Honeywell Vista-15P/Vista-20P - Install Guide - Dated 3/15 Rev. C
Related Products
Related Categories
Document Transcript
ADE
MCO VISTA S
ERIES
VISTA
-20P / VISTA
-20PSIA
VISTA
-15P
/ VISTA
-15PSIA
Security Systems
Installation and Setup Guide
K5305-
1V
10
C 3
/15 Rev.
C
ii
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for t
he
Location
of Fire and Burglary Detection
Devices Help Provide Proper Coverage for the Protected Premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
cont
ained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection
a smoke det
ector should be installed outside of
each separate sleeping area, and on each additional floor of a multi
-floor family living unit, including
basements.
The installation of smoke detectors in kitchens, attics (finished or unfinished), or
in gar
ag
es is
not
normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached
garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke cou
ld be b
locked by the closed door. Also, an alarm in the hallway outside may not wake
up the sleeper if the door is closed.
•
Install a smoke detector inside bedrooms
where electrical appliances (such as
portable heaters, air conditioners or
humidifie
rs) are
used.
•
Ins
tall a smoke detector at both ends of a
hallway if the hallway is more than 40 feet
(12 meters) long.
•
Install smoke detectors in any room where
an alarm control is located, or in any room
where alarm control connections to an AC
source
or phone
lines are
made. If detectors
are not so located, a fire within the room
could prevent the control from reporting a
fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA
REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION
APPLIANCES.
Recommenda
tions For
Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows in a
multi-
level
building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be
sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are
normally sent ov
er the phon
e lines, if connected to an alarm monitoring station).
NOTE
: Copies of the
Programming
, Installation, and User Guides
must be left with the end user.
iii
Table Of Contents
Features and I
nstallati
on
Highlights
...................................................................................................................1
-1
Capabilities and Functions
..................................................................................................................................................
1-1
Compatible Devices
............................................................................................................................................................
1-2
Impo
rtant Installation Highlights (Installer Please Read)
.....................................................................................................
1-2
Mounting and Wiring the Control
........................................................................................................................2
-1
Installing the Control
Cabinet and
PC Board
.......................................................................................................................
2-1
Cabinet and Lock
..........................................................................................................................................................
2-1
Mounting the PC Board Alone (no RF Receiver)
...........................................................................................................
2-1
Mounting Board with RF Receiver
.................................................................................................................................
2-1
Auxiliary Device Current Draw Worksheet
.....................................................................................................................
2-2
AC Power, Battery,
and Groun
d Connections
.....................................................................................................................
2-3
1321 Transformer
..........................................................................................................................................................
2-3
Battery Connections
......................................................................................................................................................
2-3
Battery Saver Feature
...................................................................................................................................................
2-3
Earth Ground
.................................................................................................................................................................
2-3
Sounder (Bell) Connections
................................................................................................................................................
2-4
Basic Connections
.........................................................................................................................................................
2-4
Supervised output
.........................................................................................................................................................
2-4
Connecting the Keypads and Other Addressable Devices
..................................................................................................
2-4
Co
nnections
..................................................................................................................................................................
2-4
Supplementary Power (optional)
...................................................................................................................................
2-4
Keypad Notes
................................................................................................................................................................
2-5
Communication Device..................................................................................................................................................
2-5
(Long Range Radio) Connections
.................................................................................................................................
2-5
Table
of Device Addresses
.................................................................................................................................................
2-5
Hardwire Zones and Zone Expansion
.................................................................................................................................
2-6
Hardwire Zones
.............................................................................................................................................................
2-6
Double-Balanc
ed
Zones
................................................................................................................................................
2-6
Zone Doubling
...............................................................................................................................................................
2-6
Smoke Detectors
...........................................................................................................................................................
2-6
Smoke Detector N
otes
..................................................................................................................................................
2-7
4219/4229 Expansion Zones
.........................................................................................................................................
2-7
Installing the RF Receiver and Wirel
ess Transmitter Zones
...............................................................................................
2-8
Compatible Receivers
...................................................................................................................................................
2-8
Receiver Connections
...................................................................................................................................................
2-8
RF Recei
ver Notes
........................................................................................................................................................
2-8
Installing the Transmitters
.............................................................................................................................................
2-9
Transmitter Battery Life
.................................................................................................................................................
2-9
Connecting Relay Modul
es and Output Triggers
..............................................................................................................
2-10
4204/4229 Relay Modules
...........................................................................................................................................
2-10
On
-Board Triggers
.......................................................................................................................................................
2-10
Phone Line
and Audio Alarm Verification (AAV) Connections
..........................................................................................
