Resideo Honeywell Home Vista-21iPLTE - Install Guide Dated 8/19



Related Products

Honeywell VISTA-21iPLTE - Internet Alarm Control Panel
Honeywell VISTA-21iPLTE
Internet Alarm Control Panel
List Price: $392.00
Our Price: $242.99

Related Categories


Document Transcript

Document ID 800-25358V1A Rev. A

ADEMCO
VISTA SERIES
VISTA-
21iP
LTE
/V21SIALTE

Security System
s




Installation and Setup Guide
























800-
25358V1A
8/19
Rev
A iii

RECOMMENDATIONS FOR PROPER PROTECTION

The Following Recommendations for the Location of Fire and Burglary Detection Devices
Help Provide Proper Coverage for the Protected Premises.

Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Prote
ction Association's (NFPA) Standard #72 noted below.

Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be install
ed outside of
each separate sleeping area, and on each additional floor of a multi
-floor family living unit, including
basements.
The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.

For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.

In addition, we recomme
nd the following:

• Install a smoke detector inside every bedroom where a smoker sleeps.

• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an ala
rm in the hallway outside may not wake
up the sleeper if the door is closed.








Install a smoke detector inside bedrooms
where electrical appliances (such as
portable heaters, air conditioners or
humidifiers) are used.


Install a smoke detector at both ends of a
hallway if the hallway is more than 40 feet
(12 meters) long.


Install smoke detectors in any room where
an alarm control is located, or in any room
where alarm control connections to an AC
source or phone lines are made. If detectors
are not
so located, a fire within the room
could prevent the control from reporting a
fire or an intrusion.


THIS CONTROL COMPLIES WITH NFPA
REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION
APPLIANCES.




Recommendations For Proper Intrusion Protect
ion
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows in a
multi-
level building.

In addition, we recommend
that radio backup be used in a security system so that alarm
signals can still be sent to the alarm monitoring station in the event that the telephone lines
are out of order (alarm signals are normally sent over the phone lines, if connected to an
alarm m
onitoring station).
i

Table
of Contents


Features and Installation Highlights
................................
................................
................................
......................
1

Capabilities and Functions
................................
................................
................................
................................
... 1
Compatible Devices
................................
................................
................................
................................
..............
2
Important Installation Highlights (Installer Please Read)
................................
................................
.....................
2
Mounting and Wiring the Control
................................
................................
................................
...........................
3

Installing the Control Cabinet and PC Board
................................
................................
................................
.......
3
Cabinet and Lock
................................
................................
................................
................................
............
3
Mou
nting the PC Board Alone (no RF Receiver)
................................
................................
............................
3
Mounting Board with RF Receiver
................................
................................
................................
..................
3
AUXILIARY DEVICE CURRENT DRAW WORKSHEET
................................
................................
................
4
AC Power, Battery, and Ground Connections
................................
................................
................................
......
5
1361
-GT Transformer
................................
................................
................................
................................
.....
5
Battery Connections
................................
................................
................................
................................
........
5
Battery Saver Feature
................................
................................
................................
................................
.....
5
Earth Ground
................................
................................
................................
................................
...................
5
Sounder (Bell) Connections
................................
................................
................................
................................
. 6
Basic Connections
................................
................................
................................
................................
...........
6
Supervised Output
................................
................................
................................
................................
..........
6
Connecting the Keypads and Other Addressable Dev
ices
................................
................................
..................
6
Connections
................................
................................
................................
................................
....................
6
Supplementary Power (optional)
................................
................................
................................
.....................
6
Keypad Notes
................................
................................
................................
................................
..................
7
Optional LTE
-21V Module
................................
................................
................................
...............................
7
Table of Device Addresses
................................
................................
................................
................................
.. 7
Hardwire Zones and Zone Expansion
................................
................................
................................
..................
8
Hardwire Zones
................................
................................
................................
................................
...............
8
Double-
Balanced Zones
................................
................................
................................
................................
.. 8
Zone Doubling
................................
................................
................................
................................
.................
8
Smoke Detectors
................................
................................
................................
................................
.............
9
Smoke Detector Notes
................................
................................
................................
................................
.... 9
4219/4229 Expansion Zones
................................
................................
................................
..........................
9
Installing the RF Receiver and Wireless Transmitter Zones
................................
................................
..............
10
Compatible Receivers
................................
................................
................................
................................
... 10
Receiver C
onnections
................................
................................
................................
................................
... 10
RF Receiver Notes
................................
................................
................................
................................
........
10
Installing the Transmitters
................................
................................
................................
.............................
11
Transmitte
r Battery Life
................................
................................
................................
................................
. 11
Installing a Keyswitch
................................
................................
................................
................................
.........
12
Keyswitch Connections
................................
................................
................................
................................
. 12
Keyswitch Notes
................................
................................
................................
................................
............
12
Connecting Relay Modules and Output Triggers
................................
................................
...............................
13
4204/4229 Relay Modules
................................
................................
................................
............................
13
On-
Board Triggers
................................
................................
................................
................................
.........
14
Audio Alarm Verification Connections
................................
................................
................................
...........
15
Internet (IP) Connection
................................
................................
................................
................................
17
LTE
-21V Module Installation
................................
................................
................................
..............................
17
General Information
................................
................................
................................
................................
......
17
Mounting the Module
................................
................................
................................
................................
.....
17
IP/Cell Status LEDs
................................
................................
................................
................................
.......
19
Signal Quality
................................
................................
................................
................................
................
19
Signal Quality and Status LEDs
................................
................................
................................
....................
19
S
ignal Strength and Status LED locations
– Status LED Functions Table
................................
........................
20
Inadequate Signal Strength;
................................
................................
................................
..........................
20
Using St
and
-Alone Communication Device
................................
................................
................................
.. 20
Programming Overview
................................
................................
................................
................................
........
21

About Programming
................................
................................
................................
................................
............
21
Mechanics of Programming
................................
................................
................................
................................
.........
21
Data Field Programming Procedures
................................
................................
................................
.....................
21
Interactive Mode Programming (

56, *57,

58,

79,

80,

81,

82)
................................
................................
......
22
Loading Factory Defaults/Initializing for Download
................................
................................
................................
22
Exiting the Programming Mode
................................
................................
................................
..............................
22
Zone Type Definitions
................................
................................
................................
................................
..................
22 ii



Data Field Programming
................................
................................
................................
................................
.......
25

About Data Field Programming
................................
................................
................................
..........................
25
System Setup Fields (

20


29)
................................
................................
................................
.......................
25
Zone Sounds & Timing (

31–

39)
................................
................................
................................
......................
26
Dialer Programming (

40


50)
................................
................................
................................
........................
26
System Status Report Codes
................................
................................
................................
.............................
28
Miscellaneous System Fields
................................
................................
................................
.............................
29
Pager Programming Fields
................................
................................
................................
................................
. 31
Miscellaneous System Fields
................................
................................
................................
.............................
32
Configurable Zone Type Fields
................................
................................
................................
..........................
33
Touch Screen K
eypad (AUI) Enable
................................
................................
................................
..................
35
Keypad Programming Fields
................................
................................
................................
..............................
35
Menu Mode Programming
................................
................................
................................
................................
.... 37


29 Menu Mode for IP and Cell Module Programming
................................
................................
......................
37
IP/Cell Diagnostic Commands (

29 Menu Mode)
................................
................................
..............................
43
Registering the Control with AlarmNet
................................
................................
................................
...............
46
Upload/Download via the Internet
................................
................................
................................
......................
46
Zones and Partitions
................................
................................
................................
................................
..........
47
About Zone P
rogramming (

56 and *58 Menu Modes)
................................
................................
......................
47

56 Zone Programming Procedure
................................
................................
................................
....................
47
Completing Zone Programming
................................
................................
................................
.........................
50

58 Expert Programming Mode Procedures
................................
................................
................................
......
50
Wireless Key (Key Fob) Programming & Templates
................................
................................
..........................
52
About Output Dev
ice Programming (*79/*80 Menu Mode)
................................
................................
................
54
Programming Output Devices
................................
................................
................................
............................
54
*79 Menu Mode: Output Device Mapping
................................
................................
................................
..........
54
*80 Menu Mode: Defining Output Functions
................................
................................
................................
......
56
About Zone Lists (*81 Menu Mode)
................................
................................
................................
....................
58
Zone List Programming
................................
................................
................................
................................
......
59
About Function Keys (*57 Menu Mode)
................................
................................
................................
.............
60
Programming Function Keys
................................
................................
................................
..............................
60
About
Descriptor Programming (*82 Menu Mode)
................................
................................
.............................
61
Programming Zone Descriptors (Menu Mode

82)
................................
................................
............................
61
Adding Custom Words (will not be annunciated by a voice keypad)
................................
................................
. 62
Programming Installer and User Schedules
................................
................................
................................
.......
64
AVS System Enable and Quick Programming Commands
................................
................................
...............
65
System Communication and Operation
................................
................................
................................
..............
66

Panel Communication with Central Station
................................
................................
................................
........
66
Report Code F
ormats
................................
................................
................................
................................
.........
66
Ademco Contact ID
®
................................
................................
................................
................................
..........
68
System Security Codes
................................
................................
................................
................................
......
69
Panic Keys
................................
................................
................................
................................
..........................
71
Setting the Real
-Time Clock
................................
................................
................................
...............................
71
Various System Trouble Displays
................................
................................
................................
......................
72
Testing the Sys
tem
................................
................................
................................
................................
................
73

About Test Procedures
................................
................................
................................
................................
.......
73
System Test
................................
................................
................................
................................
........................
73
Checking Transmitter Enrollme
nt (Sniffer Mode)
................................
................................
...............................
73
Go/No Go Test Mode
................................
................................
................................
................................
.........
74
Dialer Communication Test and Periodic Test Reports
................................
................................
.....................
74
Automatic Standby Battery Tests
................................
................................
................................
.......................
75
Specifications & Accessories
................................
................................
................................
..............................
77

Security Control
................................
................................
................................
................................
..................
77
Compatible Devices
................................
................................
................................
................................
............
77
5800 Series Transmitter Input Loop Identification
................................
................................
..............................
79
Regulatory Agency Statements
................................
................................
................................
...........................
81

Limitations and Warranty
................................
................................
................................
................................
.....
83

CONTACTING TECHNICAL SUPPORT
................................
................................
................................
............
84
1
SECTION 1

Features and Installation Highlights


Co
mpatibility: This document applies to systems with microprocessor version
4.25
or higher.


Features and procedures apply to both the VISTA
-21iPLTE and V21SIALTE, except where differences are
noted.


SIA Installations:
The V21SIALTE is a certified SIA-
comp
liant control that meets SIA specifications for
False Alarm Reduction. The V21SIALTE is not certified as SIA
-compliant, but can be programmed for
False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the
applicable
programming fields.


NOTE:
Throughout this manual, device model numbers are
Honeywell
Home
model numbers
unless otherwise noted.


Capabilities and Functions
Feature/Function

Description

Partitions




2 partitions, can protect two independent areas


Com
mon zone option allows either partition to arm, while leaving a common area (ex.
lobby or foyer) disarmed for access into the other partition.

Zones

Up to 48 protection zones plus 16 keyfob zones (zones 49
-
64) for total of 64 zones:



8 basic hardwired zones
(zones 1
-8) with optional zone-doubling feature



Up to 40 additional wired zones (zones 9-
48) using up to 5 4219/4229
modules



Up to 40 wireless transmitter zones (5800 series; zones 9-
48)



Up to 4 c
onfigurable zone types

Security Codes

Up to 48 Security Codes
, with separate authority levels and partition access

One
-
button arming

Dedicated keys can arm the system.

Schedules

Up to 32; can control devices and/or auto
-
arm/disarm

Keypad macros

Up to 4; activated by wired keypads

Paging

Up to 4 pagers; certain system conditions can report to pagers; can use a dedicated key
on keypads to send a signal to a pager

Event Logging

100 events; log display is done via Compass Downloader

software or installer/master
code at Keypad

Zone descriptors

Can assign for all zones (for alpha display keypads
).

Bell supervision

Optional, detects external sounder wiring short

(when in alarm)

or open

(when bell is off)
;
causes a
trouble condition, keypad display, and sends a report to the central monitoring
station, if enabled

(field

91, option 1)
.

RF jam detection

Optional,

for wireless systems detects a condition that may impede proper RF reception
(i.e., jamming or other RF interference); causes keypad display, and sends a report to the
central monitoring station (if trouble reporting is enabled).

Telephone Line
Monitoring

Built
-
in option can monitor the

telephone l
ine voltage and can cause a local display, or a
display and trouble/alarm sound

Downloading via
Phone Line or
Internet



Via
Standard Phone Line:
Using
an IBM compatible computer, Compass downloading
software, and a compatible HAYES o
r CIA modem specified by Honeywell
Home.


Via Internet: Supports upload/download programming capability via the Internet using
the AlarmNet network and Compass downloading software. This allows site
maintenance independent of central station monitoring, and modification to sites
globally via the Internet. Also see Internet Reporting below and Internet Connection on
the next page.

Internet Reporting

Primary telephone number messages can be reported over the Internet via hardwired
high speed Internet connec
tion and/or via an optional on-board
cellular
module (using the
wireless
cellular network). The Internet connection and optional module are collectively
referred to as the Internal IP/
Cell

Device.

Installation and Setup Guide

2
Compatible Devices

Device

Limits

Notes

Addressable Keyp
ads

8

6150 Fixed
-
Word Keypad, 6160 Alpha Keypad, 6160V Alpha Display
Voice Keypad, 6150RF

or 6160RF

Keypad/Transceiver

Touch Screen (AUI)
Devices

4

Touch Screen (AUI) devices are in addition to the 8 addressable
keypads. E.g.,
6280
S/6280W
, Tuxedo

4219
, 4229

Zone
Expander Modules

Up to 5 for
up to 40 exp.
zones

Zone numbers are predefined according to the device addresses
used. See Expander Module Addresses table in Wiring section and
set addresses accordingly.

5800 Series Wirele
ss

Up to 40 RF
zones

Uses 5881/5883 Series Receivers/Transceivers.

(See Page 10 for
more information)

Output relays

and/or
Powerline Carrier
Devices

(X
-
10 type)

Up to 16

Use any combination of 4204
, 4229

and or Powerline Carrier
Devices
.
Map output devices via *79 Menu mode.

On
-
Board Triggers

2

Can be used to reset 4
-
wire
smoke detectors.

Output functions

Up to 48

Program output functions

via *80 Menu mode.

Audio Alarm Verification

Using AAV
module

Honeywell

Home

AVS

system

can be used to permit voice dialog
between an operator at the central station and a person at the
premise
s

via phone line


Alarm output

12VDC, 2
AMP output

Can drive

the compatible sounders; steady output for burglary/panic,
or temporal pulse (3 pulses –
pause
– 3 pulses –
pause
– 3 pulses. .
.) for fire. Uses current limiting circuitry for protection.

Auxiliary Power Output

See note.

12VDC, 600 mA maximum; uses

circ
uit

protection.

Backup Battery

See note.

Rechargeable

(sealed lead
-
acid type) 12VDC, 4AH minimum.

Internet Connection and
Optional
Cellular
Module

See note.

Internet connection is made via an on
-
board Ethernet connector for
high s
peed (broadband) hardwire connections, and/or use of the
optional on
-
board
Cell

module.

AC Power Supply

See note.

Plug
-
in 120VAC transformer, ADEMCO
1361
-
GT

(
1361CN
-
GT

in
Canada)
.


NOTE:
All devices and accessories
used in a Canadian installation must be Listed for use in Canada.


Important Installation Highlights (Installer Please Read)


This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in
Section 2. Mounting and Wiring
– Conne
cting
the Keypads and Other Addressable Devices
).


Keypads must be set for addresses 16-
23 (first keypad is address 16, which is different from previous
controls) and programmed in data fields *190
-*196.


Zone Expander Modules must be set for specific addresses (07
-11), based on the zone numbers used.


4204
Relay Modules
must be set for specific addresses (12-
15).


This control will not power
-up unless AC power is connected (will not power
-up on battery alone).
However
, once the system is powered up, it will operate on battery power in the event of AC loss.


Relays have two programming menu modes: Use *79 Menu mode to map module addresses and
device (output) numbers. Use *80 Menu mode to define the output functions.


This system supports programmable function keys. Use *57 Menu mode to define the function keys.


This system provides various paging features. Refer to the
Programming Overview

section for a
summary on pager programming.





3
SECTION 2

Mounting and Wiring the Contr
ol

Installing the Control Cabinet and PC Board
Cabinet and Lock





1.

Mount the control cabinet to a sturdy
wall in a clean, dry area, which is not
readily accessible to the general
public, using fasteners or anchors
(not supplied) with the four cabinet

mounting holes.



Cell
Module Note:
If using the cell

module with this control, take signal
quality
into consideration when
choosing a mounting location. Refer
to the
LTE
-21V
Module Installation

section for details on signal quality
.
2. Remove cabinet door, then remove
the lock knockout from the door.
Insert the key into the lock.





Figure 1. Installing the Cabinet

Lock


3.

Position the lock in the hole, making certain that the latch will make contact with the latch
bracket when the do
or is closed. When correctly positioned, push the lock until the snap
tabs hold it securely.


The cabinet can be secured without a lock by using 2 screws in the cover's edge.

Mounting the PC Board
Alone (no RF Receiver
)

Before installi
ng the cabinet's contents, remove the metal cabinet knockouts required for
wiring entry. Do not remove the knockouts after the circuit board has been installed.

1. Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B).

2. a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that
the board rests on the correct row (see Detail A).


b. Swing the base of the board into the mounting clips and secure the board to the cabinet
with the accompanying screws (see Detail B).



Figure 2. Mounting the PC Board


Optional
Cell
Module Note:
Refer to the
LTE
-21V
Module
Installation

section later in this
manual for instructions on mounting this optional module.


Mounting Board with RF
Receiver



Do not mount

the cabinet on or near metal objects. This will decrease RF range and/or block
RF transmissions from wireless transmitters.


Do not locate the cabinet in an area of high RF interference (revealed by frequent or
prolonged lighting of the LED in the receiv
er (random flicker is OK)

1. a. Remove the receiver board from its case, then insert the top of the board into the slots
at the top of the cabinet, as shown in Detail A in Figure 3 on the next page. Make sure
that the board rests on the correct row of tabs
.

b. Swing the base of the board into the mounting clips and secure it to the cabinet with the
accompanying screws.


c. Insert the top of the control's board into the slot in the clips and position two clips at the
lower edge of the board.


d. Swing this board into place and secure it with two additional screws.

2. Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the
left
-hand terminals of the antenna blocks (at the upper edge of the receiver board) and
secure them to the cabinet top with the screws provided (see Detail B).

3. Insert the receiver's antennas through the top of the cabinet, into the blocks' right
-hand
terminals, and tighten the screws.

Installation and Setup Guide


4

Figure 3. Mounting the PC Board and RF Receiver


AUXILIARY DEVICE CURRENT DRAW
WORKSHEET

DEVICE

CURRENT

No. UNITS

TOTAL CURRENT

6150 Fixed
-
Word Keypad

40mA/70mA**



6160 Alpha Keypad

40mA/150mA**



6160V Alpha Display Voice Keypad

60mA/190mA**



6280
Touch Screen

Keypad

180mA/280mA**



Tuxedo Touch™ Screen Keypad

130mA/340mA**



5881 RF Receiver

60mA



5883 Transceiver

80mA



4219

Zone Expander

30mA



4204

Relay Unit

15/180mA




4229

Zone Expander/Re
lay Unit

30/100mA




(Current available from Aux. terminals = 600 mA max.)


TOTAL =



*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.


** Values are for standby/alarm; alarm for keypads means
armed with backlighting on and sounder on


†In
UL installations, maximum current draw from the Auxiliary Output and the
Alarm Output
combined

must not exceed 600 mA (500 mA max from Aux. Output
).

‡Values are for relays OFF/relays ON.


CALIFORNIA STATE FIRE MARSHALL

(CSFM
) AND UL RESIDENTIAL FIRE

24-HOUR BATTERY BACKUP REQUIREMENTS

The California State Fire Marshal
and UL have r
egulations which require that all residential fire alarm control panels must be provided with a
backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the int
ended standby
condition, followed b
y at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without
using a supplementary power supply,
provided that the panel’s auxiliary power and bell output currents are limi
ted as indicated below.

OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES

OUTPUT CURRENT LIMITATIONS

BATTERY INFORMATION

Output Current Total

Maximum Auxiliary Current

Battery Capacity

To Use (Amp/Hrs)

Recommended Battery

(Yuasa Model No.)

600
mA maximum total of
auxiliary power plus bell
output currents

45mA

160mA

200mA

425mA

500mA

4AH

7AH
8AH
14AH

17.2AH

NP4
-
12 (or ADEMCO 467)

NP7-
12

NP4-
12 (two) ‡

NP7-
12 (two) ‡

NPG18
-
12




NOTE:

Use two batteries, connected in parallel. Obtain Battery Harne
ss Kit
100
-
02111.

(Both batteries will fit inside the cabinet.)

Mounting and Wiring

5
AC Power, Battery, and Ground Connections

1361
-
GT

Transformer



Connect
the
1361
-
GT

Transformer
(1361CN
-GT
in Canada) to terminals 1 and
2 on the control board. See Wire Run Chart
for wire size to use.



Use caution when wiring the
transformer to the control to guard
against blowing the transformer fuse
(the fuse is non-replaceable).

Wire Run Chart

Distance from control

Wire Size

Up to 50 feet

# 20

50–
100 feet

# 18

100-
250 feet

# 16





Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The voltage
reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC
LOSS” message will be d
isplayed.



Do not plug the transformer into the AC outlet
until all wiring connections to the control
are complete. As a safety precaution, always power down the control when making such
connections.

Battery Connections




1.

Place the 12
-
volt backup b
attery in the cabinet.

2. After all connections to the control are completed and AC power has been applied,
connect the red and black flying leads on the control board to the battery. Do not attach
these leads to the battery terminals until all connections
are completed.

UL

For UL installations and Residential fire installations, refer to the chart on
page 4 at left for the correct battery size required to meet the mandatory
standby time.


Battery Saver Feature


The battery will disconnect from the system

after its voltage decreases below 9VDC. This
assists the control panel in recharging the battery when AC is restored.

IMPORTANT:
The panel will not power up initially on battery power only. You must plug the
transformer in first, and then connect the bat
tery.

Earth Ground





This product has been designed and laboratory
-
tested to ensure its resistance to damage
from generally expected levels of lightning and electrical discharge, and does not normally
require an earth ground.

If an earth ground is desired for additional protection in areas of severe electrical activity,
terminal 25 on the control board, or the cabinet, may be used as the ground connection
point. The following are examples of good earth grounds available at most installations.

Metal C
old Water Pipe:
Use a non-corrosive metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is electrically connected and secured.

AC Power Outlet Ground:
Available from 3-prong, 120VAC power outlets only. To test the
integr
ity of the ground terminal, use a 3-
wire circuit tester with neon lamp indicators, such as
the UL Listed Ideal Model 61-
035, or equivalent, available at most electrical supply stores.


Installation and Setup Guide


6
Sounder (Bell) Connections
Basic Connect
ions



1.

Make sounder connections

to
alarm output terminals 3 (+) and 4 (

).


2. If not using bell supervision, connect the supplied 820 ohm resistor across terminals 3 and
4. If using bell supervision, s
ee
Supervised Output paragraph below.


The 12VDC sounder output activates when an alarm occurs.


Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will
overload the power supply
, or may cause the electron
ic circuit protecting the sounder
output to trip).


You must install a battery, since the battery supplies this current.


Supervised
Output

1. Connect the supplied 820-
ohm

Bell Supervision EOL resistor across the terminals of the last
sounder. See Figure
5.

Bell Supervision Note
:
The value of the Bell Supervision EOL Resistor is 820 ohms.


High Impedance Device Note:
If a high impedance sounding device is used (ex. Voice
Siren Driver
), the bell supervision resistor (included) must be installed at the device.

2. Set field

91 Option Selection for Bell Supervision (option 1).


This control complies with NFPA requirements for temporal pulse sounding of fire notification
appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses –
pause – 3 pulses
–etc..




UL



Use only
UL Listed sounding
devices for UL installations.


Bell supervision is required for
fire alarm installations.


The total current drawn from
the alarm output and the

auxiliary power output,
combined, cannot exceed 600
mA. In addition, the sounding
device must be a UL Listed
audible signal appliance rated
to operate in a 10.2-
13.8 VDC
voltage range, and must be
mounted indoors.





Figure 5. Sounder Wiring (Supervised)


Connecting
the Keypads and Other Addressable Devices
Connections




Connect keypads and other addressable devices (4204, 4219, 4229, 5881, etc.) to the
control’s keypad terminals as shown on the Summary of Connections diagram. The system
supports up to 8 keypads, w
hich can be assigned to partitions in any combination (see
program fields *190-*196).


Use the Table of Device Addresses to determine the appropriate address for each device.


Determine wire size using the Wire Run Chart
on the follo
wing page. For single 4-
wire runs,
determine the current drawn by all units, then refer to the Wiring Run chart to determine the
maximum length that can be safely used for each wire size.

Supplementary Power

(optional)


UL

Use a UL Listed,
battery
-backed supply for
UL installations. The battery
supplies power to these
keypads in case of AC
power loss.
The battery
-backed power
supply
should have enough
power to supply the
keypads with the UL
required minimum standby
power time.


Use supplementary power if the
control’s aux. power load for all
devices exceeds 600mA (suggested
power supply
: AD12612). Connect
as shown in Figure 6. Be sure to
connect the negative (
–) terminal on
the power supply
unit to terminal 4
(AUX
–) on the control.


IMPORTANT:
Keypads powered
from supplies that do not have a
backup battery will not function if
AC power is lost. Make sure to
power at least one keypad in each
partition from the control’
s auxiliary
power output.






Figure 6. Using a Supplementary Power

Supply

Mounting and Wiring

7

Keypad Notes



Set device addresses
. Refer to the instructions included with the devices and set each
address
according to the
Table of Device Addresses
.

See
Keypad Programming Fields
(fields *190-*196) in
Section 4. Data Field
Programming
for details on enabling keypad addresses
, assigning keypad partitions and
selecting keypad sounding options.


IMPORTANT:
Each keypad must be assigned a unique, predefined address,
from 16 to 23.
The first keypad is address 16

(default = partition 1, all sounds enabled).

TOUCH SCREEN KEYPAD (AUI)
NOTES:



Use of up to four
AUI d
evices (e.g.,
6280, Tuxedo) is independent from standard keypads
and does not affect the number of standard keypads the system can support.



AUI devices must be set for address 1 or 2,
or address 5
or 6 depending on which unit is
enabled in field *189.

Optional
LTE
-
21V

Module



Refer to the
LTE
-
21V

Module Installation

section later in this manual for detailed
explanation of its installation.


The
module’s
address
is internally set to 03
and cannot be changed.




Wire Run Chart Fo
r Devices* Drawing Aux Power From The Control (12V+ & 12V

)

Wire

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

Size

50 mA or less

100 mA

300 mA

500 mA

600 mA

#22

900 ft (274m)

450 ft (137m)

150 ft (46m)

90 ft (27m)

75 ft (23m)

#20

1400 ft (427m)

700 ft (213m)

240 ft (73m)

140 ft (43m)

120 ft (37m)

#18

1500 ft (457m)

1100 ft (335m)

350 ft (107m)

220 ft (67m)

170 ft (52m)

#16

1500 ft (457m)

1500 ft (457m)

550 ft (168m)

350 ft (107m)

270 ft (82m)

*
Includes Keypads, RF Receiver
s, Zone Expander/Relay Units, and
etc
.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on
the current draw of that device
alone
.
The length of al
l wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 f
eet if shielded
cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.


Table
of Device Addresses

This Device

Uses Address

Reports as
††

Enabled By...

RF Receiver

00

100

*56 zone programming: input device type entry

AUI 1

01


automatic if AUI enable field *189 enabled for AUI 1

AUI 2

02


automatic if AUI enable field *189 enabled fo
r AUI 2

AUI 3

05


automatic if AUI enable field *189 enabled for AUI 1

AUI 4

06


automatic if AUI enable field *189 enabled for AUI 2

Internal IP/
Cell
Device

03

103

automatic if
enabled in

menu mode

*29

Zone Expanders (4219/4229):

module 1 (for zones 09 -
16)

module 2 (for zones 17 -
24)

module 3 (for zones 25 -
32)

module 4 (for zones 33 -
40)

module 5
(for
zones 41
-

48
)


07**

08
09
10
11


107
108
109
110
111

*56 zone programming: input device type, entry 2, then:

automatic if zone no. 9-
16 set as AW
type or relay assigned
automatic if zone no. 17-
24 set as AW type or relay assigned
automatic if zone no. 25-
32 set as AW type or relay assigned
automatic if zone no. 33-
40 set as AW type or relay assigned
automatic if zone no. 41
-
48 set as AW type or rel
ay assigned

Relay Modules (4204):

module 1
module 2
module 3
module 4


12

13
14
15


112

113
114
115

*79 output device programming: device address prompt:

entered at device address prompt

entered at device address prompt

entered at device address prompt

en
tered at device address prompt

Keypads:

keypad 1

keypad 2

keypad 3

keypad 4

keypad 5

keypad 6

keypad 7

keypad 8


16

17

18

19

20

21

22
23


n/a

n/a

n/a

n/a

n/a

n/a

n/a
n/a

data field programming as listed below:

always enabled for partition 1, all sounds enabled.

data field *190

data field *191

data field *192

data field *193

data field *194

data field *195

data field *196

RIS Communication

25

n/a

automatic

(used for Remote Interactive Services)


** address 07 not available if zone
-doubling enabled

††
Addressable devices are identified by “1” plus the device address
when reporting. Enter a report code for zone 91 to enable addressable device reporting
(default = reports enabled). See field *199 for addressable device (ECP) 3
-digit
/2-digit identification keypad display options.
Installation and Setup Guide


8

Hardwire Zones and Zone Expansion

Hardwire Zones



Normally Open Zones/ N.O. EOLR Zones

1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the
EOLR
across the
loop wires at the last device.

2. Enable normally open/EOLR
zones using Zone Programming mode, “Hardwire Type”
prompt.


Normally Closed Zones/ N.C. EOLR Zones

1. Connect closed circuit devices in series in the high (+) side of the loop; for E
OLR zones,
connect the EOLR
in series following the last device.

2. Enable normally closed/EOLR
zones using Zone Programming mode, “Hardwire Type”
prompt.


End of Line Resistor (EOLR) Notes


If the EOLR is not at the end of the l
oop, the zone is not properly supervised and the
system may not respond to an “open” on the zone.


Zone 1 is intended for EOLR
only.


UL

For UL commercial burglar alarm installations, use EOLR zones.



Double
-
Balanced Zones



Connect as shown below (resistor provided for
one device).


IMPORTANT:
Double-
balanced zones provide
zone tamper protection, and should be used as
burglary zones only.
Do not use double
-balanced zones as fire
zones.





Fig. 7. Typical Double B
alanced Zones

Zone Doubling



This feature provides two hardwired
NORMALLY CLOSED
zones for each standard
hardwired zone connected to the control’s
terminals (but does not increase the total
number of zones supported by the control).
If
enabled (Zone Programming mode, “Hardwire
Type” prompt, option “3”), hardwire zones are
automatically paired as shown in the table.
Connect as shown (resistors provided).


Do not use zone doubling for fire zones.


