost, any system activity performed after
the low battery notification will not be saved in the event log. Additionally, the panel will revert to the status condition as before the low
battery notification.
Contact ID® & SIA Event Log Codes
CID
Code
110
121
122
123
131
132
134
135
137
145
146
150
162
301
302
305
316
341
344
351
353
373
374
380
381
383
384
401
403
406
407
408
441
455
459
570
601
602
606
607
623
627
628
654
655
759
760
761
762
SIA
Code
AT/AR
BA/BR
CA/CD
CI
CL
CQ
CR
DF/DR
EA
ES/EJ
ET
FA
FT/FJ
HA/HR
GA/GR
FT/FJ
LT/LR
OA
OC
OP
OQ
PA
RP
RX
TA/TH
TJ
TS/TE
TT
UA
UB/UU
UT/UJ
XG/XH
XT/XR
YT/YR
Definition
Alarm, Fire
Alarm, Duress
Alarm, Silent
Alarm, Audible
Alarm, Perimeter
Alarm, Interior
Alarm, Entry/Exit
Alarm, Day/Night
Alarm, Tamper
Expansion Module Tamper
Silent Burglary
24-Hour Non-Burglary
Carbon Monoxide Detected
Trouble, AC Loss
Trouble, Low System Battery
Trouble, System Reset
System Tamper*
Trouble, Case Tamper
Trouble, RF Receiver Jam Detect
Trouble, Telco 1 Fault
Trouble, Long Range Radio Transmitter Fault
Trouble, Fire Trouble
Trouble, Exit Error Alarm
Trouble, Sensor
Trouble, Loss of Supervision RF
Trouble, Sensor Tamper
RF Low Battery
Open/Close by User
Open/Close Automatic
Cancel
Remote Arm/Disarm
Quick Arm
Armed Stay
Auto-Arm Failed
Recent Close
Zone/Sensor Bypass
Manual Trigger Test Report
Periodic Test Report
Listen-in to follow
Walk Test
Event 90% Full
Program Mode Entry (Logged in Event Log Only)
Program Mode Exit (Logged in Event Log Only)
System Inactivity
Reset Master Code (Logged in Event Log Only)
Resident Monitor Zone Response
Resident Response Zone Response
General Monitor Zone Response
General Response Zone Response
Definition
AC Trouble/AC Restoral
Burglary Alarm/Burglary Restoral
Automatic Closing/Closing Delinquent
Fail to Close (Log only)
Closing Report
Remote Closing
Recent Closing
Door Forced/Door Restoral
Exit Alarm
Expansion Device Tamper/Expansion Tamper Restore
Expansion Trouble
Fire Alarm
Fire Trouble/Fire Trouble Restore
Holdup Alarm/Holdup Restoral
Gas Alarm/Gas Restoral
Fire Trouble/Fire Trouble Restore
Phone Line Trouble/Phone Line Restoral
Automatic Opening
Cancel Report
Opening Report
Remote Opening
Panic Alarm
Automatic Test
Manual Test
Tamper Alarm/Tamper Alarm Restore
Tamper Trouble Restore
Test Start/Test End
Tamper Trouble
Untyped Zone Alarm
Untyped Zone Bypass/Untyped Zone Unbypass
Untyped Zone Trouble/Restore
RF Interference/RF Interference Restore
Transmitter Battery Trouble/Transmitter Battery Restoral
System Battery Trouble/System Battery Restoral
*If APL is enabled, AlarmNet will generate a special comm. fail
message (E316) if it does not hear from a unit within 15 minutes
after a delayed alarm is delivered. This message is meant to alert
the Central Station that the system has been tampered with and
may have been compromised.
- 66 -
LYNX Touch Installation and Setup Guide
System Operation
Central Station Messages
The following messages are sent by the communications modules (4GL/4GLC or 3GL/3GLC, ILP5 and L5100-WiFi) for
the conditions listed below.
Alarm Condition
Power On / Reset
Primary Communication Path Supervision
Secondary Communication Path Supervision
Test
Alarm Code
E339 C0803
E350 C0951
E350 C0952
5555 5555 9
Restore Code
R350 C0951
R350 C0952
The Control Panel sends its own general code (E353) for a trouble condition. The Control panel sends tamper trouble
(E341), tamper alarm (E145), power loss (E301) and low battery (E302) messages.
- 67 -
LYNX Touch Installation and Setup Guide
Testing the System
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user are vital
to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to the
user as well as acquainting the user with the proper operation and limitations of the alarm system and its
component parts. Recommendations must be included for a specific program of frequent testing (at least
weekly) to ensure the system’s proper operation at all times.
Test Modes
The “Test” button provides access to the following functions and test modes:
Option
Walk Test
RF Sniffer Test
Go-No-Go Test
Dialer Test
Zone Discovery
Diagnostics
Function
Refer to the User Manual for additional information
Refer to the Installing Wireless Zones section of this manual for additional information.
Refer to the Installing Wireless Zones section of this manual for additional information.
Refer to the to the paragraph in this section and the User Manual for additional information.
Note: This test is not available on the LYNX Touch L7000/L7000CN.
Provides access to Zone Discovery. Refer to the paragraph in this section for additional
information regarding the Zone Discovery feature.
Provides access to the Reboot Feature and Web Content Usage. Refer to the paragraph in
this section for additional information regarding these features.
Testing the System
After installation is completed, the security system should be carefully tested, as follows:
1. With the system in the disarmed state, check that all zones are intact. If the “Panic” or “Home” function
key is not lit, select the Zones icon to display the faulted zone(s). If necessary, restore faulted zone(s) so
that the “Panic” or “Home” function key lights. Fault and restore every sensor individually to assure that
it is being monitored by the system.