2-11
Phone Line
..................................................................................................................................................................
2-11
Au
dio Alarm Verification Connecti
ons
.........................................................................................................................
2-11
Audio Alarm Verification Connections
.........................................................................................................................
2-12
iv
Table Of Contents
System Communication a
nd
Operation
..............................................................................................................3
-1
Panel Communication with Central Station
.........................................................................................................................
3-1
Report Code Formats
..........................................................................................................................................................
3-1
Ademco C
ont
act ID
®
..........................................................................................................................................................
3-3
Uploading/Downloading via the Internet
..............................................................................................................................
3-4
System Security Codes
.......................................................................................................................................................
3-5
Panic Keys
..........................................................................................................................................................................
3-7
Settin
g the Real
-Time Clock
...............................................................................................................................................
3-7
Various System Trouble Displays
.......................................................................................................................................
3-8
Testing the System
...............................................................................................................................................4
-1
About Test Procedures
.......................................................................................................................................................
4-1
System Test
........................................................................................................................................................................
4-1
Checking Transmitter Enrollment (Sn
iffer Mode)
................................................................................................................
4-1
Go/No Go Test Mode
..........................................................................................................................................................
4-2
Dialer Communi
cat
ion Test
and Periodic Test Reports
.......................................................................................................
4-2
Automatic Standby Battery Tests
........................................................................................................................................
4-2
Specifications & Acc
essories
..............................................................................................................................5
-1
Securit
y Control
...................................................................................................................................................................
5-1
Compatible Devices
............................................................................................................................................................
5-1
Regulat
or y Agency Statements
...........................................................................................................................6
-1
Limitations and Warranty
.....................................................................................................................................7
-5
1-1
SECTION 1
Features and Installation Highlights
This manual applies to the following Resideo
security systems:
ADEMCO VISTA-
20P/ADEMCO VISTA-
20PSIA/ADE
MCO VISTA-
20PCN (
collectively referred to as
VISTA-
20P series), ADEMCO VISTA-
15P/ADEMCO VISTA-
15PSIA/ADEMCO VISTA-
15PCN (collectively
referred to as VISTA
-15P series)
NOTE
: Canadian units and power supplies
have not
been evaluated by ULC
Features a
nd proced
ures apply to al
l, except where differences are noted.
SIA Installations:
The VISTA
-20PSIA and VISTA-
15PSIA are certified SIA
-compliant controls that meet
SIA specifications for False Alarm Reduction. The other c
ontrols described in this manu
al are not c
ertified
as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm
Reduction, follow the SIA Guidelines noted in the applicable programming fields.
Capabilities and Functions
Fe
ature/Function
VISTA
-
20P Serie
s
V
ISTA
-
15P
Series
Partitio
ns
•
2 partitions, can protect two independent
areas
•
Common
partition
option allows either
partition to arm, while leaving a common
area (ex. lobby or foyer) disarmed for
access into the other p
artition.
VISTA
-
15P is not a p
art
itioned
s
ystem.
Zon
es
Up to 48 protection zones plus 16 keyfob
zones (zones 49-64) for total of 64 zones:
•
8 basic hardwired zones
(zones 1
-8) with
optional zone-doubling feature
•
Up to 40 additional wired zones (zones 9
-
48) u
sin
g up to 5
4219/4229
modules
•
Up to 40 wireless transmitter zones (5800
series; zones 9
-48)
•
Up to 4 configurable zone types
Up to 32 zones plus 8 keyfob zones (zones
49-56) for total of 40 zones:
•
6 basic hardwired zones
(zone 1
-6)
•
Up to 16 additional wired zones (zones 9-
24) using up to 2 4219/4229
modules
•
Up to 26 wireless transmitter zones (5800
series; zones 9
-34)
•
Up to 2 configurable zone types
Security Codes
Up to
48
Securit
y
Codes
, with separate
authority levels and partition access
Up to 32 Security Codes
, with separate
authority levels
One
-
button arming
Dedicated keys can arm the system
.
Dedicated keys can arm the s
yst
em.
Sch
e
dules
Up to
32; can control devices and/or auto
-
arm/disarm
Up to 8; can control devices and/or auto
-
arm/disarm
Keypad macros
Up to 4; activated by wired keypads
Up to 2; activated by wired keypads
Paging
Up to 4
pagers; certain system conditi
ons
can
rep
ort to pager
s; can use a dedicated key on
keypads to send a signal to a pager
Up to 2 pagers; certain system conditions can
report to pagers; can use a dedicated key on
keypads to send a signal to a pager
Event Log
ging
100 events; display via C
omp
ass Down
l
oader
softw
are or installer/master code at Keypad
50 events; display via Compass Downloader
software or installer/master code at Keypad
Zone descriptors
Can assign for all zones (for alpha display keypads
).