NOTE:

A short across the EOL (i.e., a
t
terminal) on either zone of a zone-
doubled pair
or on a double-
balanced zone causes a tamper
condition (displayed as CHECK plus zone
numbers).



Fig. 8. Typical Zone Doubling Wiring


Zone Doubling Table

Zone

Paired with zone

2
10
3
11
4
12
5
13
6
14
7
15
8
16

NOTE:
Zone numbers used for zone
doubling cannot be used for anything else
(ex. cannot be used for 4219 zones)

Mounting and Wiring

9

Smoke Detectors



1.

Connect up to 16 (10, if
ESL
“clean me” option used) 2
-
wire smoke detectors across
zone 1 terminals 8 (+) and 9 (
-) as shown in the Summary of Connections diagram at the
back this manual. Observe proper polarity when connecting the detectors.
2. Connect an EOL resistor across the loop wires at the last detector.

3.

Connect 4-
wire smoke detectors (up to tr
igger output 17’s maximum
current draw

100mA
) to any zone from 2-8 as shown in Figure 9a and 9b (on next page).


Power Reset:
This control does not automatically reset power to 4-
wire smoke detector
zones, so you must use a relay (e.g., 4204,
4229)
, or on-board trigger to reset power
(also required for fire verification). Do this by programming the designated relay/trigger
as zone type 54 (fire zone reset); see
On-Board Trigger
section for other information.


NOTE:
Maximum current on trigger 17 is 100mA.



Smoke Detector Notes



Fire Verification (zone type 16):

The
control panel will “verify” a fire alarm by resetting the
smoke detectors after the first alarm trigger, and then waiting up to 90 seconds for a
second alarm trigger. If the smoke detector or thermostat does not trigger again, the control
will disregard the first trigger, and no alarm signal will occur. This feature eliminates false
alarms due to electrical or physical transients.

SIA Installat
ions:
If using fire verification on zones other than zone 1, UL Fire Alarm Listed
relay accessories must be used to reset power as described in the Power Reset paragraph
above.



The zone 1 alarm current supports only one smoke detector in the alarmed state.


Clean Me Option
:
If enabled (field *174 = 1; *56 zone programming, response time prompt
= 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the
maximum number of detectors is reduced to 10 (not stan
dard 16). Refer to the ESL
documentation included with the smoke detector for information regarding compatibility with
the clean-me option.



Do not use 4
-
wire smoke detectors on zone 1.




Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset




Figure 9b. 4
-Wire Smoke Detector Using Output 17 for Power Reset

4219/4229

Expansion
Zones





1.

Connect each module to the control’s keypad terminals and set the device addresses.


See the Table of Device Addresses to select an appropriat
e address for each module.



Supports
up to 40 expansion zones using up to 5 Zone Exp. Modules.

2. Connect sensors to the module’s loops.

Use end-of
-line resistors at the end of loops connected to the 4219/4229
modules.



Exp
ansion zones have normal response time
(300–
500 msec), except zone connected
to each module’s loop “A,” which can be set for fast response (10–
15 msec).

3. If using relays with the 4229, connect the desired field wiring t
o the unit's relay contact
terminals.
Installation and Setup Guide


10

Installing the RF Receiver and Wireless Transmitter Zones

Compatible
Receivers


Use any ADEMCO 5800 Series Wireless Receivers, such as:

RF Receiver

No. of Zones

5881ENL

u
p to 8

5881ENM, 6150RF

up to 16

5881ENH, 5883
H
,
6160RF

up to 40 plus 16 buttons

1

Receiver
Connections





WIRELESS
ZONE
NUMBERS


transmitter
zones 9-
48

button zones
49-
64

1.

Set Device Address to “00” (set all switches to the right, “off” position).

2. Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal
range of 200 feet.

3. Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the
other end of the harness into the receiver. Refer to the installation instructions provided with the
receiver for further installation procedures regarding antenna mounting, etc.


5881 RF Receiver


Figure
10. RF Receiver
(cover removed)

RF Receiver
Notes


† These fields
must be
enabled for
Residential
Fire, UL
Residential
Burglar Alarm,
and UL
Commercial
Burglar Alarm
installations.


Set the following options:


*22
RF Jam Option


*24
RF House ID Code
(if using wireles
s keypads) for each partition


*67
Transmitter Low Battery Report Code†


*75
Transmitter Low battery restore report code†


The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if communication
between the panel and receiver is i
nterrupted, or if no valid RF signals from at least one supervised
transmitter are received within 12 hours.

If the receiver is mounted remotely:


Place the RF receiver in a high, centrally located area for best reception.


Do not locat
e the receiver or transmitters on or near metal objects. This will decrease range and/or
block transmissions.


Do not locate the RF receiver in an area of high RF interference (indicated by frequent or prolonged
lighting of the LED i
n the receiver; random flicker is OK).


Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from the
microprocessors in those units.

Mounting and Wiring

11

Installing the
Transmitters








Refer to the table of compatible devices at th
e back of this manual.


Supervised transmitters† send check
-in signals to the receiver at 70-90 minute intervals. If
at least one check
-in message is not received from each transmitter within a 12-
hour period,
the “missing” transmitter number(s) and “CHEC
K” is displayed. († Hand-
held transmitters,
e.g.,
5802WXT
and 5834
do not send check
-in signals.)


To
be sure reception of the transmitter's signal at the proposed mounting location is
adequate, perform a Go/No Go Test, des
cribed in the

Testing the System
section.


Install transmitters in accordance with the instructions provided with each.


Set
wireless keypads
(5828)
to the programmed
House ID (field *24), follow the instructions
provided with t
he device.


Use *56 or *58 Zone Programming Menu modes to program zone information and enroll
transmitters (zones 9
-48, buttons 49-
64).


Wireless Keys:
Use Wireless Key Programming Templates section of the *58 Zone
Programming Menu mode to program zone i
nformation and enroll each button of the
wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before it
becomes active. See Adding/Deleting Security Codes section for procedure.


ULC NOTE:
In accordance with ULC standards, the RF supervision period for the VISTA
-21iPLTE is
three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone types.

Transmitter Battery Life



See Wireless Transmitter paragraph in the
Limitations of This Alarm System

statement
located
at the end of this manual for information on transmitter battery life.

• Button-type transmitters (such as 5802WXT and 5834) should be periodically tested for
battery life.

• The
5802WXT
and
5834
Button Transmitters have replacea
ble batteries.


Do
not install batteries in wireless transmitters until you are ready to enroll during system
programming. After
enrolling, batteries need not be removed.


Installation and Setup Guide


12
Installing a Keyswitch
Keysw
itch Connections





1.

Connect the keyswitch's normally open momentary switch

to a zone’s (2
-
8) terminals.
Remove the 2000 ohm EOL resistor if connected across the selected zone.

2. Using a standard keypad cable as shown:

Connect
the yellow and white keyswitch wires to trigger connector pin 3 (+12V).


Connect the Red and Green LED wires to the appropriate output 17/output 18 trigger
connector pins
.
3. Connect a 2000 ohm EOL resistor across the momentary sw
itch.

4. You can wire an optional closed-circuit tamper switch
(model 112) in series with the
zone. If the switch plate
is then removed from the wall, the tamper will open, disabling
keyswitch operation until the s
ystem is next disarmed from the keypad.


If the tamper is opened when the system is armed, an alarm will occur.





Figure 12. Keyswitch
Wiring Connections


Keyswitch Notes



UL

A UL Listed keyswitch is required for fire installations

and UL commercial and residential
burglar alarm installations.


If a keyswitch is used on:


an installation that transmits opening and closing signals, the keyswitch zone must be
programmed to send opening and closing signals.


a UL commercial burglar alarm installation, the keyswitch’s tamper switch must be
connected in to the alarm system. This tamper switch zone must also be programmed
for Zone Type 05 – Trouble by Day / Alarm by Night.

a fire alarm installation, the keyswitch must be located next to an alphanumeric
display keypad.




Use any N.O. keyswitch.


Use only one keyswitch per partition.


When using a keyswitch, the zone it is connected to is no longer available for use as a
protective zone.


Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.


Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system
operation zone type 78 (red LED) and 79 (green LED) as appropriate (see
Output Device
Programming

section).

Mounting and Wiring

13

Co
nnecting Relay Modules and Output Triggers
4204/4229 Relay Modules




UL

For UL
installation
requirements,
refer to the
Installation
Instructions for
the 4204
.


1.

Mount either remotely or in the control panel

cabinet
.

2. Connect each module to the control’s keypad terminals and set the device addresses
as previously described in the
Connecting Keypads and Other Addressable Device

section. Use the connector harness supplied with the module. Use standard
4-conductor twist
ed cable for long wiring runs.



Up to 16 relays (if no powerline carrier devices are used)

3. Connect the desired field wiring to the unit's relay contact terminals.



Figure 13.
4204
Connections to Control



Supervision: 4204
and 4229
modules are supervised against removal. The module’s
device address
is displayed as follows if a module is disconnected from the control’s
terminals, or if the module cover is removed and the tamper jumper is i
nstalled:

Alpha:
CHECK
xx Wire
Expansion


FAULT xx Wire
Expansion


ALARM xx Wire Expansion

Fixed
-Glass: lxx (or 91 if field *199 set for 2-
digit display)

where “xx is the module’s address.


If communication/tamper failure occurs on a device with zones wired to it, all zones on the
device will be displayed in their respective partitions.

Installation and Setup Guide


14

On
-
Board Triggers




Connect field wiring to the desired trigger pin on the 8
-
pin trigger connector centrally located
above the terminal strip.


If only using the
on-board triggers, you can use a 4-
wire cable (N4632-4, supplied with
the control) as shown below.




Figure 15a. On
-Board Trigger Connector

Figure 15b. On
-Board Trigger Connector

with SA4120XM
-1 Cable

with 4
-Wire Cable for Trigger Use Only



Trigger
outputs
are normally open collector (no voltage)
, and go low upon programmed
condition.


The outputs can be programmed for inverted operation (normally low, go open) using *79
Menu mode.


Program these triggers using *80/*81 Menu
modes as you would for any other relay
output.


When using these outputs, note:

pin 1 =
output number 17 (trigger 1):


15 ohms to ground when closed (output low), open when off (output high,
normal default); can be used to reset smoke detector power (m
ust set “output
normal low = yes” in *79 Menu mode, and set for zone type 54, fire zone reset,
in *80 Menu mode); or can support 12V relay module (
e.g., Altronix AX
-RBS)
that
draws less than 100mA

pin 5 =
output number 18 (trigger 2):


100 ohms to ground
when closed (output low); open when off (output high,
normal default); or can support 12V relay module that draws less than 20mA


UL

If on
-
board triggers are used, the wiring between the control unit and the UL
Listed device must be run in conduit, be no more than 3 feet apart, and
have no intervening barriers or walls.



Mounting and Wiring

15


Audio Alarm Verification
Connections

(AVS System
)



Using the AVS System with AVS Module and AVST Remote Stations

The AVS system provides audio alarm verification via the phone li
ne.

Refer to the instructions included with the AVS system for installation procedures. The
following is a summary.

Mounting the AVS Base Unit

As shipped, the AVS Base unit board
comes pre
-mounted on its mounting
bracket, which is designed to mount
inside
the control cabinet.

Refer to the diagram at right.

a. Position the mounting plate/PC
board assembly in the bottom of the
control’s cabinet.

b. Slide the mounting plate to the right
so that the plate’s left
-hand tang
slides under the cabinet’s tie-
wrap
loo
p.
c. Secure the assembly to the cabinet
using the two self
-tapping screws
provided.



BATTERY NOTE:
When using a 7AH battery, mount the battery vertically on the bottom left
-
hand side of the cabinet, with the terminals facing down and right (negative terminal closest
to the PC board bracket).


Wiring the AVS to the Control

The AVS Base unit board has several terminal blocks for making connections to remote
stations, telephone lines, and to the control panel. The AVS base unit connects to the
control’s EC
P terminals, with all other ECP devices connecting to the AVS base unit ECP
terminals. See the diagram on the next page for specific wiring connections.


DIP Switch:

Set the address AVS DIP switch to device address 11.


IMPORTANT:
The AVS should be the onl
y ECP device connected to the control’s ECP
terminals. Connect all other ECP devices (keypads, expander modules, etc.) to the ECP
terminals on the AVS board.



The following summarizes the programming steps for AVS operation (refer to the Programming
Guide
for details of the AVS Quick Command options):


a. Install the AVS module according to its instructions.


b. Use one of the control’s AVS Quick Program commands as follows :



installer code + [#] + 03:
enable AVS operation without panel sounds on the A
VST



installer code + [#] + 04:
enable AVS operation and enable panel sounds on the AVST
speaker




installer code + [#] + 05:
remove all programming options set by [#] + 03 quick
command



installer code + [#] + 06
: remove all programming options set
by [#] + 04 quick
command


c. Use data field

55 Dynamic Signaling Priority to select the desired reporting paths.




Installation and Setup Guide


16



Figure 18. Connections for the AVS System


Mounting and Wiring

17

Internet (IP) Connection

Connection to the Internet
can be
made

via
hardwired high

speed Internet connection
a
nd/or
via an optional on-board
LTE
-21V
module (using the wireless
digital cellular network).
Use

29 Menu mode to program various internet reporting and supervision options.


Hardwire Internet Connection:
Connect an
active
Ether
net
cable
(with RJ45 connector)
to
the IP connector on the upper left corner of the control board.
The control must be registered
before
internet
communication can occur. Refer to the Registering the Control section for
details.


IMPORTANT!
(1) Use of the
Internet connection (hardwire or LTE
-21V
module)
requires
an AlarmNet
–I account. If an account for the control does not yet exist, please obtain the
account information from the central station prior to programming this module.

(2) The control must be registered with AlarmNet before normal operation. See
Registering the Control
with AlarmNet
section for registration procedures.


When the internet connection is active, the Network LEDs have the following functions:


IP (web) Network LED Functions

LED Color

LED

Description

Top Green

Ethernet Link/Activity

ON


link is active; OFF


no link

Middle Green

Link Speed

ON


100 MB/S; OFF


10 MB/S

Yellow

Network Collision

BLINK


collision detected; OFF


normal


LTE
-
21V

module:

See
LTE
-
21V

module Installation below.


LTE
-21V
Module
Installation

General Information

The
LTE
-
21V

is an optional communication module and provides cellular radio communication with
the AlarmNet network for delivery of alarm and other messages to the monitoring central station,
and allows upload/download via the Internet using cell
technology in combination with Compass
Downloading Software.


The
LTE
-21V
module’s parameters are programmed using the control’s *29 Menu mode.

Mountin
g the
Module






IMPORTANT!
Disconnect power from the control, including the battery, BEFORE installing the
LTE
-21V
module.


CAUTION:
ESD SENSITIVE DEVICE. To discharge any static buildup, briefly touch a chassis
ground point before installing this modul
e. Avoid performing this installation while standing on a
carpeted floor.


1. Mount the
LTE
-21V
Board.

a. Carefully align the module board over the standoff holes and the mating connector on
the
VISTA
-21IPLTE control. Then, gently push down on the board near
each standoff
until it
snaps into place and the connector is fully seated.

b. After installation, affix the “Contains Transmitter Module” FCC label to the outside surface
of the control panel cabinet so it is visible.

Installation and Setup Guide


18


2.

Install the Antenna Adapter

Plate
s
.


a. Punch out the large wiring hole knockout and the adjacent smaller knockout from the cabinet’s upper
-right
and left

topside.


b. Position the antenna adapter plate over the large knockout, aligning the plate’s pin with the smaller knockout and
push until the adapter snaps into place.


c. Remove the nut and washer from the antenna adapter cable, then secure the cable’s SMA connector to the
adapter plate with the washer and nut as shown.




3. Install the Antenna
s.
The antennas
mount
directly ont
o the antenna adapter cable at the antenna adapter plate.


Carefully align the antenna’s connector over the SMA connector protruding from the adapter plate, then screw it down
(clockwise) until it is finger tight. Do not over tighten.



RF EXPOSURE WARNIN
G

The LTE
-21V
module must be installed to provide a separation distance of at least 7.8 in. (20 cm) from all persons and
must not be co-
located or operating in conjunction with any other antenna or transmitter except in accordance with
FCC multi
-
transmitte
r product procedures.



Internal/External IP/
Cell
Power Jumper Note
:
After installation of the module, make sure the control’s PC Board
Internal/External IP/
Cell
Power
Jumper is in the ON position (factory default position). The jumper is located below th
e
RJ45 connector.
Mounting and Wiring

19

IP/
Cell
Status
LEDs

There are three status LEDs used to indicate IP/
Cell
message and internal device status:


STATUS, green


MESSAGE, yellow


FAULT, red
Each LED can have four different states -
ON, OFF, FAST BLINK and SLOW BLINK.



IP/
Cell
Status LED Meanings

COLOR/LED

DESCRIPTION

Green

Status

On


module NOT registered with AlarmNet

Off – module is registered with AlarmNet

Fast Blink –
Download session with Compass in progress

Slow Blink


In unison with yellow LED


Registratio
n in progress.

Yellow

Message
On


Message transmission pending.

Quick Periodic Blink – Normal.
Fast Blink – Message waiting for network ACK.

Slow Blink


In unison with green LED


Registration in progress.

Red

Fault
On


No contact with network.

Off
– Normal.

Slow Blink – Loss of contact with panel (ECP fault).
Fast Blink


No network contact AND loss of contact with the panel.

All

Fast Blink


In unison with the
signal quality

LEDs


Hardware Error. Call the AlarmNet
Technical Assistance Center.



Si
gnal
Quality

Signal Quality
is a measure of how well the
LTE
-
21V

is receiving the cell tower.
For reliable service,
the antenna should only be installed in locations where the
signal quality is a minimum of
two
bars.
The
signal quality value can also be vi
ewed on the keypad display by using the
shift
command
while in *29 Menu mode-Diagnostic mode.

The following are tips for maximizing signal quality
:

Find the best coverage before mounting the antenna by moving it to several locations while
monitoring
the
signal quality
.

The best signal quality can usually be found on an exterior wall at the highest point in the building.
Avoid the basement.


Maintain at least 12 inches clearance between antenna and steel I
-beams, HVAC ducts, metal
studs, steel roofs, exterior walls with metalized insulation or aluminum siding and other large metal
objects.

If a consistent signal quality of
two
bars cannot be found, the control cabinet may have to be moved
to an area of better reception.





Signal
Quality

and
Status
LEDs

The Signal
Quality,

Mode and Status LEDs normally display the module’s signal
quality

. LED 1 (top
red LED) will be lit to indicate that the display is in signal quality mode, and the other LEDs indicate
signal strength (lowest to highest, from top to
bottom) between the module and the receiving tower.
Signal strength should be within 2
-5 bars.

*
LTE
-21V
Initial Power Up
: Upon initial power up, the communicator LEDs blink in repeated
sequence from top to bottom indicating network initialization.

Green
(REG)

Yellow (TX/RX)

Red (FAULT)

This sequence may take up to 15 minutes.
Do not reset power during this time.

When initialization is complete, the Signal Quality display LEDs will light and the yellow and red
LEDs may blink (per their respective func
tions).

After initial network setup, subsequent resets or power ups can take up to 90 seconds.

Status Indicator Switch

Press and hold the Status LED Indicator Switch to change the LED functions to view the network
carrier status. When the switch is held do
wn, LED 1 (top red LED) will be off, and the other LEDs have
the following meanings (see diagram for specific functions):
Installation and Setup Guide


20


Signal Strength and Status LED Meanings

Color

Label

Indication

Red

Signal

Quality

on = signal
quality

display

off = status displ
ay

Yel
low

M
ode

off = module operating in ECP

mode

Green

Mode

off = module operating in ECP mode

Green

Web

web connection status

ON = connected to web

OFF = no web connection

Green

GPRS

Cell
service availability

ON = Cell service available

FLASH = Cell in use
OFF = no
Cell
service (messages sent via SMS)

Green

Cell

network carrier registration status

ON = registered with network carrier, no second site available

FLASH = registered with network carrier and second site available, excellent signal quality

BLINK = registered with network carrier and second site available, acceptable signal quality

SLOW BLINK = registered with network carrier and second site available, low signal quality

OFF = control not registered with network carrier



Signal Strength and Status LED locations – Status LED Functions Table




Inadequate Signal
Strength
;
Using Stand
-Alone
Communication
Device

If sufficient signal strength cannot be achieved, take one of the following actions:

1. Try relocating the cabinet to an area with better reception.


2. If moving the cabinet cannot achieve sufficient signal strength, an external, stand-alone
communication device (ex. LTE
-IV
/LTE
-IA
) can be used. Follow these steps:

a.

Power down the control.

b. Remove the Internet cable from the RJ45 co
nnector (if
connected) and disable the Internal
IP/
Cell
portion of
the control board by moving the
Internal/External
IP/
Cell
Jumper to the OFF pair of pins.

c. Connect the communication device to the control’s
ECP terminals and complete all other communication
device wiring as required.




d. Power up the control
and the communication device.


e. Refer to

29 Menu mode, Enable INT IP/
Cell
prompt,
for programming information.


f. Refer to the
Installation and Setup Guide
included with the communication dev
ice for the
registration procedure.





21

SECTION 3

Programming Overview


About Programming

You can program the system at any time, even at the installer's premises prior to the actual installation.


Programming can also be performed remotely from the installer’s office/home, using a personal computer, a
modem, and Compass downloading software.


The Real
-Time Clock must be set before completing the installation.

The following is a list of the various Programming modes used to program this system.

Programmi
ng Mode...

Used to ...

Data Field Programming

Program basic data fields used for setting the various system options.

Most of the data fields in this system have been programmed for specific default values.
However, some fields must be programmed for each part
icular installation to establish its
specific alarm and reporting features.


29 Menu Mode for IP/
Cell

For programming the IP/
Cell

options.


56 Zone Programming

Assign
zone characteristics, report codes, alpha desc
riptors, and serial numbers for 5800
RF transmitters. See
*56 Zone Programming
in
Section 5. Menu Mode Programming

for procedures for programming zones.


57 Function Key
Programming

Program each of the four alphabet function keys to perform one of several

system
operations.


58 Zone Programming
(Expert Mode)

Similar to

56 mode, but provides a faster programming procedure and is intended for
those more experienced in programming controls of this type.


79 Output Device Mapping

Assign device address
es used by
4229 or
4204 Relay modules and map specific relays
and device outputs, and assign unit codes for Powerline Carrier devices.

See
About Output Device Programming
in
Section 5. Menu Mode Programming
for
details on setting devices for manual/automatic operation.


80 Output Definitions

Define up to 48 output definitions which can control the output relays mapped using *79
Output Device Mapping

mode.


81 Zone List Programming

Create Zone Lists

for relay/powerline carrier zones, chime, night
-
stay, cross zones, and
pager zones.


82 Alpha Programming

Create alpha descriptors for easy zone identification.

Scheduling Mode

(code + [#] +64)

Create schedules to au
tomate various system functions.


Mechanics of Programming


To program the system from a keypad:


You must use a 2-line Alpha display keypad.


Both partitions must be disarmed.


Data Field Programming Procedures

Task

Procedure

Entering Program Mode

A) Press both [

] and [#] at the same time within 50 seconds after power is applied,

OR

B) After power-
up, enter [Installer code (4-1
-1-2)] + 8 0 0 (long beep indicates one of the
partitions is armed and system cannot enter program mode).

(method “B” is d
isabled if you exit Program mode using

98)

Go to a Data Field

Press [

] + [Field Number]. A display of “EE” or “Entry Error” means you have entered a
nonexistent field. Simply re
-
enter [

] plus a valid field number.

Entering Data

When the desired field
number appears, simply enter the digits required. The keypad beeps
three times after the last digit is entered and automatically displays the next data field in
sequence.

If entering less than the maximum digits available (e.g., phone number field), enter the desired
digits, then press [

] to end the entry.

Review a Data Field

Press [#] + [Field Number]. The field’s data is displayed, but no changes can be made.

Deleting an Entry

Press [

] + [Field No.] + [

] (applies only to phone number, account number,
and pager
character fields).

Installation and Setup Guide


22
Interactive Mode Programming (

56, *57,

58,

79,

80,

81,

82)

Entering Interactive Mode

Press [

] + [Interactive Mode No.] (for example,

56) while in Program Mode. The Alpha
display keypad will display the first of a series of prompts.

After making the appropriate entry, press the [

] key to accept the entry and continue to the
next prompt.


Loading Factory Defaults
/Initializing for Download

To Load Default Entries

Press

97 while in Program Mod
e. This resets all data fields to the default values shown on
the Program Form. Use

97 only if you wish to return to the original factory
-programmed
defaults.

To Initialize Download ID

Press

96 while in Program Mode. This initializes the system for down
loading and resets all
the subscriber account numbers and CSID.



Do not press
*97 to load defaults if any programming has been done previously
—data already
programmed into the system will be changed!


Exiting the Programming Mode

Prevent installer code

reentry

Press

98. Exits Programming Mode and prevents re
-
entry by:

Installer Code
+ [8] + [0] + [0]. To enter the programming mode if

98 was used to exit, you
must first power the system down. Then power up again, and press [

] and [#] at the same
time, within 50 seconds of powering up.

See field *88 for other Program mode lockout options.

Allow installer code
reentry

Press

99. Exits Programming Mode and allows re
-
entry by:

Installer Code
+ [ 8] + [0] + [0] or by: Pressing [

] and [#] at the same time, within 50 seconds
of power
-
up.


Zone Type Definitions
Zone types define the way in which the system responds to faults in each zone.


Zone Type

Description

Type 00

Zone Not Used

Program a zone with this zone type if the zone is not used.

Type 01

Entry/Exit
Burglary
#1




Assign to zones that are used for primary entry and exit.


Provides entry dela
y when zone is faulted if control is armed in the Away, Stay, or Night
-Stay
modes.


No entry delay provided when the panel is armed in the Instant/Maximum mode.


Entry delay #1 is programmable for each partition (field *35).


Exit delay begins wheneve
r the control is armed, regardless of the arming mode selected, and is
programmable (field
*
34).

Type 02

Entry/Exit
Burglary
#2



Assign to zones that are used for entry and exit and require

more time than the primary entry/exit
point.


Provides a secondary entry delay, in same manner as entry delay #1.

Entry delay #2 is programmable for each partition (field *36).



Exit delay is same as described for Type 01.

Type 03

Perimeter
Burglar
y


Assign to all sensors or contacts on exterior doors and windows.


Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Night
-
Stay, Instant or Maximum modes.
Type 04

Interior Follower



Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass
upon entry (to and from the keypad).


Provides a delayed alarm (using the programmed entry 1 time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.


Active when the panel is armed in the Away mode.

Bypassed automatically when the panel is armed in the Stay or Instant modes;

if armed in Night
-Stay mode, zones assigned to zone list 05 (ni
ght
-stay zone list) are not bypassed
when system armed in Night
-
Stay mode.
Programming Overview

23

Type 05

Trouble by Day/

Alarm by Night



Assign to a zone that contains a foil
-
protected door or window (such as in a store), or to a zone
covering a sen
sitive area such as a stock room, drug supply room, etc.

Can also be used on a sensor or contact in an area where immediate notification of an entry is
desired.


Provides an instant alarm if faulted when armed in the Away, Stay, Night
-Stay, Instant or Maximum
(night) modes.

During the disarmed state (day), the system will provide a latched trouble sounding from the
keypad (and a central station report, if desired).

Type 06

24-hr Silent Alarm



Usually assigned to a zon
e containing an emergency button.


Sends a report to the central station but provides no keypad display or sounding.

Type 07

24-hour Audible
Alarm



Assign to a zone that has an emergency button.


Sends a report to the central station, and provides an alarm sound at the keypad, and an audible
external alarm.
Type 08

24-hour

Auxiliary Alarm



Assign to a zone containing an emergency button, or to a zone containing monitoring devices such
as water or temperature sensors.


Sends a report to the central station and provides an alarm sound at the keypad. (No bell output is
provided.)

Type 09

Supervised Fire




Provides a fire alarm on short c
ircuit and a trouble condition on open circuit.


A fire alarm produces a pulsing bell output
and keypad sounding that complies with NFPA
requirements for temporal pulse sounding of fire notification appliances. Fire alarm t
emporal
pulse sounding
is as follows:
3 pulses
–pause
–3 pulses
–pause
–3 pulses
–pause. . . ,
repeated.



This zone type is always active and cannot be bypassed.


Type 10

Interior w/Delay



Provides
entry delay

(using the programmed entry time), if tripped when the panel is armed in the
Away mode.

Entry Delay 1
begins whenever sensors in this zone are violated, regardless of whether or not an
entry/exit delay zone was tripped first.


Byp
assed when the panel is armed in the Stay or Instant modes; if armed in Night
-Stay mode,
zones assigned to zone list 05 (night
-stay zone list) are not bypassed when system armed in Night
-
Stay mode.

Type 12

Monitor Zone



Works as a dynamic monitor of a z
one fault/trouble (not alarm). In the case of a short/open, the
message, "*ALARM*
-24 Hr. Non-Burg.
-#XXX " (where XXX is the zone number) will be sent to the
Central Station. The system keypad will display a “check” message indicating the appropriate zone
(but keypad beeping does not occur). Upon restoral of the zone, the message, "*RESTORE*
-24 Hr.
Non-Burg.
-#XXX

" will be sent to the Central Station.


The “check” message will automatically disappear from the keypad dynamically, when the zone
restores; a
user code + off sequence is not needed to reset the zone.


Faults of this zone type are independent of the system, and can exist at the time of arming without
interference.


Since this is a “trouble” zone type, do not use this zone type with relays set
to activate upon
“alarm.”

Type 14

24 Hour Carbon
Monoxide
Monitor



Assigned to any zone with a carbon monoxide detector.


A carbon monoxide
alarm produces keypad
and detector sounding (
does not affect
bell output)



Always active and cannot be bypas
sed.

Type 16

Fire
w/Verification



Provides a fire alarm when zone is shorted, but only after
the
alarm

is

verified

to help eliminate
false alarms due to electrical or physical transients.


System verifies alarm by resetting smoke detectors
after short is detected
(removes power 7
seconds for zone 1; 3 seconds for trigger output)
. A subsequent short circuit within 90 seconds
triggers fire alarm, otherwise the
first alarm is ignored.



Provides a trouble response when zone is open.

Type 20

Arm
-Stay (BR
only)



Arms the system in Stay mode when the zone is activated.


Pushbutton units send the user number to the central station when arming or disarming.


User number for button must be assigned.

Type 21

Arm
-Away (BR
only)



Arms the system in Away mode when the zone is activated.


Pushbutton units send the user number to the central station when arming or disarming.


User number for button must be assigned.

Type 22

Disarm (BR only)



Disarms the sys
tem when the zone is activated.


User number for button must be assigned.
Installation and Setup Guide


24

Type 23
*

No Alarm
Response



Can be used on a zone when an output relay action is desired, but with no accompanying alarm
(e.g., lobby door access).
Type 24

Silent Burglary



Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or
sirens are NOT desired.


Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the
zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.


A report is sent to the central station.

Type 77

Keyswitch



Assign to zone wired to a keyswitch.



Do not use devices assigned as inpu
t type “BR” with this zone type.

Type 81

AAV Monitor
Zone
(for AVS)


Assign to zone connected to AV
S

module.



Monitors 2-
way voice sessions as follows:


- When the zone is faulted, all alarm sounding and dialer reporting stops, except


for fire alarm
s, which immediately terminate the voice session and cause

a fire report to be sent.