Armed System Test
Alarm messages will be sent to the Central Station during the following tests 1 and 2. Notify the Central
Station in advance that tests will be in progress.
1. Arm the system and fault one or more zones. After 15 seconds (if optional dialer delay is selected),
silence alarm sounder(s) by disarming the system. Check entry/exit delay zones.
2. Check the keypad-initiated alarms by selecting the Panic key. If the system has been programmed for
audible emergency, the keypad will emit a steady alarm sound, and “ALARM” and zone number will be
displayed. For L5210/L7000 configuration, silence the alarm by entering the Security Code. For
L5210CN/L7000CN, silence the alarm by pressing the Home key and entering the Security Code.
If the system has been programmed for silent emergency, there will be no audible alarms or displays, but
a report will be sent to the Central Station.
3. Notify the Central Station when all tests are finished, and verify results with them.
4. To test the wireless part of the system and the RF receiver, perform the two additional tests described in
the Installing Wireless Zones section: Sniffer mode and Go-No-Go Test.
Note:
System Test mode and Go-No-Go Test will be automatically terminated after 3-1/2 to 4 hours if the installer or user
does not manually terminate it. This ensures that fire and panic zones will not remain disabled. However, Sniffer
mode does not automatically expire. You must manually exit Sniffer mode (by depressing the Home key and entering
the Master Code) to return to normal operation. During the final 5 minutes, the system will emit double beeps
indicating that the end of Test mode is nearing.
- 68 -
LYNX Touch Installation and Setup Guide
Testing the System
Dialer Test
Note: This test is not available for the LYNX Touch L7000/L7000CN.
The Dialer Test checks that the phone connection to the Central Station is working properly. Notify the
Central Station in advance that tests will be in progress.
1. With the System in the Installer Programming mode, select the “Test” button and then select the “Dialer
Test” button.
2. If the test is successful the system will send the Manual Trigger Test Report (E601) to the Central
Station. The test will not be recorded in the Event Log.
3. The system will make eight attempts to test the dialer for the Primary and eight attempts to test the
Secondary Central Station. If the test is unsuccessful the system will display a “Reporter Failure”
trouble message after 9-17 minutes.
Zone Discovery Mode
Zone Discovery mode requires Installer supervision when in use. The system is not fully operational for fire or life safety
while Zone Discovery Mode is active.
Zone discovery mode can be used to remotely view all zones that have been programmed in the system for
operation. The zones must have a response type programmed and in the case of RF zones, must also have a
serial number programmed. All zones programmed (except for duress) will be displayed.
Enter Zone Discovery
1. With the System in the Installer Programming mode, select the “Test” button and then select the “Zone
Discovery” button. The “Zone Discovery” button will be highlighted indicating that the mode is active.
Exit Zone Discovery
1. Select the Home key and enter the Installer Code. If you do not exit zone discovery mode manually, the
system will automatically exit zone discovery mode in approximately 1-4 minutes dependent upon the
number of zones that are programmed. The system beeps once and returns to the home screen.
Rebooting the System
The Reboot function allows you to restart the system if required. To reboot the system perform the following:
1. With the System in the Installer Programming mode, select the “Test” button and then select the
“Diagnostics” button.
2. The system advances to the next screen. Select the “Reboot” button. A confirmation screen appears.
3. Select “Yes”. The system will restart.
Note: After the reboot sequence is complete it is recommended that you perform a “Walk Test” to verify that all transmitters
are operational in the system.
Web Content Usage
This feature is used for internal diagnostics and troubleshooting.
- 69 -
LYNX Touch Installation and Setup Guide
LYNX Touch (L5210/L7000) Programming Default Values
Program Function
Installer Code
System Type
RF Jam
Speaker Phone (L5210 only)
Two Way Voice
RF House Code
Phone Notification (L5210 only)
Remote Phone (L5210 only)
Phone Detect Time (L5210 only)
Events - Log All
Events - Log Alarm
Events - Log Bypass
Events - Log Open/Close
Events - Log Trouble
Non Security
Remote Access Serial
Multi Mode Serial
Date Time
Calendar
Enter Time
Time Zone
Day Light Savings time
Start Month
Start Week
End Month
End Week
Communicator
Communications Path
APL
City ID
CS ID
Sub ID
Supervision
Old Alarm Time
Remote Acc. Comm.
Multi Mode Comm.