Bell superv
is
ion
Optiona
l
, detects external sounder wiring short
(when in alarm)
or open
(when bell is off)
;
causes a trouble condition, keypad display, and sends a report to the central monitoring
station, if enabled
(field
∗
91, option 1)
.
RF jam detection
Optional
,
for wireless systems detects a condition that may impede proper RF reception (i.e.,
jamming or other RF interference); causes keypad display, and sends a report to the central
monitoring station (if tr
ouble reporting is enabled).
Tel
ephone L
i
ne
Monitoring
Built
-
in option can monitor the
telephone line voltage and can cause a local display, or a
display and trouble/alarm sound
.
Downloading via
Phone Line or
Internet
•
Via Standard Phone Line: Us
e
an
IBM comp
a
tible computer, Compass downloading software,
and a
compatible HAYES or CIA modem specified by Resideo
.
•
Via Internet: supports Upload/Download via the Internet/Intranet when used with an
appr
opriate communications dev
ice
(ex
. 7845i
-G SM) and Compass downloading software.
This allows site maintenance independent of central station monitoring, and modification to
sites globally via the Internet.
UL NOTE:
Uploading/Downloading via the Internet
ha
s not been evaluated by UL
.
Installation and Setup Guide
1-2
Compatibl
e Devices
Device
VISTA
-
20P
VISTA
-
15P
Notes
Addressable Keypads
8
8
6150 Fixed
-
Word Keypad, 6160 Alpha Keypad, 6150V
Fixed
-Word Display Voice Keypad, 6160V Alpha Display
Voice Keypad, 6150RF Keypad/Transceiver
To
uc
h Screen (AUI)
Devices
4
2
Tou
ch
Screen (
A
UI) devices are in addition to the 8
addressable keypads. E.g.,
6280, Tuxedo
Touch
4219
, 4229
Zone
Expander Modules
Up to 5 for
up to 40 exp.
zones
Up to 2 for
up to 16 exp.
zones
Zone
nu
mbers are pr
edefined according
to
the dev
i
ce
addresses used. See Expander Module Addresses table
in Wiring section and set addresses accordingly.
5800 Series Wireless
Up to 40 RF
zones
Up to 26 RF
zones
Uses 5881/5883 Series Receivers/Transceivers.
Out
pu
t relays
U
p to 16
Up to 8
Use any combination of 4204
, 4229
.
Map output
devices via *79 Menu mode.
On
-
Board Triggers
2
2
Can be used to reset 4
-
wire
smoke detectors.
Ou
tput functions
Up to 48
Up to
24
Program
output functions via *80 Menu mode.
Audio Alarm Verification
Using AAV
module
Using AAV
module
Use
Resideo
AVS
or Eagle Model 1250 in conjunction
with an output trigger to permit voice dialog between an
operator
at the central station and a pers
on at th
e
premises.
The AVS system can be used to provide AAV
via phone line or AlarmNet
IP/GSM
(using a GSMV
4G
module).
Alarm output
12VDC, 2
AMP output
12VDC, 2
AMP output
Can d
rive the compatible sounders; steady ou
tput
for
burglary/panic, or tempor
al pulse (3
pulses
– pause
– 3
pulses
– pause
– 3 pulses. . .) for fire. Uses current
limiting circuitry for protection.
Auxiliary Power Output
See note.
See note
12VDC, 600 mA maxim
um;
uses circuit
protection.
Backup Ba
tter
y
See note.
See note.
Recharge
abl
e
(sealed lead
-
acid type) 12VDC, 4AH
minimum.
Communication Device
(Long Range Radio
)
See note.
See note.
Messages normally intended for the
p
rimary tele
phone
number
can be reported via ECP connect
ion to various
communication devices
(che
ck compatibility/availability
of specific models)
AC Power Supply
See note.
See note.
Plug
-
in 120VAC transformer,
1321 (13
21CN in Canada)
NOTE:
All devices and accessori
es u
sed in a Canadian installation
mu
st be Li
sted for use in Canada.
Important Installation Highlights (
Installer Please Read)
•
This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in
Section 2. Mounting and Wiring
– Con
nect
ing the Keypads and Other Addr
essable Devi
ces
).
•
Keypads must be set for addresses 16-
23 (first keypad is address 16, which is different from previous
controls) and programmed in data fields *190-
*196.
•
Zone Expander Modules must be set for specific addr
esses (07
-11), based on the zone
numbers
used.
•
4204 Relay Modules must be set for specific addresses (12-
15).