- When the zone is restored (session ended), sounding resumes (if bell timeout



has not expired) and reports that were stopped are sent.

Types 90
-
93

Configurabl
e
Allows for various custom responses. Options include response to entry/exit delays, response
opens/shorts, types of alarm/trouble sounding, dial delay, and unique Contact ID report codes. Types
92 and 93 can only be programmed via downloader. UL install
ations: Zone Types 90 -93 may not be
used as fire or burglar alarm zones on fire or UL burglar alarm installations.


* The system can still be armed when these zone types are in a faulted condition.


NOTE:
All of the zone types described are available for
the wireless portion of the system, if used.
Data Field Programming


25
SECTION 4

Data Field Programming

About Data Field Programming
The following pages list this control’s data fields in numerical order. Valid entries for each field are shown in
italics. Explanations and special notes a
re presented below the entries.



Use the separate Programming Guide to record the data for this installation.



Data field programming involves making the appropriate entries for each of the data fields.

Start Data Field programming by entering the
installer code + 8 0 0.


SIA Guidelines:
Notes in certain fields give instructions for programming the
V21SIALTE
for False Alarm
Reduction. Fields unique to the
V21SIALTE

are indicated by heavy borders and reverse type heading

V21SIALTE
” for easy identi
fication.



System Setup Fields (

20


29)

*20
Installer Code

Enter 4 digits, 0000-9
999

The Installer Code can perform all system functions
except it cannot disarm the system unless it was used to
arm the system.
For security purposes, the factory default
installer code should be changed.


*21
Quick Arm Enable

0 = do not allow quick arm; 1 = allow quick arm

If enabled, a user code is not needed to arm the system.
Instead, users can press the [#] followed by an arming key
to arm the system. However, the user code is always
needed to disarm the system.


*22
RF Jam Option

0 = no RF jam detection; 1 = send RF jam report

If enabled, a report is sent if the system detects an RF
jamming signal.

UL installations must be
1
if wireless devices are used.


*23
Quick (Forced) Bypass

0 = no quick bypass

1 = allow quick bypass (code + [6] + [#] )

Zones bypassed by this function will be displayed after the
bypass is initiated.
UL installations m
ust be
0
(no forced bypass)


*24
RF House ID
Code

00 = disable all wireless keypad usage

01–
31 = House ID
for partition 1, 2 and common

The House ID
identifies receivers and wirel
ess keypads. If
a 5828
Keypad
Transmitter is being used, a House ID
code
must
be entered and the keypad set to the same
House ID. You can assign RF house ID for each partition.


*26
Chime By Zone List
/ KP Sound Enables

Entry 1

0 =
no “entry 1” keypad trouble sounds, AND no chime
by zone
(keypad chimes on fault of any entry/exit or
perimeter zone when chime mode is on)

1 =
Chime by Zone enabled
2 =
Communication Device (LRR) trouble sounding
enabled (for devices such as
LTE
-IV
)
4 =
System Low Battery soundi
ng enabled

7 =
select all entry 1 options


*26
Chime By Zone List/ KP Sound Enables
(continued)

Entry 2

0 =
no “entry 2” keypad trouble sounds
1 =
RF Supervision sounding enabled

2 =
RF Low Battery sounding enabled

4 =
RF Jam sounding enabled

7 =
select
all entry 2 options


Chime by Zone

If Chime by Zone is enabled (entry 1 –
option 1), you can
define the specific zones intended to chime when faulted
while the system is in Chime mode.
List chime zones on
zone list 3 using *81 Menu mode.


Keypad (KP) Trou
ble Sounding

Keypad trouble sounding can be enabled/disabled for the
conditions listed for each entry.

For each entry, enter the sum of the desired options.
Example Entry 1: for Chime by Zone and System Low
Battery sounding, enter 5. To enable all options, enter 7.



*29
Menu Mode for IP/
Cell
Enable

For programming IP/
Cell
options. See

29 Menu Mode
section for procedures. Installation and Setup Guide


26
Zone Sounds & Timing (

31–

39)

*31
Single Alarm Sounding Per Zone
(per armed period)

0 = no limit on alarm sounding per zone

1 = limit alarm sounding at the bell output to once per
arming period for a given zone
V21SIALTE:

If “0” selected, “alarm sounding per
zone” will be the same as the “number of reports in
armed period” set in field *93 (1 i
f one report, 2 if 2
reports, unlimited for zones in zone list 7).


*32
Fire Alarm Sounder Timeout

0 =
yes;
sounder timeout after time selected in field

33
1 =
no timeout; sounds until manually
turned off

This control complies with NFPA requirements for temporal
pulse sounding of fire notification appliances. Temporal
pulse sounding for a fire alarm consists of the following:
3
pulses – pause – 3 pulses – pause – 3 pulses.

UL fire alarm installations: must be
1
.


*33
Alarm Sounder Timeout

0 = No timeout; 1 = 4 min; 2 = 8 min; 3 = 12 min; 4 = 16 min
This field determines whether the external sounder will
shut off after time allotted, or continue until manually
turned of
f.
UL Installations: For residential fire alarm installation, must
be set for a minimum of 4 min (option
1
); for UL
Commercial Burglary installations, must be minimum of 16
min (option
4
).


*34
Exit Delay

00
- 96 = 0 -
96 seconds; 97 = 120 seconds

V21SIAL
TE:

45
- 96 = 45 -
96 secs; 97 = 120 secs

NOTE: Entries less than 45 will result in a 45-
sec delay.

The system waits the time entered before arming
entry/exit zones. If the entry/exit door is left open after this
time expires, an alarm will occur. Common z
ones use
same delay as partition 1.

UL installations: For UL Commercial Burglar Alarm and UL
Residential Burglar Alarm installations with line security,
total exit time must not exceed 60 seconds.

SIA Guidelines: minimum exit delay is 45 seconds.


*35
Entr
y Delay 1 (*35), Entry Delay 2 (*36)

*36
00
- 96 = 0 -
96 seconds; 97 = 120 secs; 98 = 180
secs; 99 = 240 secs

V21SIALTE
:
30
-96 = 30 -
96 secs;

97 = 120 secs; 98 = 180 secs; 99 = 240 secs

NOTE: Entries less than 30 will result in a 30-
sec delay.

Upon entering, the system must be disarmed before the
time entered expires, otherwise it sounds an alarm.
Common zones use same delay as partition 1.

UL Installations:
For UL Residential Burglary Alarm
installations, must be set for a maximum of 30 seconds;
entry
delay plus dial delay should not exceed 1 min. For
UL Commercial Burglar Alarm, total entry delay may not
exceed 45 seconds.

SIA Guidelines: minimum entry delay is 30 seconds

*37
Audible Exit Warning

0 = no; 1 = yes

Warning sound c
onsists of slow continuous beeps until the
last 10 seconds, and then it changes to fast beeps. Sound
ends when exit time expires.

SIA Guidelines: must be enabled (enter
1
)

V21SIALTE:

Feature always enabled; field does not
exist.


*38
Confirmation Of Arming
Ding

0 =
no ding; 1 = confirmation ding after arming system

2 = ding after arming from RF button or RF keypad only

(except 5827/5827BD)

Confirmation of arming is 1/2-
sec external sounder “ding.”

If
1
selected, ding oc
curs when closing report is sent
if
open/close reporting is enabled, or at the end of Exit
Delay
. If
2
selected, ding occurs upon reception of the
wireless arming command.

UL Installations: must be

1
for UL Commercial Burglar
Alarm insta
llations.

SIA
Installation: must be enabled with a 2, 2.


*39
Power
-Up In Previous State

0 = always power
-up in a disarmed state

1 = assume the system status prior to power down
When the system powers up armed, an alarm
will occur 1
minute after arming if a zone is faulted.
Note that if the previous state was armed Away or Stay, the
system
ignores
sensor changes for 1 minute, which allows
sensors such as PIRs to stabilize.

UL Installations: must be
1
(power
-up in previous state)

SIA Guidelines: must be 1
V21SIALTE:

Feature must be enabled.


Dialer Programming (

40


50)

*40
PABX Access Code or Call Waiting Disable

Enter
up to 6 digits if PABX is needed to access an
outside line. Do not fill unus
ed spaces. 0
–9, # + 11 for ‘

’,
# + 12 for ‘#’, # + 13 for a pause (2 seconds)

To clear entries from field, press

40

. If fewer than 6
digits need to be entered, exit by pressing [

].
Call Waiting:
If the subscriber’s phone service has “call
waiting” (an
d is not using PABX), enter “*70” (“# + 11”)
plus “# + 13” (pause) as the PABX entry to disable “call
waiting” during control panel calls. If the subscriber does
not have “call waiting” and is not using PABX, make no
entry in this field.

NOTES:

1. The cal
l waiting disable feature cannot be
used on a PABX line. 2. Using Call Waiting Disable on a
non-call waiting line will prevent successful communication
to the central station.

V21SIALTE:

If call waiting is used, enter call waiting
disable digits as descri
bed above, and also set Call
Waiting Disable option in field *91.


*41
Primary (*41) and Secondary (*42) Phone No.

*42
Enter
up to 20 digits. 0–
9, # + 11 = ‘

’, # + 12 = ‘#’,

# + 13 = pause (2 secs)

If entering fewer than 20 digits, exit by pressing [

] + next
field number. To clear entries, press

41

or *42*
respectively. Do not fill unused spaces.

NOTE:
Backup reporting (see field *49) is automatic only if
there is a secondary phone number (field

42).

Data Field Programming

27
*43
Primary/Secondar
y Account Numbers

*44
Enter 4 or 10 digits, depending on selection in
*45
*48 Report Format field. Enter 0–
9; # + 11 = B,

*46
# + 12 = C, # + 13 = D, # + 14 = E, # + 15 = F.


*43:
Partition 1 primary. To clear entries:

43

.

*44:
Partition 1 secondary.
To clear entries:

44

.

*45:
Part. 2 prim. To clear entries:

45

.

*46:
Part. 2 second. To clear entries:

46

.

*47
Phone System Select

If Central Station Receiver
is

not
on WATS line:
0 = Pulse Dial; 1 = Tone Dial

If Central Station Receiver
is
on
WATS line:
2 = Pulse Dial; 3 = Tone Dial

Select the type of telephone service.


*48
Report Format (Primary/Secondary)

0 = 3+1, 4+1 ADEMCO L/S STANDARD

1 = 3+1, 4+1 RADIONICS STANDARD

2 = 4+2 ADEMCO L/S STANDARD

3 = 4+2 RADIONICS STANDARD

5 = ADEMCO 10
-d igit Contact ID®

6 = 4+2 ADEMCO EXPRESS
7 = ADEMCO 4
-digit Contact ID®

8 = 3+1, 4+1 ADEMCO L/S EXP.

9 = 3+1, 4+1 RADIONICS EXP.

Select format for primary/secondary phone numbers.


*49
Split/Dual Reporting

0 = standard/backup reporting only (see Backup Rep
orting
below)


To Primary No.

To Secondary No.

1 =
alarms, restore, cancel

others

2 =
all except open/close, test

open/close, test

3 =
alarms, restore, cancel

all
4 =
all except open/close, test

all
5 =
all
all
Backup Reporting:
All reports are sent only t
o the
primary number unless unsuccessful after 8 attempts. If
unsuccessful, the system will make up to
8 attempts to
send all reports to the secondary number. If still
unsuccessful after the 16 attempts, the system displays
the “COMM. FAILURE” message (FC for fixed-
word
displays).


*50
Burglary Dialer Delay

0 = no dial delay; 1 = 15 secs; 2 = 30 secs; 3 = 45 secs

UL: must be

0.

SIA Guidelines: delay must be minimum 15 seconds

V21SIALTE:

Delay Time:
1 = 15 secs; 2 = 30 secs; 3 = 45 secs

Delay Disable:

0 =
use delay set in entry 1

1 =
dial delay disabled for zones listed in zone list 6
(use zone list 6 to enter those zones that require
dial delay to be disabled; these zones ignore the
setting in entry 1)

UL: Dial delay plus entry delay must not exceed one
minute; use zone list 6 to disable dial delay from
appropriate zones, if necessary.


Provides delay of “BURGLARY ALARM” report to the
central station, which allows time for the subscriber to
avoid a false alarm transmission. This delay does not
apply to zone type 24 alarms (silent burglary) or to 24-hour
zone types 6, 7, and 8 (silent panic, audible alarm,
auxiliary alarm), which are always sent as soon as they
occur.

*53
SESCOA/Radionics Select

0 = Radionics (0-9, B
-F); 1 = SESCOA (0
-9 only)

Select SESC
OA or Radionics format.

Select
0
for all other formats.

*54
Dynamic Signaling Delay

0 = disabled (both signals sent);

1–15 = entry times a 15-second delay.
e.g., 1 = 15 seconds, 2 = 30 seconds, etc.

Intended for use with IP/
Cell
reporting.

This field le
ts you select the time the panel should wait for
acknowledgment from the first reporting destination
(primary
dialer or IP/
Cell;
see

55) before it attempts to
send a message to the second destination. Delays can be
selected from 0 to 225 seconds, in 15-se
cond increments.
This delay is per message. If
0
is entered in this field, the
control panel will send redundant reports to both Primary
Dialer and IP/
Cell.

NOTE:
If

55 is set to “0,” use minimum of
30 sec
onds
to
avoid redundant IP report.
However, this v
alue may need
to be adjusted (ex. 45 secs) depending on the reporting
environment.

UL Installations:

For UL Burglar Alarm installations with Line Security,
Dynamic Signaling Delay must be

0
. Reports will be sent
to both the dialer and the IP/
Cell
.


*55
Dy
namic Signaling Priority
/ AAV
Enable

0 = Primary Dialer first / using
AAV via phone line

1 = IP/
Cell
module first
for alarm reports / not using AAV


This field selects the primary communication path
(dialer
or communication device)
for reporting of prim
ary phone
number events

(see

49 Split/Dual Reporting) and
if
used, enables
AAV
(AAV sessions use
the phone line
only)
.

Use

29 IP/
Cell
menu mode to enable the communication
device being used.


Reports intended for the secondary phone number are
not sent via the communication device.


For Dynamic Signaling Priority:
Select the initial
reporting destination for messages as follows:

Primary Dialer First selected (
0
):

If acknowledged before delay expires (see

54), then
message will not be sent via LRR.


If not acknowledged before delay expires, message is
sent to both the Primary Phone No.
and via LRR.

Communication Device First (
LRR
) selected (
1
):

If acknowledged before delay expires, then message
will
not be sent to the primary dialer.


If not acknowledged before delay expires, message is
sent to both the Primary Phone No.
and via LRR.


For AAV Path Select:


If using the AVS system, option 0 (primary dialer first)
mus
t always be used; AAV sessions can occur only over
the phone line with this control.


*56

Zone Programming Menu Mode

For programming zone information.

See Zone Programming section for procedures.


*57

Function Key Menu Mode

For programming keypad function
keys.

See Function Key section for procedures.

NOTE:
For SIA Compliance, panic functions for the A, B,
and C function keys must be disabled, leaving the 1+*,
3+#, and *+# as panics.

Installation and Setup Guide


28
*58

Expert Zone Programming Menu Mode

For quickly programming zone inf
ormation, but is
recommended only for those already familiar with *56
menu mode. See Zone Programming section.


System Status Report Codes

Zone report codes are programmed using interactive

56
or

58 Zone Programming modes, while system status
(non-
alarm) codes and restore codes are entered in data
fields *59 -
*68, *70 -
*76, *89. The actual report code digits
that you enter depend upon the particular installation, and
should agree with the Central Station office receiv
ing the
signals.

3+1 or 4+1 Standard Format:
Enter a code in the first
box:
1–9, A, B, C, D, E, or F. Enter #+10 for A (this reports
a 0 on some receivers), #+11 for B, #+12 for C, #+13 for
D, #+14 for E, #+15 for F.

An entry of
0
in the first box disables
a report. Entering
0

in the second box advance to the next field.

Expanded or 4+2 Format:
Enter codes in both boxes
(first/second digits) for 1
–9 or A
–F, as described above. A
0
in the first box disables a report. A
0
in the second box
eliminates the expa
nded message for that report.

ADEMCO Contact ID® Reporting:
Enter a digit in the
first box to enable the zone to report. Use a different digit
for each zone until you have used up available digits. If the
number of zones exceeds the number of available digits,
begin with digit 1 again. This is an “enabling” code only
and is not the actual code sent to the Central Station
office. Entries in the second boxes are ignored. An entry of
0
in the first box disables the report.


U
L
Report codes are required in fields *61, *65, *71, *72, for
UL Commercial Burglar Alarm installations.


Report codes are required in fields *60, *62, *63, *64, *70, *73,
*74, *75, *76, for UL Commercial Burglar Alarm installations and
required for Residential Fire Alarm installations.


*59
Exit Error Report Code

0 = no report; 1-F = see description above

V21SIALTE
:
[1] Always enabled. Also see field *69.

After arming the system, entry/exit and interior zones
remaining open after exit delay expires cause an alarm
sound at the keypad and external sounder (keypad also
displays “EXIT ALARM”), and entry delay begins.
Disarming before the end of the entry delay stops the alarm
sounding and no message is sent to the central station.
The keypa
d will display “CA” (fixed
-word
) or “ALARM
CANCELED” (alpha display).


If the system is not disarmed before entry delay expires, an
“EXIT ALARM” message (
V21SIALTE:

also zone alarm
message) will be sent to the central station. The keypad
will
display “EA” (fixed
-word
) or “EXIT ALARM” (alpha display),
and alarm sounding continues until the system is disarmed
(or timeout occurs).


An Exit Alarm condition will also result if a fault occurs in an
exit or interior zone within
2 minutes following the end of
the exit delay, and an “EXIT ALARM” message will be sent
to the central station (except for
V21SIALTE
, see field *69
Recent Closing report).
With Contact ID format, the
message will contain the zone number and error
code 374
(“ALARM
–EXIT ERROR”).

*60
Trouble Report Code

(0 = no report; 1-F = see description above *59

Sent if a zone has a trouble condition. See UL System
Reporting Note above *59.


*61
Bypass Report Code

0 = no report; 1-F = see descripti
on above *59

Sent when a zone is manually bypassed. See UL System
Reporting Note above *59.


*62
AC Loss Report Code

0 = no report; 1-F = see description above *59

Timing of this report is random with up to a 4-hour
delay. If
AC restores before the report goes out, there is no “AC
LOSS
” report. See UL System Reporting Note above *59.


*63
Low Bat Report Code

0 = no report; 1-F = see description above *59

Sent when the system’s backup battery has a low
-battery
condition. See UL System Reporting Note above *59.


*64
Test Report Code

0 = no report; 1-F = see description above *59

Sent periodically to test that the communicator and phone
lines are operational. See System Reporting
UL Note above
*59. Frequency of report is set in Scheduling mode (event
11) or by the following key commands:


installer code + [#] + 0 + 0
= test report sent every 24 hrs


installer code + [#] + 0 + 1
= test report sent once per week


installer code + [#] + 0 + 2
= test report sent every 28 days

Each of these modes sets schedule 32 to the selected
repeat option; first test report sent 12 hours after
command†.

† NOTE:
Make sure the Real
-Time Clock is set to the proper
time
before
entering the test report s
chedule command to
ensure that test reports are sent when expected. (see Setting
the Real
-Time Clock section)


*65
Open Report Code

0 = no report; 1-F = see description above *59

Sent upon disarming the system in the selected partitions.
See UL System Reporting Note above *59.


*66
Arm Away/Stay Report Code

0 = no report; 1-F = see description above *59

This
option allows for independent programming of Away
and Stay reports for eac
h partition, including the common
lobby.

NOTE:
“OPEN” reports are not sent if the associated
closing report is not enabled.


*67
RF Trans. Low Batt. Report Code

0 = no report; 1-F = see description above *59

Sent when a transmitter low
-battery condition exists.
UL installations: must be enabled if wireless devices are
used.


*68
Cancel Report Code

0 = no report; 1-F = see description above *59

Sent upon disarming the system after an alarm condition
was reported.

V2
1SIALTE:
[10] Report enabled.


Data Field Programming

29
*69
Recent Closing Report
V21SIALTE
only

Always enabled. Field does not apply to other controls.

Similar to the Exit Error condition described in field *59,
but occurs if any burglary zone is faulted within two
minutes

after
the initial exit delay expires. Disarming the
system within the two minutes stops the alarm sound and
displays "ALARM CANCELED " or "CA
" and the faulted
zone number. No message is sent to the Central
Monitoring Stat
ion.

If the system is not disarmed within two minutes, the alarm
sound continues and a “recent closing” and a “zone alarm”
message are sent to the Central Monitoring Station (after
dial delay expires).

*70
Alarm
/Dynamic
Restore Report Code

0 = no report;
1-F = see description above *59

See UL System Reporting Note above *59.

Alarm restore signals indicate that respective alarm
zone(s) are no longer faulted. Alarm restore reports are
sent to the central station at bell timeout (field *33), if the
zone(s) in alarm are actually restored to a non-faulted
state at that time. Otherwise, alarm restore report(s) for
respective alarm zones are sent when the system is
disarmed.

Dynamic Restore:
Zone restore occurs when the zone returns to a norma
l
state or when alarm memory is cleared (system disarm twice). This allows
the faulted zone to send a new alarm if the zone faults a second time
without waiting for bell timeout.


Value

Alarm Restore
Report is Sent to
Central Station

Zone Restore
s...
0

No

a
fter bell timeout or disarm twice**

1

(also 5, 9, D) *

Yes

after bell timeout or disarm twice**

2

(also 6, A, E) *

No

upon restore of zone (dynamic
restore) or disarm twice**

3

(also 7, B, F) *

Yes

upon restore of zone (dynamic
restore) or disarm twice*
*




* Equivalent alternatives codes for formats other than ADEMCO Contact ID


** Upon clearing of alarm memory


NOTES:

1. Dynamic Restore applies to all zone types except Configurable Zones and
Monitor Zone Type.

2. The number of times a zone can generate an alarm is controlled by the
following four data fields:

Field

Title

Program Values to allow unlimited alarms


31

Single Alarm
Sounding per
zone

Set to 0 -
Unlimited


50

Burglary Dialer
Delay

Must be 0 (No dialer delay), or multiple faults
during Dialer Del
ay will be ignored.


59

Exit error

Must be 0, or multiple faults will not occur
within 2 minutes of arming on Delay zones
and Interior Followers.


93

Reports per
Armed period

Set to 0 –
Unlimited reports



*71
Trouble Restore Report Code

0 = no report;
1-F = see description above *59

Sent when a zone
trouble is restored
and code + OFF
performed. See UL System Reporting Note above *59.


*72
Bypass Restore Report Code

0 = no report; 1-F = see description above *59

Sent when a zone that has been bypassed is unbypassed.
See UL System Reporting Note above *59.


*73
AC Restore Report Code

0 = no report; 1-F = see description above *59

Sent
after
AC power has been restored after an AC power
outage. S
ee UL System Reporting Note above *59.


*74
Low Bat Restore Report Code

0 = no report; 1-F = see description above *59

Sent
after
a system low
-battery condition is restored to
normal. See UL System Reporting Note above *59.


*75
RF Xm
tr Low Batt. Restore Code

0 = no report; 1-F = see description above *59

Sent when a transmitter’s low battery condition is restored
(i.e., new battery installed).

UL: must be enabled if wireless devices are used. See UL
System Reporting Note above *59.


*76
Test Restore Report Code

0 = no report; 1-F = see description above *59

This
is sent when the Test mode is exited
or upon timeout
.
See UL System Reporting Note above *59.

Miscellaneous System Fiel
ds

*77
Daylight Saving Time Start/End Month

0 = Disabled; 1 = Jan; 2 = Feb; 3 = Mar; 4 = April;
# + 10 = Oct; # + 11 = Nov; # + 12 = Dec

Enter the start and end month for daylight saving time, if
applicable to the region.


*78
Daylight Saving Time Start/End Weekend

0 = disabled; 1 = first; 2 = second; 3 = third; 4 = fourth;

5 = last; 6 = next to last; 7 = third to last

Enter the start and end weekend for daylight saving time,
if applicable to the region.


*79
Output Device Mapping Menu Mode

Use this menu mode to enter output devices/powerline
carrier devices into the system. See Output Device
Programming section for procedures.


*80
Output Programming Menu Mode

Use this menu mode to define output functions for use
with output devices/powerline carrier devi
ces. See Output
Programming section for procedures.


*81

Zone List Programming Menu Mode

Use the menu mode to define zone lists. See Zone List
Programming section.


*82
Alpha Descriptor Programming Menu Mode

Use this menu mode to assign alpha descriptors
to zones
and/or create partition descriptors.


*84
Auto
-Stay Arm

0 = no; 1 = partition 1 only; 2 = part. 2 only; 3 = both parts.

If enabled, the system will automatically change AWAY
mode to STAY mode if the entry/exit door
is not
opened
and closed within
the exit delay time after a user arms in
AWAY mode from a wired keypad (non-RF device). An
Opening report followed by an Armed Stay report is sent
to the Central Station.

If the door
is
opened and closed within the exit delay
period, the system remains in
AWAY mode.

Any RF device that arms the system AWAY overrides this
feature and the system remains armed AWAY.


*85
Cross Zone Timer

0 = 15 secs
4 = 90 secs

8 = 4 min

#+12 = 8 min

1 = 30 secs
5 = 2 min

9 = 5 min

#+13 = 10 min

2 = 45 secs
6 = 2-1/2 min

#+10
= 6 min

#+14 = 12 min

3 = 60 secs
7 = 3 min

#+11 = 7 min

#+15 = 15 min

Sets the maximum amount of time in which two cross zones
must be tripped in an armed system to send an alarm
message to the Central Station. If only one cross zone is
tripped during this time, a trouble message (CID code 380)
for that zone is sent to the Central Station. Assign cross
zone pairs in zone list 4.

This option not for use in UL installations.

NOTE:
Cross zoning takes effect only after Exit Delay
expires.

Installation and Setup Guide


30
*86
Cancel Verify
Keypad Display

0 = no “alarm canceled” display

1 = display “Alarm Canceled” when system is disarmed
after an alarm has occurred. (To clear the “ALARM
CANCELED” display, the user must enter the security
code + OFF again.)

This feature causes a “
ALARM CANCEL
ED”

display on
the LCD keypad under the following conditions:


After the kissoff of the cancel message to the Central
Station, indicating a successful transmission.


When an alarm is successfully canceled before the
Central Station received the Alarm message. E.g., if an
alarm is incorrectly triggered and the user presses code
+ OFF before the dial delay time has expired, the
message will never go out to the CS.



When the Cancel report is not enabled and the system
is disarmed:

a.
before
dialer delay expires (alarm report not sent)
message “Alarm Canceled” is displayed.

b.
after
dialer delay expires message “Alarm Canceled”
is not displayed
.

*87
Misc. Fault Delay Time

0 = 15 secs

4 = 90 secs

8 = 4 min

#+12 = 8 min

1 = 30 secs

5 = 2 m
in
9 = 5 min

#+13 = 10 min

2 = 45 secs

6 = 2-1/2 min
#+10 = 6 min
#+14 = 12 min

3 = 60 secs

7 = 3 min

#+11 = 7 min
#+15 = 15 min

Used with zones assigned to a configurable zone type with
fault delay on (configurable zone type digit “6”), and sets a
zone response time
of 15 seconds to 15 min. It can be
assigned to zones with sensors that provide a trouble
indication when an oil tank is low, or similar applications
for critical condition monitoring where a non-
alarm
response is desired.

UL: May only be used on non-
burglar alarm and non-fire
alarm zones when used on a fire and/or UL burglar alarm
installation.


*88
Program Mode Lockout Options

0 = standard *98 installer code lockout

1 = lockout [

] + [#] reentry after *98 exit (reentry via
installer code only)

2 = lockout all local programming after *98 exit (reentry via
downloader only)

The following table summarizes the Program mode
lockout options:


Exit

*88
Reentry By:

Command

Entry

Installer

Power
-up†

Downloader

*99
n/a
yes

yes

yes


*98
0
no
yes

yes


*98
1
yes

no
yes


*98
2
no
no
yes


pressing [

] + [#] within 50 seconds of power up


*89
Event Log Full Report Code

0 = no report; 1-F = see description above *59

If an Event Logging
selection is made in field

90, a
message can be sent to the central station receiver when
the log is 80% full. If the log becomes full, new messages
overwrite the oldest messages in the log.


*90
Event Log Enables

0 = no event logging; 1 = log Alarm and Restore; 2 = log
Trouble and Restore

4 = log Bypass and Restore; 8 = log Open/Close

x = log combination of events (add value of entries)

This system can record up to 100 system events in a
history log. At any time, the downl
oader operator can then
upload the log and view or print out all or selected
categories of the log. The downloader operator can also
clear the log. Event log can also be viewed at an alpha
keypad. The display/printout at the central station will
show the d
ate, time, event, and description of the
occurrences.

Data Entry Example: To select Alarm/Alarm Restore” and
“Open/Close”, enter 9 (1+ 8); to select all events, enter
#15.

*91
Option Selection
/ Remote Interactive
Services (RIS) Enable

Options

0 = none

1 = Bell Supervision Processing†

4 = using Audio Alarm Verification
(AAV) unit

8 = Enable Exit delay restart/reset ††

V21SIALTE
:
Entry 1 Options:
Same as above.

Entry 2 Call Waiting Disable / RIS Enable:

0 =
call waiting not
used

1 =
use call waiting disable digits (

70) entered in field

40; (when selected, the system dials the entry in

40 only on alternate dial attempts; this allows
proper dialing in case call waiting service is later
canceled by the user).

2 =
RIS (Remo
te Interactive Services) enabled

3 =
Call Waiting disable and RIS enabled


Select by adding the values of each option.
E.g., for both
AAV and Exit delay restart, enter # + 12 (4 + 8).


††
“Exit Delay
Restart/reset” option allows use of t
he [

] key to restart the
exit delay at any time when the system is armed STAY or INSTANT. This
feature also enables automatic exit delay reset, which resets exit delay if
the entry/exit door is re
-opened and closed before exit delay time expires
after arm
ing AWAY. Automatic Exit Delay Reset occurs only once during
an armed
AWAY
period.

IMPORTANT:
AAV should not be used when Paging or Alarm
Reports are sent to a secondary number unless the monitoring zone
option is used (which pauses calls). Otherwise, the call to the
secondary number by the communicator after the alarm report will
prevent the AAV from taking control of the telephone line, and the
AAV “Listen in” session cannot take place.


UL

UL installations using the AAV feature must use the
Honeywell
Home
AVS system.

Exit Delay Restart/Reset must be disabled.
SIA Guidelines: Exit delay should be enabled.



*92
Phone Line Monitor Enable

Entry 1
–Timeout:

0 = disabled; 1
-15 = 1 minute to 15 minutes respectively

(2 = 2 min, 3 = 3 min, etc.; # + 10 =10 min, # + 11 = 11 min,

# + 12 = 12 min, # + 13 = 13 min, # + 14 = 14 min, # + 15 = 15 min)

Entry 2
–Display/Sound:

0 =
keypad display only when phone line is faulted.

1 =
keypad display plus keypad trouble sound when line is
faulted.
Each partiti
on turns off its own trouble sound. No
automatic timeout.

2 =
Same as “1” plus programmed output device STARTS.
If either partition is armed, external sounder activates. External
sounder will be turned off by normal bell timeout, or by security
code plus O
FF from either partition (it does not have to be the
one that was armed).
Data Field Programming

31
*92
Phone Line Monitor Enable (continued)

Entry 1:

Sets the length of time a phone line fault must
remain after detected before the second digit option is
activated.


