Resideo 5800COV - Installation and Setup Guide (2022)



Related Products

Taxons
Resideo 5800COV
Wireless Carbon Monoxide Detector
List Price:
Our Price: $137.99

Document Transcript




5800CO
V

Carbon Monoxide Detector with

Built
-
in Wireless Transmitter


Installation and Setup Guide

GENERAL INFORMATION

The 5800CO
V is a 3V battery
-powered wireless Carbon Monoxide (CO)
detector
intended for use with wireless alarm systems that support 5800
series devices
. Consult
your
control panel
’s installation instructions for
compatibility.

Compatible Controls:
T his detector can be used with
5800 series
compatible controls
(Listed to UL864 and/or UL985) that support a
carbon monoxide zone type
and utilize a 5881 receiver.


The detector consists of an electrochemical carbon monoxide sensor
assembly
coupled to
a wireless transmitter. The transmitter can send
alarm, trouble,
end-
of-life,
tamper, and battery condition messages to
the system’s receiver. Refer to the wireless system’s instructions for the
maximum number of tran
smitters that can be supported.

IMPORTANT:
This detector must be tested and maintained regularly
following NFPA 72 requirements.

WARNING:
This product is not intended for use in industrial factories or
commercial parking garages.

FEATURES



Conforms to
UL standard 2075
CO sensitivity is evaluated to UL 2034


Certified to CSA Standard 6.19-
17


10-
year life

Carbon Monoxide (CO) sensor



CO Detector End-
of-Life reporting (detector needs replacing)



Low Battery Detection



Supervised


Local sounder



Dual LEDs



CO
Test/Hush button



Functional Gas Test

Refer to
the Limitations of Carbon Monoxide Detectors (P/N K14670V1).

The 5800COV's carbon monoxide alarming circuit is designed to detect
carbon monoxide gas from ANY source of combustion. The carbon monoxide
alarming circuit of this device is NOT designed to det
ect smoke, fire, or any
other gases.

The 5800CO
V contains a piezoelectric horn which generates the ANSI
S3.41 temporal 4
pattern in an alarm condition
(see note below Table 1
for
a description of the temporal 4 pattern). In alarm, a message is also sent
to the control panel and the detector’s zone number is displayed at the
console. The alarm message is transmitted every 4
secs
until the carbon
monoxide
condition has cleared and the detector has reset. During an
alarm condition, pressing the detector’s CO
Test/Hush
button
will silence
the piezoelectric horn for 5 minutes
if level drops below 350ppm
. Once
the detector has reset, a RESTORE message is transmitted to the
control panel and the transmitter’s zone number can be cleared from the
panel.

LED Indicators

LEDs located on the top and side of the
5800COV
and a sounder
provide local visual and audible indication of the detector’s status.

Top multi
-color Status LED:
Green =
Blinks during power on, and during
CO
Functional testing

Amber =
Signal maintenance and trouble events

Red =
CO Alarm condition

Side LED windows
(4)
indicate alarms:

Blue =
CO alarm

Refer to Table 1
for additional LED information.

Figure 1. 58
00CO
V Wireless Carbon Monoxide Detector




Table 1: Detector LED Modes

Mode

Status

LED

(Top)

Side
L
ED
s

(
Window
)

Sounder

Power Up

Blink
s

green one time

Dark

Silent

Normal (standby)

---

Dark

Silent

CO Alarm

Blinks
red
every 10
seconds

Blinks
blue

every
10 seconds

Temporal 4 pattern
1

CO Alarm Silence

Blinks
red
every 8
seconds

Blinks
blue
every 8
seconds

Silent

Low Battery
2

Blink
s

amber
every
45 seconds

Dark

Chirps every 45
seconds after 7 days

Low Battery Mute

Blink
s

amber
every

45 seconds

Dark

Silent for 12 Hours

Tamper

Dark

Dark

Silent

Low Battery (30 days
later)

Dark

Dark

Silent

CO
Alarm Test
3

Blink
s

red
during
alarm

Dark

Temporal 4 pattern

(
two

time
s
)