GSM Fault Time
GSM Rollover
GSM 24 Hour Test
IP Fault Time
Use DHCP
NIC IP Address
Subnet Mask
Gateway IP Address
DNS Server IP Address
Zones
Reporter
Primary CS info
Phone Type
Communicator Type
Phone Number
Account Number
Dynamic Priority
Dynamic Delay
Report All
Report Alarms
Report Troubles
Report Open/Close
Report Tests
Configuration 1
Configuration 2
Configuration 3
Configuration 4
4112
4112
4112
4112
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Log All Set
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Log All Set
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Press To Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Press To Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
None
Disabled
None
None
None
24 Hours
10 Minutes
Disabled
Disabled
00
No
No
00
Yes
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
None
None
Disabled
Disabled
None
None
None
None
None
None
24 Hours
24 Hours
10 Minutes
10 Minutes
Disabled
Disabled
Disabled
Disabled
00
00
No
No
No
No
00
00
Yes
Yes
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
See Zone Programming Default Values
None
Disabled
None
None
None
24 Hours
10 Minutes
Disabled
Disabled
00
No
No
00
Yes
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
- 70 -
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
LYNX Touch Installation and Setup Guide
LYNX Touch (L5210/L7000) Programming Default Values
Program Function
Secondary CS info
Phone Type
Communicator Type
Phone Number
Account Number
Dynamic Priority
Dynamic Delay
Report All
Report Alarms
Report Troubles
Report Open/Close
Report Tests
Follow Me Phone 1 (L5210 only)
Phone Type (L5210 only)
Phone Number (L5210 only)
Report All (L5210 only)
Report Alarms (L5210 only)
Report Troubles (L5210 only)
Report Open/Close (L5210 only)
Report Tests (L5210 only)
Follow Me Phone 2 (L5210 only)
Phone Type (L5210 only)
Phone Number (L5210 only)
Report All (L5210 only)
Report Alarms (L5210 only)
Report Troubles (L5210 only)
Report Open/Close (L5210 only)
Report Tests (L5210 only)
Report Selection
Arm Away
Arm Stay
Disarm
Exit Error
Recent Closing
Event Log Full
Trouble
Trouble Restore
Alarm Restore
Alarm Cancel
Test
Test Restore
Bypass
Bypass Restore
AC Loss
AC Loss Restore
Low Battery
Low Battery Restore
RF Low Battery
RF Low Battery Restore
Options
PBX (L5210 only)
Call Wait Cancel (L5210 only)
Number of Reports
Alarm Report Delay
First Report Offset
Report Frequency
Configuration 1
Configuration 2
Configuration 3
Configuration 4
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Blank
Blank
2 Reports
30 Sec.
6 Hrs
Never
Blank
Blank
2 Reports
30 Sec.
12 Hrs
30 Days
Blank
Blank
2 Reports
30 Sec.
12 Hrs
Never
Blank
Blank
2 Reports
30 Sec.
12 Hrs
Never
- 71 -
LYNX Touch Installation and Setup Guide
LYNX Touch (L5210/L7000) Programming Default Values
Program Function
Downloader
Phone Answer (L5210 only)
Ans. Machine Defeat (L5210 only)
Modem Speed (Future Use)
Ring Counter
Callback Number
Flexible Callback
Number
Sounder
Burglary Alarm Sound
Burglary Bell Timeout
Fire Bell Timeout
Arm Confirm
System Settings
Entry Delay 1
Entry Delay 2
Exit Delay
Backlight Timeout
Quick Arm
Quick Exit
Restart Exit Time
Force Bypass
Exit Warning
Auto Stay Arming
Lack Of Usage Notify
Power-Up In Previous
Display Alarm Cancel
Display Exit Time
Cross Zone Delay
Cross Zone 1
Cross Zone 2
Z-Wave
Z-Wave
Temperature
Configuration 1
Configuration 2
Configuration 3
Configuration 4
Yes
Yes
Slow
2
Blank
No
1
Yes
Yes
Slow
2
Blank
No
1
Yes
Yes
Slow
2
Blank
No
1
Yes
Yes
Slow
2
Blank
No
1
Yes
4 Minutes
4 Minutes
RF Keyfob
Yes
4 Minutes
4 Minutes
RF Keyfob
Yes
4 Minutes
4 Minutes
RF Keyfob
Yes
4 Minutes
4 Minutes
RF Keyfob
30 Seconds
30 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
30 Seconds
30 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
30 Seconds
30 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
30 Seconds
30 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
Enabled-Installed
Fahrenheit
Enabled-Installed
Fahrenheit
Enabled-Installed
Fahrenheit
Enabled-Installed
Fahrenheit
- 72 -
LYNX Touch Installation and Setup Guide
LYNX Touch (L5210CN/L7000CN) Canada Programming Default Values
Program Function
Installer Code
System Type
RF Jam
Speaker Phone (L5210CN only)
Two Way Voice
RF House Code
Phone Notification (L5210CN only)
Remote Phone (L5210CN only)
Phone Detect Time (L5210CN only)
Events - Log All
Events - Log Alarm
Events - Log Bypass
Events - Log Open/Close
Events - Log Trouble
Non Security
Remote Access Serial
Multi Mode Serial
Date Time
Calendar
Enter Time
Time Zone
Day Light Savings time
Start Month
Start Week
End Month
End Week
Communicator
Communications Path
APL
City ID
CS ID
Sub ID
Supervision
Old Alarm Time
Remote Acc. Comm.
Multi Mode Comm.