Entry 2:

Selec
ts the desired phone line fault response.

Option 2 may be used even if a relay unit or Powerline
carrier device is not connected to the control.

If option 2 used, programmed Output Device must either
be programmed to be STOPPED in field

80 or STOPPED
by e
ntry of [security code] + [#] + 8 + device number.
Partition in

80 should be set to “0,” for STOP.

UL

Field *92 must be enabled for fire alarm installations, UL
commercial burglar alarm installations and UL residential
burglar alarm installations.


If the control unit is used on a UL commercial burglar alarm
system which requires 2 methods of remote communication,
then the control unit’s DACT and the other method of signal
transmission must monitor each other against communication
failure and line fault. T
he fault must be received and
annunciated within 200 seconds of its occurrence.

*93
No. of Reports In Armed Period
per Zone
(Swinger Suppression)

0 = unlimited number of reports

1 = 1 report pair
per zone per armed period

2 = 2 report pairs per zone per armed period

Selection limits the number of alarm/alarm restore
message pairs per zone sent to the CS in an armed period
and applies to burglary zones only.

SIA Guidelines: Must be set for option 1
or 2.


V21SIALTE
:
Report Pairs:
1 = 1 report pair; 2 = 2 report pairs

Unlimited Reports Enable:

0 =
restrict reports to the setting in entry 1

1 =
unlimited reports for zones listed in zone list 7;
(use zone list 7 to list zones that require unlimited
reporting; these zones ignore the setting in entry 1)



*94
Download Phone Number
Enter up to 20 digits as follows: 0–
9, # +11 for “

”,
# + 12 for “#”, # + 13 for a pause.

Enter the phone number of the downloading computer.

Do not fill unused spaces. End
field by entering

. To
clear entries from field, press

94

.
UL
Up/downloading via phone
line may be performed
only if a technician is at the site.


Up/downloading via the Internet has not been
evaluated by UL.


*95
Ring Count For Downloading

0–15 = number of rings before control picks up phone line.

Refer to the chart below and program accordingly.

phone

answer

down
-

module

machine

loading

Set field

95 to...
yes

no
no
1- 14 (not 0)

yes

yes

no
higher than num
ber of rings
set on answer machine (e.g., if
ans. machine is 4 rings, set
this field to 5). This allows
access to the phone module if
the answer machine is off.

yes

no
yes

1- 14 (not 0)

yes

yes

yes

15 (bypasses answer
machine

)
no
no
no
0
no
yes

no
0
no
no
yes

1- 14

no
yes

yes

15


*96
Command to Initialize CSID and Subscriber
Account Number
Use this command, if necessary, to reset all subscriber
account numbers and the internal CSID to the factory
default values.


*97
Command to Reset System to Factory
Def
ault Values

Pressing

97 resets all data fields to the factory default
values (shown on the Program Form).

IMPORTANT:
Do not press

97 to load defaults if any
programming has been done previously
—data already
programmed into the system will be changed!


*98
Command to Exit Program Mode (with
installer code lockout)

Exits Programming Mode and prevents re-entry by:
Installer Code
+ [8] + [0] + [0].
To enter the programming mode if

98 was used to exit,
you must first power down the s
ystem. Then power up
again, and press [

] and [#] at the same time, within 50
seconds of powering up. See field *88 for other Program
mode lockout options.


*99
Command to Exit Program Mode

Exits Programming Mode and allows re-entry by: Installer
Code
+ [ 8] + [0] + [0]
or by: Pressing [

] and [#] at the
same time, within 50 seconds of power
-up.


Pager Programming
Fields

The system can send various reports to up to four
pagers.

To program pager reporting, do the following:

1. Enter the pager phone number(s), preface characters, and
pager report options in data fields *160 -
*171:

2. Enable Pager Delay, if desired, in field *172 (delays
alarm reporting for ALL pagers).

3. Mak
e sure appropriate user open/close pager reports
are enabled (see Security Codes, Assigning Attributes
in
Section 6. System Communication and
Operation
). Users that perform actions in partition 1
will, if enabled, attempt to report to all pagers enabled
for open/close reporting in partition 1. Users that
perform actions in partition 2 will, if enabled, attempt to
report to all pagers enabled for open/close reporting in
partition 2.

4. If using latchkey pager report, define the latchkey
report schedule using
Scheduling mode (master code
+ [#] [6] [4] then select event type
03
). System must be
armed for the Latchkey report to be sent.

5. If using a function key to manually send a message to
a pager, use *57 Function Key
Menu mode to define
the key (function
01
).

6. If reporting zone alarms and troubles to a pager, use
*81 Zone List menu mode to assign the zones
associated with each pager (zone lists 9-12).
Installation and Setup Guide


32
*160
Pager 1 Phone No.

Enter
up to 20 digits.

If entering fewer than 20 digits, exit by pressing [

] + next
field number. To clear entries, press

160

.


*161
Pager 1 Characters

Enter up to 16 characters.

Up to 16 optional characters may be sent as a prefix to the
7-digit system status code sent to Pager #1 (i
f used).
Phone number in field *160 must have been entered. If
fewer than 16 characters, exit by pressing [

] and next field
number. To clear entries: press

161

.
The 16 characters may be composed of the following:

PIN number, Subscriber account number,


(enter # + 11 to send

), # (enter # + 12 to send #),
Pause (enter # + 13 to allow a 2-second pause),


special character(s) the user may decide to transmit

† Some paging systems require pause(s) before the prefix.

The Pager format for the 7-digit status c
ode is defined as
follows: XXX
-YYYY where:

XXX
= 3-digit event code:
911 = Alarm, 811 =
Trouble, 101 = Opening (disarm), 102 =
Closing (arm AWAY)
YYYY
= 4-digit user or zone number (depending on type
of event). The first digit indicates partition (0 = sy
stem, 1
= part 1, 2 = part 2, 3 = common), followed by the 3-
digit
user or zone number.

Display Example 1. 911
– 1004
Indicates an alarm
(911) caused by a fault in zone 4 (0004) in part. 1.

Display Example 2. 102
– 2005
Indicates the system is
reporting a clo
sing
–system arming (102) by User 5 (0005)
in partition 2.


*162
Pager 1 Report Options

0 = No reports sent; 1 = Open/close for all users enabled
to page†; 4 = All alarms and troubles

5 = All alarms, troubles, and open/close for
all users
enabled to page
12 = Alarms and troubles for zones entered in zone list 9
13 = Alarms and troubles for zones listed in zone list 9
and open/close for all users enabled to page
Enter the types of reports to be sent to Pager 1 for each
partition.

† For users enabled for paging.
Reports to pager only when
arming (close)/disarming (open) from a keypad using a security
code; auto-
arming/disarming, arming with assigned button, and
keyswitch arming do not send pager messages.

*163
Pager 2 Phone No.

up to 20 digits

If entering fewer than 20 digits, exit by pressing [

] + next
field number. To clear entries, press

163

.


*164
Pager 2 Characters

up to 16 characters

See field

161 for explanation of entries. If fewer than 16
characters, exit by pressing [

] and next field number. To
clear entries, press

164

.


*165
Pager 2 Report Options

See pager 1 reports, field *162 for entries, except use
zone list 10


*166
Pager 3 Phone No.

Enter
up to 20 di
gits

If entering fewer than 20 digits, exit by pressing [

] + next
field number. To clear entries, press

166

.

*167
Pager 3 Characters

Enter up to 16 characters

See field

161 for explanation of entries. If fewer than 16
characters, exit by pressing [

] and next field number. To
clear entries, press

167

.


*168
Pager 3 Report Options

See pager 1 reports, field *162, except use zone list 11


*169
Pager 4 Phone No.

Enter
up to 20 digits

If entering fewer than 20 digits, exit b
y pressing [

] + next
field number. To clear entries, press

169

.


*170
Pager 4 Characters

Enter up to 16 characters

See field

161 for explanation of entries. If fewer than 16
characters, exit by pressing [

] and next field number. To
clear entries, pre
ss

170

.


*171
Pager 4 Report Options

See pager 1 reports, field *162, except use zone list 12


*172
Pager Delay Option for Alarms

0 = none; 2 = 2 minutes; 1 = 1 minute; 3 = 3 minutes

This field determines the delay of alarm reports to the
pager. This giv
es the Central Station enough time to verify
the alarm report that it received, before the dialer attempts
to dial the pager.

This delay is for ALL pagers in the system


Miscellaneous System Fields

*174
Clean Me Option

0 = disable; 1 = enable

This is a ma
intenance feature for ESL 2-
wire smoke
detectors on Zone 1. If used, this option limits the number
of smoke detectors to a maximum of 10, rather than 16.
To enable the “clean me” feature, a time response setting
of “3” (1.2 seconds) must be entered in

56
Zone
Programming for zone 1.


*177
Device Duration 1, 2
0 = 15 secs

4 = 90 secs

8 = 4 min

#+12 = 8 min

1 = 30 secs

5 = 2 min

9 = 5 min

#+13 = 10 min

2 = 45 secs

6 = 2-1/2 min

#+10 = 6 min

#+14 = 12 min

3 = 60 secs

7 = 3 min

#+11 = 7 min

#+15 = 15 min

These
entries set the duration for output action options 5
(duration 1) and 6 (duration 2) programmed in

80 Output
Function Programming.


*181
50/60 Hz AC Operation

0 = 60 Hz; 1 = 50 Hz

Select the type of AC power applied to the control (option
is used for Rea
l-Time Clock synchronization)
Data Field Programming

33
Configurable Zone Type Fields

The system allows you to define up to four custom zone
types based on the options described at right.


All configurable zone types can be programmed via the
downloader.


Configurable zone types 90 and 91 can also be
programmed from a keypad using data fields *182-
*185.


IMPORTANT: Be careful when selecting combinations of
options for configurable zone types. Contradictory
options can cause unpredictable results.

UL installations: Do not configure zones as fire alarm or
UL burglar alarm zones.


*182
Configurable Zone Type 90

0-15 = values for each of 10 entries
(0-9, # + 10 = 10,
# + 11 = 11, # + 12 = 12, # + 13 = 13, # + 14 = 14, # + 15 = 15
)

Enter the appropriate value for each entry, 1-10, based on
the charts on the next page.
To calculate the value for
each entry, add the values of the selected options in each
of the entry’s columns shown in the respective chart (one
option per column). For example, to program entry 2 for
“alarm response to short,” “auto restore on,” but not a
“vent zone,” enter 5 (“1” for alarm short + “4” for auto
restore
-yes + “0” for vent zone-no).


*183
Zone Type 90 Report Code
s

90 ALARM ID: XXX

TR
OUBLE ID: XXX


Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to this
zone type. Use existing Contact ID® codes, if appropriate,
or define unique codes in CID code range 750-789. Press
[

] to accept and continue.

NOTE:
Zone alarm report codes (prompt in

56 Menu
mode) and trouble report code (

60) and relevant restore
codes (

70,

71) must be enabled in order for the
configurable zone type codes to be reported.


Important Notice on Report Code
s:
To avoid confusion
at the central station, it is recommended that existing
Contact ID® codes be used with configurable zone types
whenever possible. See list in
System Communication

section and/or check with the c
entral station for a
complete list of Contact ID® report codes. If none of the
codes are suitable, choose a code in the reserved range
of 750-789 and make sure to define the code with your
central station.


*184
Configurable Zone Type 91

0-15 = values for each of 10 entries (see field *182 for
explanation of entries.)


*185
Zone Type 91 Report Code
s

91 ALARM ID: XXX

See field *183 for explanation of
TROUBLE ID: XXX

entries and read the Important


notice on using these codes.


Configur
able Zone Type Options

Auto Restore
(entry 2): Faults on zones set for this option are
cleared; restore messages sent upon restoral of faults.

Vent Zone
(entry 2): Zones set for this option are ignored if
faulted when arming the system, but are protected i
f the zone is
later restored (e.g., an open window can be ignored when arming,
but if the window is later closed, it will be protected; opening the
window again causes an alarm.)

Bypass Disarmed
(entry 4): Zones set for this option can be
bypassed only whi
le the system is disarmed.

Bypass Armed
(entry 4): Zones set for this option can be
bypassed when the system is armed or disarmed.

Dial Delay
(entry 6): Alarms on zones set for this option
participate in dial delay central station reporting, if system dial

delay enabled in field *50.

Fault Delay
(entry 6): Faults on zones set for this option are
delayed
when the panel is in the Armed State by the time set in
field *87. Do not use this option if using entry/exit delay for this
zone type.

Faults Display
(entr
y 7): Selects how faults on zones set for this
zone type are displayed.

Power Reset/Verification

(entry 7): Selects whether the system
resets power (when user enters code + OFF), and whether the
system performs alarm verification (see description for zone type
16 in
Zone Type Definitions
section) when a fault occurs on
these zones.

Use Entry Delay

(entry 8): Selects whether to use the system’s
entry delay times.

Use Exit Delay

(entry 8): Selects whether to use the sys
tem’s exit
delay time.

Interior Type
(entry 8):
Zones set for this option are treated same
as standard zone type 4 (bypasses when armed STAY, faults
displayed).

Alarm Sounds
(entry 9): Selects the type of alarms sound for
zones
set for this zone type.

Bell Timeout
(entry 9): Alarm sounding on zones
set for this
option remain for the duration set in fields *32 / *33.

Fire Zone
(entry 9): Zones set for this option respond in the same
manner as if programmed for zone type 9. Do not set fire zones to
respond as
a “fault” in entries 1-
6.

Trouble Sounds
(entry 10): Selects the type of trouble sounds for
zones set for this zone type (periodic beeps = once every 30
seconds; trouble beeps = rapid beeping).

Chime Enable
(entry 10):
Zones
set for this option cause a chime
when Chime mode is on.


Installation and Setup Guide


34
Configurable Zone Type Charts

ENTRY 1


ENTRY 2

Response when system disarmed and zone is:

Auto

Restore


Vent Zone

Intact EOL

RF zone normal

Open

RF zone N/A

Shorted

RF zn off
-
normal

0 = normal

1 = alarm

2 = trouble

3 = fault
0 = normal

4 = alarm

8 = trouble

12 = fault

see note 5


0 = normal

1 = alarm

2 = trouble

3 = fault

see note 6

0 = no

4 = yes

0 = no

8 = yes

Entry 1 = EOL + Open


Entry 2 = Short + auto restore + vent zone


ENTRY 3


ENTRY 4

Response whe
n armed STAY and zone is:

Byp. when
disarmed

Byp. when
armed

Intact EOL

RF zone
normal

Open

RF zone N/A

Shorted

RF zn off
-
normal

0 = normal

1 = alarm

2 = trouble

3 = fault


0 = normal

4 = alarm

8 = trouble

12 = fault

see note 5


0 = normal

1 = alar
m
2 = trouble

3 = fault

see note 6

0 = no

4 = yes


0 = no

8 = yes


Entry 3 = EOL + Open


Entry 4 = Short + byp. disarmed + byp. armed


ENTRY 5


ENTRY 6

Response when armed AWAY and zone is:

Dial Delay

(see field *50)

Fault Delay

(see field *87)

Intact EOL

RF zone normal

Open

RF zone N/A

Shorted

RF zn off
-
normal

0 = normal

1 = alarm

2 = trouble

3 = fault
0 = normal

4 = alarm

8 = trouble

12 = fault
see note 5


0 = normal

1 = alarm

2 = trouble

3 = fault

see note 6

0 = no

4 = use delay


0 = no

8 = use delay


see note 1

Entry 5 = EOL + Open


Entry 6 = Short + dial delay + fault delay



ENTRY 7


ENTRY 8

Display Faults

Power Reset/

Verification

Use Entry

Delay 1/2

Use Exit

Delay

Respond as
Interior Type

0 = show alarms
when armed
& di
sarmed
1 = don’t show
alarms when
armed
(show
alarms, trbles,
faults when
disarmed)

3 = never show
any alarms,
trbles, faults

0 = no

4 = power reset
after fault


(with code +
OFF)

12 = verification

(see zone
type 16)


0 = no

1 = delay 1

2 = delay 2

0 =
no

4 = use exit
delay

0 = no

8 = yes


see note 2

Entry 7 = fault display + power
reset/verification


Entry 8 = entry delay 1/entry delay 2 + exit delay +


interior zone type


ENTRY 9


ENTRY 10

Alarm Sounds

Use Bell
Timeout

Respond as

Fire Zone

Trou
ble
Sounds

Chime when Chime
Mode

On

0 = none

1 = steady
keypad

2 = steady bell
and keypad

3 = pulsing bell
and keypad

0 = no

4 = yes


see fields *32,
*33
0 = no

8 = yes


see zone type
09; see note 4


0 = none

1 = periodic
beep

2 = trouble
beeps

0 = no

4 = yes

Entry 9 = alarm sounds + bell timeout + fire zone


Entry 10 = trouble sounds + chime




Zone Conditions Represented
in Entries 1-6


Configurable Zone Type Notes


1.
Do not use the “fault delay” option
with a configurable zone type if it is
set for an entry or exit delay,
otherwise unpredictable results may
occur.

2.
To create an interior type zone,
select “respond as interior zone
type” (entry 8, interior type = yes),
and set zone response to “fault” in
entries 3-
4 to ensure fault displays;
do not set as “normal,” “alarm,” or
“trouble.”


3.
Do not set fire zones to respond as
a “fault” (entries 1-
6), otherwise
faults will not display unless the [

]
key is pressed.

4.
4219/4229 modules must use
EOLRs or unpredictable results may
occur.

5.
RF Zones: The “open” options in
entries 1, 3, and 5 are not
applicable for RF zones. Use the
“intact EOL” option for normal RF
zone conditions and “shorted” for
off-
normal RF zone conditions.

6.
a.
Zone-
Doubling/Double-
Balanced:
A short on either zone of a zone-
doubled pair or on a double-
balanced zone causes a tamper
condition.

b.
For double-
balanced zones, this
entry must be “0”.

c. For zone
-doubled zones,
both

zones of the dou
bled pair must
be assigned the same response
to a short.
Data Field Programming


35
Touch Screen Keypad (AUI) Enable

The system supports up to four
touch screen style
keypads (e.
g.,
6280, and Tuxedo
Touch Screen keypad).


NOTE:
Use of touch screen devices does not affect the
number of standard keypads supported.


*189
AUI Device 1
- 4 Enable

(for Touch
Screen Style Keypads)


For Touchscreen device usage
0 = disable

1 = partition 1

2 = partition 2

3 = partition 3 (common)


For Remote Services device usage

5 = part. 1 (auto-stay arm disabled)

6 = part. 2 (auto-stay arm disabled)

7 = part. 3 (common; auto-stay arm disabled)



Device Addresses:

Set
AUI addresses as follows:

AUI 1 address
= 1
AUI 2 address
= 2
AUI 3 address = 5
AUI 4 address = 6


To enable a touchscreen keypad, enter the option
corresponding to each touchscreen’s home partition.


Note for Remote Services Devices:
If using the Remote
Services feature of the communication device, select an
option 5-7, depending on the partition the Remote
Services device is associated with (these options
automatically disable auto-stay arming when the system is
armed from the respective Remote Services device).
Refer to the communication device’s installation
instructions for details on enabling the Remote Services
feature.

By default, the Total Connect (virtual) keypad will be set to
address 2 in the communicator programming.
To avoid a
“Setup/Programming” error message
, when installing
this
system for use with Total Connect 2.0, the suggested
input of 1,5,0,0 assumes this programming has been left
at default and assumes you have a touchscreen keypad
installed for partition 1 at address 1.

NOTE:
If using Remote Services (IP/
Cell
feature)
, one of
the touch screen (AUI) addresses may be used for
enhanced Remote Services feature set, though a physical
touch screen is not installed. See

29 Menu Mode section
for enabling Remote Services.


Remote Services Device Address:
Using an AUI device
address for Remote Services provides enhanced remote
services features, but an actual AUI device cannot use the
same address. If no AUI addresses are available (all four
AUIs are being used), Total Connect 2 cannot be used for
remote services.

Keypad Programming Fields

To enable keypads:

1. Set desired address at keypad (refer to keypad’s
instructions for setting the address).

2. Use data field program mode to enable keypad
addresses
, assign a par
tition, enable sound options in
fields *190-
*196 as shown in the table above.

3. If desired, use data field *198 to turn on the display of
the partition number.

4. Set the following keypad-related data fields as required
by the installation:

*21
Quick Arm
Enable,
*23 Forced Bypass, *84 Auto
STAY Arm

5. If using touch screen devices (AUI), enable each unit in
field *189 and set
appropriate
AUI address
es.

NOTE
S:

1. Options for keypad 1, address 16 are set by the factory
and cannot be changed.

2. Each keypad must be assigned a unique address,
starting at address 16

(address 16 is reserved for
keypad 1, which is automatically set to partition 1 with
all sounds enabled). Keypads programmed with the
same address will give unpredictabl
e results.

3. If using Remote Services (IP/
Cell
feature), one of the
keypad addresses may be used for limited Remote
Services features, though a physical keypad is not
installed. See

29 Menu Mode section for enabling
Remote Services.


*190
Keypad 2 Device Address 17

Entry 1 –
Partition Assignment:

For Touchscreen device usage
0 = disable

1 = partition 1

2 = part. 2
3 = part. 3 (common)


For Remote Services device usage

5 = part. 1 (auto-stay arm disabled)

6 = part. 2 (auto-stay arm disabled)

7 = part. 3 (
common; auto-stay arm disabled)


Entry 2 –
Sound Option:

0 = no suppression

1 = suppress arm/disarm and E/E/ beeps

2 = suppress chime beeps only

3 = suppress arm/disarm, E/E/ beeps and chime beeps


Entry 1:

Enter the partition in which the keypad is located.

Entry 2:

Enter the desired sound option for this keypad

Note for Remote Services Devices:
If using the Remote
Services feature of the communication device, select an
option 5-7, depending on the partition the Remote
Services device is associated with (t
hese options
automatically disable auto-stay arming when the system is
armed from the respective Remote Services device).
Refer to the communication device’s installation
instructions for details on enabling the Remote Services
feature.



Installation and Setup Guide


36
*191
Keypad
3 Device Address 18

See field *190 for entries and explanation.




*192
Keypad 4 Device Address 19

See field *190 for entries and explanation.




*193
Keypad 5 Device Address 20

See field *190 for entries and explanation.




*194
Keypad 6 Device Addr
ess 21

See field *190 for entries and explanation.




*195
Keypad 7 Device Address 22

See field *190 for entries and explanation.




*196
Keypad 8 Device Address 23

See field *190 for entries and explanation.




*197
Exit Time Display Interval

0 =
no display; 1-5 = seconds between display updates

If enabled, keypads display the exit time remaining after
arming the system, updated at the interval selected (i.e. if
the exit delay is 30 seconds and “2” is selected in this field,
the keypad display ref
reshes every 2 seconds, displaying
30, 28, 26, 24, etc.).

An interval greater than “1” may be necessary for some
older keypads to allow users time to enter key presses
between display updates.


TOUCH SCREEN DEVICE NOTE:
If using more than one
touch screen device with the system, leave field *197 Exit
Time Display Interval set to the default value “0.” The 628
0
automatically displays remaining exit time in one-second
increments.




*198
Display Partition Number

0 = no; 1 = yes

If selected, the partition number is displayed in the upper
-
left corner of the display. This is useful when using the
GOTO partition function.



*199
ECP Fail Display

0 = 3-digit display (“1” + device address
)
1 = 2-digit fixed
-display as “91”

Select “0” if usi
ng Alpha keypads and/or 3-digit Fixed
-Word
Display keypads. ECP faults will display “1” plus the device
address
(00-15) of device causing the fault (e.g., faults on
device 07 display as “107”).

Select “1” if using 2-digit Fixed
-Word
Display keypads (e.g.,
certain 6128 series keypads). If selected, ECP faults for all
devices will display as “91” on 2-digit displays, and “191” on
3-digit or Alpha keypads. Data Field Programming


37
SECTION 5

Menu Mode Programming


29 Menu Mode for IP and Cell Module Programming
This mo
de is for programming the Internet connection (IP) and optional LTE
-21V Module configuration,
collectively referred to as the Internal Device.

NOTE:
The Internal Device is automatically set to address 3 and cannot be changed.


The following section describes the programming of the Internal Device using an alpha keypad. Alternatively,
these options can be programmed via the AlarmNet 360 website. After programming is complete, the
control
must be registered
with AlarmNet
via the Internet connection
. Refer to
the Registration with AlarmNet section
for procedures.


IMPORTANT:
The use of the IP connection or the LTE
-21V module requires an AlarmNet
–I account. Please
obtain the account information from the central station prior to programming this module.


Using a
n Alpha Keypad as a 7720P Programming Tool

When programming IP/Cell features (with

29 menu
mode), the alpha keypad mimics the functions of the
7720P Programming Tool. See figure at right and
table below for 7720P key functions. Each key has
two possible
functions: a normal function and a
SHIFT function.


Normal functions:
The numeric values labeled
directly on the keys and the left
-hand functions
shown in diagram on the ABC keys. To perform a
normal key function, simply press the desired key.


SHIFT fu
nctions:
Those functions shown in
diagram above the numerical keys and the right
-
hand functions shown on the ABC keys. To perform
a SHIFT key function, press SHIFT key (D key), then
press the desired function key (shift function is
indicated by the lit REA
DY LED).





7720P Emulation Template for Alpha Keypads
Normal and SHIFT key Functions While in

29 Menu Mode

Key

Normal Key Function

SHIFT Key Function

(A) = BS/ESC

[BS]: Press to delete entry

[ESC]: Press to quit Program Mode


Also, can reset
EEPROM

defaults



(B) =

/


[

]: Scroll down programming

[

]: Scroll up programming

(C) = N/Y

[N]: Press for "NO" answer

[Y]: Press SHIFT
-
Y for "YES" answer

(D) = SHIFT

Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a ke
y is pressed. Press again
for each SHIFT function desired.

1/A

[1]: For entering the number 1

[A]: Used for entering C.S. ID number

2/B

[2]: For entering the number 2

[B]: Used for entering C.S. ID number

3/C

[3]: For entering the number 3

[C]: Used for

entering C.S. ID number

4/D

[4]: For entering the number 4

[D]: Used for entering C.S. ID number

5/E

[5]: For entering the number 5

[E]: Used for entering C.S. ID number

6/F

[6]: For entering the number 6

[F]: Used for entering C.S. ID number

7/S

[7]:

For entering the number 7

[S]: Press to display diagnostic status

8/T

[8]: For entering the number 8

[T]: Press to send TEST messages

9/X

[9]: For entering the number 9

[X]: Press to reset the IP/Cell

[

] / SPACE

[

]: Used to select programming option
s

[SPACE]: Not used

0

[0]: For entering the number 0


[#] / ENTER

[#] / ENTER: Press to accept entries

No SHIFT function





Active only when the "REVIEW?" prompt is displayed

Installation and Setup Guide


38
Internal Device (Ip and Cell) Default Values
The programming default values
for

29 Menu Mode are listed in the Table below.


OPTION

STANDARD DEFAULT VALUE

ACTUAL ENTRY

1

Internal Device

IP


2

Multi
-
Mode

disabled


3

Multi
-
Mode Address

?? (if Multi
-
Mode enabled)


4

Primary City ID

??


5

Primary CS ID

??


6

Primary Sub ID

??
??


7

Remote Access

N (disabled)


8

Keypad Address (for remote access)

?? (if Remote Access enabled)


9

Supervision

24 Hours


10

Cell Rollover Y/N

N (if Cell enabled)


11

Cell 24Hr Tst Y/N

N (if Cell enabled)


12

Old Alarm Time

10 Minutes


13

IP Fa
ult Time

00 Minutes


14

Cell Fault Time

00 Minutes (if Cell enabled)


15

Notify Panel Of

Neither Fault (if IP and Cell enabled)


16

Use DHCP Y/N

Y (if IP or IP/Cell enabled)


17

NIC IP Address

255.255.255.255 (if DHCP not used)


18

Subnet Mask

255.255
.255.255 (if DHCP not used)


19

Gateway IP Addr

255.255.255.255 (if DHCP not used)


20

DNS IP Addr.

255.255.255.255 (if DHCP not used)



Status and Contact ID Reporting Codes

The Internal Device (IP/Cell) sends status messages to the control panel for network connectivity failures. Trouble messages
are displayed on the keypad as “Check 103,” with status displayed as “LngRng Radio” followed by a 4-digit keypad display
status code, defined below.

Keypad Display Status Codes

CODE

DESCRIPTION

0000

Con
trol panel lost communication with internal device

0005

internal device has lost contact with AlarmNet

000F

internal device is not registered; account not activated

0019

Cell module shut down

0400

internal device Power
-
on reset AND the control panel

lost
communications with IP/Cell



Contact ID Codes (as displayed at 685) sent to CS via IP/Cell

CODE

DESCRIPTION

E339 C803

Power
-
on reset

E350 C951

Primary communication path failure (Ethernet) **

R350 R951

Primary communication path restore (
Ethernet) **

E350 C952

Secondary communication path failure (Cell) **

R350 C952

Secondary communication path restore (Cell) **

E355 C000

Module lost ECP communication with control

R355 C000

Module restore ECP communication with control

E353 C103

Long range transmitter fault trouble

R353 C103

Long range transmitter fault restore

E903 C0803

Application Code Update

R903 C0803

Application Code Update Success

E904 C0803

Application Code Update Failure

E365 C0803

Module Firmware Update Success

E
366 C0803

Module Firmware Update Failure


** reports only if IP and Cell enabled
Start

29 Menu Mode by pressing *29 while in Data Programming mode.

Note for remote services
:

When installing this system for use with Total Connect 2.0, DO NOT USE *29 PROG
RAMMING TO FULLY PROGRAM THE
COMMUNICATOR to avoid overwriting any Total Connect settings that may have been previously programmed.
Enter 1 to
enable IP/Cell, then the star key (*).
If you are installing this system with an IP connection, press 0 to exit
field *29
programming.
If you are installing this system with LTE
-21V
only (no IP connection), press 1 to enter program mode and
toggle the Internal Device option to Cell only.
Then exit *
29 programming by pressing 0.

ENABLE IP/Cell?

0=No, 1=Yes

Enable
INT IP/Cell?

0 = no, not using either IP or Cell; 1 = yes using IP and/or Cell module; [

] to continue

NOTE: Default = 1 (IP and/or Cell)


IMPORTANT:
If using an external communication device, first follow the instructions in the
Inadequate Signal Strength
paragraph in the
LTE
-21V Module Installation
section for
physical installation of an external communication device. When complete, enter 1 at this
prompt and enter 1-Prog at the next prompt. Then program the external device using the
Installation and Setup Guide included with the external communication device.

Note for remote services:
If using an IP connection, enable the IP/Cell option, press
the
star
key
[*] to continue and 0 to exit *29 programming menu.
DO NOT FULLY ENTER *29 MENU
MODE.
Then program *189 (See *189 for more information).

Fixed
-Word Keypad Note:
Although programming IP/Cell options cannot be done via a fixed-
word keypad, IP/Cell can be enabled by doing the following:
Enter

29

(to enter IP/Cell menu mode), then press
1 + [

] + [

]




1=PROG 2=DIAG

0=QUIT

Programming/Diagnostics Select

1 = Prog (program the IP/Cell options)

2 = Diag (enter diagnostic mode)

NOTE:
If using an external communicator, Diagnostic mode
option available only for communicators with firmwa
re version 2.4.16 or higher.