Functional Gas Test
5



Waiting for gas entry

Blinks green once
every second

Dark

Silent

Functional Gas Test


Successful gas entry

Blinks
red
every 10
seconds

Blinks
blue
every
10 seconds

Temporal 4 pattern
1

CO Trouble

Double
-
blinks amber
every 4 seconds

Dark

Double
-
chirps every
45 seconds

CO End of Life
-

First
29 days
4

Double
-
blinks amber
every 4 seconds

Dark

Silent

CO End of Life
-

After
30 days
4


Double
-
blinks amber
every 4 seconds

Dark

Chirps every 45
seconds

1 T
emp
oral
4 pattern
is a repeated series
of 4 short beeps
followed by a 5
sec
pause. If ambient conditions
return to
normal, the
CO
detector will switch
from
Alarm
mode
to its
previous
mode.

2 If the detector goes into alarm prior to the 7-
day delay expiration, the LED blink will match the alarm
condition. Upon exiting the alarm, the 7-
day delay is bypassed, and the sounder will begin the chirp every
45 seconds.

3 Test activated by pressing (1
-2 seconds) and releasing the CO TEST/HUSH button; d
etector is
functioning properly (within proper sensitivity).

Note:
If Test mode is activated and the LED and Sounder
do not function, check for maintenance or trouble conditions
.
4 Starts chirping after 30 days, continues until the battery dies
.
5 See Functional Test section for Functional Test activat
ion and procedure.

Hush feature:

If necessary
, the audible alarm can be silenced for
5
minutes by pushing the CO
Test
/Hush
button. The LED will continue to
flash
red
every 8 seconds and the side LED window
s will flash Blue

every 8 seconds. If carbon
monoxide is still present after the 5-
minute
hush period, the audible alarm will sound. The
Hush
feature
will not
operate at levels above 350 ppm (parts per million) carbon monoxide.

Trouble feature:
When the sensor supervision is in a trouble condition,
the detector
will send
a trouble signal to the panel.

The Status LED and
sounder will respond as noted in Table 1.
Trouble
conditions include an
open circuit, sensor removal
(tamper),
and
sensor end of life.
End of Life Timer feature:
This detector’s lifespan is approximately ten
years from its date of manufacture. When the detector has reached the
end of its life, the detector will send a trouble signal to the panel
. This
indicates that the CO sensor inside the detector has passed the end of
its life and the detector must be replaced.
The Status LED blinks Amber
two times every 4 seconds,
and the sounder will be silent. If 30 days
have passed, the Status LED will continue to blink Amber two times
every 4 seconds and the sounder will chirp every 45 seconds. Refer to
Detector Replacement section
of this manual.

Low Battery Detection:

The 5800CO
V is powered by a single 3-
volt
CR123A Lithium battery (included). The detector checks for a low battery
at least every 65 minutes. If a low battery is detected, the transmitter
sends a low battery message to the control panel, which beeps and
displays the detector’s zone number. In addition, the detector’s Status
LED
wil
l blink Amber
every 45 sec
onds
. After
7 days
, the detector’s sounder
will
“chirp” about every 45 seconds
and the Status LED will continue to blink
Amber every 45 seconds
for up to 30 days. Pressing the CO
Test/Hush
button
during this time will silence the chirps for 12 hours, if no other
trouble conditions exist. The battery should be replaced BEFORE the
chirps begin. Be sure to replace the battery with a fresh one.


Tamper Protection:
The 5800COV has a built
-in tamper swit
ch that will
cause a signal to be displayed at the alarm system console
and an
alarm will sound if
it is removed from its mounting base
.

POWER UP AND ENROLL
MENT

1. Remove the detector from its mounting base by twisting the detector
counterclockwise.
(Refer to
Figure 2)
2. Remove battery pull tab. Be sure battery is seated properly to avoid a
low battery condition after 15 seconds.