GSM Fault Time
GSM Rollover
GSM 24 Hour Test
IP Fault Time
Use DHCP
NIC IP Address
Subnet Mask
Gateway IP Address
DNS Server IP Address
Zones
Reporter
Primary CS Info
Phone Type
Communicator Type
Phone Number
Account Number
Dynamic Priority
Dynamic Delay
Report All
Report Alarms
Report Troubles
Report Open/Close
Report Tests
Configuration 1
Configuration 2
Configuration 3
Configuration 4
4112
4112
4112
4112
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Press To Log All
Enabled
Disabled
Disabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Log All Set
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Press To Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
0
Disabled
Enabled
2 Minutes
Press To Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2014
10:00AM
Eastern (EST)
Yes
March
Second
November
First
None
Disabled
None
None
None
24 Hours
10 Minutes
Disabled
Disabled
00
No
No
00
Yes
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
None
None
Disabled
Disabled
None
None
None
None
None
None
24 Hours
24 Hours
10 Minutes
10 Minutes
Disabled
Disabled
Disabled
Disabled
00
00
No
No
No
No
00
00
Yes
Yes
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
See Zone Programming Default Values
None
Disabled
None
None
None
24 Hours
10 Minutes
Disabled
Disabled
00
No
No
00
Yes
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
- 73 -
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
Contact Id: 4 Digit
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
LYNX Touch Installation and Setup Guide
LYNX Touch (L5210CN/L7000CN) Canada Programming Default Values
Program Function
Secondary CS Info
Phone Type
Communicator Type
Phone Number
Account Number
Dynamic Priority
Dynamic Delay
Report All
Report Alarms
Report Troubles
Report Open/Close
Report Tests
Follow Me Phone 1 (L5210CN only)
Phone Type (L5210CN only)
Phone Number (L5210CN only)
Report All (L5210CN only)
Report Alarms (L5210CN only)
Report Troubles (L5210CN only)
Report Open/Close (L5210CN only)
Report Tests (L5210CN only)
Follow Me Phone 2 (L5210CN only)
Phone Type (L5210CN only)
Phone Number (L5210CN only)
Report All (L5210CN only)
Report Alarms (L5210CN only)
Report Troubles (L5210CN only)
Report Open/Close (L5210CN only)
Report Tests (L5210CN only)
Report Selection
Arm Away
Arm Stay
Disarm
Exit Error
Recent Closing
Event Log Full
Trouble
Trouble Restore
Alarm Restore
Alarm Cancel
Test
Test Restore
Bypass
Bypass Restore
AC Loss
AC Loss Restore
Low Battery
Low Battery Restore
RF Low Battery
RF Low Battery Restore
Options
PBX (L5210CN only)
Call Wait Cancel (L5210CN only)
Number of Reports
Alarm Report Delay
First Report Offset
Report Frequency
Configuration 1
Configuration 2
Configuration 3
Configuration 4
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
None
Blank
FFFF
None
None
Press to Report All
Enabled
Enabled
Disabled
Enabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
None
Blank
Press To Report All
Disabled
Disabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Blank
Blank
Unlimited
No Delay
6 Hrs
Never
Blank
Blank
Unlimited
15 Seconds
12 Hrs
30 Days
Blank
Blank
Unlimited
No Delay
12 Hrs
Never
Blank
Blank
Unlimited
No Delay
12 Hrs
Never
- 74 -
LYNX Touch Installation and Setup Guide
LYNX Touch (L5210CN/L7000CN) Canada Programming Default Values
Program Function
Downloader
Phone Answer (L5210CN only)
Ans. Machine Defeat (L5210CN only)
Modem Speed (Future Use)
Ring Counter
Callback Number
Flexible Callback
Number
Sounder
Burglary Alarm Sound
Burglary Bell Timeout
Fire Bell Timeout
Arm Confirm
Alarm Options
System Settings
Entry Delay 1
Entry Delay 2
Exit Delay
Backlight Timeout
Quick Arm
Quick Exit
Restart Exit Time
Force Bypass
Exit Warning
Auto Stay Arming
Lack Of Usage Notify
Power-Up In Previous
Display Alarm Cancel
Display Exit Time
Cross Zone Delay
Cross Zone 1
Cross Zone 2
Z-Wave
Z-Wave
Temperature
Configuration 1
Configuration 2
Configuration 3
Configuration 4
Yes
Yes
Slow
2
Blank
No
1
Yes
Yes
Slow
2
Blank
No
1
Yes
Yes
Slow
2
Blank
No
1
Yes
Yes
Slow
2
Blank
No
1
Yes
4 Minutes
4 Minutes
RF Keyfob
Unlimited
Yes
4 Minutes
4 Minutes
RF Keyfob
2
Yes
4 Minutes
4 Minutes
RF Keyfob
2
Yes
4 Minutes
4 Minutes
RF Keyfob
2
30 Seconds
60 Seconds
60 Seconds
No
Yes
Yes
No
No
No
No
Disabled
Yes
No
Yes
3 Minutes
Disabled
Disabled
45 Seconds
60 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
30 Seconds
60 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
30 Seconds
60 Seconds
60 Seconds
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
Enabled-Installed
Fahrenheit
Enabled-Installed
Fahrenheit
Enabled-Installed
Fahrenheit
Enabled-Installed
Fahrenheit
- 75 -
LYNX Touch Installation and Setup Guide
Zone Programming Default Values
Zone Programming Notes
1.
2.
3.
4.
Zone 1 is a hardwire zone; Zones 95, 96 and 99 are keypad panics.
For the LYNX Touch L5210/L5210CN Zones 2 to 64 are RF zones (Zones 46 to 48 are reserved for Garage Door Zones); Zones 140-155
are RF Button Zones and 180-185 are Temperature Zones.
For the LYNX Touch L7000/L7000CN Zones 2 to 80 are RF zones (Zones 45 to 48 are reserved for Garage Door Zones); Zones 140-163
are RF Button Zones and 180-187 are Temperature Zones.
The default values shown below are for the LYNX Touch L5210/L5210CN.