0 = Quit; return to data field programming mode

Menu Mode Programming


39
Internal Device Programming Prompts

The keys used to select and enter options now follow 7720P keypad emulation. Refer to the table on the previous page for
detailed key functi
ons. The following is a summary:

[

] = scroll the options of a particular prompt

[#] = accept the entry and move to the next prompt

[A] = backspace or shift
-
[A] for escape

[B] = scroll to next prompt or shift
-
[B] scroll to previous prompt

[C] = answer No or shift
-[C] answer Yes to prompt

[D] = shift key


Internal Device
IP

Internal Device Selection

Disable
– IP
– Cell
– IP & Cell

Select the desired type of internal device usage, IP and/or Cell (press [

] to scroll choices).

NOTE:
If re
configuring from IP only to Cell only via the 7720P (or the panel keypad) a “Forced
Server Update” is required.
Exiting programming causes the device to reset, once reset
press [0] via the 7720P (or the panel keypad). Or, from AN 360, perform a “Get Data”

command.

Note for remote services and the LTE
-21V:

If you are installing
this system with LTE-21V only (no IP connection), toggle the Internal Device
option to Cell only, then exit programming as follows without entering the Primary City ID at the
next
prompt:

After toggling to Cell Only: select Function Key D, then Function Key A, then select the pound
key (#) to exit at the
Review? Y/N
prompt.


Press [#] to continue




Multi mode

Disabled

Multi
-
Mode (email reporting)

Disabled =
no email reporting of events

4204 Sourced =
up to four types of events reported (relay numbers 1-4 report as events 1-4
respectively)

2-4204 Sourced =
up to eight types of events reported (first module’s relay numbers 1-4 report
as events 1-4 respectivel
y; second module’s relay numbers 1-4 report as
events 5-8 respectively)

Enhanced Reports =
Enables full panel status reporting via email and reporting to TC2 web
services. If used, RIS must be enabled in field *91; when enabled, address 25
is automaticall
y assigned.

[#] to continue


Select the desired multi mode option (press [

] to scroll choices).

This feature is available only after authorization for it is set via the web-based programming tool
on the AlarmNet 360 website.

Multi
-mode emulates 4204 Relay
Module outputs to send up to four (4204 sourced) or up to
eight (2-4204 sourced) reports of system events to the user via email (email address is entered
at the AlarmNet 360 website). Use the AlarmNet 360 website to customize event titles, if desired.
If enabled, a multi
-mode address must be entered in the next prompt.

Use *79/*80 Menu modes to program each emulated relay output to trigger a desired system
event that, upon occurrence, will be sent to the user’s email address.


NOTES:

1. Multi
-mode has not been evaluated by UL.

2. Multi
-mode (email notification) is intended as a convenience for the user, and does not
replace Central Station reporting of critical events (alarms, troubles, etc.).




Multi mode Addr

(12)

Multi
-
Mode Address

This prompt appears if Multi Mode is enabled.
12-15 =emulated 4204 Relay Module address.

25 = automatically assigned if Enhanced Reports selected

Select the desired address. If using “2-4204-
sourced,” the address of the second module is
automaticall
y assigned an address one higher than the first module’s address.

NOTE:
A 4204 Relay module address is required for multi
-mode purposes, but an actual 4204
Relay module is not used at the selected address.




Primary City ID

(??)

Primary City ID

NOTE:
Account information is provided by the central station administrator.

01-99 (decimal) = 2-digit primary city code





Primary CS ID
(??)

Primary CS ID

01-FE (HEX)
Enter the primary central station's system ID number,




Installation and Setup Guide


40
Primary Sub ID

(????)

Primary Subscriber ID

0001-9999 (decimal)

Enter the 4-digit customer account number.




Remote AccessY/N
(N)

Remote Access

This feature is available only after authorization f
or it is set via the web-based programming tool
on the AlarmNet 360 website.

[Y] = use remote services

[N] = do not use remote services

[#] to continue

Remote Services allow the end user to access their security system from their computer via the
remote services (ex. Total Connect) website. Most system functions can then be performed.


Keypad Address

(28)

Keypad Address (for Remote Access)

This prompt appears if remote access is enabled.
1, 2, 5, 6 = emulated AUI address

17-23 = emulated standard keypad a
ddress

For enhanced remote access features, choose an AUI address. If no AUI addresses are
available (all four AUIs are being used), choose an available standard keypad address (some
remote access features will be unavailable).

By default, the Total Connec
t (virtual) keypad will
be set to address 2.
To avoid a “Setup/Programming Error” message, when installing this
system for use with Total Connect 2.0, s
ee *189 for more information.

NOTE:
An AUI or standard keypad address is required for remote access pur
poses, but an
actual AUI device or keypad is not used at the selected address.




Supervision

24 Hours

Supervision

if using IP and/or Cell

if using IP only (not for Cell usage)


30 day


6 Min

24-hours


90 Sec


None (no supervision)


3 Min


75
Sec



1 hour

To scroll the choices: [

] key scrolls forward; [backspace] key scrolls backward
[#] to continue


The supervising station must hear from the IP/Cell at least once during the supervision period.
AlarmNet transmits a communications failure alarm to the central station if the supervision
message is not received within the period.


This selection sets the supervision timing for one of the following values:




Cell Rollover Y/N

(N)

Cell Rollover

Appears only if IP & Cell is selected as Internal
Device option.

[Y] =
all messages (including AlarmNet network supervisory messages) are sent over the Cell
network in the event of an Internet failure

[N] =
all messages (except AlarmNet network supervisory messages) are sent automatically
over the Cell n
etwork in the event of an Internet failure




Cell 24Hr Tst Y/N

N
Cell 24Hr Tst

Appears only if IP & Cell is selected as Internal Device option.

[Y] =
have a message sent once a day to verify Cell operation. A "secondary communication
path loss" message is generated if the message is not successfully delivered.

[N] = disable 24hr test




Old Alarm Time
10 Minutes

Old Alarm Time

The old alarm time sets how long an undeliverable alarm is retried for delivery to AlarmNet. If
the message is not validated, i
t is retried until the old alarm time is reached or the message is
validated. The choices available are:

10 Minutes


4 Hours


15 Minutes


8 Hours


30 Minutes


12 Hours


1 Hour


24 Hours


2 Hours


To scroll the choices: [

] key scrolls forward; [backspace] key scrolls backward
[#] to continue



Menu Mode Programming


41
IP Fault Time

(00 mins)

IP Fault Time

Appears only if IP or IP & Cell is selected as Internal Device option.

00-99 = time delay (in minutes) before the control notifies the central station that there i
s a loss
of contact with the network over the Ethernet (IP) connection.

0 = no delay (valid only If using IP only)

Must be two (2) minutes for UL installations.




Cell Flt Time
(00 mins)

Cell Flt Time

Appears only if Cell or IP & Cell is selected as Int
ernal Device option.

00-99 = time delay (in minutes) before the control notifies the central station that a loss of
contact with AlarmNet network has occurred.

0 = no delay (valid only if using Cell only)

Must be two (2) minutes for UL installations.


N otify Panel Of _

Neither Fault

Notify Panel Of

Appears only if IP & Cell is selected as Internal Device option.
Select from the following choices:



Neither Fault



Both IP and Cell must fail before fault code is sent (status code 4005 displayed); panel
recei
ves primary and secondary path failure messages. No message sent if only one or the
other path fails.

To scroll the choices: [

] key scrolls forward; [backspace] key scrolls backward


[#] to continue


NOTE:
IP failure will always be sent to the central station as Primary Path Failure, and Cell
failure will always be sent as Secondary Path Failure.

IP address information prompts

The following prompts appear only if IP or IP & Cell is selected as Internal Device.

It is recommended to use dynamically allocate
d IP addresses, but if fixed IP addresses are desired, contact your
network administrator for the appropriate information.

NOTE:
A valid IP address must be entered in each prompt before the system continues to the next prompt.
Entries
cannot be left with
the default values.


Use DHCP Y/N

(Y)

Use DHCP

[Y] = have the IP addresses dynamically allocated (recommended), skip to Review prompt.

[N] = use fixed IP addresses; continue with next prompt

[#] to continue




NIC IP Address

255.255.255.255
NIC IP Addr
ess

Enter the 4-part IP address for this device, separating each part with a space ([

] key, displayed
as periods).
[#] to continue




Subnet Mask

255.255.255.255
Subnet Mask

Enter the 32-
bit address mask used to indicate the portion (bits) of the IP address that is being
used for the subnet address, separating each part with a space ([

] key, displayed as periods).
[#] to

continue




Gateway IP Addr

255.255.255.255
Gateway IP Addr

Enter the 4-part IP address assigned to the Gateway, separating each part with a space ([

]
key, displayed as periods). If unused set to 0.0.0.0.


[#] to continue




DNS IP Addr

255.255.255.255
DNS IP Addr

Enter the 4-part IP address assigned to the DNS (Domain Name System) server, separating
each part with a space ([

] ke
y, displayed as periods). If unused set to 0.0.0.0.

[#] to continue



Installation and Setup Guide


42
Review? Y/N


Review (and Exit

29 Menu mode or Reset Defaults)

You can review the

29 Menu mode options to ensure that the correct responses have been
made. When satisfied with entr
ies, select [N] to exit

29 Menu mode.

To review prompts or exit

29 Menu mode:

[Y] =
review prompts and entries, starting with Internal Device. Use the up/down arrow keys to
scroll through the program fields without changing any of the values. If a value requires
change, simply type in the correct value. When the last field is displayed, the “REVIEW?”
prompt again appears.

[N] =
Exit *29 menu mode and return to data field programming mode. The prompt briefly
displays “DONE” before returning to data field m
ode prompt “Enter

or #.”

[#] to accept Y or N selection (# alone exits same as N)


To reset

29 Menu mode defaults:

Press [ESC] at the Review prompt to display the “Reset Factory Defaults” prompt.

[Y] =
reset

29 menu mode options to factory values; if s
elected, all programmed

29 Menu
mode options are reset to the factory settings

[N] =

cancel reset defaults function

Menu Mode Programming


43
Programming IP/Cell Options via AlarmNet 360 Website

To program the IP/Cell options via the AlarmNet 360 website (if you are already si
gned up for this service), go to:
www.alarmnet360.com

Log in and follow the on
-screen prompts.

Please have the following information available:

1. Primary City ID (two
-digit number)

2. Primary Central Station ID (two
-digit hexadecimal number)

3. Primary Subscribe
r ID (four
-digit number)

4. MAC ID and MAC CRC number (located on the outside of box and on label inside module) or MIN number of
the device you are replacing
5. Mode of operation of existing module if replacing a "C" series radio.

After programming is complete, you must transfer the data to the module and the module must be registered.
Refer to the Registration section for details.

IP/Cell Diagnostic Commands (

29 Menu Mode)

Diagnostic commands can be used to quickly view your Internet and Cell connectivity set
tings and options. For
each command (except [

] and [0]) press the [shift] key and then the designated command key. For example,
press [shift] then [1/A] to display the software revision screen.


To enter Diagnostic mode:

1. Press

29 while in data field
programming mode.

2. Enter “1” at the “Enable IP/Cell” prompt then press [

].
3. Select “2” (Diag) at the next prompt.

4. Enter the desired command at the “Sel Key Command” prompt.

For subsequent commands, enter the next command at the currently display
ed screen.


To exit Diagnostic mode, press ESC (shift
-[A]).


Key

Prompt

Function


[A]
INTERNAL IP/Cell

x.x.xx mm/dd/yy


Software Revision

"x.x.xx" indicates the installed software Revision. Mm/dd/yy indicates month, day and year of the
revision.


[B]
MAC xxxxxxxxxxxx
MAC CRC yyyy


MAC, SCID, IMEI
“xxxxxxxxxxxx” indicates the IP/Cell’s unique identification number. Yyyy indicates the 4 digit MAC CRC
needed to enroll the device in AlarmNet 360.

[

] to go to SCID.


SCID xxxxx xxxxx
xxxxx xxxxx

Only if Cell or IP/Cell enabled. Displays the identification number assigned to the SIM card (SCID) in
this device.

[

] to go to IMEI.


IMEI xxxxxxxx
Xxxxxx x

Only if Cell or IP/Cell enabled. Displays the identification number assigned to the Cell module in this
device.

[

] returns to MAC.


[C]
Mon 01 Jan 2006
05:48:39 am


Time

Retrieves the current date and time from the AlarmNet network in Greenwich Mean Time (GMT). This
display confirms that the module is in sync wi
th network.


[D]

Physical Link

Good/Bad

Physical Link

Only if IP or IP/Cell enabled. Indicates whether the device has detected a physical connection to the
internet. [

] to continue to NIC IP address.


NIC IP Address

xxx.xxx.xxx.xxx

IP Information Displays

Displays the IP address assigned to this device.

[

] to go to subnet mask.


Subnet Mask

xxx.xxx.xxx.xxx

Displays the 32-
bit address mask used to indicate the portion (bits) of the IP Address that is being used
for the subnet address.
[

] to go to gat
eway IP.


Gateway IP Addr

xxx.xxx.xxx.xxx

Displays the IP Address assigned to the Gateway.

[

] to go to DNS server IP.

DNS Serv IP

xxx.xxx.xxx.xxx

Displays the IP Address assigned to the DNS (Domain Name System) server.

[

] to go to encryption test.

Encryption Test
AES Passed!

Performs a self-
test of the AES encryption algorithm.
[

] to go to DHCP.

DHCP

OK

DHCP (Dynamic Host Configuration Protocol) indicates server is okay.

[

] returns to Physical Link prompt. Installation and Setup Guide


44
IP/Cell Diagnostic Commands (contin
ued)

LTE Status Displays


[E]

RAT SigQual REG
LTE/3G ***** X












Press the [space] key
to get to the next
screen.
Press the [backspace]
key to go to the
previous field.
Cellular Status Display Screen 1
RAT

Radio Access Technology. – LTE or 3G

SigQual
– Signal Quality (1-
5 “*”)

REG
– Registration status where “x” can be:


RSRP
:

Greater than -
85dBm = 5 stars

-86dBm to
-95dBm = 4 stars

-96dBm to
-105dBm = 3 stars

-106dBm to
-115dBm = 2 stars

-
116dBm and lower = 1 star

RSRQ
:

Greater than -
10dB = 5 stars

-11dB to -
12dB = 4 stars

-13dB to -
14dB = 3 stars

-15dB to -
16dB = 2 stars

-
17dB and lower = 1 star


N – Not Registered
H – Registered Home
S – Searching

D – Registration Denied

R – Registered Roaming
? – Unknown Registration State
If the RAT is LTE, the number of stars is derived from received power (RSRP) and the received quality
(RSRQ). The lower number of stars of the two ratings is what is displayed as overall quality.

NOTE:
For adequate signal strength, must be 2 stars or more.



RAT RSRP RSRQ

XXXX XXXX XXXX

Signal Display for LTE

RAT

Radio Access Technology.
RSRP
– Reference Signal Received Power

RSRQ

Reference Signal Received Quality

Press the [space] key to get to the next screen.

Press the [backspace] k
ey to go to the previous field.


RSRP MIN MAX

XXXX XXXX XXXX


Min/Max Signal Display for LTE

RSRP
– Current Reference Signal Received Power
MIN
– Minimum Receive Signal Level

MAX
– Maximum Receive Signal Level

Press the [space] key to get to
the next screen.

Press the [backspace] key to go to the previous field.


RSRQ MIN MAX
XXXX XXXX XXXX


Min/Max Signal Quality Display for LTE

RSRQ

Current Reference Signal Received Quality

MIN
– Minimum Receive Signal Quality

MAX
– Maximum Receive Signal Quality

Press the [space] key to get to the next screen.

Press the [backspace] key to go to the previous field.


Cntry Netw TAC
XXX XXX XXXXX

Location Display for LTE

Cntry – Country Code

Netw – Network Code

TAC – Tracking area code

Press the [space] key to get to the next screen.

Press the [backspace] key to go to the previous field.

GCell Chan

XXXXXX XXXX

Cell Display for LTE

GCell – Global Cell ID
Chan – RF Channel number (EURFCN)

Press the [space] key to go to the next screen.

Press the [backspace] key to go to the previous field.


Band Mode

XXX XXXX

LTE Status Display Screen 5

Band – LTE Band Number

Mode – LTE Mode either FDD or TDD

Press the [space] key to go to Status Display Screen 1.

Pres
s the [backspace] key to go to the previous field.
Menu Mode Programming


45
Operating with 3G Service


[E]

RAT RSCP EC/No

3G
-xxx -
xxxxxx
Signal Display for 3G

RAT – Radio Access Technology.
RSCP –Received Signal Code Power

Ec/N0 – Carrier Noise Ratio (CNR)

Pres
s the [space] key to get to the next screen.

Press the [backspace] key to go to the previous field.


RSCP MIN MAX

xxxx xxxx xxxx

Min/Max Signal Display for LTE

RSRP – Current Reference Signal Received Power
MIN – Minimum Receive Signal Level

MAX – Maximum Receive Signal Level

Press the [space] key to get to the next screen.

Press the [backspace] key to go to the previous field.


Cntry Netw LAC
xxx xxx xxxxx

Location Display for 3G

Cntry – Country Code

Netw – Network Code

LAC – Local area code
Press the [space] key to get to the next screen.

Press the [backspace] key to go to the previous field.



Cell Chan PSC
xxxxxx xxxx xxx

Cell Display for 3G

Cell – Global Cell ID
Chan – Control Channel in use
PSC – Primar
y Sync Code

Press the [space] key to go to the next screen.

Press the [backspace] key to go to the previous field.



Second Site RSSI
Available

3G Status Display Screen 5

Secondary Site RSSI availability. Available or Not Available will be displayed.

Press the [space] key to go to Status Display Screen 1.

Press the [backspace] key to go to the previous field.


[F]


Testing Gateway

Redir 1


Network Diagnostic Test

Only if IP or IP/Cell enabled.
Performs a set of network diagnostics that tests the integrity of the links between the IP/Cell and the
various connection points (Redirs) to AlarmNet.



[S]


FLT

OK



Status request

OK = normal

i = IP off line

I = IP fault reported
g = Cell off line
G = Cell fault reported


[T]


Test Msg Sent



Test Alarm

Sends a Test alarm to AlarmNet. Functional for a registered IP/Cell only. If the device is not
registered, a message is displayed indicating that the command cannot be executed.



[X]


Reset CPU Y/N



Reset the IP/Cell.

[N] = return to diagnostic mode (blank screen = enter next command or escape).

[Y] = resets the module (blank screen = when reset complete, enter next command or escape).


[

]



Registering ...



Registration

(Shift-UP arrow)

Registers a programmed IP/Cell with AlarmNet. If it is confi
gured to report to AlarmNet, the IP/Cell will
register with AlarmNet.


[

]


Enter PIN#




Registration with PIN for Replacement Module (DN arrow)

Registers a programmed IP/Cell with AlarmNet if it is configured to report to AlarmNet.

[0]


Force Serv
er Update
Y/N



Force Upload of Configuration File to Server

[Y] = force the device to upload its entire configuration file to the server.

[N] = cancel the operation.

NOTE:
If the internet is not available, and the module is not initialized when you enter
this command,
the following screen will be displayed:

Cannot Upload

Try Later! _

Wait for the Signal Quality LEDs to light, indicating the module has completed its initialization, and try
again.

46
Registering the Control with AlarmNet
The control must be
registered with AlarmNet before internet communication (via IP or Cell) can occur.

To register, the control must be connected to the Internet.

Register the control by using one of these methods:


Register by phone

1. Call 1
-800
-222
-6525


You will need the
following information:



MAC ID and MAC CRC number (found on the label)



Subscriber information (provided by the central station), including a city code, CSID, and a subscriber ID



Activation ID (AID) and AID CRC numbers (found on the module’s label
or on its carton)

2. When instructed to do so, triple-
click the Test switch to complete the registration.


Register with AlarmNet 360 Website

To register via AlarmNet 360 Website, please go to: www.alarmnet360.com

Log in and follow the on
-screen prompts.
Please have the following information available:


Primary City ID (two
-digit number provided by central station)


Primary Central Station ID (two
-digit hexadecimal number provided by central station)


Primary Subscriber ID (four
-digit number provided by
central station)


MAC ID and MAC CRC number (located on outside of box and on label on control’s PC board)


Activation ID (AID) and AID CRC numbers (found on the module’s label or on its carton)

Once the control is registered, you may log out of the AlarmNet 360 website.


Register with Alpha Keypad using *29 Menu mode

1. Enter *29 Menu mode, select Diagnostic mode, then press Shift then [

] key (D key followed by the B key).
The registration message is sent (“Registering” displayed) and the control wait
s for the acknowledgment.

2. “Registration SUCCESS” displayed, indicating successful registration.


Register with Test Switch on control’s PCB (triple
-click)

1. Click the switch three times.

2. Watch the Cell Status LEDs: The Message (yellow) LED and the S
tatus (green) LED will blink slowly in
unison while registration is in progress.

3. When registration is complete, the Status (green) LED goes out.


Upload/Download via the Internet

This control supports upload/download programming capability via the Inter
net by using the AlarmNet network and
Compass downloading software. The control must be connected to the Internet (via the on-
board RJ45 connector or
LTE
-21V module), have all IP features programmed (

29 Menu mode), and be registered with AlarmNet. The
fol lowing is required at the Downloading Office:


Broadband Internet Access and Broadband (Cable/DSL) Modem


Broadband (Cable/DSL) Router (optional, if connecting more than one device to the Internet)


Computer running Compass Downloading Software version
that supports Internet upload/download for this
control.


To perform upload/download functions:

1. Connect the computer to the Internet and start the Compass downloading software.

2. Open the control’s account, then select the Communications function and
click the
Connect
button.

3. At the Connect screen, check that the control’s MAC address is entered and the TCP/IP checkbox is checked.

4. Click
Connect
. The Internet connection to the control is made automatically via AlarmNet.

5. Once connected, use the Compass downloading software as normal to perform upload/download functions.

Menu Mode Programming

47
Zones and Partitions

Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or
*
58
Expert Programming Mode.

The system can control two independent areas of protection (known as partitions) for use by independent users, if
desired, by simply assigning zones to one or the other partition during zone programming. The
system
, by defaul
t,
automatically distributes users between the two partitions. The master user can change the user number
distributions.

Zones can also be assigned to a common partition, which is an area shared by users of both partitions (such as a
lobby in a building).
This allows either partition to arm, while leaving the common partition disarmed for access
into the other partition. The following describes the functioning of the common partition:

• The common zone
sounds and reports alarms only when both partitions are armed. If only one partition is
armed, the system ignores faults on the common zone.

• Either partition may arm its system if the common zone
is faulted, but once armed, the other partition will not be
able to arm
unless the common zone is first bypassed or the fault is corrected.

• Faults on the common zone
are displayed on common zone keypads, and will also appear on another
partition’s keypad when that partition is armed.

• Either partition can clear and restore the common zone
after an alarm.


About Zone Programming (

56 and *
58 Menu Modes)


Used to program zones, zone types, report codes, enroll
5800 RF Wireless Transmitter serial numbers, and
identify
the type of loop input device(s).


Can also be used to enter alpha descriptors for programmed zones; however, we recommend entering
descriptors in menu mode
*
82 (
Alpha Descriptor
Programming

after all zone programming has been
com
pleted).


*58 Expert Programming mode provides a faster method of zone programming than *56 Menu mode, but is
recommended only for those who have had previous experience in programming controls of this type.


NOTE:
Alpha display prompts are shown in a double
-line box.



56 Zone Programming Procedure
1. Enter the zone number to be programmed.

2. Make appropriate entries at the prompts.

3. Confirm the serial number of wireless transmitter zones.


Start Zone Programming mode
by pressing
*56 while in Data Programming mode.






SET

TO CONFIRM?

0 = NO 1 = YES

Set to Confirm

0 = no; 1 = yes

If 1 (Yes) is entered, you will be prompted to confirm each transmitter after entering the serial
and loop numbers (at the “XMIT TO CON
FIRM” prompt later in this procedure).
We
recommend that you confirm the programming of every transmitter.
Installation and Setup Guide


48




Enter Zn Num.

(00 = Quit)

10

Zone Number

wired 01-08 (and 09-
48†); wireless 09-
48; RF button zones 49-64

91 = addr. device report enable; 92 = duress report enable;
95, 96, 99 =emerg. zones

[

] to continue; 00 to quit

† if zone expanders are used.


Enter the zone number that you wish to program. Zone 10 has been entered in the example
display at left.

Enter a report code for zone 91 to enabl
e addressable device reporting.

Enter a report code for zone 92 to enable duress reporting.

95, 96, 99 are emergency (panic) key zones.




Zn
ZT
P RC In: L
10 00 1 10
RF: 1

OR

Zn
ZT
P RC In: AD

10 00 1 10 AW: 07
OR

Zn
ZT
P RC
HW: RT

10 00 1 10 EL 1

Summary Screen

[

] to continue

A summary display appears.

“IN: L” appears for wireless zones and indicates input type and loop.

“IN: AD” appears for hardwire expansion zones (AW) and indicates the module’s address (AD),
which is based on the zone number.

“HW: RT” appears for hardwire zones and indicates configuration (EOL, NO, NC, zone
doubling, double-balanced) and response time
selection.







10 Zone Type

Perimeter

03


Zone Type (ZT)

See tabl
e below.

Each zone must be assigned to a zone type, which defines the way in which the system
responds to faults in that zone. Enter the Zone Type code from the list below:

Note:
If 00 is entered,
Delete Zone ?
will be displayed.

00 =
Not used

07 = 24-
Hr Audible
20 = Arm
–STAY*

01 = Entry/exit #1
08 = 24-
Hr Aux

21 = Arm
–AWAY*

02 = Entry/exit #2
09 = Fire

22 = Disarm*

03 = Perimeter

10 = Interior w/Delay

23 = No Alarm Resp

04 = Interior Follower

12 = Monitor Zone
24 = Silent Burglary

05 = Day/Night

14 = Carbon Monoxide**

77 = Keyswitch
06 = 24-
Hr Silent
16 = Fire w/Verify

81 = AAV Mon. Zone
*5800 button-
type transmitters only


90-
91 = Configurabl
e
** For wireless zones set for zone type 14,
use
only compatible wireless carbon monoxide detectors (ex. 5800C0)




10 Partition


1

Partition No. (P)

1-3 = partition (3 = common); [

] to continue

Enter the Partition number for this zone. Partition 1 is

shown entered.




10 Report Code
1st 01 2nd 00
10

Report Code

(RC
)

First Digit: 1
-9, 10 for 0, 11 for B, 12 for C, 13 for D, 14 for E, 15 for F

00 to disable

Second Digit: same as above; [

] to continue

Enter
the report code for this zone, which consists of 2 hexadecimal digits, each in turn
consisting of 2 numerical digits. For example, for a report code of “10,” enter
01

and
00
.
For Contact ID
®, e
ntering any non-zero entry as the first digit enables the report code for this
zone. Refer to the
System Communication
section for information about report codes and
formats.




02 HARDWIRE TYPE

EOL

0

Hardwire Type

0 = EOL; 1 = NC; 2 = NO; 3 = zn doubling
(ZD)
;
4 = dble-
balanced (DB)

[

] to continue


This prompt appears only for zone numbers 02-08.

Zone 1 is automatically set for EOL operation.




02 Response Time


1

Response Time

(RT)

0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 seconds; [

] to continue

This prompt appears only for hard-
wired zones 01-08 (zone 02 is the display shown).

Option 3: used for “clean me” option on zone 1 (see field

174).

NOTE:
If zone doubling is being used, the response time selected for zones 02-08
automatically applies to each zone
’s associated doubled zone.
Menu Mode Programming

49




10 INPUT TYPE

RF TRANS

3

Input Device
Type
(In)

2 = AW (Aux wired zone)

3 = RF (supervised RF transmitter
)
4 = UR (unsupervised RF transmitter)

5 = Button type RF transmitter (unsupervised).

[

] to continue

This prompt is skipped for zones 2-8, or 2-16 if zone-doubling was enabled at “Hardwire Type”
prompt.

All
of the RF transmitters have one or more unique factory
-assigned input (loop) ID codes. Each
of the inputs requires its own programmi
ng zone

(e.g., a 5804's four inputs require four
programming zones).
RF Transmitters can be enrolled as one of the following types:

Type

Description

RF

(Supervised RF)

Sends periodic check
-
in signals, as well as fault, restore, and low
-
battery signals.
The trans. must stay within receiver's range.

UR

(Unsupervised RF)

Sends all the signals that the “RF” type does, but the control does not
supervise the check
-in signals. The transmitter may therefore be carried
off
-
premises.

BR

(Unsupervised
Button RF)

Sends only fault signals. It will not send a low
-
battery signal until it is
activated. The transmitter may be carried off
-premises.


NOTE:


For the built
-in hardwired zones
, the Input Device type is automatically displayed as HW and
cannot be edited.


To change the input type of a previously programmed wireless device (type RF, UR, BR) to a
wired zone (type AW), you must first delete transmitter’s serial number (see To Delete A
Serial Number prompt on next page)




10 INPUT S/
N:
L
A022-
4064
1

Serial number Entry and Loop Number Entry

[

] to continue

Used only when enrolling wireless transmitters.

a. Transmit two open/close sequences. If using a button-type transmitter, press and release
the button twice, but wait ab
out 4 seconds before pressing the button the second time.
OR

b. Manually enter the 7-digit serial number printed on the label of the transmitter. Then press
the [

] key
– the cursor will move to the “L” position. You can edit the loop number, if
necessary
. When the loop number is acceptable, press [

].
c. Press key [C] to copy the serial number previously enrolled (used when programming a
transmitter with several input loops).




10 INPUT S/N
L
A022-
4064

?

Loop Number Change

[

] to continue
NOTE:
If the [C] key is used to copy the previously enrolled serial number, the cursor will move
to the Loop column (L) with the previous serial number displayed, and display a highlighted
question mark for the loop number.


Enter the loop number and pr
ess [

]. The system will now check for a duplicate serial/loop
number combination.




10 INPUT S/N
L


A022-
4064
1

Enroll Summary

[

] to continue

If the serial/loop number combination is not a duplicate in the system, a display showing the
serial number and loop number entry will appear.




XMIT

TO

CONFIRM

PRESS
*
TO SKIP


Confirmation Option

[

] to continue

This prompt will only appear if you answered “Yes” at the first prompt in this section.

The system will enter a confirmation mode s
o that the operation of the actual programmed input
can be confirmed.

Activate the loop input or button that corresponds to this zone.
Installation and Setup Guide


50




Entd A022-
4063 1
Rcvd A022-
4064 1

If Serial or Loop Numbers do not match after activating the transmitter


[

] to
continue

If the serial number transmitted does not match the serial number entered, a display similar to
the one shown appears. If the loop number does not match, it will also be displayed.

If so, activate the loop input or button on the transmitter once again. If a match is not obtained
(i.e., summary display does not appear), press the [#] key twice and then enter (or transmit) the
correct serial number.




10 INPUT S/N:

L
A000-
0000
0

To Delete a Serial No.

0 in loop number field = delete serial number; # = undo deletion; [

] to continue

To delete an existing serial number, enter 0 in the loop number field. The serial number will
change to 0's.
If 0 was entered in error, simply re-
enter the loop number or press [#], and the serial number
will return to the display.




Zn
ZT
RC
In:
L
10
03
10
RF: 1s

Summary Screen

[

] to continue

If the serial number transmitted matches the serial number entered, the keypad will beep
3 times and a summary display will appear, showing that zone's programming. Note that
an “s” indicates that a transmitter’s serial number has been enrolled.