3. During initial power
-up, the LED will blink green one time and the
sounder will remain silent. It takes about 30 secs for the detector
’s
CO sensor to stabilize.

4. After power
-up has completed and the detector is functioning
normally, the LEDs will remain dark and the sounder will be silent.


Figure 2. Powering up the 5800COV

ENROLLMENT

The detector must be enrolled in the control panel before it can operate
in the system. A
larms and trouble conditions from the detector
are
reported on one protection zone, which is programmed
as
"Carbon
Monoxide" OR "24-
hour CO" zone type (VISTA Series = ZT 14). Refer to
the Security System Control Panel's Installation Guide for the types of
Contact ID (CID) e
vents
reported
to the Central Station
.
1. Enter the control’s Zone Programming mode.

2. Enter the
alarm
zone number to be programmed.

3. Enter the applicable zone type when prompted.
Use zone type 14 for
Resideo
residential controls.

4. When prompted,
select
input type
– "Supervised" or "RF Supervised"
(VISTA Series = 03 Supervised RF)
.
5. When prompted for the serial number
:
a. R emove the detector from its base (rotate the detector counter
-
clockwise on the base until it snaps open).
NOTE
: D
etector must be removed from its
base to enroll.

b. P ress the detector’s
CO
Test
/Hush
button
twice (for each press,
hold the button down
for
several
sec
onds
).
c. Reinstall
the
detector onto
its base
(twist
the detector clockwise
until
it snaps into place)
.
d. Check that the detector
is enrolled as Loop 1.

6. If End-
of-Life monitoring is desired:

VISTA-
15P/20P, LYNX Touch, Lyric and ProSeries –
automatically
enrolled.

VISTA-
32, 128/250 Series
– program a separate zone for the CO
serial number.

a. Loop 2 = Zone Type (Choose a zone type based on the desired
operation i.e.; "24-
hour Trouble" or "24-
hour Auxiliary Alarm"
(VISTA Series =
ZT 19 or 08).

b. Input Type -
"Superv
ised" or "RF Supervised" (VISTA Series = 03
Supervised RF).

7. Exit Programming mode when programming is complete and
test the
detector. Refer to the Testing Section
of this manual
.
Refer to
the
Control Panel's
installation instructions for
additional
information
.

MOUNTING THE DETECTOR

First, determine the best location for the detector, one that provides

proper
carbon monoxide
detection and a strong wireless transmission
path.
Refer to Figure 5
for suggested detector locations.

Proper
Carbon Monoxide
Detection Location

In a wall location, the detector should be at least as high as a light
switch, and at least 6
inches (15.24
cm)
from the ceiling. In a ceiling
location, the detector should be at least 12 inches (30.48
cm)
from any
wall.
( Refer to Figure
3)



Figure
3. Mounting the 5800CO
V
DO NOT attach the detector to removable ceiling panels. Attach the
detector across panel support as shown in Figure 4

Figure
4. Mounting
Detector Across Ceiling Panel Support

Where to install, ideally:

• Within 10 feet (3m)
of all sleeping areas

• Inside the bedroom if it contains a fuel burning appliance

• O

n every floor of the building

• Ideally, install in any room that contains a fuel burning appliance

• If the appliance in the room is not normally used, such as the boiler
room, the detector should be placed just outside the room so the
alarm can be heard more easily


Where NOT to install, ideally:

• Detectors operate best when installed 10 feet (3m)
or further from any
cooking appliance

• Directly above a sink, cooker, stove or oven

• Next to a door or window affected by drafts i.e.,
extractor fan or air
vent

• Outside

• Do not install in any environment that does not comply with the
detector’s environmental specifications
• In or below a cupboard

• Where air flow would be obstructed by curtains or furniture

• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed


Good transmission path

A good transmission path must be established from the proposed
mounting location before permanently installing the detector.
P erform
the test described in the TESTING SIGNAL STRENGTH section
of this
manual
. Prior to mounting the detector to the mounting base, you must
“enroll” the detector’s serial number into the system
.