Zone Assignment/Alarm Response Types for Configuration 1
Zone
Number
1
2
3
4
5
46
47
48
140
141
142
143
144
145
146
147
180
181
182
183
184
185
95
96
99
Loop
Number
--2
2
2
1
1
1
1
3
2
4
1
3
2
4
1
-------------------
Device Type
Response Type
New
Door
Door
Window
Motion Sensor
New
New
New
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Fire
Medical
Police
Not Used
Entry Exit 1
Entry Exit 1
Perimeter
Interior With Delay
Not Used
Not Used
Not Used
Arm Away
Disarm
Arm Stay
No Response
Arm Away
Disarm
Arm Stay
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Fire No Verification
Not Used
24-Hour Silent
Alarm
Report
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Chime
Supervision
Disabled
Standard
Standard
Standard
Disabled
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
Panic Trigger
Panic Trigger
Panic Trigger
Arm
Night
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Front
Back
n/a
n/a
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Arm
Night
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Front
Back
Garage
n/a
n/a
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Zone Descriptor
Zone Assignment/Alarm Response Types for Configuration 2
Zone
Number
1
2
3
4
5
6
46
47
48
140
141
142
143
144
145
146
147
180
181
182
183
184
185
95
96
99
Loop
Number
--2
2
2
1
1
1
1
1
3
2
4
1
3
2
4
1
-------------------
Device Type
Response Type
New
Door
Door
Door
Motion Sensor
Smoke Detector
New
New
New
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Fire
Medical
Police
Not Used
Entry Exit 1
Entry Exit 1
Entry Exit 1
Interior With Delay
Fire No Verification
Not Used
Not Used
Not Used
Arm Away
Disarm
Arm Stay
No Response
Arm Away
Disarm
Arm Stay
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Fire No Verification
24-Hour Auxiliary
24-Hour Audible
Alarm
Report
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
- 76 -
Chime
Supervision
Disabled
Standard
Standard
Standard
Disabled
Disabled
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
Panic Trigger
Panic Trigger
Panic Trigger
Zone Descriptor
LYNX Touch Installation and Setup Guide
Zone Programming Default Values
Zone Assignment/Alarm Response Types for Values 3 and 4
Zone
Number
1
2
3
4
5
6
7
8
9
46
47
48
140
141
142
143
144
145
146
147
180
181
182
183
184
185
95
96
99
Loop
Number
--2
2
2
2
2
2
1
1
1
1
1
3
2
4
1
3
2
4
1
-------------------
Device Type
Response Type
New
Door
Door
Window
Window
Window
Window
Motion Sensor
Smoke Detector
New
New
New
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
4 Button
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Fire
Medical
Police
Not Used
Entry Exit 1
Entry Exit 1
Perimeter
Perimeter
Perimeter
Perimeter
Interior With Delay
Fire No Verification
Not Used
Not Used
Not Used
Arm Away
Disarm
No Response
No Response
Arm Away
Disarm
No Response
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Fire No Verification
Not Used
24-Hour Silent
Alarm
Report
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Chime
Supervision
Disabled
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
Panic Trigger
Panic Trigger
Panic Trigger
Arm
Night
n/a
n/a
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Zone Descriptor
n/a
Front
Back
n/a
n/a
n/a
n/a
n/a
n/a
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
x
Carbon Monoxide Detector
x
x
x
x
x
x
x
x
x
Temperature
x
x
x
x
Flood
Environmental
x
x
x
x
x
x
x
x
x
Medical
x
Fire
x
x
x
x
x
Police
x
x
x
x
x
x
x
Garage Door
Other
Trouble
x
Garage Monitor
x
Garage
x
Silent Burglary
x
x
Disarm
x
x
No Response
x
x
Arm Away
x
x
Arm Stay
x
Glass Break
Not Used
Motion Sensor
Monitor
x
24 Hour Silent
x
x
24 Hour Audible
x
x
24 Hour Auxiliary
x
x
Carbon Monoxide
Fire With Verification
x
x
Interior With Delay
x
x
Window
Interior Follower
x
x
Device Type
Door
Day/Night
General Response
x
Response Type
General Monitor
x
Resident Response
Heat Sensor
Resident Monitor
x
Perimeter
x
Entry Exit 2
Smoke Detector
Entry Exit 1
Fire No Verification
Zone Response Type Matrix
x
x
x
x
x
x
x
x
x
- 77 -
x
x
x
x
x
x
x
x
LYNX Touch Installation and Setup Guide
Regulatory Agency Statements
Federal Communications Commission (FCC) Part 15
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
•
•
•
•
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC IC Statement
This device complies with Part 15 of FCC Rules and RSS-210 of Industry Canada. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired
operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS-210 des Industries Canada. Son fonctionnement est soumis aux conditions
suivantes: (1) Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les
interferences causant une reception indésirable.
TELEPHONE/MODEM INTERFACE
Federal Communications Commission (FCC) Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration number and
Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state tariffs. This equipment is
hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets telecommunications network
protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The
Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company.
The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe
system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority, or electrician, as
appropriate.
AVIS: l’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme aux normes de protection,
d’exploitation et de sécurité des réseaux de télécommunications, comme le prescrivent les documents concernant les exigences techniques relatives
au matériel terminal. Le Ministère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le raccorder aux installations de l’enterprise locale de télécommunication. Le
matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est possible que la
conformité aux conditions énoncées ci-dessus n’empêche pas la dégradation du service dans certaines situations.
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise de télécommunications
peut demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de modifications effectuées par l’utilisateur ou à cause de mauvais
fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la source d’energie électrique, de lignes téléphoniques et des
canalisations d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir racours à un service d’inspection des installations
électriques, ou à un électricien, selon le cas.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the
sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif terminal indique le nombre maximal de terminaux qui peuvent être
raccordés à une interface. La terminaison d’une interface téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition
que la somme d’indices d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.
!
RF Exposure
WARNING: The LYNX Touch must be installed to provide a separation distance of at least 7.8 in (20 cm) from all
persons and not co-located or operated in conjunction with any other transmitter except in accordance with FCC
multi-transmitter product procedures.
- 78 -
LYNX Touch Installation and Setup Guide
WARNING
THE LIMITATIONS OF THIS ALARM SYSTEM
While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or
other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a
variety of reasons. For example:
•
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
•
Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not work
without power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put
in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
•
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
•
A user may not be able to reach a panic or emergency button quickly enough.
•
While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the
Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may
not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not
sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector,
for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke
detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, children playing with matches, or arson. Depending on the nature of the fire
and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to
allow all occupants to escape in time to prevent injury or death.
•
Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams
of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion
or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows.
Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical
system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90° to 105°F (32° to 40°C), the detection
performance can decrease.
•
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the
other side of closed or partly open doors. If warning devices are located on a different level of the residence from the
bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not
hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing
traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people.
•
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
•
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect
themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond
appropriately.
•
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to
last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad
(and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device
being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce
the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus
allowing time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for
insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to
insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones
to learn about these developments.
- 79 -
LYNX Touch Installation and Setup Guide
UL Notices
1. For UL Residential Burglar Alarm installations with line security, total exit delay time must not
exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time
must not exceed 120 seconds.
2. Periodic testing must be at least every 24 hours.
3. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for UL installations.
4. Auto-disarming is not a UL Listed feature.
5. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the
alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
- 80 -
LYNX Touch Installation and Setup Guide
SIA Quick Reference Guide
Programming Section
Feature
Range
Installation and Setup Guide or Programming Guide
Exit Error
Enabled or Disabled
Reporter/
Report Selection
Recent Closing
Enabled or Disabled
Alarm Cancel
Enabled or Disabled
Reporter/Options
Call Wait Cancel
Enabled or Disabled
System Settings
Shipping Default
Enabled
Enabled
Enabled
Field is blank (a PBX prefix
is entered to enable)
SIA Requirement
Enabled
Enabled
Enabled
Enabled if User has call
waiting
Number of Reports
1 to 6 Reports
2 Reports
2 Reports
Alarm Report Delay
(Abort Window)
Entry Delay # 1
15, 30 and 45 seconds
30 Seconds
30 Seconds*
30 Seconds
30 Seconds minimum
Entry Delay # 2
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or 4
minutes
None, 15, 30, 45, 60 and
30 Seconds
30 Seconds minimum
Exit Delay
90 seconds and 2, 3 or 4
minutes
45, 60, 90 seconds and 2
60 Seconds
45 seconds minimum
Enabled
minutes
Restart Exit Time
Enabled or Disabled
Yes (Enabled)
Exit Warning
Not selectable
Always enabled
Enabled
Auto Stay Arming
Enabled or Disabled
Yes (Enabled)
Enabled
Cross Zone Delay
30 seconds and 2 minutes
(in 30 second increments),
3 minutes and 4 minutes
None (Disabled)
Enabled and two zones
programmed
Zones
Fire Alarms
Zone Type “Fire with
Verification” must be
selected for Fire Zone 95
Disabled
Disabled
User Guide
User Functions/
User Access
Duress
Duress Code is
Programmed by Master
User as User 16
System tests provided as a
User Function
Disabled
Disabled
n/a
n/a
Disabled
Disabled
System Functions/
Testing the System**
System Test
Communications
While the system is in Test
mode, no alarm reports are
sent to the Central Station
* Combined Entry Delay and Alarm Report Delay (Abort Window) should not exceed 1 minute.
** Refer to the User Guide for procedures on Testing the System.
Note: Using the Call Waiting Cancel feature on a non-Call Waiting line will prevent successful communication to the Central Station.
- 81 -
LYNX Touch Installation and Setup Guide
Specifications
LYNX Touch Series Security Controls
Physical:
Dimensions:
8.5” W x 6” H x 1.875” D
Electrical:
Voltage Input:
9 Vdc from plug-in 2.7A power supply
Rechargeable Backup Battery: Nickel-metal hydride battery pack rated at 7.2 Vdc
Communication:
Formats Supported:
ADEMCO Contact ID® Reporting, 10 characters/sec., DTMF (TouchTone)
Data Tones, 1400/2300Hz Handshake, 1400Hz Kissoff.
Line Seize:
SIA/DCS Format, 2225Hz Handshake, Data Tones, 2025/2235Hz, baud
Double Pole
Ringer Equivalence:
0.5B
ACTA Registration No.:
US: AC3AL05BL5000
Hardwire Zone:
2K ohms, End of Line Resistor (EOLR), 200 ohms max wire resistance, dry
contacts only
Trigger Output:
1K ohms to ground when closed (output low) 3ma
- 82 -
LYNX Touch Installation and Setup Guide
Contacting Technical Support
PLEASE, before you call Technical Support, be sure you:
• READ THE INSTRUCTIONS!
•
Check all wiring connections.
•
Determine that the power supply and/or backup battery are supplying proper voltages.
•
Verify your programming information where applicable.
•
Note the proper model number of this product, and the version level (if known) along with any
documentation that came with the product.
•
Note your Honeywell customer number and/or company name.
Having this information handy will make it easier for us to serve you quickly and effectively.
Technical Support: ..................................................................................................... 1-800-645-7492 (8 a.m.-10 p.m. E.S.T.)
MyWebTech: .............................................................................. http:// www.honeywell.com/security/hsc/resources/MyWebTech
- 83 -
LYNX Touch Installation and Setup Guide
Glossary
AES – Advanced Encryption Standard
APL – Advanced Protection Logic
dBM – decibels milliwatt (power ratio)
DHCP – Dynamic Host Configuration Protocol, which provides a mechanism for allocating IP addresses
dynamically so that addresses can be reused when hosts no longer need them.
DNS – Domain Name System, which is a distributed hierarchical naming system used to resolve domain
names (e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1).
Gateway IP Address – A gateway (sometimes called a router) is a computer and/or software used to connect
two or more networks (including incompatible networks) and translates information from one network to the
other. The Gateway IP address is the IP address for the gateway.
GPRS – General Packet Radio Service
GSM – Global System for Mobile communications, which is an international standard for digital mobile
phone systems used for cellular communication.