Press [

] to accept the zone information and continue.




PROGRAM ALPHA?

0 = NO 1 = YES 0

Alpha Descriptor
s

0 =
no; 1 = yes; [

] to continue

If you want to program descriptors for zones now, enter
1
(Yes) and refer to the
Alpha
Descriptor

Programming

section for available descriptors
.




ENTER ZN NUM.

(00 = QUIT)
11

Next Zone Number

[

] to continue; 00 = quit

If 0 (No) was entered above, the system will return you to the ENTER ZN NUM. prompt for the
next zone.

When all zones have been programmed, enter 00 to quit.


Completing Zone Programming

When you have finished programming all zone
s, test each zone using the system’s TEST mode.



Do not use the Transmitter ID Sniffer Mode
for checking wireless transmitting devices
, as it will only check
for transmission of one zone on a particular transmitter, NOT the zones ass
igned to each additional loop.


NOTE:
Following the successful enrollment of each wireless device, note the device serial number in the
appropriate column on the ENROLLED TRANSMITTERS worksheet in the Programming Form; then enter the
other information (zone number, zone type, loop number, etc.) relevant to that device.




58 Expert Programming Mode
Procedures
This method is designed for use by installers with previous experience in programming ADEMCO control panels.
This mod
e is also used to program wireless keys using pre
-defined templates.


Start Expert Programming mode by pressing

58 while in Data Programming mode.






SET TO CONFIRM?

0 = NO 1 = YES 0

Confirm?

0 = no; 1 = yes; [

] to continue

This display appears upon entry into this mode.
The default is
0
(No).

If
1
(Yes) is entered, you will be prompted to confirm each transmitter after entering the serial
and loop numbers (at the “XMIT TO CONFIRM” prompt later).
Menu Mode Programming

51




Zn ZT P RC HW: RT

01 09 1 10 EL 1


Zn

ZT P RC IN: L

10 00 1 10
:RF –

Summary Screen

01-64 = zone number; [

] to continue; 00 =
quit

OR [D] to go to prompts for wireless key programming templates

A summary screen appears, showing zone 1’s currently programmed values.


Enter the zone number being programmed, then press [

], which displays a summary screen
for that zone. See next prompt (zone 10 in this example).


If programming a wireless key,
press the [D] key then skip to the Wireless Key Programming
Templates section following this section. When [D] is pressed, you can choose from a series of
preset templates for easy programmi
ng of wireless key zones.


When all zones have been programmed, press
00

at this prompt to quit this menu mode.




Zn

ZT P RC IN: L

10 00
1 10 RF

1

Zone Programming

ZT =
see Zone Type chart shown in *56 Menu Mode “Zone Type” prompt

P =
par
tition 1, 2, 3 (common); RC = 1 (send CID report); 0 (no report)

IN =
input type; L =
loop number

[

] to continue

A summary screen with the selected zone’s current programming appears.
Begin programming zone information as follows:


Enter Zone Type
(ZT), Partition (P), Report Code
(RC; 0
-9 only; use *56 mode to enter hex
codes), and Input Device Type
(IN)* sequentially, but not the Loop No. (L).


Use the [A] (Advance) and [B] (Back) keys
on the keypad to move the cursor within the
screen.


Use the [C] key to copy the previous zone’s attributes.



Press [

] to save the programming and continue to the serial number/loop number prompt. If
needed, you can press the [#] key to back up without saving.

* If HW (hardwired) or AW (Auxiliary) is entered for Input Device Type, the next screen will be
similar to the prompt shown, except that HW or AW will be displayed under “IN”.

If RF, BR, or UR is entered, a prompt for Seri
al and Loop number will be displayed, as follows.




10 INPUT S/N:
L


A X XX-
XXX



Serial number

S/N = serial number; L = loop number; [

] to continue

Manually enter the serial number
(found on the transmitter
label), by typing digits in the “X”
locations, using the [A] (advance) or [B] (back) keys as required. You can also perform two
open and close sequences; for button-type transmitters that means pressing and releasing the
button twice.

NOTE
: If you want to
copy the previous zone’s serial number, press the [C] key.

Press [

] to advance to the loop number, then enter loop number.

Press [

] to accept the existing serial and loop number and continue to the “Confirm” prompt
below. If necessary, press [#] to back

up and re
-
enter or edit the serial number.




10 INPUT S/N:

L
A000-
0000
0

To Delete a Serial Number

[

] to continue

To delete an existing serial number, enter
0
in the loop number field. The serial number will
change to all 0's as shown.

If
0
was entered in error, simply re-
enter the loop number, and the serial number will return to
the display.




10 XMIT TO C
ONFIRM

PRESS * TO SKIP

Confirm

[

] to continue

The prompt to confirm
appears. This prompt wi
ll only appear if the first prompt after entering
*58 was answered “Yes.” To confirm, activate the loop input or button that corresponds to this
zone.

The system checks for duplicate. If a duplicate exists, a long error beep will sound.
Press [#] to bac
k up and re
-
enter the serial and/or loop number.

Installation and Setup Guide


52




Entd A022-
4063

Rcvd A022-4064


If Serial or Loop Numbers do not match after activating the transmitter


[

] to continue

If the serial/loop number combination transmitted does not match the
serial and loop number
entered, a display similar to the one below will appear.
If the loop number does not match, it
will also be displayed.

If so, activate the transmitter’s loop input or button one or more times.
If a match is still not obtained (i.e., summary display does not appear), press the [#] key twice
and enter the correct loop input or, if correct, press [#] again and then enter the correct serial
number.




Zn ZT P RC In L

10 03 1 10 RF:

1s
Note that an “s” indicates
that a transmitter’s serial
number has been
enrolled.

Summary Screen

If the serial number transmitted matches the serial number entered, the keypad will beep 3
times and a summary display will appear, showing the programmed information for that zone.


Press [

] to begin programming the next zone. See first “Summary Screen” prompt paragraph
on previous page.


To exit this mode,

enter 00 at the Summary Screen prompt.


Wireless Key (Key Fob) Programming & Templates

This procedure programs the wireless keys,
but a key is not active for arming/disarming until it is assigned
to a user number

(see
System Operation
section, assigning attributes command).


To program a wireless key,
do the following:

1. Use Zone programming mode to manually program a zone for each button being used on the wireless key.



OR, use the Template program mode described below to automatically program each button (loop) to a zone
type based on the selected wireless key template number. Wireless key zone numbers range from zone 49-
64.


2. Enroll the wireless key serial number into the system.


3. Assign the wireless key to a user number if it is intended to arm/disarm the system. Refer to the assigning
attributes command in the
System Operation
section of the Installation Instructions manual.


Programming Wireless Key Templates

Enter this mode by pressing the D key while at the *58 Menu mode Summary Screen. The following prompts
appear.





TEMPLATE
?
1–6
1

Template Number

1–6 = 5834-4
templates



Enter Template
number 1–
6 (see chart on next page).


See the defaults provided for each template in the chart that follows these procedures.



Select from templates. Press [

] to display template (1 shown selected).
NOTE
: If necessary, press [#] to back up and re-enter template number.



Press [#] if you want to return to *58 Menu mode summary screen.




L 01 02 03 04
T 23 22 21

23

Template Display



When [

] is pressed, the selected template will be displayed.


Top line of display represents loop numbers; bottom line represents zone type assigned for
each loop.



Press [

] to accept template.




PARTITION


1

Partition

1 = partition 1; 2 = partition 2



Enter the partition in which the key is to be active, then press [

] to continue.




ENTER START ZONE

00 = QUIT

36


Start Zone Number



The system will search for the highest available consecutive 4-zone group (the four zones in
the case of the 5834-
4), and display the lowest zone number of the group.


If you want to start at a different zone, enter the zone desired, and press [

]. If that zone
number is displayed, the system has the required number of consecutive zones available,
beginning with the zone you entered. If not, the system will again display a suggested zone
that can be used.
If the required number of consecutive zones is not available at all, the system will display
“00”.


To quit this mode
and return to *58 Menu mode, enter 00 at t
his prompt.




Press [

] to accept.



Menu Mode Programming

53
INPUT S/N L

AXXX
-XXXX –


Serial Number



Manually enter the serial number printed on the label for the wireless key or press and
release the button to transmit its serial number.



Press [

] to accept the serial number. The system will check for a duplicate.



If necessary, press the [#] key to back up without saving, and re-enter the serial number.



Use the [A] key to move forward within the screen, and the [B] key to move backward.





XMIT
TO CONFIRM

PRESS

TO SKIP


Confirm

[

] to continue



If “Yes” was entered at the
SET TO CONFIRM?
prompt previously (see first prompt
following entry into the

58 Expert Programming Mode), the display on the left will appear.
Confirm serial and loop numbers by activating the wireless key.


IMPORTANT:

When confirmed, the key is not active for arming/disarming until it is assigned to a user number
(using the assigning attributes command, attribute “4”). See
System Operation
section for
procedure.




Entd A022-4063
Rcvd A022-
4064


Not Confirmed

[

] to continue

If the serial number transmitted does not match the serial number entered, a display similar to
the one shown will appear. If the loop number
does not match, it will also be displayed.

If so,

activate the button on the wireless key once again. If a match is not obtained (i.e.,
summary display does not appear), press the [#] key and then enter the correct serial number.

If the serial number transmitted matches the serial number entered, the keypad will beep 3
times and will return you to the Zone Number prompt to enter the starting zone for the next
wireless key.
Or you can return to *58 Menu mode by pressing 00 at the Zone Number prompt.


NOTE:
Following the successful enrollment of each wireless device, remove
ONE
of the serial
number labels from the device and affix it in the appropriate column on the ZONE
PROGRAMMING worksheet of the Programming Form; then enter the other information (zone
nu
mber, zone type, loop number, etc.) relevant to that device.

Wireless Key Predefined Default Templates




5834-4 Wireless Key

Transmitter



NOTE:
Some transmitters are not intended for use in UL install
ations.



For button Type Devices



For Button Type Devices

TEMPLATE 1

Loop

Function

Zone Type

TEMPLATE 4

Loop

Function

Zone Type


1
No Response

23


1
No Response

23

2
Disarm

22


2
No Response

23

3
Arm Away

21


3
Arm Away

21

4
No Response

23


4
Disarm

22
TEMPLATE 2

Loop

Function

Zone Type

TEMPLATE 5

Loop

Function

Zone Type


1
No Response

23


1
No Response

23

2
Disarm

22


2
Arm Stay

20

3
Arm Away

21


3
Arm Away

21

4
Arm Stay

20


4
Disarm

22
TEMPLATE 3

Loop

Function

Zone Type

TEMPLATE 6

Loop

Function

Zone Type


1
24-
hour audible

7


1
24-
hour audible

7

2
Disarm

22


2
Arm Stay

20

3
Arm Away

21


3
Arm Away

21

4
Arm Stay

20


4
Disarm

22
Installation and Setup Guide


54
About Output Device Programming (*79/*80 Menu Mode)


Output Devices:

The system supports up to 16 relays and/or Powerline Carrier devices (X
-10 devices) plus
2 built
-in trigger outputs in any combination. These 18 “outputs” are assigned to system
-
wide output numbers (01
-18). Use *79 Menu Mode to assign output numbers and map
them to dev
ice address
es.



Output Functions
:

The system also provides installer
-defined output functions, which can be assigned to any
of the physical outputs. Therefore, the action of any one of the outputs can be bas
ed on as
many of these functions as desired. This lets a single relay or
trigger
perform many
functions.


The controls support up to 48 output functions.


Use *80 Menu Mode to define output functions.



Relays and output devices are not recommended for l
ife safety applications.


NOTE:
When navigating the *79 and *80 menus: The [

] key is used to accept an entry and advance to the next
prompt. The [#] key is used to revert back to the last question to check or change an entry. Press [

] to go
forward agai
n.

Programming Output Devices
1. Use *79 Menu Mode to assign module and output numbers and map them to device address
es.


NOTE:
You must map output devices using *79 Menu Mode
before
you can use *80 menu Mode.

2. Use *80 Menu Mode
to create output definitions, which control the output devices, if desired.

3. Use *81 Zone List Menu mode to define zone lists for use with output devices if the device action is based on
more than one zone.


To program a device for manual activation (us
er code + [#] [7] / [#] [8] + 2
-digit device number) or for scheduled
automatic activation, simply map the device using *79 Menu mode.


To program a device to automatically activate upon a system event (or function key), use *79 Menu mode to map
the devic
e, then use *80 Menu mode to define the automated device action.


*79 Menu Mode: Output Device Mapping
Use this menu to assign Relay Module device address
es and specific relay numbers, and Powerline Carr
ier unit
numbers. The system is based on predefined module addresses for 4204
and 4229
modules. Refer to the table
shown at the “Module Address” prompt on the next page and set the modules’ addresses (via module DIP switches)
acco
rdingly.

The following table shows how these outputs are identified.

Output Identification

This output...

is identified by...

Relays

the Relay Module’s device address

and the relay position on that module (i.e. the physical relay
number
, 1
-
4, on that module).

Built
-
in Outputs

the output number assigned, 17 for Trigger 1 and/or 18 for Trigger 2.


Menu Mode Programming

55
Start Output Device Mapping
by pressing *79 while in Data Programming Mode.



79
Output Device
Menu Mode





ENTER OUTPUT NO.

00 = QUIT

xx

Device Output Number

01-18 = relays

[

] to continue; 00 to quit

This is the logical (or reference) relay number as used in the system. Relay
s are numbered 01-
16; the on-
board triggers are numbered 17 and 18 and can be progr
ammed for inverted output,
if required.




17 OUT NORM LOW

0 = NO 1 = YES

0


Output Normally Low
(p
rompt appears only for Triggers 17 and 18)

0 = no (standard default); 1 = yes
[

] to continue

Selecting
0
(no) sets the output level normally high (defau
lt setting).

Selecting
1
(yes) sets the output normally low.

Output Trigger 17 can be used for resetting 4-
wire smoke detectors

by connecting it to the
negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as zone
type 54,
fire zone reset, in *80 Menu mode.

After entry, display returns to Output Number prompt. Use *80 Menu mode to program the
function of the trigger.

† Power Reset:
This control does not automatically reset power to 4-
wire smoke detector
zones, so you must use a relay (e.g., 4204, 4229)
or on-
board trigger to reset power (also
required for fire verification).





XX OUTPUT TYPE
DELETE

0


Output Type

0 = delete; 1 = relay on 4204/4229
module; 2 = Powerline Carrier device (X
-10)

[

] to continue

Select whether this is a relay or a Powerline Carrier (X
-10) device.

If Powerline Carrier is selected, go to “A” prompt.

If relay is selected, skip to “B” prompt.

“A”

XX UNIT No.


yy
Unit Number
(p
rompt appears

if
X
-
10 is selected)


01-16 = predefined address

[

] to continue

Enter the unit code (set at the device) and press [

].
The system returns to the Output Number prompt.

“B”

XX MODULE ADDR

07-
15

yy
Module Address
(p
rompt appears

if relay is selected)


07-15 =
predefined address

[

] to continue

Enter the predefined address for this module as listed below. Make sure the module’s DIP
switches are set to the selected address.


NOTE:
If using Multi
-Mode (IP/
Cell
feature), select one of the 4204 addresses, though a
physical 4204 module is not installed. If using 2-4204 multi
-mode option, the second 4204
address is automatically one number higher than the first one selected. Make sure these
addresses are not used by physical 4204 modules that may be installed. If usin
g Multi
-Mode
Enhanced Reports option, RIS must be enabled in field *91; when enabled, address 25 is
automatically assigned. See

29 Menu Mode section for enabling Multi
-Mode.


Module Addresses

Address
Module



07
1st 4229 (with zones 09-
16)

08
2nd 4229
(with zones 17-
24)

09
3rd 4229
(with zones 25-
32)

10
4th 4229 (with zones 33-
40)

11
5th 4229 (with zones 41-
48)

12
1st 4204

13
2nd 4204

14
3rd 4204

15
4th 4204


Installation and Setup Guide


56




XX REL POSITION

1- 4
zz

Relay Position

1-4 = relay position

[

] to continue

This is the actual (or physical) relay number with respect to the Relay Module upon which it is
located. For 4204
modules, relay numbers are 1-4. For 4229
modules, relay numbers are 1-2.

The system returns to the Output Number prompt for programming the next device.


NOTE:
If using multi
-mode, program the relays to trigger on those system events t
o be sent to
the user’s email address. (4204 option = up to 4 events; 2-4204 option = up to 8 events) See

29
Menu Mode section for enabling Multi
-
Mode.



*80 Menu Mode: Defining Output Functions
Use this mode to program
output function definitions (up to 48 functions) that provide automated control of any of
the output devices, based on events occurring on individual zones or zones with certain zone types.
Each output
definition is identified by an output function number,
and includes the following components:


Output Definition Components

Component

Description

Output Function No.

A reference number that defines an output’s characteristics.

Activated By

Determines whether the initiating event occurs on a zone, a zone lis
t, or a zone type.

Event

Event that triggers the output action. Can be an event occurring on a specific zone number or a
zone list, or a specific zone type.

Partition

If the output is activated by zone type, this defines the partition in which the progra
mmed event is
to cause the device action.

Output Action

Defines the action of the relay device when the defined event occurs. Can close for 2 seconds,
stay closed until reset, continuously pulse (1-
second close-open-close-
open, etc.), toggle the
device st
ate, or activate for a defined duration (set in data field *177).

Output No.

Assigns this function to a specific output number (defined in *79 Menu Mode). This is the output
number that will perform this function upon the triggering event. Note that each defined function is
associated with only one output number. This means that if more than one output device needs to
perform this particular function, you need to define another output function number with the same
attributes, but assign the appropriate out
put number. (i.e. output devices can be assigned more
than one function number, but each function number can only be assigned a single output number.


For example,
if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output
number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:

Prompt

Entry

Output Funct. #
=
01 (assuming this is the first output function)

Activated By:

=
3 (zone number)

Enter Zn No.

=
04 (requires 2-
digit zone numbers)

Output A
ction

=
3 (continuous pulse)

Output Number

=
02 (device mapped in *79 Menu Mode)


Start Output Definition mode by pressing
*
80 while in Data Programming mode.



80
Output Function
Menu Mode





Output Funct. #

(00 = Quit)

01

Output Function No.

01-48 = output function number

[

] to continue; 00 to quit

Enter the output function number to be defined (or 00 to exit).




01 A E P Trig

?00 0 0 –
ZL=00

Summary Screen

[

] to continue

This screen displays a summary of the current output progra
mming (for this example, Zone List
has been selected-this is the default screen).
A
= Output Action;
E

= Triggering event;
P
= Partition;
Trig
= Trigger type


NOTE:
A question mark in the summary screen indicates that the device number shown has
not been
mapped. Use *79 Menu mode to map the device.

Menu Mode Programming

57




01 Activated By:

Zone List

Activated By

0 = delete

1 = zone list (go to “A” prompt)
2 = zone type (go to “B” prompt)

3 = zone number (go to “C” prompt;)

[

] to continue

Select where the initiating event for this output definition is to occur as follows:

If you enter “0,” the following prompt appears:

Delete?

Press 1 to delete this output definition. The system

0 = NO, 1 = YES

deletes the output function and any previous programming.



A


01 Zn List


1

Zone List
(p
rompt appears

if zone list was selected)

01-08 = zone list; [

] to continue

Enter the desired zone list number associated with this output number.

NOTE:
Do not use pager zone lists 09-12 in output definitions.

Enter the zone list event that
will activate this output.

Enter Event

0 = restore; 1 = alarm;
Alarm

1
2 = fault; 3= trouble

NOTE:
For alarm, fault, and trouble, an event on ANY zone in the list activates the output, but
ALL zones in the list must be restored before the output is rest
ored.

Press [

] to continue and skip to the “Output Action” prompt.



B


01
Enter Zn type

Perimeter

03

Zone Type
(p
rompt appears

if zone type was selected)

Enter the desired zone type associated with this output number. See below for a list of available
zone types.

CHOICES FOR ZONE TYPES:

00 = Not Used

05 = Day/Night

12 = Monitor Zone

01 = Ent/Exit #1

06 = 24 Hr Silent

14 = Carbon Monoxide††

02 = Ent/Exit #2

07 = 24 Hr Audible

16 = Fire w/verification
03 = Perimeter

08 = 24 Hr Aux

23
= No Alarm Response

04 = Interior Follower

09 = Fire

24 = Silent Burglary


10 = Interior w/Delay
77 = Keyswitch Zone



81 = AAV Monitor Zone



90-91 = Conf
igurable
CHOICES FOR

SYSTEM OPERATION:

20 = Arming–Stay

36 = **At Bell Timeout***

58 = Duress

21 = Arming–Away

38 = Chime

60 = AAV

22 = Disarming

39 = Any Fire Alarm

61 = AVS session begin §

31
= End of Exit Time

40 = Bypassing

62 = AVS session end
§
32 = Start of Entry Time
41 = **AC Power Failure

66 = Function Key†

33 = Any Burglary Alarm
42 = **System Battery Low
67 = Bell Fail


43 = Comm. Failure

68 = Telco Line Cut


52
= Kissoff

78 = Keyswitch Red LED


54 = Fire Zone Reset

79 = Keyswitch Green LED




** Use 0 (Any) for Partition No. (P) entry.

*** Or at Disarming, whichever occurs earlier.

Use *57 Menu Mode to assign the function key (function “07”)
.

†† when used with an output function, the carbon monoxide zone type activates upon CO alarms only. Does
not activate for trouble conditions.

§ automatically set when appropriate AVS Quick Command performed.


Note:
In normal operation mode:

Code + # +
7 + NN Key Entry
starts
Device NN.

Code + # + 8 + NN Key Entry
stops
Device NN.


Enter the partition in which this zone type will occur.

01 Partition

0 = any partition; 1 = partition 1;
Any partition

0
2 = partition 2; 3 = common

Press [

] to continue an
d skip to the “Output Action” prompt.


Installation and Setup Guide


58

C


01
Enter Zn No.


12

Zone Number
(p
rompt appears

if zone number was selected)

Enter the desired zone number associated with this output number.

Press
[
*
] to continue.

Enter the zone event that will activate t
his output.

01 Enter Event

0 = restore; 1 = alarm/fault/trouble

Restore

0
Press [

] to continue to the “Output Action” prompt




01 Output Action

Close for 2 sec

1

Output Action

0 = off

4 = Change Device State
1 = Close for 2 seconds

5 = Duration 1 (see data field *177)

2 = Stay Closed
6 = Duration 2 (see data field *177)

3 = Pulse on & off (1 sec ON, 1 sec OFF)

Enter the desired device action as listed above. Press the [

] key to continue.





Enter Output No.

R02

02

Output Number

01-16 = output no.
; 17-18 = on
-board triggers

Enter the device output number (programmed in *79 Menu Mode) you want associated with this
output. Press [

] to continue.




02 A E P TRIG

R02 1 1 3 ZL=00

Summary Screen

A summary screen appears showing the programmed settings.

Press [

] to continue.


About Zone Lists (*81 Menu Mode)

Zone lists let you group individual zones for use with certain system actions. The following table shows the
available zone lists and their purposes:

List No.

Use
d for...

Notes

1, 2

general purpose (GP)



Any list may include any or all of the system's zone numbers.


A zone list can be assigned to more than one output relay.


Zone List 4: When creating zone list 4 for cross zoning, include
only zones assigned to z
one types 3, 4, or 5. Do not include
zones that have delays (entry/exit zones, interior w/delay) or
24-hour zones, as these zone types may produce
unpredictable operation and may not function as intended.

See
field *85 for Cross Zone Timer option.


Zone List 6:
V21SIALTE
:

See field *50 for Dial Delay Disable
option.


Zone List 7:
V21SIALTE
:
See field *93 for Unlimited Reports
option.

3

chime
-
by
-
zone
(see field *26 to enable option)

4

cross zones (see note at right)

5

night stay zones

6

general purp
ose

V21SIALTE
: dial delay disable

7

general purpose

V21iPSIA
: unlimited reports

8

general purpose

9

zones that activate Pager 1

10

zones that activate Pager 2

11

zones that activate Pager 3

12

zones that activate Pager 4

Menu Mode Programming

59
Zone List Programming

1. Select an appropriate zone list number.

2. Add the desired zone numbers to be included in that list.

Start Zone List Program Mode by pressing
*
81
while in Data Programming mode.


*81 Menu Mode

Zone List No.

(00 = Quit)

01

Zone List Number

01-12
= zone list number; [

] to continue

Enter the Zone List Number to program (or 00 to quit). Press [

] to advance.

In the following displays, zone list 01 has been selected for programming.




01
Enter Zn Num.

(00 = Quit)

00

Zone Number

01-64 = zone numbers followed by [

] to accept each zone; 00 to continue

Enter each zone number to add to the zone list, followed by pressing [

] (example, 01

, 02

,
03

). After all zones are entered, press 00 to continue.

IMPORTANT:

Do not include fire zones in zone lists
that are used to STOP device actions.




01 Del Zn List?

0 = No 1 = Yes

0

Deleting Zone Lists

0 = don’t delete list; 1 = delete this zone list; [

] to continue

To delete the zone list, enter 1. All zones in the zone list will be delet
ed automatically and the
system returns to the Zone List No. prompt.

To save the zone list, enter 0.




01 Delete Zone?

0 = No 1 = Yes

0

Deleting a Zone

0 = don’t delete zones; 1 = go to next prompt to delete zones; [

] to continue

To save the zone lis
t, enter 0 and the system returns to the Zone List No. prompt.

To delete a zone or zones in a zone list, enter 1 to continue.




01 Zn to Delete?

(00 = Quit)

00

Delete the Zone

01-64 = zones to be deleted from list followed by [

] to accept each zone; 00
to continue

Enter each zone to be deleted from the list, followed by [

]. After all zones to be deleted are
entered, enter 00 to return to the Zone List No. prompt so that another list can be programmed,
if desired.

Installation and Setup Guide


60
About Function Keys (*57 Menu Mode)

The system provides the ability to program each of the four keypad function keys
to perform one of 12 system
operations. The end user can then activate the function by simply pressing and holding the programmed key for 2
seconds. Typical functions (listed below) include single-
button arming, turning lights on/off, or single-
button
paging.

To assign emergency key functions (function key option “00”), first program the respective emergency zone
number (9
5 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming
mode, then use *57 Function Key menu mode to assign the desired key.

To use a function key to activate a relay action (*57 Menu mode key function 07), use
*79 Menu mode to map the
output, and use *80 Menu mode to define the output’s action; select system operation type “66.”

To use a function key for a user macro, use *57 menu mode to activate the desired key, then define the actual
macro functions using the
user code + [#] + [6] [6] command.

Programming Function Keys

1. Assign the function key number and partition.

2. Select the desired function for that key.


Start Function Key Programming
mode by pressing

57 while in Data Programming mode.

NOTE:
For SIA Compliance, panic functions for the A, B, and C function keys must be disabled, leaving the 1+*,
3+#, and *+# as panics.


Press Key to Pgm

0 = Quit

0

Function Key

Press the desired function key, A
-D .
[

] to continue

0 = Exit this mode

Press the desired function key (A
-D) you
want to program.

NOTE:
A key programmed as a function
key is no longer available to be used as an
end-
user macro key or panic key.






Partition


1

Partition Numbe
r

1 = parti
tion 1

2 = partition 2

3 = common partition

[

] to continue


Enter the partition in which the function key is active.




Key "A" Func

Zone 95

00



† System defaults to
these function key
settings.



†† If Night-
Stay zones
are listed in zone list 5.

D
efine Key Function

00

= For the Function key selected, the functions
are pre-defined
as follows:


If A selected = Zone 95 (emergency key, same as [1] [

] pair)


If B selected = Zone 99 (emergency key, same as [

] [#] pair)


If C selected = Zone 96 (emergency key, same as [3] [#] pair)


If D selected = Single-button paging

01 =
Single
-button paging (sends a 999-9999 message to pager)

02 =
Display time

03 =
Arm AWAY (reports as User 00 if closing reports are enabled)
04 =
Arm STAY (reports as User 00 if closing reports are enabled)

05 =
Arm NIGHT
-STAY (reports as User 00 if closing reports enabled)

06 =
Step Arming (arms STAY, then NIGHT
-STAY
††
, then AWAY)

07 =
Output Device Command (for device programmed as system operation type 66
–function
key in *80 Menu Mode)

08 =
Communication
Test (sends Contact ID code 601)

09 =
Macro Key 1 (define macro by user code + [#] [6] [6] command)

10 =
Macro Key 2 (define macro by user code + [#] [6] [6] command)

11 =
Macro Key 3 (define macro by user code + [#] [6] [6] command)

12 =
Macro Key 4 (define macro by user code + [#] [6] [6] command)

[

] to continue


Enter the desired function for this key, 00 to 12, from the options listed. (00 selected for
example display shown at left). Press [

] to r
eturns to key number prompt with the next function
key letter displayed.


Menu Mode Programming

61
About Descriptor Programming (*82 Menu Mode)

The system lets you assign
zone descriptors for protection zones, keypad panics, and RF receiver supervision
faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196
words stored in memory (see a following page). In addition, up to 10 installer
-defined words can be added to those
already in memory, plus 3 additional words can be assigned as partition descriptors. Thus, when an alarm or trouble
occurs in a zone, an appropriate description for that zone's location can be displayed at the keypad.
Zone
descriptors are recommended for systems using Alpha di
splay keypads
.
NOTE:
You can enter zone descriptors when the zone is being defined in
*
56 Menu mode, but we recommend
you do it using
*82 Menu mode.



Programming Zone Descriptors (Menu Mode

82)

1. Enter index numbers for up to three words from the Alpha
Vocabulary List for each descriptor by following the
prompts.

2. Enter up to ten 10-
digit custom words, if desired, which can then be used in descriptors.


When defining descriptors:

Pressing...

Does This...

[6]

Accepts the entered index number and moves

the cursor to the next position for a descriptor.

[8]

Saves the entered descriptor and moves to the next descriptor.


Start Zone Descriptor Programming
mode by pressing *82 while in Data Programming mode.


Program Alpha ?
0=No, 1=Yes
00

Program Alpha

0 = no; 1 = yes; [

] to continue

The “Program Alpha ?” prompt will appear. Press 1 to continue.




Custom Words
?
0=No, 1=Yes
00

Custom Words

0 = no; 1 = yes; [

] to continue

The “Cus
tom Words
” prompt will appear.

Press 0 to program standard alpha descriptors from the fixed vocabulary. The system will then
automatically display the descriptor for zone 1.

Press 1 to define custom words (described later in “Adding Cu
stom Words”

section).




*

ZN 01


Summary Screen

[

] to continue

Note that this is a “Summary mode,” and that no entries can be made. Entries can be made only
when the display contains a flashing cursor, which signifies the “Entry m
ode.”

To exit the
Alpha descriptor mode, press


+ 0 + 0 at the summary display.




*

ZN 01




Flashing Cursor

[

] to continue

To delete or change the default descriptor for zone 1, press the same zone number (01).
This will
clear that descriptor and allow changes to be made at the flashing cursor.

NOTE:
If you do not wish to change the existing descriptor for zone 1, enter the next zone
number for which you wish to enter (or check) a descriptor. A summary display for that zone will
appear. You must then press [

] plus the same zone number again to gain access to the entry
mode (flashing cursor) for that zone.