Mounting
Procedure

Once a suitable location is found,
mount the detector
as follows
:
1. Refer to Figure 3 and
install the mounting base on the ceiling or on
the wall (if local ordinances permit)
. Use
the two screws and anchors
provided.
Rotate
the base so the screws are at the elbow of the screw
slots and secure.

2. Fit the detector
inside the base by align
ing
it over the base,
then t
urn
the detector in a clockwise direction until it clicks into place.

3. Test the detector after completing the installation (as described in the
TESTING
THE DETECTOR
section of this manual). Refer to the
control system’s instructions for additional information concerning the
use of wireless devices
.
CAUTION

Airborne dust particles can enter the detector. Resideo recommends the
removal of detectors before beginning construction or any other dust
-
producing activity. Carbon monoxide detectors are not to be used with
detector guards unless the combination has been evaluated and found
suitable for that purpose.




Figure
5.
CO
Detector Location Diagram

TESTING THE DETECTOR
NOTE:
The
5800CO
V detector must be
functionally
tested after
installation. The
5800CO
V features
a
Functional Gas Test
mode that

can be used to verify the detector’s ability to sense carbon monoxide
gas. To perform the functional gas test
:

1. D epress and hold the CO
Test/Hush
button
for approximately 3-5
full
seconds
. Refer to Figure
6.
2. Within a few
secs
, the
Status
LED will blink
green once each second,
indicating the detector is in functional test mode. At this time, the unit
is waiting for the user to dispense the test CO sample
.
3. Spray a very small amount of
Solo

C6
canned CO directly into the
gas
test hole (
Refer to Figure
6). Solo™ C6 is available through
many security equipment vendors.

4. Upon successful gas entry and if functioning properly, the detector will
begin
sounding in a
temporal
4 pattern.
The Status LED will blink red
and the Side LED window will blink Blue every 10 seconds. An alarm
signal
is sent to the panel
, providing verification of the alarm signal.
5. The alarm condition at the detector will
stop
when the CO gas has
cleared.
6. If gas entry is unsuccessful, the test
will
automatically end
after 2
0
second
s.


Figure
6. CO Detector Functional Test


TESTING SIGNAL STRENGTH
NOTE:
Remove battery tab before installation. (Refer to figure 2)
This test should be performed before
installation to determine a strong
communication path with the control panel. The test should be repeated
after installation is complete. Also, the owner/user should test the unit
’s
signal strength
at least weekly.

1. Activate the wireless system’s GO/NO GO TEST mode from the
keypad
(refer to the control
panel’s
instruction manual).
2. Depress the detector’s
CO
TEST
/HUSH
button
. If the detector has not
previously sensed
a low battery condition and is
operating
within
proper sensitivity limits,
it should immediately transmit an alarm signal
to the control panel. The built
-in horn will start to sound after pressing
the button.

3. The wireless system’s keypad should emit at least
3 tones
when the
alarm transmission is received and will display the transmitting
detector’s zone number.


4. When the control panel has received the test signal, release the CO
TEST
/HUSH
button
. The horn will stop and a few sec
onds
later the
detector’s zone number will clear from the console di
splay.

5. If the console does not respond as described above
:
a. Make sure the
battery is installed with the correct polarity
.
b. Make sure
the battery is
fresh.

c. If this is an initial installation, try moving the detector to another
location that provides proper reception. Also be sure that the
detector has been enrolled
by the control panel (refer to the

ENROLLMENT section
). Then, repeat the signal strength
test.

6. Exit
TEST mode from the keypad (security code + OFF).


TESTING PROGRAMMED LOOPS

This test should be performed before installation to ensure that
the
detector has
been programmed and is
operational in the system.

1. Activate the system’s TRANSMITTER ID SNIFFER mode from the
keypad (see
the
control panel’s instruction manual
). All programmed
wireless zones will be displayed, one
by one, on the system keypad.
Make sure the
detector zone
is displayed in the sequence. (If not,
recheck that the detector zone has
been properly programmed.)

