Qolsys IQ Smoke Installation manual

ATTENTION:
This manual should be read prior to use and retained for
further information.
GENERAL INFORMATION
The Wireless Smoke Heat Alarm is a 3xAAA battery powered wireless
detector intended for use with a compatible wireless alarm system. The
detector has a built-in wireless transmitter, which communicates with
the control panel. When smoke is detected, the alarm sounds a loud
local alarm and the built-in transmitter sends a signal to the control
panel. The Wireless Smoke Heat Alarm contains an integrated
fi
xed
41°F temperature freeze sensor that will send a warning signal based on
temperature detected. This detector is designed to provide protection
with 70-foot spacing capability.
The detector can send alarm, tamper and battery condition messages to
the system’s receiver. Refer to the wireless system’s instruction for the
maximum number of transmitters that can be supported.
CONTENTS OF BOX:
• Wireless Smoke Heat Alarm with base
• Installation guide (APD0595)
• Pack of screws and anchors
• Labels or decals as appropriate
• 3 AAA PC2400 Duracell Procell batteries (1.5V 1100mAh) or 3 AAA
Energizer E92 batteries (1.5V 1100mAh)
IQSmoke (QS5110-840)
Wireless Smoke Heat Alarm
Installation Guide
2
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
Status
LEDs
Sounder
(do not pulse the sounder
and LED concurrently)
Normal
Green
fl
ash every 12 seconds
Off
Heat Alarm
Red
fl
ash every 1 second
ANSI S3.41 temporal 3
Heat Test
Red
fl
ash every 1 second
ANSI S3.41 temporal 3
Smoke Alarm
Red
fl
ash every 1 second
ANSI S3.41 temporal 3
(press button to hush
for 5-10 minutes)
Smoke Test
Red
fl
ash every 1 second
ANSI S3.41 temporal 3
(press button to hush
for 5-10 minutes)
Test Alarm
Red
fl
ash every 1 second
ANSI S3.41 temporal 3
Freeze Warning
3 yellow
fl
ashes
every 4 seconds
Off
Detector Trouble
Yellow
fl
ash every 4 seconds
One chirp every 48 seconds
Low Battery
Yellow
fl
ash every 12 seconds
One chirp every 48
seconds (press button
to hush for 12 hours)
Detector Dirty
Yellow
fl
ash every 8 seconds
One chirp every 48 seconds
Power-up
Red, yellow, green
fl
ash sequence
One chirp at the end
of power-up sequence
Tamper
Red, yellow, green
fl
ash
sequence every 12 seconds
Off
The Wireless Smoke Heat Alarm contains a sounder which generates the
ANSI S3.41 temporal 3 pattern in an alarm condition. In alarm, a message
is also sent to the control panel and the detector’s ID is displayed at
the console. During an alarm condition, pressing the detector’s hush
button will silence the sounder (see table below). The mounting base
installation is simpli
fi
ed by the incorporation of features compatible
for both drywall fasteners (not supplied) and other methods.
Tricolored LED (red, yellow, green) and a sounder on the detector
provide local visual and audible indication of the detector’s status as
listed in Table 1.
During initial power-up the LED blinks alternately red, yellow then
green. It takes about 8 seconds for the detector to stabilize.
After power-up has completed and the detector is functioning normally,
the green LED blinks once every 12 seconds.
Detector Trouble:
When the detector has a general fault, the yellow LED
blinks once every four seconds and there is a chirp every 48 seconds.
After 12 hours the panel will display a loss of supervision message.
Table 1. Detector status and indication
Qolsys
1900 The Alameda, Suite 420
San Jose, CA 95126
www.qolsys.com
Tech Support: 1-855-476-5797
22
Guide d'installation du détecteur de chaleur et de fumée sans
fi
l INST APD0595 A140618
Cette réimpression n’exprime pas la position complète et of
fi
cielle de la National
Fire Protection Association sur le sujet cité qui est représenté uniquement par la
norme dans son intégralité.)
(Code national d’alarme incendie® et NFPA 72
®
sont des marques déposées de la
National Fire Protection Association, Inc., Quincy, MA 02269.)
Dans les maisons d'habitation à niveau unique et à plusieurs niveaux ainsi que
dans les immeubles d'habitation équipés de systèmes de détecteurs de fumée
similaires, il est possible que les signaux envoyés par des capteurs sans
fi
l soient
bloqués ou ré
fl
échis par le métal avant d'atteindre le panneau de commande du
détecteur et ce, même si le parcours du signal a été récemment véri
fi
é au cours
d'un test hebdomadaire. Un blocage peut se produire si un objet métallique a été
déplacé dans le parcours du signal du capteur.
3
INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide
Detector Dirty Feature:
When the detector has been contaminated, the
yellow LED blinks once every 8 seconds and there is a chirp every 48
seconds. Refer to MAINTENANCE section for cleaning your alarm. After
12 hours the panel will display a loss of supervision message.
Low Battery Detection:
The Wireless Smoke Heat Alarm is powered by
3 AAA Duracell Procell or 3 AAA Energizer E92 batteries (included). The
detector regularly checks for a low battery. If a low battery is detected,
the transmitter sends a low battery message to the control panel, which
displays the detector’s ID at low battery. In addition, the yellow LED
of the detector will blink every 12 seconds. The detector’s sounder
will chirp every 48 seconds (yellow LED continues to blink) until the
batteries are replaced. Pressing the hush button will silence the chirps
for 12 hours, if no other trouble conditions exist. The batteries should
be replaced WHEN the chirps begin. Be sure to replace the batteries
with fresh ones.
BATTERY INSTALLATION AND REPLACEMENT
To replace the batteries:
1. Remove the detector from its mounting base by twisting the
detector counterclockwise. Remove and dispose of the batteries
according to your local regulations.
2. To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new batteries.
3. Install 3 new AAA batteries (available from your local Duracell or
Energizer dealer) in the battery compartment. Follow the polarity
diagram inside the compartment. If the batteries are incorrectly
inserted please remove gently with a non-conductive tool and
correctly reinsert.
%$77(5<&203$570(17
HUSH/TEST BUTTON
Fig 1. Wireless Smoke Heat Alarm
of 12


Uploaded