*

ZN 01
B
ACK


First 3
-
Digit Index No.

see index for entries; [

] to continue

Press [#] plus th
e 3-digit number for the first word from the
Alpha Vocabulary
List
. Example: If
the descriptor for zone 1 is BACK DOOR. From the list, BACK = 013. Therefore, you would
enter #013. If you accidentally enter the wrong word, simply press [#] plus the correct 3-digit
number for the word you want.
Installation and Setup Guide


62

*

ZN 01
BACK




Accept First Word

6 = save word and go to next word in this descriptor; 8 = save word and go to next zone

Press [6] to accept the selected word and continue to the next word, or press [8]

if this is the
only word you are using for the descriptor.




*

ZN 01
BACK

D
OOR

Second 3
-
Digit Index No.

see index for entries; [

] to continue

Enter the 3
-digit number for the next word. In our example, the word is DOOR, whose number
is “057.” Enter # 0 5 7.




*

ZN 01
BACK

DOOR




Accept Second Word

6 = save word and go to last word in this descriptor;
8 = save word and go to next zone

Press [6] to accept the selected word and continue to the next word, or press [8]

if these are the
only words you are using for the descriptor.
When descriptor is finished, press [8] to save all words in memory.




*

Z N 01
BACK

DOOR


Summary Screen

[

] to continue

The flashing cursor will disappear, indicating that the word(s) are stored in memory for that
zone, as shown in the summary display at the left.

To enter a descriptor for the next zone, press [

]
plus the des
ired zone number. The summary
display appears. Repeat the previous steps to enter the descriptor for the zone.


Adding Custom Words
(will not be annunciated by a voice keypad)

You can
add
up to 10 installer
-defined words to the built
-in vocabulary, which can then be used when
programming zone descriptors. Each of the 10 words can actually consist of a
word string of one or more words,
but no more than
ten
characters
can be used for each word or word string.

When adding custom words, the keypad keys perform the following functions:

[4] Moves cursor one space to the left.

[6] Moves cursor one space to the right.

[8] Saves the new word in the system's memory.

1. Select
Custom Word mode (enter 1) when the prompt “
CUSTOM WORD ?
” is displayed.

2. Enter the number (01–
10†) of the custom word or word string to be created, corresponding to index numbers
245
- 254 respectively (for example, if you are creating the first custom
word or word-
string, enter 01, for the
second, enter 02, etc.). A cursor will now appear at the beginning of the second line.


† or 11, 12, 13 for partition 1, partition 2 and common lobby descriptors respectively. See Assigning Partition Descriptors parag
raph
below.


NOTE:
Custom words 8, 9, and 10 are “reminder words” that are programmed using Scheduling Mode.

3. Refer to the
Character List of letters, numbers, and symbols on a following page.


Press [#], followed by the two-
digit
entry for the first letter you would like to display (e.g., # 65 for “A”).


The cursor will then move to the right, in position for the next character.


To delete a character, simply enter the SPACE character (#32).

4. Repeat Step 3 to create the desired w
ord(s). Note that the “4” key can be used to move the cursor to the left, if
necessary. Remember, no word or word
-string can exceed 10 characters.

5. Press the [8] key to save the custom word(s) and return to the “
CUSTOM WORD ?
” display.


Repeat Steps 2–
5 for other custom words to be entered. To change a custom word, just overwrite it. If no more
are to be entered now, press [0] to return to the Descriptor entry. The custom word(s) will be automatically
added to the built
-in vocabulary.


Assigning Partition/Custom Message
Descriptors

You can assign a partition descriptor (up to 16 characters) for each partition plus the common lobby. The system
displays the appropriate partition’s word instead of “DISARMED READY TO ARM.”

Use the same
procedure as for adding custom words (described above), but use these word numbers in step 2:


11 = partition 1 ___________________________________________

12 = partition 2 ___________________________________________

13 = common lobby ________________________________________


Once a custom word is entered in any of these word locations (11
-13),
the system displays the appropriate
partition’s word instead of the default “DISARMED READY TO ARM” message.
Menu Mode Programming

63
ALPHA VOCABULARY LIST

(For Entering Zone Descriptors)



000
(Word Space)




– A –

001
AIR


002
ALARM



004
ALLEY


005
AMBUSH


006
AREA


007
APARTMENT


009
ATTIC



010
AUDIO



– B –


012
BABY



013
BACK



014
BAR


016
BASEMENT



017
BATHROOM



018
BED


019
BEDROOM



020
BELL


021
BLOWER


022
BOILER


023
BOTTOM


025
BREAK

026
BUILDING



– C –


028
CABINET


029
CALL


030
CAMERA

031
CAR

033
CASH


034
CCTV


035
CEILING


036
CELLAR


037
CENTRAL


038
CIRCUIT


040
CLOSED



046
COMPUTER


047
CONTAC
T



– D –


048
DAUGHTERS


049
DELAYED


050
DEN



051
DESK

052
DETECTOR



053
DINING



054
DISCRIMINATOR

055
DISPLAY


057
DOOR



059
DOWN


060
DOWNSTAIRS


061
DRAWER


062
DRIVEWAY


064
DUCT



– E –


065
EAST


066
ELECTRIC



067
EMERGENCY



068
ENTRY


069
EQUIPMENT


071
EXIT



072
EXTERIOR



– F –


073
FACTORY


075
FAMILY

076
FATHERS


077
FENCE


079
FIRE



080
FLOOR



081
FLOW


082
FOIL


083
FOYER


084
FREEZER


085
FRONT




– G –


089
GARAGE



090
GAS


091
GATE


092
GLASS


093
GUEST


094
GUN



– H –


095
HALL



096
HEAT


098
HOLDUP


099
HOUSE





– I –


100
INFRARED


101
INSIDE



102
INTERIOR


103
INTRUSION



– J –


104
JEWELRY



– K –


105
KITCHEN




– L –


106
LAUNDRY



107
LEFT


108
LEVEL


109
LIBRARY



110
LIGHT


111
LINE


113
LIVING



114
LOADING


115
LOCK


116
LOOP


117
LOW


118
LOWER



– M –


119
MACHINE


121
MAIDS


122
MAIN



123
MASTER



125
MEDICAL



126
MEDICINE


128
MONEY


129
MONITOR


130
MOTHERS


131
MOTION



132
MOTOR



– N –


134
NORTH


135
NURSERY



– O –


136
OFFICE



138
OPEN



139
OPENING


140
OUTSIDE


142
OVERHEAD



– P –


143
PAINTING


144
PANIC



145
PASSIVE

146
PATIO



147
PERIMETER


148
PHONE


150
POINT


151
POLICE



152
POOL



153
POWER



– R –


155
RADIO

• 156
REAR


157
RECREATION


159
REFRIGERATION

160
RF


161
RIGHT


162
ROOM



163
ROOF



– S –


164
SAFE

165
SCREEN


166
SENSOR


167
SERVICE


168
SHED



169
SHOCK


170
SHOP



171
SHORT


173
SIDE



174
SKYLIGHT


175
SLIDING



176
SMOKE



178
SONS


179
SOUTH


180
SPRINKLER


182
STATION


184
STORE


185
STORAGE



186
STORY


190
SUPERVISED



191
SUPERVISION


192
SWIMMING


193
SWITCH



– T –


194
TAMPER



196
TELCO


197
TELEPHONE


199
TEMPERATURE


200
THE
RMOSTAT


201
TOOL


202
TRANSMITTER



– U –


205
UP


206
UPPER


207
UPSTAIRS



208
UTILITY





– V –


209
VALVE

210
VAULT


212
VOLTAGE



– W –


213
WALL

214
WAREHOUSE


216
WEST


217
WINDOW



219
WING


220
WIRELESS



– X –


222
XMITTER



– Y –



223
YARD



– Z –


224
ZONE (No.)


225
ZONE



226
0


227
1


228
1ST



229
2


230
2ND



231
3


232
3RD



233
4


234
4TH


235
5


236
5TH


237
6


238
6TH


239
7


240
7TH


241
8


242
8TH


243
9


244
9TH


245
Custom Word #1


246
Custom Word #2


247
Custom Word #3


248
Custom Word #4


249
Custom Word #5


250
Custom Word #6


251
Custom Word #7


252
Custom Word #8


253
Custom Word #9


254
Custom Word #10

NOTE:
Custom words 8,
9, 10 are “reminder
words” that can be
programmed to displ
ay
using Scheduling Mode.


NOTE
:

Italicized
words followed by an asterisk indicate those words supported by the 6160V Voice Keypads


Bullet and
b
old

words
indicate those words spoken by the 6280W, 6280S, and Tuxedo Touch™ series keypads.

–––––––––––––––––––––––––––
CHARACTER (ASCII) CHART

–––––––––––––––––––––––––––

(For Adding

Custom Words)

32 (space)

33
!
34

35
#
36
$
37
%
38
&
39
'
40
(
41
)
42


43
+
44
,
45

46
.
47
/
48
0
49
1
50
2
51
3
52
4
53
5
54
6
55
7
56
8
57
9
58
:
59
;
60
<
61
=
62
>
63
?
64
@
65
A
66
B
67
C
68
D
69
E
70
F
71
G
72
H
73
I
74
J
75
K
76
L
77
M
78
N
79
O
80
P
81
Q
82
R
83
S
84
T
85
U
86
V
87
W
88
X
89
Y
90
Z
64
Programming Installer and User Schedules
The s
ystem provides
up to 32 schedules
, which can be used to automatically control 11 types of system events at
pre
-defined times. Some events are reserved for the installer only.

There are
16 schedules for use by the end-
user, 16 for use by the installer.


NOT
ES:


The master code can only access schedules 01-
16 and events 00
-07.


System clock must be set before schedules can be used.


Programmed schedules do not take effect until the next scheduled “start” time. (e.g., if programming a schedule
time window f
or 8AM to 5PM, the schedule does not take effect until 8AM after the schedule has been
programmed.)


Start Scheduling mode by entering installer code + [#] + [6] [4] while in normal operating mode.





ENTER SCHED NO.

00=QUIT

00
Schedule Number

01-16 = end-user schedules

17-32 = installer
-only schedules

[

] to continue

Enter the desired schedule number.




ENTER EVENT



NOTE:
Events 07 and 10
cause the keypad to
beep every 30 seconds
when messages are
displayed. Stop the
beeps by pressing any
key.


Ente
r Event

00 = clear event

05 = Forced Away Arming


01 = Relay On/Off

06 = Auto Disarm

02 = User Access
07 = Display “Reminder”

03 = Latch Key Report to Pager

10 = Display custom words
††

04 = Forced Stay Arming


11 = Periodic Test Report
†††


Press [

] to c
ontinue

Enter the desired event number for event you want to occur at a specified time.

Events 10-11 are reserved for the installer only.


Latch key report (option 03) is sent to all pagers in the user’s partition and is active only when
the system is arme
d (message sent is 777-7777). User must be enabled for paging (see User
Attributes in
System Operation
section).


† Forced bypass is automatically enabled regardless of setting in field *23.

†† If selected, system displays custom w
ords 8, 9, and 10 at defined time. Can be used as
installer’s reminder message to the end user.

††† See key commands in
Testing the System
section to quickly set periodic test reporting
intervals.




DEVICE NUMBER


XX

Device Number
(For event 01
-
relay o
n/off)

01-18 = device number; press [

] to continue

Enter the physical device number as programmed in

79 Menu Mode, then press [*] to continue
to the “Start” prompt.
Device numbers

17 and 18 designate built
-
in triggers 1 and 2 respe
ctively.




GROUP NUMBER


X
Group Number
(For event 02
-
user access)

1-8 = group number; press [

] to continue to the “Start” prompt




PARTITION


X
Partition
(For events 03
-
07, 10)

0 = all partitions; 1 = partition 1; 2 = partition 2; 3 = common

Press
[

] to continue to the “Start” prompt.




START SMTWTFS

HH MMAM
0010000

Start Time

01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; Days = place “1” under days

Press [

] to continue.

Enter the event’s start time and days of the week to occur.

To select days, position the cursor under the desired days using the [

] key to move forward,
then press “1” to select the day.
Menu Mode Programming


65

STOP SMTWTFS

HH MMAM
0010000


Stop Time
(For events 01
-
relay on/off; 02
-
user access; 03
-
latch key report)

01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; Days = place “1” under days

Press [

] to continue.

Enter the event’s stop time and days of the week to occur.

To select days, position the cursor under the desired days using the [

] key to move forward,
then press “1” to select the day
.




REPEAT OPTION

0 - 4
X

Repeat Option

0 = do not repeat; 1 = repeat weekly; 2 = repeat biweekly (every other week)

3 = repeat every third week; 4 = repeat every fourth week

Press [

] to continue.

Enter the desired repeat option for this schedule.

e.g.,
To make a schedule that happens everyday you would select all days with a repeat count
of 1. To make a schedule that runs for one week then stops, select everyday with a repeat
count of 0.




RANDOMIZE

0=NO 1=YES X

Randomize
(For events 01 and 11)

0 = no; 1 = yes
Press [

] to continue.

If selected, the scheduled start and stop times will vary within 60 minutes of the “hour” time. For
example, if a schedule is set to start at 6:15pm, it will do so the first time 6:15pm arrives, but on
subsequent days
it will start anytime between 6:00 and 6:59 p.m.


NOTE:
Do not use the random option if the start and stop times are within the same “hour”
setting, otherwise unpredictable results may occur (e.g., the randomized stop time may occur
before the start time)
.




AVS System Enable and Quick Programming Commands

Applies to an AVS system using an ECP connection to the control.


1. Install the AVS module according to its instructions.


2. Use one of the control’s AVS Quick Program commands as follows (see Quick Program Command Results below for
results of each command):




installer code + [#] + 0 + 3:
enable AVS operation without panel sounds on the AVST speaker




installer code + [#] + 0 + 4:
enable AVS operation and enable panel sounds on the AVST speaker

3. Use data field

55 Dynamic Signaling Priority to enable the reporting path for AAV communication.


4. To undo the Quick Command programming, use the following commands:




installer code + [#] + 0 + 5
: remove all options set by [#] + 03 quick command




installer code + [#] + 0 + 6
: remove all options set by [#] + 04 quick command


Quick Program Command Results

When either the #03 or #04 Quick Program command is used, the following are automatically programmed and no longer
available for other control
panel purposes.


Pre
-
Programmed

#03 Command

#04 Command

Output Function No.

(

80 mode)

46 (zone type 60, relay 15)

47 (zone type 61, relay 16)

48 (zone type 62, relay 16)



Same as #03 plus:

41 (zone type 14, relay 13)

42 (zone type 22, relay 13)

43 (zone type 39, relay 14)

44 (zone type 33, relay 14)

45 (zone type
36
, relay 14

Output Relay No.

(

79 mode)

15 (addr 11, relay pos 2)

16 (addr 11, relay pos 1)


Same as #03 plus:

13 (addr 11, relay pos 4)

14 (addr 11, relay pos 3)

Protection Zone

(

56/

58
mode)

4229 zn 48 (zt 81, addr 11)

Same as #03 command

Device Address

address 11 (AVS module)

Same as #03 command

Data Field

91

AAV enabled

AAV enabled


66
SECTION 6

System Communication and Operation


Panel Communication
with Central Station
This
system accommodates several formats for reporting alarms and other system conditions to the Central Station.
The process of a successful transmission consists of both the method of communicatio
n between the control panel
and the Central Station receiver; and the actual way the information is sent and displayed at the Central Station.

When the panel calls the Central Station receiver, it waits to hear a “handshake” frequency from the receiver to
confirm that the receiver is on-
line and ready to receive its message. Once the panel hears the handshake
it is
programmed to listen for, it sends its message. The panel then waits for a “
kissoff” frequency from the receiver
acknowledging that the message was received and understood.

If the handshake frequency is not given or is not understood by the panel, the panel will not send its message. Once
the handshake frequency is received and understood by the panel, the panel s
ends its message. If there is an error
in the transmission (the receiver does not receive a “valid” message), the kissoff frequency is not given by the
Central Station receiver.

The panel makes a total of eight attempts to the primary telephone number and
eight attempts to the secondary
telephone number (if programmed) to get a valid message through. If the panel is not successful after its numerous
attempts, the keypad displays COMM. FAILURE (on alpha keypads) or FC (on fixed-
word keypads).


Report Code
Formats
The following chart indicates the types of (handshake/kissoff) frequencies that the panel supports and the different
formats that can be sent with each.


FORMAT

HANDSHAKE

TRANSMITS DATA

KISSOFF

TRANS
MIT TIME

Low Speed

1400 Hz

1900Hz (10PPS)

1400 Hz

Under 15 secs

3+1, 4+1, 4+2




(Standard report)

Sescoa/Rad

2300 Hz

1800Hz (20PPS)

2300 Hz

Under 10 secs

3+1, 4+1, 4+2




(Standard report)

Express

1400

2300 Hz

DTMF (10 cps)

1400 Hz

Under 3 secs

4+2





Contact ID

1400

2300 Hz

DTMF (10 cps)

1400 Hz

Under 3 secs


The following table describes each format in greater detail.

FORMAT TYPE

DESCRIPTION

3+1 and 4+1

Standard Formats

Comprises a 3
-

(or 4
-
) digit subscriber

number and a single
-
digit report
code (e.g., Alarm, Trouble, Restore, Open, Close, etc).

3+1 and 4+1

Expanded Formats

Comprises a 3
-

(or 4
-
) digit subscriber number and a two
-
digit report code.
The first digit is displayed on the first line. On the second line, it is repeated
3 (or 4) times and is followed by the second digit. This is the “expanded”
digit.

4+2 Format

Comprises a 4
-
digit subscriber number and 2
-
digit report code.

ADEMCO Contact ID

Reporting Format

Comprises a 4
-

or 10
-
digit subscriber
number (depending on format
selected), 1-digit event qualifier (“new” or “restore”), 3-digit event code, and
3-digit zone number, user number, or system status number (see the
following page).

System Communication

67
The following table lists codes for reports sent in different formats:


Code for

Code for

Type of

3+1/4+1
3+1/4+1
Code for

Report

Standard

Expanded

4+2
Alarm
SSS(S) A
SSS(S) A
SSSS AZ


AAA(A) Z

Trouble

SSS(S) T

SSS(S) T

SSSS Tt



TTT(T) t

Bypass

SSS(S) B
SSS(S) B

SSSS Bb


BBB(B) b

AC Loss

SSS(S) E
SSS(S) E

SSSS EA
C



EEE(E) A
C
Low Batt

SSS(S) L

SSS(S) L

SSSS LL
B


LLL(L) L
B
Open

SSS(S) O

SSS(S) O

SSSS OU



OOO(O) U

Close
SSS(S) C

SSS(S) C

SSSS CU



CCC(C) U

Test

SSS(S) G

SSS(S) G

SSSS Gg



GGG(G)g

Restore

SSS(S) R

SSS(S) R

SSSS RZ

Alarm


RRR(R) Z

AC Restore

SSS(S) R
A

SSS(S) R
A

SSSSR
A
A
c


R
A
R
A
R
A
(R
A
)A
c
LoBat Res.

SSS(S) R
L

SSS(S) R
L

SSSS R
L
L
B


R
L
R
L
R
L
(R
L
)L
B
Trouble Res.
SSS(S) R
T

SSS(S) R
T

SSSS R
T
t


R
T
R
T
R
T
(R
T
)t
Bypass Res.
SSS(S) R
B
SSS(S) R
B
SSSS R
B
b


R
B
R
B
R
B
(R
B
)b

Where:


SSS or SSSS =
Subs
criber ID

C =
Close Code–1st Digit


A =
Alarm Code–1st digit
U =
User Number (in hex)


Z =
Typically Zone Number*
–2nd digit
Gg =
Test Code (1st & 2nd digits)


Tt =
Trouble Code (1st & 2nd digits)

R =
Restore Code (Alarm)


Bb =
Bypass Code (1st & 2nd digits)

R
T
t =
Restore Code (Trbl) 1st & 2nd digits


EA
C =
AC Loss Code (1st & 2nd digits)

R
B
b =
Restore Code (Byps) 1st & 2nd digits


LL
B =
Low Battery Code (1st & 2nd digits)
R
A
A
C
=

Restore Code (AC) 1st & 2nd digits


O =
Open Code–1st Digit
R
L
L
B =
Restore Code (Bat) 1st & 2nd digits

*Zone numbers for:


& #, or B = 99; 1 +

, or A = 95;
3 + #, or C = 96; Duress = 92

Installation and Setup Guide


68
Ademco Contact ID
®

The Ademco Contact ID
®
Reporting Format comprises the following:

4-digit or 10-
digit subscriber
number (depending on format selected).

1-digit event qualifier (“new” or “restore”).

3-digit event code.

2-digit Partition No.

3-digit zone number, user number, or system status number (see the following page).


Ademco Contact ID
®
Reporting takes the foll
owing format: CCCC(CCCCCC) Q EEE GG ZZZ

where:

CCCC(CCCCCC) =
Customer (subscriber) ID


Q =
Event qualifier, where:


E = new event , and R = restore


EEE =
Event code (3 hexadecimal digits)


Note:

For a complete list of event codes, refer to the central
office receiver
manual.


GG =
Partition Number (system messages show “00”)


ZZZ =
Zone/contact ID number reporting the alarm, or user number for open/close
reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes in
the ZZZ location.


TAB
LE OF CONTACT ID EVENT CODES
(some event codes may not apply to certain control panels)


Code

Definition

110

Fire Alarm

121

Duress

122

Alarm, 24
-
hour Silent

123

Alarm, 24
-
hour Audible

131

Alarm, Perimeter

132

Alarm, Interior

134

Alarm, Entry/Exit

135

Alarm, Day/Night

143

Alarm, Expansion Module

145

ECP Module cover tamper

146

Silent Burglary

150

Alarm, 24
-
Hour Auxiliary/Monitor zone

162

Carbon Monoxide

301

AC Power

302

Low System Battery/Battery Test Fail

305

Syste
m Reset (Log only)

321

Bell/Siren Trouble

333

Trouble, Expansion Mod. Supervision

341

Trouble, ECP Cover Tamper

344

RF Receiver

Jam

351

Telco Line

Fault

353

Long Range Radio

Trouble

354

Comm Fail (log only)

373

Fire Loop Trouble

374

Exit Error Alarm

380

Global Trouble, Trouble Day/Night

Code

Definition

381

RF Sensor Supervision

382

Supervision Auxiliary Wire Zone

383

RF Sensor Tamper

384

RF Sensor Low
-
b
attery

393

Clean Me

401

Disarmed, Armed AWAY, Armed
MAXIMUM

403

Schedule Arm/Disarm AWAY

406

Cancel by User

407

Remote Arm/Disarm (Downloading)

408

Quick Arm AWAY

409

Keyswitch

Arm/Disarm AWAY

441

Disarmed/Armed STAY/INSTANT,

Quic
k
-
Arm STAY/INSTANT

442

Keyswitch

Arm/Disarm STAY

455

Scheduled Arm Fail

459

Recent Closing

570

Bypass

601

Manually Triggered Dialer Test

602

Periodic Test

606

AAV to Follow

607

Walk Test Entered/Exited

623

Event Log 80% Full

62
5

Real
-
Time Clock was Changed (log only)

627

Program Mode Entry (log only)

628

Program Mode Exit (log only)

642

Latch Key (log only)


750
-
789

Reserved for Configurable Zone Type
report codes (check with central station
when using these codes)


System Operation

69
Sy
stem Security Codes
The systems provides one Installer code, one System Master code, plus a set of other user codes intended for
other users of the system. These codes can each be assigned one of 5 authority levels, which determine t
he
functions each code can perform as listed in the table below.

Number of Codes
: Provides 48 security codes (plus Installer code), including one System Master code,

two Partition Master codes, and 45 general user codes.

Authority Levels

(can be assigned to users 03
-49 only; users 1 and 2 cannot be changed)

Level

User No.

Functions

Installer

01

(default=4112) perform all security functions except can disarm only if used to arm; can enter
program mode; can change System Master code; cannot assign other user codes

NOTE: For security purposes, the factory default installer code should be changed.

System Master

02


(default 1234) only one system master code per system; can perform all security functions,
add/delete users in either partition, change system master code, view event log, set system
clock, program keypad macro, program scheduled events, activate output devices
(triggers/relays)
Partition
Master
(default)

P1 = 03

P2 = 33
Same as Master, except add/delete users limited to a
ssigned partition only, (these users
can be assigned different authority levels, if desired; any user can be assigned the partition
master authority level)

0
-
User

03
-
49

perform security functions (arm, disarm, etc.) only; cannot add/delete users, view eve
nt log,
set system clock or program scheduled events

1
-
Arm Only

see “user”

arm system only

2
-
Guest

see “user”

can disarm the system only if it was used to arm the system

3
-
Duress

see “user”

performs security functions, but also silently sends a duress m
essage to the central station;
reports as duress code user number.

4
-
Partition
Master

see “user”

See Partition Master paragraph above; used to assign other user numbers as partition
masters


Refer to the user guide for procedures on adding/deleting secur
ity codes and changing user attributes.


The following is a brief description of how to add user
s and user
codes.

Changing the System Master code...

Using Installer code: Installer code + [8] + 02 + new code

Using current System Master code: System Maste
r code + [8] + 02 + new code + new code again

Adding a User:

Master code + [8] + 2-
digit user no. + user’s code

Deleting a User:

Master code + [8] + 2-
digit user no. + [#] [0]

Assigning Attributes:

Master code + [8] + 2-
digit user no. + [#] [attribute no.]
+ value


Attributes:

Values



1 =
Authority Level

0-4 (see Authority Level table above)


2 =
Access Group

0-8 (0 = not assigned to a group)


3 =
Active Partition(s)

1, 2, 3 (common)


for this user;

Enter partitions consecutively if more than one and pr
ess [#] to end
the entries.


4 =
RF Zone No.

Assigns user number to button type zone for arm/disarm (
keyfob
must be enrolled in system first
; see
Wireless Key Templates

section).




Deactivating a key fob:
You can deactivate the arming/disarming
functions
for a key fob (ex. if lost or stolen) by deleting the
associated key fob user. See “Delete a User” above. Other key fob
functions such as panic or device activation (if programmed) remain
active. To fully remove
the programming for a key fob, delete the
zone(s) associated with the keyfob functions.

IMPORTANT SECURITY NOTICE

Please inform the User about the security importance of their key fob, and what to do if it is lost.

Explain that the key fob is similar to their keys or access card. If lost or stolen, another person can
compromise their security system. They should immediately notify the Dealer/Installer of a lost or stolen key
fob. The Dealer/Installer will then remove the key fob programming from the security system.


5 =
Open/Close Paging

1 for yes
, 0 for no
Installation
and Setup Guide


70
Keypad Functions
The following is a brief list of system commands. For detailed information concerning system functions, refer to
the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI)
User’s Gui
de.


Voice Keypads

The 6160V Voice Keypad provide
s the following features:


Message Center, which lets the user record and playback one message.


Voice Status, which can announce system status by using the STATUS key.


Voice Chime, which can alert users
to the opening of doors/windows while the system is disarmed.

Refer to the User Guide for specific procedures for activating and using these features.


Keypad Commands

Function

Description

Silence
Burglary A
larms

Pressing any key will silence the keypad
sounder for 10 seconds. Disarming

the system will
silence both keypad and external sounders.

Silence Fire or Carbon
Monoxide Alarms

Press the OFF [1] key to silence the keypad sounder and, for fire alarms, the external sounder.
The detec
tor sounding stops when the contaminated air is cleared from the detector; see the
detector’s instructions for further information.

Quick Arm

If enabled (field

21), you can press [#] in place of the system's security code, plus the desired
arming key (Aw
ay, Stay, Instant, Maximum)

Single
-
Button arming

If programmed (*57 Function Key menu mode), lettered keys A
-
D can be used for arming, using
options 3-AWAY, 4
-STAY, 5
-NIGHT
-STAY, or 6
-Step-Arming

If used, no security code is required to arm the system.

A
larm Memory

When the system is disarmed, any zones that were in an alarm condition during the armed
period will be displayed. To clear this display, simply repeat the disarm sequence (enter the
security code and press the OFF key) again.

Arming Away

Enter

code + AWAY [2] or simply press appropriate lettered key on the keypads (see “Single
-
Button Arming” above). If the “Auto-Stay Arm” feature is enabled (field *84) and the entry/exit
door
is not
opened and closed within the programmed e
xit delay time, the system will
automatically arm in STAY mode if armed from a wired keypad (non-RF device). If the door
is

opened and closed within the exit delay period, the system arms in AWAY mode.

Arming Stay

Enter

code + STAY [3
] or simply press appropriate key on the keypads (see “Single
-
Button
Arming” above). See “Arming Away” above for Auto
-
Stay arming feature.

Arming Night
-
Stay

Enter

code + STAY [3] + STAY [3] or simply press appropriate key on the keypa
ds (see “Single
-
Button Arming” above).

Arming Instant

Enter

code + INSTANT [7].

Arming Maximum

Enter

code + MAXIMUM [4] or simply press appropriate lettered key on the keypads (see
“Single
-
Button Arming” above
).

Disarming

Enter
code + OFF [1].

If entry delay or an alarm is active, you do not need to press OFF.

Bypassing Zones

Enter
code + BYPASS [6] + zone number(s).

Forced (Quick) Bypass

To automatically bypass al
l faulted zones, use the “Quick Bypass” method. Enter code +
BYPASS + [#], then wait for all open zones to be displayed. Arm when display indicates “ZONE
BYPASSED” and “READY TO ARM”.

Chime Mode

Enter

code + CHIME [9]. To turn chime of
f, enter code + CHIME again.

Activate Output Devices

If relay outputs (via a
4204, or
4229), or
Powerline Carrier devices are used, two keypad entries
available to the user are included. If pr
ogrammed, these entries can be used to manually
activate or deactivate the device(s) for starting or stopping some action, such as turning lights
on or off, etc. These keypad entries are:

[Security Code] + # + 7 + [2-digit Device #] activates (starts) that device.

[Security Code] + # + 8 + [2
-
digit Device #] deactivates (stops) that device.


System Operation

71
SUMMARY OF ARMING MODES

Arming Mode

Features for Each Arming Mode

Exit Delay

Entry Delay

Perimeter Ar
med

Interior Armed

AWAY

Yes

Yes

Yes

Yes

STAY

Yes

Yes

Yes

No

NIGHT
-
STAY

Yes

Yes

Yes

only those zones
listed in Night-
Stay
zone list

INSTANT

Yes

No

Yes

No

MAXIMUM

Yes

No

Yes

Yes


Panic Keys

There
are three Panic k
eys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a
report to the central station.

Each key can be programmed for 24
-hour Silent, 24
-hour Audible, Fire, or Personal Emergency responses.

The programmed Panic response i
s activated when the appropriate key is pressed for at least 2 seconds.

The Panic keys are identified by the system as follows:

Keys

Displayed as Zone

[A]
(

/1)

95

[B]
(

/#)

99

[C]
(3/#)

96

IMPORTANT:

For a
Silent panic function
(if programmed) to be of practical value, you must program a report
code for the zone and the system must be connected to a central station.


NOTE:
For SIA Compliance, panic functions for the A, B, and C function keys must be disabled, leaving the 1+*,
3+#, and *+# as panics.
See *57 for other functions.


Setting the Real
-Time Clock
NOTE: All partitions must be disarmed before date/time can be set.

Set the time and date by doing the following:

1.



+[#] + [6] [3]


(Master
Code)

Alpha Display:

DISARMED

READY TO ARM




2.

Press [

] when the time/date is displayed.