2. With the
detector mounted to the mounting base, press the detector’s
TEST
/HUSH
button
. The
zone associated with the detector should
disappear from the keypad on the next display cycle. This means that
the system has received a transmission from the detector zone
you
have programmed.

3. When testing is complete, enter the Installer code + the OFF key to
exit TEST mode.

When all system testing has been completed, notify the central
monitoring
station that the system is back
online
.

BATTERY REPLACEMENT

1. Remove the detector from its mounting base by twisting the detector
counterclockwise. Remove the battery and dispose of properly.

2. Wait 10 seconds and then install a new 3-
volt CR123A Lithium battery
in the battery compartment.

NOTE:
Follow the polarity diagram inside the battery compartment.

3. Reinstall the detector onto its mounting base by turning the
detector
clockwise.

4. Test the detector as described in the TESTING SIGNAL STRENGTH
section of this manual. If the battery is not installed correctly, the
detector will not operate and the battery may be damaged. If the
detector does not appear to be sending a signal during any of the
tests, check for correct battery installation and for a fully charged
battery.


Figure
7. Battery Replace
ment

MAINTENANCE

Occasionally clean the outside casing with a cloth. Ensure that the holes
on the front of the alarm are not blocked with dirt and dust.

Do not paint

or
use cleaning agents, bleach, or polish on the detector.


Figure
8. Cleaning the 5800COV

CAUT
ION
: CARBON MONOXIDE GAS AND ITS DETECTION

This carbon monoxide detector is designed for indoor use only. Do not
expose
it to rain or moisture. Do not drop the detector
or subject it to
other physical shock
. Do not open or tamper with the detector as this
may
cause
it to
malfunction. The detector will not protect against the risk
of carbon monoxide poisoning if not properly
installed.

NOTE
: The detector will only indicate the presence of carbon monoxide
gas
in the vicinity of the
detector itself.
Carbon monoxide gas may be
present in other areas
.
THIS CARBON MONOXIDE DETECTOR IS NOT
:


Designed to detect smoke, fire or any gas other than carbon
monoxide



A substitute for the proper servicing of fuel
-burning appliances or the
sweeping of chimneys



To be used on an intermittent basis, or as a portable alarm for the
spillage
of combustion products from fuel
-burning appliances or
chimneys

Carbon monoxide gas is a highly poisonous gas which is released when
fuels are burned. It is invisible, has no smell and is therefore impossible
to detect with the human senses. Under normal conditions in a room
where fuel burning appliances are well maintained and correctly
ventilated, the amount of carbon monoxide released into the room
by
such
appliances should not be dangerous.


SYMPTOMS OF CARBON MONOXIDE POISONING
: Carbon monoxide
bonds to the hemoglobin in the blood and reduces the amount of oxygen
being circulated in the body. The following symptoms are related to
carbon monoxide poisoning and should be discussed with all members
of the household:



Mild exposure: Slight headache, nausea, vomiting, fatigue (often
described as “flu-
like” symptoms).



Medium exposure: Sever throbbing headache, drowsiness,
confusion, fast heart rate.



Extreme exposure: Unconsciousness, convulsions, cardio respiratory
failure, death.

Many causes of reported carbon monoxide poisoning indicate that while
victims are aware that they are not well, they become so disoriented that
they are unable to save themselves by either exiting the building or
calling for assistance.

Also
, young children and pets may be the first to be affected
.

WARNING: IMPORTANT INFORMATION FOR THE USER

Actuation of your CO alarm indicates the presence of carbon monoxide
(CO),
which can cause injury or death.


Individuals with medical problems may consider using warning devices
which provide audible and visual signals for carbon monoxide
concentrations under 30ppm.


What to do if the carbon monoxide detector goes into alarm:

1. Push the CO
Test
/Hush
button. If t
he detector reactivates or the
detector does not silence, continue with
Step
2.
2. Immediately move to fresh air, outdoors or by an open window. Check
that all persons
are accounted for. Do not reenter the premises nor
move away from the open door/window until emergency service
responders have arrived.