IMEI – International Mobile Equipment Identity number
IP – Internet Protocol
IP Address – A unique number consisting of four parts separated by periods, sometimes called a "dotted
quad.," for example: 204.17.29.11, assigned to every computer/workstation connected to the Internet. IP
numbers can be "static" (assigned and unchanging) or "dynamic," assigned via DHCP at each and every
startup.
ISP – Internet Service Provider
KBPS – Kilobits per second
MAC ID – Media Access Code; located on the module label.
NIC – Network Interface Card
RSSI – Received Signal Strength Indication
SCID – SIM Card ID
Subnet Mask – A Subnet is a portion of a network that shares a network address with other portions of the
network, and is distinguished by a subnet number. The Subnet Mask is a 32-bit address mask used in IP to
indicate the bits of an IP address that are being used for the subnet address.
WEP – Wired Equivalent Privacy
WPA – WiFi Protected Access
WPS – WiFi Protected Setup
- 84 -
LYNX Touch Installation and Setup Guide
– Index –
24-hour silent ................................................................. 60
300-03866 ......................................................................... 5
300-04063/300-04063V1 ................................................ 10
300-04064/300-04064V1 ................................................ 10
300-04065/300-04065V1 ................................................ 10
300-04705/300-04705V1 ................................................ 10
5800 Series transmitter loop numbers ......................... 19
5800 Series transmitters ............................................... 17
5802MN .......................................................................... 17
5804BD........................................................................... 17
5804BDV ........................................................................ 17
5804E ............................................................................. 17
5805-6 ............................................................................. 17
5806 ................................................................................ 19
5816 ................................................................................ 17
5817 ................................................................................ 17
E
Enroll the WiFi module ................................................. 55
Enter installer programming mode .............................. 23
Enter/change the master code....................................... 60
Entry delay .............................................................. 25, 48
Entry/exit burglary ........................................................ 25
Ethernet information .................................................... 51
Exit delay ............................................... 22, 25, 48, 68, 80
Exit door......................................................................... 48
Exit warning .................................................................. 48
Exiting program mode ................................................... 24
F
Factory defaults ............................................................. 57
Flexible callback ............................................................ 58
Follow me reminder feature .......................................... 63
Follow me system announcement ................................. 62
Force bypass .................................................................. 48
A
AC Power ................................................................. 10, 11
AC Power loss ................................................................ 10
ADEMCO Contact ID .................................................... 82
Armed system test ......................................................... 68
Audio alarm verification (two-way voice feature) ........ 65
Auto stay arming ........................................................... 48
G
Garage (burglary) .......................................................... 26
Garage monitor .............................................................. 26
General programming information............................... 23
Go-No-Go test ................................................................ 18
GSM information ........................................................... 51
B
Babysitter code .............................................................. 61
Backup battery .................................................. 10, 11, 82
Button transmitters....................................................... 17
H
Home screen................................................................... 21
House identification ...................................................... 17
C
Change installer code .................................................... 27
Communication modules ............................................... 12
Communications ID numbers ....................................... 52
Communications status ................................................. 51
Configuring communication & home automation
modules ...................................................................... 12
Contact ID event log codes ............................................ 66
Contact ID reporting ..................................................... 82
Contacting technical support ........................................ 83
Cross zone 1/cross zone 2............................................... 48
Cross zone delay ................................................ 48, 49, 50
I
ILP5................................................................................ 30
ILP5 ethernet communications module ................. 12, 14
Installer code ................................................................. 60
Installer menu ............................................................... 23
Installing wireless zones ......................................... 18, 19
Installing/configuring communication & home
automation modules ............................................ 13, 15
D
Data encryption ............................................................. 58
Desktop mounting ........................................................... 7
Diagnostics ............................................................... 51, 52
Dialer delay .................................................................... 68
Dialer test ...................................................................... 69
Dip switches ................................................................... 17
Display alarm cancel ..................................................... 48
Display exit time............................................................ 48
Duress code .................................................................... 61
L
L5000DM ......................................................................... 7
L5100-WiFi module ....................................................... 15
L5100-Zwave home automation module ....................... 15
Lack of usage notify....................................................... 48
Liquid crystal display (lCD) touch-screen .................... 20
Loading factory defaults................................................ 24
LYNX Touch (L5100CN) Canada programming default
values ......................................................................... 73
LYNX Touch programming default tables ................... 73
LYNXRCHKIT-SC ......................................................... 10
LYNXRCHKIT-SHA ........................................................ 5
K
Key/touchscreen operation ............................................ 60
Keys ................................................................................ 17
- 85 -
LYNX Touch Installation and Setup Guide
T
Technical support .......................................................... 83
Test communications ..................................................... 52
Test ethernet .................................................................. 52
Test modes ..................................................................... 68
Testing the system ................................................... 68, 69
Touchscreen display ...................................................... 20
Traffic ............................................................................. 21