A cursor appears under the first digit of the hour.


To move cursor ahead, press [

]. To go back, press [#].



Enter the 2-
digit hour s
etting.



Enter the 2-
digit minute setting.



Press [1] for PM or [2] for AM.



Enter the last two digits of the current year.



Enter the 2-
digit month setting.



Enter the 2-
digit day setting.

3.

To exit, press [

] when cursor is at the last digit,
or wait
30
seconds.

TIME/DATE SAT

04:04PM 10/17/00
Current time display


TIME/DATE SAT

04:04P2000/10/17
Time/date editing display



Installation
and Setup Guide


72
Various System Trouble Displays

Alpha Display

Fixed Disp.

Meaning

ALARM CANCELED

CA

will
appear if an exit or interior zone contained a fault during closing at the time the
Exit Delay
ended (e.g., exit door left open), but the system was disarmed during
the Entry Delay
time. The alarm sounder and keypad sound continuously, but stop
when the system is disarmed. No message will be transmitted to the central
station.

EXIT ALARM

EA

appears when Exit Delay

ends if an exit or interior zone contained a fault

during
closing. The alarm sounder and keypad sound continuously until the system is
disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central
station. Also results if an alarm from an exit or interior zone occurs within 2 minutes
after
the end of an Exit Delay.

CHECK

CHECK

indicates that a problem exists with the displayed zone(s) and requires attention.

ALARM 1xx

FAULT 1xx

CHECK 1xx

1xx

1xx

1xx

91

indicates that communication between control and a zone expander or wireless
receiver is
interrupted, where “xx” is the device address
. Check the wiring and DIP
switch settings on the units.

If field *199 is set to “1,” all ECP module problems are displayed as “91.”

If there are wireless sensors in the system, the Check
condition may also be
caused by some change in the environment that prevents the receiver from
receiving signals from a particular sensor.

SYSTEM LO BAT

BAT

with no zone number indicates that the system's standby battery is weak.

LO BAT

BAT

with a zone
number and a once
-
per
-
minute beeping at the keypad indicates that a
low
-battery condition exists in the wireless sensor displayed (zone “00” indicates a
wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display
may occur.

NOTE: Som
e wireless sensors contain a non-replaceable long-
life battery which
requires replacement of the entire unit at the end of battery life
.

TELCO FAULT

94

Telephone Line Failure, indicates that a monitored telephone line (if programmed
in field *92) has been
cut or disconnected. Depending on how the system was
programmed, the keypad may also produce a trouble sound, and the external
sounder may be activated. Silence by entering installer code + OFF.

Busy
-
Standby

dl

If this remains displayed for more than 1 m
inute, the system is disabled.

Modem

Comm

CC

The system is in communication with the central station for change of function or
status verification.

no display

no display

Power Failure

If there is no keypad display at all and the LEDs are un
lit,
operating power (AC and
battery) for the system has stopped and the system is inoperative.

If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed
-Word
display keypads) is displayed, the keypad is operating on battery
power only.

If the battery standby capacity is used up during a prolonged AC power outage, the
control's power will shut down to minimize deep discharge of the battery.

Comm. Failure

FC

A communication failure has occurred

(event log 354;
.
message not del
ivered)

Open Circuit

0C

The keypad is not receiving signals from the control; sees an open circuit.

Long Rng Trbl

bF

Backup
communication device (
LRR
/
Cell
)

had
communication failure.

Bell Failure

70

Bell supervision failure.

RCVR Jam

90

RF jam detected
.

KEYPAD LOW BAT

00 BAT

Wireless keypad low battery.

Phone Okay

Cd

The dialer test has been successful (CID code 601).

Dialer Off

d0

The dialer is disabled.

Test in Progress

dd

Walk test mode is active

(CID code 607).

Upload Completed

dC

The upload or

download session was completed.

Upload Failed

dF

The upload or download session failed before completion.






73
SECTION 7

Testing the System


About Test Procedures

After the installation is complete, you should perform the following tes
ts:
System Test
:

Checks that all zones have been installed properly and the system responds to faults.

Dialer Test:

Checks that the phone connection to the central station is working properly.

Go/No Go Test:

Checks that transmissions ca
n be received from transmitters. Should be performed before
permanently mounting transmitters.

RF Sniffer Mode
:

Checks that RF transmitter serial numbers have been properly enrolled.

Battery Tests:

Automatic battery tests are performed by the system.


System Test

NOTE:
Test mode can be entered from any keypad. However, faulted zones appear only on those keypads
assigned to the partition to which the zone is assigned (i.e., partition 1 zones appear only on partition 1 keypads,
etc.). To see another partition’s faulted zones, view a keypad assigned to that partition or use the GOTO
command (code +
[

] + partition number 0-
3, where 0 is the keypad’s home partition).


With the system in the disarmed state, check that all zones are intact (not faulted). Doors and windows with
contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary). If a “NOT
READY” message is displayed, press [

] to display the faulted zone(s). Restore faulted zone(s) if necessary, so
that the “READY” message is displayed.


1. Enter Installer Code
+ 5 [
TEST
], then press “0” at the prompt to start Walk Test mode.

1=DIAL, 0=WALK

(no special display on Fixed
-Word keypads)



The following wi
ll be displayed
on the initiating keypad
and a Contact ID report will be sent (code 607):

TEST IN PROGRESS
(“dd” displayed on Fixed
-Word Display Keypads)




2. Upon entering the system test mode, the outside sounder should sound for 1 second.


If the backu
p battery is discharged or missing, the sounder may not turn on and a “LOW BATTERY” report will
be transmitted with a “TEST” report.


The keypad will beep about every
30
seconds as a reminder that the system is in the
Test mode.


NOTE:
Wireless motion detectors (Passive Infrared units) will send signals out only if they have been inactive
for 3 minutes (conserves battery life).

3. Test all sensors using the procedure described in the User’s Guide “Testing the System” section.

4. After
checking sensors, turn off the test mode by entering installer code + OFF.


NOTE
: Test mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55 minutes of
Test mode), the keypad emits a double
-beep every 30 seconds to alert that
the end of Test mode is nearing.

Checking Transmitter Enrollment (Sniffer Mode)

Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are
disarmed before trying to enter this mode, sinc
e this is a system
-wide command.


1. From a keypad in partition 1, press [Installer code] + [#] + 3.

(sniffer mode can be started only from partition 1)

NOTE:
If the communicator is in the process of sending a report to the central station, the system wil
l not go
into the Sniffer mode. If so, wait a few minutes, and try again.


The keypads in both partitions will display all zone numbers of wireless units (in both partitions) programmed
into the system. Fault each transmitter in turn, causing each one to s
end a signal.

As the system receives a
signal from each of the transmitters, the zone number of that transmitter disappears from the display.


2. After all transmitters have been checked, exit the sniffer mode by keying
[Installer code] + OFF.

IMPORTAN
T:
Sniffer mode does not automatically expire. You must manually exit Sniffer mode (by entering
[Installer code] + OFF) to return to normal operation.

NOTES:



All BR type units must physically be activated to clear the display.



When
one
button of a tr
ansmitter (RF, UR, or BR) is activated, all zones assigned to other
buttons on that transmitter are cleared from the display. This also applies to 5816 and 5817
transmitters, which have multiple loops (zones).



Any transmitter that is not “enrolled” will
not turn off its zone number.
Installation
and Setup Guide


74
Go/No Go Test Mode
The
Go/No Go Test verifies adequate RF signal strength from the proposed transmitter location, and allow you to
reorient or relocate transmitters if necessary, bef
ore mounting the transmitters permanently. This mode is similar
to the Transmitter Test mode, except that the wireless receiver gain is reduced. This will enable you to make sure
that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the
normal operating mode.

1. Enter
[Installer code] + [#] + 4 f
rom the partition being tested. For multi
-partition systems, repeat this test for
each partition.

2. After you have placed transmitters in their desired locations and the approximate length of wire to be run to
sensors is connected to the transmitter's screw terminals (if used), fault each transmitter. Do not conduct this
test with your hand wrapped around the transmitter, as this will cause inaccurate results.

a. The keypad will beep three times to indicate signal reception and display the zone number.

b. If the keypad does not beep, you should reorient or move the transmitter to another location. Usually a few
inches in either direction is all that is required.

3. If each transmitter produces the proper keypad response when it is faulted, you can then permanently mount
each of the transmitters according to the instructions provided with them.

4. Exit the Go/No Go Test mode by entering: [any user code (partition
-specific)] + OFF.


Dialer Communication Test
and Periodic Test Reports
1. Enter Installer Code
+ 5 [
TEST
], then press “1” at the prompt to start the Dialer Test
(checks p
hone line
integrity only; does not confirm report transmissions)
.
1=DIAL, 0=WALK

(no special display on Fixed
-Word keypads)



The
keypad beeps twice and displays the following
if test is successful:

PHONE OKAY
(“Cd” displayed on Fixed
-Word Display Keypads)



A Contact ID report will also be sent (code 601)


If the dialer test is unsuccessful, “COMM FAILURE” (or FC) is displayed.


2. Enter Installer code + OFF to clear the display and exit.


Automatic Periodic Test Report

The system can be set to automatical
ly send test reports (enabled in field *64; Contact ID code 602) at specified
intervals. Frequency of the reports is set in Scheduling mode (event 11) or by the following key commands:


installer code + [#] + 0 + 0
= test report sent every 24 hours


instal
ler code + [#] + 0 + 1
= test report sent once per week


installer code + [#] + 0 + 2
= test report sent every 28 days


Each mode sets schedule 32 to the selected repeat option; the first test report is sent 12 hours after command.


To ensure that test reports are sent at the times expected, set the Real
-Time Clock to the proper time
before

entering the test report schedule command.

NOTES:



SYSTEM MUST BE “READY TO ARM” (and communicator cannot be active) to enter the ‘Manual Dialer
Test mode’ (Installer, m
aster, or partition master code + 5 + 1).



If there is a ‘Test’ report code in *64 the panel will attempt to send a Test Report (CID message of E601)
to Central Station via the Dialer and Radio (if enabled) ignoring both *54 and *55.



With no ‘Test’ report
code in *64, the panel will not attempt to send a ‘Test’ report, and will behave as if
you've entered ‘Walk’ test mode (Installer, Master, or Partition Master code + 5 + 0)



You can also program a function key to perform a dialer test.



The dialer test DOE
S NOT sound the bell output

KEYPAD DISPLAY



No display is generated for LRR communication success or fail. Panel exits dialer test mode once either
message appears.



Clear 'Phone OK' with code+1. Comm Fail can only be cleared with a successful phone line
communication or enter/exit program mode

For DIALER COMMUNICATION ONLY



The Keypad will display "Phone Okay" or "Cd" on Fixed English Keypads upon kissoff from CS.



If the Test report fails over the Dialer the keypad will display "Comm Failure" or Fc on fix
ed english
keypads.
Testing the System

75
Automatic Standby Battery Tests

1. An automatic test is conducted every 3 minutes to ensure that a standby battery is present and properly
connected. If a battery is not present or is not properly connected, a “
LOW BATTERY” message is displayed
and, if so programmed, will be reported to the central station.


2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours after exiting
the Programmi
ng mode or after powering up the system. In addition, entry into the Test mode will also cause
a battery capacity test to be initiated. If the battery cannot sustain a load, a “
Low Battery” message is
displayed and, if so programmed, will be reported to the central station.
Installation
and Setup Guide


76
77
SECTION 8

Specifications & Accessories


Security Control

1. Physical:

12-
1/2” W x 14
-1/2” H x 3” D (318mm x 368mm x 76mm)

2. Electrical:

VOLTAGE INPUT: 16.5VAC from plug
-in 40VA transformer, ADEMCO 13
61-GT
(in U.
S.A.)

RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type).
Charging

Voltage: 13.8VDC.

ALARM SOUNDER: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two
702
(series connected) self
-contained 20
-watt siren
s. Do
not
connect
two 702s in parallel.

AUXILIARY POWER OUTPUT: 12VDC, 600mA max.


NOTE
: For
UL installations, Alarm Sounder plus Auxiliary Power currents should not
exceed 600mA total.

FUSE:
Battery
Resettable Fuse: 3A hold. 6A trip at 23 degrees Celsius.

3. Communication:

FORMAT SUPPORTED:

ADEMCO Express:

10 characters/sec, DTMF (TouchTone) Data Tones,

1400/2300Hz ACK, 1400Hz KISSOFF.

ADEMCO Low Speed:
10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF.

Radionic
s/SESCOA:;

20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF.

Can report 0-
9, B-
F
Ademco Contact ID

10 characters/sec., DTMF (TouchTone) Data Tones,

1400/2300Hz ACK, 1400Hz KISSOFF.

LINE SEIZE: Double Pole

RINGER EQUIVALENCE: 0.1B
FCC REGISTRATION No.: 5GBUSA-
44003
-AL
-E
4.

Maximum Zone Resistance:
Zones 1
–8 = 300 ohms excluding EOLR
standard zones


Compatible Devices

Keypads:

6160 Alpha Keypad, 6160V Voice Keypads,
6280S/6280W
Touch Screen
Keypad,
Tuxedo Touch Keypad

Wireless Receivers:

5881EN
L: accepts up to 8 transmitters


5881EN
M: accepts up to 16 transmitters


5881ENH: accepts up to system maximum transmitters


5883
H Transceiver: accepts up to system maximum transmitters


6150RF Keypad/Transceiver: accepts up to
16
transmitters


6160RF Keypad/Transceiver: accepts up to the system max. transmitters

Zone Expansion:

4219
WIRED EXPANSION MODULE


4229
WIRED EXPANSION/RELAY MODULE

Relay Module:

4204
RELAY MODULE

Communica
tion


Device (LRR):

LTE
-21V
Installation
and Setup Guide


78
2-Wire Smoke Detector:


Detector Type

Model No.

Photoelectric w/heat sensor

2WT
-
B

(System Sensor)

Photoelectric

2W
-
B

(System Sensor)

Photoelectric

2151 w/B110LP base

(System Sensor)

Photoelectric

F
W
-
2S (Napco)


Transformers:

136
1-GT
: 16.5VAC, 40VA Plug
-In Transformer (No. 136
1CN
-GT
in Canada)




Sounders:

AB12M 10” Motorized Bell & Box

702 Outdoor Siren


719 2-
Channel Siren


713 High Power Speaker


746 Indoor Speaker


747 I
ndoor Siren


747PD Two-Tone Piezo Dynamic Indoor Siren

747UL Indoor Siren


748 Dual Tone Siren


749 Speaker/Horn


705-
820, 5-
inch Round Speaker


WAVE Speaker

WAVE2 Two
-Tone Siren


WAVE2PD Two
-Tone Piezo Dynamic Siren


5800WAVE Wireless Siren


System Sensor PA400B (beige)/; PA400R (red) Indoor Piezo Sounder

Specification and Accessories

79
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input
loops requires its own pr
ogramming zone

(e.g., a 5834-4's
four inputs require four programming zones).





NOTE
: For information on any transmitter not shown, refer to the instructions accompanying that transmitter for details
regarding loop numbers, etc.


UL NOTE:
The following transmitters are not intended for use in UL installations:


5802WXT,
5819S,
and
5819S
BR
. Installation
and Setup Guide


80
Specification and Accessories

81


SECTION 9

Regulatory Agency Statements


FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANADA (IC) STATEMENTS

The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's
Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT

This equipment has been tested to FCC requi
rements and has been found acceptable for use. The FCC requires the following
statement for your information:

This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordanc
e with
the manufactur
er's instructions, may cause interference to radio and television reception. It has been type tested and found to
comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which ar
e
designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause interference to radio or televisi
on reception,
wh
ich can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:


If using an indoor antenna, replace it with a quality outdoor antenna.


Reorient the receivi
ng antenna until interference is reduced or eliminated.


Move the radio or television receiver away from the receiver/control.

Move the antenna leads away from any wire runs to the receiver/control.

Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.

Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEMENT

This Class B digital apparatus complies with Canadian ICES
-003.

Cet appareil numérique de la classe B est conforme à la norme NMB
-003 du Canada.
FCC / IC STATEMENT

This device complies with Part 15 of the FCC Rules, and Industry Canada’s license-
exempt RSSs. Operation is subject to the
following two conditions: (1) This dev
ice may not cause harmful interference, and (2) This device must accept any interference
received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC et exempt de licence RSS d’Industrie Canada. Son fonctionnement
est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit acc
epter
toute interférence reçue y compris les interférences causant une réception indésirable.

Responsi
ble Party / Issuer of Supplier’s Declaration of
Conformity: Ademco Inc., a subsidiary of Resideo
Technologies, Inc., 2 Corporate Center Drive., Melville, NY
11747, Ph: 516
-577-
2000



TELEPHONE/MODEM INTERFACE

FCC Part 68

This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC registration
number and Ringer Equivalence Number (REN). You must provide this information to the telephs
one company when requested.


This equipment uses the following USOC jack: RJ31X


This equipment may not be used on telephone-
company
-provided coin service. Connection to party lines is subject to state tariffs. This
equipment is hearing-
aid compatible.


Ringer Equivalence Number Notice:

The
Ringer Equivalence
Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals
allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to
the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
Installation
and Setup Guide


82




RF EXPOSURE WARNING

The LTE
-21V
module must be installed to provide a separation distance of at least 7.8 in. (20 cm) from all persons and
must not be co-
located or operating in conjunction with any other antenna or transmitter except in accordance with FCC
multi
-
transmitter product procedures.



UL NOTICES

1.
Entry Delay No. 1 and No. 2 (fields

35,

36) cannot be greater than 30 seconds for UL Residential Bur
glar Alarm
installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm
installations, total entry delay may not exceed 45 seconds.

2.
For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installati
ons with line security, total exit delay
time must not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time
must not exceed 120 seconds.

3.
The maximum number of reports per armed period (field

93) must be set
to “0” (unlimited) for UL installations.
4.
Periodic testing (see scheduling mode) must be at least every 24 hours.

5.
Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA
max.).

6.
All partitions
must be owned and managed by the same person(s).

7.
All partitions must be part of one building at one street address.

8.
If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9.
For UL commercial burglar alar
m installations, the control unit must be protected from unauthorized access. The
tamper switch
installed to protect the control unit enclosure door is suitable for this purpose.

10.
Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for
UL installations.

11.
Auto-disarming is not a UL Listed feature.

12.
As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential
applications, th
e following UL requirements per UL681 are provided:


The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote
monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to
enter and disarm the system, or to arm the system and exit shall not exceed:

a) 60 seconds for a system with standard line security or encrypted line security,


b) 120 seconds for a system without standard line security or encrypted l
ine security, or


c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.

13.
This control is not intended for bank safe and vault applications.



SIA Quick Reference Guide

1.
*31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zone” will be the same as the “number
of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in zone list 7).

2.
*34 Exit Delay: Minimum exit delay is 45 seconds.

3.
*35/*36 E
ntry Delay 1 and 2: Minimum entry delay is 30 seconds.

4.
*37 Audible Exit Warning: Feature always enabled; field does not exist.

5.
*39 Power Up in Previous State: Must be “1,” power up in previous state.

6.
*40 PABX Access Code or Call Waiting Disable: I
f call waiting is used, call waiting disable option in field *91 must
be set.

7.
*50 Burglary Dial Delay: Delay must be minimum of 30 seconds.

8.
*59 Exit Error Alarm Report Code: Always enabled.

9
*68 Cancel Report Code: Default is “code enabled.”

10.
*69
Recent Closing Report Code: Always enabled.

11.
*91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be
set to “1” (enabled).

12.
*93 No. reports in Armed Period: Must be set for 1 or 2 report pairs
.
13.
Cross zone timer programming is set in field

85; cross zone pairs are assigned in zone list 4 using

81 Zone List
mode.

14.
Duress code is assigned by using the “add a user code” procedure found in the User Guide. Enable Duress code
reporting by programming zone 92 using

56 Zone Programming mode.
15.
Fire alarm verification is a built
-in system feature when a zone is programmed for zone type 16.

16.
P
anic functions for the A, B, and C function keys must be disabled, leaving the 1+*, 3+#, and *+# as
panics. See
*57 for other functions.



83
SECTION 10


Limitations and Warranty

WARNING

THE LIMITATIONS OF THIS ALARM SYSTEM

While this System is an advanced design security system, it does not offer guaranteed protection against burglary,
fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to
warn for a variety of reasons. For example:

• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm
sensor
or disconnect an alarm warning device.

• Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not
work without power. Battery
-operated devices will not work without batteries, with dead batteries, or if the batteries
are not put in properly. Devices powered solely by AC will not work if their AC power supply
is cut off for any
reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal bef
ore they reach the alarm receiver.
Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is
moved into the path.

• A user may not be able to reach a panic or emergency button quickly enough.

• While sm
oke detectors have played a key role in reducing residential fire deaths in the United States, they may
not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data
published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in
conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed
and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as
in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level of a residence or building. A second floor detector, for example, may not sense a first floor or
basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire
every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like
smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson. Depending on the nature of the fire and/or location of the smoke
detectors, the detector, even if it operates as anticipated, ma
y not provide sufficient warning to allow all occupants
to escape in time to prevent injury or death.

• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple
beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They
cannot detect motion or intrusion that takes place behind walls, ceilings, f
loors, closed doors, glass partitions,
glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors,
windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense
changes in temperature; however, as the ambient temperature of the protected area approaches the temperature
range of 90° to 105°F (32° to 40°C), the detection performance can decrease.

• Alarm warning devices such as sirens, bells or horns may not aler
t people or wake up sleepers if they are located
on the other side of closed or partly open doors. If warning devices are located on a different level of the residence
from the bedrooms, then they are less likely to waken or alert people inside the bedroom
s. Even persons who are
awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other
appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired
people.

• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of
service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.

• Even if the system responds to
the emergency as intended, however, occupants may have insufficient time to
protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not
respond appropriately.

• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is
designed to last as long as 10 years, the electronic components could fail at any time.

(Continued)
Installation
and Setup Guide


84

WARNING

THE LIMITATIONS OF THIS ALARM SYSTEM

(Continued)


The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate
maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working
properly. The security keypad (and remote keypad) should be tested as we
ll.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating
conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the
specific wireless device being
used. External factors such as humidity, high or low temperatures, as well as large
swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however,
can identify a true low
-battery situation, thus allow
ing time to arrange a change of battery to maintain protection for
that given point within the system.

Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a
substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting
themselves and continue to insure their lives and property.

We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their
loved ones
to learn about these developments.





CONTACTING TECHNICAL SUPPORT


PLEASE, before you call Technical Support
, be sure you:

• READ THE INSTRUCTIONS!

• Check all wiring connections.

• Determin
e that the power supply and/or backup battery are supplying proper voltages.

• Verify your programming information where applicable.

• Note the proper model number of this product, and the version level (if known) along with any documentation that
came wit
h the product.

• Note your Honeywell
Home
customer number and/or company name.


Having this information handy will make it easier for us to serve you quickly and effectively.



Technical Support:
..........................................................................................
1-800-645-7492 (8 a.m.
-10 p.m. E.S.T.)



85
– INDEX

1361-
GT
...............................
2, 5, 79, 80

24-
Hour Audible Alarm
.......................
24

24-
Hour Auxiliary Alarm
.....................
24

24-
Hour Silent Alarm
..........................
24

3+1 and 4+1 Standard Formats
.......
67
3- Digit Number
.............................
53, 54

4204
...
2, 4, 9, 13, 22, 46, 47, 48, 71, 79

4219
...................................
1, 2, 4, 9, 79

4229
1, 2, 4, 9,
13, 22, 46, 47, 48, 71, 79
5800 Series Transmitters
...................
11
5801
...................................................
11
5802CP
..............................................
11
5827
...................................................
11
8-pin connector
..................................
12
AC Power Supply
.................................
2
AC Transformer
..............................
5, 80

Ademco Contact ID

............................
69
Alarm Bell Timeout

.............................
27
Alarm Output
....................................
4, 6

Alarm Sounder Timeout
..................
27
Alpha Descriptor
.....................
38, 41, 53

Alpha Vocabulary
...............................
53
Alpha Vocabulary List

........................
53
ALPHA VOCABULARY LIST
............
55
Arm Away/Stay Report Code
.............
29
Arm
–Away
..........................................
24
Arming Away
......................................
71
Arming Instant
....................................
71
Arming Modes
....................................
72
Arming Stay
........................................
71
Arm
–Stay
...........................................
24
Audio Alarm Verification
.....................
31
AUI
.......................................................
7
Authority Levels
..................................
70
Auxiliary Output
....................................
4
Backup Battery
.....................................
2
Battery Life

.........................................
11
Battery Tests
..............................
75, 77

Bypassing Zones
................................
71
CA
......................................................
30
Cabinet
.................................................
3
CALIFORNIA STATE FIRE MARSHALL
.........................................................
4
CANCELED ALARM
..........................
30
Character (ASCII) Chart
...................
55
Character List

.....................................
54
Charging Voltage

...............................
79
Chime Mode
.................................
35, 71

Clean Me Option

..................................
9
common zone

.....................................
38
Communication

......................
52, 67, 79

Configurable Zone Type Programming
Fields
.............................................
34
Confirmation Of Arming Ding
.............
27
Contact ID Reporting

..........................
79
Contacting Technical Support

............
87
CSFM
...................................................
4
Custom Message

...............................
54
Custom Words
...........
53, 54, 55, 57, 58
Defining Output Functions
..................
48
Descriptor Programming
....................
53
device address
.......
7, 13, 22, 37, 46, 73
Device number
...................................
65
Dialer Communication Test

................
76
Disarm
................................................
24
Disarming

.....................................
49, 71

Double-
Balanced
..................................
8
Enrolling

.......................................
11, 38

entering serial number
.......................
42
Entry Delay
.......................
24, 34, 72, 73

Entry Delay 02
..................................
27
Entry/Exit Burglary
.............................
23
En
try/Exit Burglary
.................................

Entry/Exit Burglary
.................................

E O LR
.............................................
8, 79

Event Logging
....................................
31
Exit Delay
...................
27, 31, 34, 72, 73
Exit Error Alarm
...................................
69
Exit Error Alarm
...................................
73
Exit Error Report Code
........................
29
Expansion Zones
................................
9
Expert Programming Mode
.....
38, 41, 44

Factory Defaults
................................
.. 23

Fault Delay Time

...............................
31

Fire Sounder Timeout
.........................
27

Forced Bypass Function

.....................
26

Function Key Programming
................
52

Function Keys
...............................
32, 52

Go/No Go Test Mode
..........................
76

Handshake
................................
..........
67

hardwired zones
..............................
1, 40

HAYES Modem
................................
.....
1
House ID
................................
.......
11, 26

Ideal Model 61–035
..............................
5
Input Device Type
...............................
42

Installer Code
....................
23, 32, 75,
76

Interior Follower
......................
23, 39, 49

Interior w/Delay
.......................
24, 39, 49

keypad addresses
...........................
7, 36

Keypad Programming Fields
...............
36

Keyswitch
..........................
12, 25, 39, 69

Kissoff
................................
...........
49, 67

Lock
................................
......................
3
Long Range Radio
..................
28, 69, 79

Low Battery Message
.........................
77

model 112
................................
...........
12

Modem
................................
................
73

Module Addresses
..............................
47

mome
ntary switch
...............................
12

No Alarm Response
......................
25, 49

Output Device Mapping
..........
22, 46, 47

Output Devices
................................
... 46

Output Functions
................................
. 46

Output relays
................................
.........
2
PABX Access Code
............................
27

Pager #1 Phone No.
..........................
33

Pager Programming
............................
32

Pager Programming Fields
.................
32

Pager Report Options
.........................
33

Paging
................................
.................
31

Pa
nic Keys
................................
..........
72

Partitions
................................
.............
38

Perimeter Burglary
..............................
23

Periodic Test Reports
.........................
76

Phone Module
.............................
1, 7, 17

Power Failure
................................
49, 73

power supply
...............................
4, 6, 86

Power Up In Previous State

................
27

Powerline Carrier Devices
..............
2, 71

Primary Phone No.
..............................
28

Primary Phone No.

..............................
27

prompt to confirm
................................
42

Quick Arm Enable
...............................
36

Registering the Control
....................
17

Relay Modules
................................
2, 13

Relay Programming
............................
22

Report Code
. 29, 30, 31, 34, 39, 42, 67

Report Code Formats
.........................
67

Reports In Armed Period
..................
32

response time
...........................
9, 31, 39

RF House ID Code
........................
10, 26

RF Interference
................................
... 10

RF ja
m detection
.............................
1, 26

RF Jam Option
................................
....
10

RF Receiver
......................
3, 4, 7, 10, 69

RF System
................................
..........
26

Ring Detection Count For Downloading
................................
........................
32

Schedules
................................
...........
65

Security Codes
................................
1, 70

Silent Burglary
...................
25, 39, 49, 69

Silent Panic
................................
.........
72

Single Alarm Sounding Per Zone
........
27

Sniffer Mode
................................
.. 41, 75

sounder connections
.............................
6
Supervised Fire
................................
... 24

Supplementary Power
...........................
6
Swinger Suppression
.......................
32

System Communication
..........
34, 39, 67

System Operation
.............
43, 44, 49, 65

System Status Report Codes
..............
29

System Test
................................
.......
75

tamper switch
................................
12, 84

Technical Support
...............................
87

Telco Line
................................
...........
69

Telephone Line Monitoring
...................
1
Temporal pulse sounding
....................
24

Test Mode
................................
.....
75, 76

Test Restore Report Code
..................
30

Touch Screen Device (AUI) Enable
....
36

touchpads
................................
...........
29

Transmitter Input Types
......................
40

Trigger outputs
................................
....
14

Trouble by Day/
................................
... 24

Trouble Displays
.....................
72, 73, 74

UL
................................
...............
4, 6, 79

Verify Operation
................................
....
9
Vocabulary List
................................
... 53

Wire Run Chart
................................
. 6, 7

Wireless Key Predefined Default
Templates
................................
......
45

Wireless Key Programming Templates
................................
........................
43

wireless key templates
........................
43

Word String
................................
.........
54

Worksheet
................................
.............
4
Zone Doubling
................................
.......
8
Zone Lists
...............................
22, 50, 51

Zone Not Used
................................
....
23

Zone Programming Pr
ocedure
............
38

Zone Type
................................
...........
42

Zone Types
.............................
23, 39, 49
Installation
and Setup Guide


86


NOTES


87
NOTES Installation
and Setup Guide


88
NOTES

89
NOTES
Installation
and Setup Guide


90
NOTES

91


Figure 17. Summary of Connections



SUPPORT, WARRANTY, & PATENT INFORMATION

For the latest documentation and online support information, please
go to:

https://mywebtech.honeywellhome.com/
For the latest warranty information, please go to:

https://www.security.honeywellhome.com/hsc/resources/wa/index.html



For patent information, see
:https://www.resideo.com/patent



MyWebTech


Warranty


Patents



The product should not be disposed of with other household waste. Check for the nearest authorized collection
centers or authorized recyclers.
The correct disposal of end
-of
-life equipment will help prevent potential negative
consequences for the environment and human health.































This product is manufactured by Resideo Technologies
and its affiliates
. The Honeywell Hom
e Trademark is used under license from
Honeywell International Inc.



2 Corporate Center Drive, Suite 100

P.O. Box 9040, Melville, NY 11747


2019 Resideo Technologies, Inc.

www.resideo.com
















Ê800-25358V1AXŠ

800-
25358V1A
8
/19 Rev
A


Uploaded