3. Call your local fire department from a phone in an area where the air is
safe.

4. If your detector reactivates within a 24-
hour period, repeat steps 1
- 3
and call a qualified appliance technician to investigate possible
sources of CO
from fuel burning equipment and appliances, and
check
for proper operation of this equipment
. If problems are identified
during this inspection, have the equipment serviced immediately. Note
any combustion equipment not inspected by the technician and
consult the manufacturer’s instructions, or contact the manufacturers
directly, for more information about CO safety and this equipment.
Make sure that motor vehicles are not, and have not been, operating
in an attached garage or adjacent to the residence.
IMPORTANT:
This detector should be tested and maintained regularly
following National Fire Protection Association (NFPA) 72
requirements. (Generally
, this detector should be ful
ly tested at least
once per month.)


DETECTOR REPLACEMENT

This detector is manufactured with a long-
life carbon monoxide sensor.
Over time the sensor will lose sensitivity, and
will need to be replaced
with a new carbon monoxide detector. This detector’s lifespan is
approximately ten
years from the date of manufa
cture.

The user should periodically check the detector’s replacement date.
Remove the detector
from its base and
check the replacement date label

on the underside
of the detector. The label
indicate
s the date that the
detector should be replaced
.
NOTE:
When the detector is removed from its base, a message is sent
to the central station. If the system is armed, a tamper alarm
message is
sent; if disarmed, a trouble message is sent.

The
detector
will also indicate
a trouble condition
when
it has reached
the end of its useful life. If this occurs, it is time to replace the detector.

NOTE:
Before replacing the detector, notify your central station
that
maintenance is being performed and the system will be temporarily out
of service. Disable the zone
or system undergoing maintenance to
prevent any unwanted alarms. Dispose of detector in accordance with
any local regulations.

CAUTION

It should be noted
that
installation, operation, testing and maintenance of
the 5800CO
V is different than smoke
detectors.
Per NFPA 72 the
detector shall not be connected to a zone that signals a fire condition (i.e.
smoke detector
zones
). Therefore, the 5800COV
detector must be
programmed as
a non-
fire zone.
See the control panel’s Installation
Instructions for the
appropriate carbon monoxide
zone type to be
programmed.

Please see insert for Limitations of Carbon Monoxide Detectors.


This device

complies with Part 15 of the FCC Rules, and ISED’s
license
-
exempt RSSs. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including
interference that may cause undesired operation.


Unautho
rized changes or modifications could void the user’s authority to
operate the
equipment.


SPECIFICATIONS

Power Source
:
One 3-
volt CR123A Lithium Battery (included). (Replace
only
with Panasonic CR123A)

Audible Signal
: .........................
85 dB
A minimum
in alarm at 10ft
(3m
)
Height
: ..................................................................
1.99
inches (50
mm)

Diameter
: ...............................
6.2
inches (157
mm) with mounting base

Weight
: .................................................
14.3
oz. (
406
g) without battery

Operating Ambient Temperature Range
: .....
32° to 100°F (0° to 38°C)
Relative
Humidity
: .......................
95%
RH
maximum
, non-
condensing
Agency Listings
:..................................................
UL standard 2075,
....................................................
Certified to CSA STD 6
.19-17


FOR
SUPPORT & WARRANTY INFORMATION AND FOR DETAILS REGARDING
THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, GO TO:

https://www.resideo.com


The product should not be disposed of with other household waste. Check for the nearest
authorized collection centers or authorized recyclers. The correct disposal of end
-of-life
equipment will help prevent potential negative consequences for the environment and human
health.

Any a
ttempt to reverse-
engineer this device by decoding proprietary protocols, de-
compiling
firmware, or any similar actions is strictly prohibited


This product is manufactured by Resideo Technologies, Inc. and its affiliates
.


R800
-
26839A
9
/22 Rev. A




2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville
, NY 11747
© 2022 Resideo Technologies, Inc. Inc.

www.resideo.com



Uploaded