Transmitter battery life................................................. 17
Transmitter input type .................................................. 17
Transmitter loop numbers............................................. 19
Transmitter supervision ................................................ 17
Unsupervised button ..................................................... 17
Unsupervised RF ........................................................... 17
Update server................................................................. 55
User menu ...................................................................... 23
M
Master code .................................................................... 60
Master Code ................................................................... 61
Memory of alarm ............................................................ 60
Menu screens ................................................................. 22
Mounting base .................................................................. 7
N
Navigating menus .................................................... 20, 22
Navigation keys ............................................................. 21
News ............................................................................... 21
O
Operator commands ....................................................... 65
P
Panic key/icons ............................................................... 60
Plug-in power supply ..................................................... 10
Power-up in previous ..................................................... 48
Program date and time .................................................. 30
Program keys ........................................................... 38, 39
Program the communications module .......................... 31
Program the Z-wave module.......................................... 34
Program zones ................................................................ 35
W
Wall mounting ..................................................... 7, 10, 12
Wireless buttons ............................................................ 17
Wireless keypads ..................................................... 17, 18
Wireless zones ................................................................ 17
Wiring connections .......................................................... 8
World wide web address ................................................ 83
Q
Quick arm ....................................................................... 48
Quick exit ....................................................................... 48
Z
Zone discovery ................................................................ 69
Zone programming default tables ........................... 76, 77
Zone response type definitions ...................................... 25
R
Range .............................................................................. 17
Reboot ............................................................................. 69
Rebooting the system ..................................................... 69
Register by phone........................................................... 53
Register device with pin ................................................ 54
Register through AlarmNet Direct website .................. 53
Register through LYNX Touch diagnostics .................. 53
Registering the LYNX Touch ........................................ 52
Regulatory agency statements ...................................... 78
Remote phone control .................................................... 63
Remote programming .................................................... 58
Remote programming/control ........................................ 58
Reporter .................................................................... 40, 41
Reset master user code .................................................. 61
RF sniffer test mode....................................................... 18
S
Secondary user codes ..................................................... 61
Security code .................................................................. 48
Security code handshake ............................................... 58
Security codes................................................................. 60
Setup communication .................................................... 52
SIA event log codes ........................................................ 66
Silent burglary ............................................................... 26
Site-initiated remote programming .............................. 58
Sniffer mode ................................................................... 68
Sounder .......................................................................... 47
Specifications ................................................................. 82
Station-initiated remote programming ......................... 58
Super high capacity battery .......................................... 12
Supervised RF ................................................................ 17
System features............................................................ 5, 6
System operation ..................................................... 60, 61
System settings .................................................. 48, 49, 50
- 86 -
- 87 -
EDGE
CONNECTOR
(L5100ZWAVE)
REPLACE EVERY FOUR YEARS
P/N 300-03864-1/LYNXRCHKIT-SC
P/N 300-03866/LYNXRCHKIT-SHA
THE LYNX TOUCH CONTROLS ARE COMPATIBLE WITH THE
FOLLOWING INTEGRAL RECHARGEABLE BATTERY PACKS:
SUPER HIGH CAPACITY
BATTERY CONNECTOR
EGND
EARTH GROUND
STANDARD CAPACITY
BATTERY CONNECTOR
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM
TAMPER
SWITCH
COMMUNICATIONS MODULE
RECEPTACLE
ZONES
2K
OHM
EOLR
HARD
WIRED
ZONE
GND
NOTE: THE HARDWIRE ZONE CANNOT BE USED AS A FIRE ZONE.
IMPORTANT
WARNING
Be sure to observe
polarity when
connecting the
power supply to
the terminal strip.
02 - 48
ZT16
CIRCUIT
(ZONE)
30 seconds
CONTROL UNIT
DELAY-SEC
5806W3
5200-100-SOC-V1
10 seconds
SMOKE DETECTOR
MODEL
DELAY-SEC
THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM
VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING
DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
EDGE
CONNECTOR
(L5100-WiFi)
POWER SUPPLY
CONNECTOR
300-04705/300-04705V1
or 300-04065/300-04065V1
(300-04063/300-04063V1 or
300-04064/300-04064V1CANADA)
POWER SUPPLY 9V, 2.7A
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS
SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY
NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
POWER
GND
LYNX TOUCH SERIES SUMMARY OF CONNECTIONS
TIP
TIP
PHONE
(L5200/L5200CN ONLY)
RING
TIP
RING
RING
COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION
No. AC3AL05BL5000
RINGER EQUIVALENCE: 0.5B
UL INSTALLATIONS
THE MINIMUM WIRE
SIZE USED FOR
TELEPHONE
INSTALLATIONS
MUST BE #26 GAGE
H/S T
PREMISES
TELEPHONE
H/S R
INCOMING
PHONE LINE
HWZ1
WARNING
TO PREVENT RISK OF
SHOCK, DISCONNECT
TELEPHONE LINE
AT TELECOM JACK
BEFORE SERVICING
THIS UNIT
TRIG
TRIGGER OUTPUT (NEG)
(3ma)
LYNX TOUCH SERIES ALSO COMPLIES WITH THE FOLLOWING:
CANADIAN STANDARDS ASSOCIATION (CSA) C22.1,
CANADIAN ELECTRICAL CODE, PART 1, SAFETY STANDARD
FOR ELECTRICAL INSTALLATIONS AND CAN/ULC-S540
INSTALLATION OF RESIDENTIAL FIRE WARNING SYSTEMS.
+9VDC
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION STANDARDS ANSI/NFPA 70 NATONAL ELECTRIC CODE AND
NFPA 72 NATIONAL FIRE ALARM CODE, CHAPTER 2 (NATIONAL FIRE PROTECTION
ASSOC., BATTERY MARCH PARK, QUINCY, MA 02169). PRINTED INFORMATION
ESCRIBING PROPER INSTALLATION, EVACUATION PLANNING AND REPAIR SERVICE IS TO
BE PROVIDED WITH THIS EQUIPMENT.
LYNX Touch Installation and Setup Guide
Notes: Connection of the fire alarm signal to a fire alarm headquarters or a Central Station shall be permitted with the
approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a police
emergency number. The System must be checked by a qualified technician once every three years
SUPPORT & WARRANTY INFORMATION
For the latest documentation and online support information, please go to:
https://mywebtech.honeywell.com
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa.
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2014 Honeywell International Inc.
www.honeywell.com/security
Ê800-19974$Š
800-19974
12/14 Rev. A
MyWebTech
Warranty
- Uploaded