•
This control will not power
-up unless AC power is connected (will not power
-up on battery alone).
However, once the system is powered up,
it w
ill operate on battery power i
n t
he event
of AC loss.
•
Relays have two programming menu modes: Use *
79 Menu mode to map module addresses and
device (output) numbers. Use *80 Menu mode to define the output functions.
•
This system supports programmable
fun
ction keys. Use *57 Menu mode to
define t
he function keys.
2-1
SECTION 2
Mounting and Wiring the Control
Instal
ling the Control Cabinet and PC Board
Cabinet and Lock
1.
Remove the cabinet door.
Remove
the cabinet knockouts needed for
wiring entry.
2. Mount th
e control cabinet to a sturdy
wall
in a clean,
dry area, which is not
readily accessible to the general
public, using fasteners or anchors
(not supplied) with the four cabinet
mounting holes.
3. When installation and wiring is
completed, install the cabinet do
or
and secure by using 2 screw
s
(supplied
) through the door's edge.
OPTIONAL KEY LOCK:
If desired, a
key lock can be installed (K4445V1
).
Remove the lock knockout from the
door. Insert the key into the lock.
Position the lock in the hole, making
certa
in t
hat the latch will make contac
t
with the l
atch bracket when the door is
closed. When correctly positioned, push
the lock until the snap tabs hold it
securely.
CABINET DOOR
BOTTOM
LOCKED
UNLOCKED
cab_lock_snap-001-V0
PUSH
SNAP
TAB
SNAP
TAB
PUSH
ON LOCK
UNTIL IT
IS SEATED
SECURELY
STEP 2
STEP 1
CHECK
POSITION
Figure 1. Installing
the Door and
Cabinet
Lock
Mounting the PC Board
Alo
ne (no RF Receiver
)
B
e
fore installing the cabinet's contents, remov
e the metal cabinet knockouts required for
wiring entry. Do not remove the knockouts after the circuit board has been installed.
1. Hang two short mounting clips (pr
ovid
ed) on the raised cabinet tabs
(see Detai
l B).
2. a. Insert the top of the circuit boar
d into the slots at the top of the cabinet. Make sure that
the board rests on the correct row (see Detail A).
b. Swing the base of the board into the mounting clips
and
secure the board to the cabinet
with the
accompanying screws (see Detail B).
Figur
e 2. Mounting the PC Board
Mounting Board with RF
Receiver
•
Do not mount the cabinet on or near metal objects. This will decrease RF range and/or block
RF transmis
sion
s from wireless transmitters.
•
Do not loc
ate the cabinet in an area of high RF interf
erence (revealed by frequent or
prolonged lighting of the LED in the receiver (random flicker is OK)
1. a. Remove the receiver board from its case, then insert the top of
the board into the slots
at the
top of t
he cabinet, as shown in Detail A in Figure 3 on the next page. Make sure
that the board rests on the correct row of tabs.
b. Swing the base of the board into the mounting clips and secure it to the cabinet with
the
accompanying screws.
c. Inse
rt the top o
f the control's board into the slot in the c
lips and position two clips at the
lower edge of the board.
d.
Swing this board into place and secure it with two additional screws.
Insta
llation and Setup Guide
2-2
Mounting Board
with
RF
Receiver (continued)
2.
In
ser
t ground
i
ng lugs (supplied with the receiver) through
the top of the cabinet into the
left-hand terminals of the antenna blocks (at the upper edge of the receiver board) and
secure them to the cabinet top with the screw
s pr
ovided (see Detail B).
3. Inse
rt the recei
ver's antennas through the top of the cabinet, into the blocks' right
-hand
terminals, and tighten the screws.
Figure 3. Mounting the PC Board and RF Receiver
Auxiliary Device Current D
raw
Worksheet
DEVICE
CURRENT
No. UNITS
TOTAL CURRENT
615
0 Fixed
-
Word Keypad
40mA/70mA**
6160 Alpha Keypad
40mA/150mA**
6150V Fixed
-
Word Display Voice Keypad
60mA/160mA**
6160V Alpha Display Voice Keypad
60mA/190mA
**
62
8
0 Touch Screen Keypad
1
4
0
mA/
2
5
5
mA**
Tuxedo Touch
140mA/260mA
**
Tux
-
WiFi
140mA/260mA
**
5881/
5882 RF Receiver
60mA
5883
H
Transceiver
80mA
4219
Zone Expander
30mA
4204
Relay
Uni
t
15/180mA
‡
4229
Zone Exp
a
nder/Relay Unit
30/100mA
‡
(Current available from Aux. terminals = 600 mA max.)
†
TOTAL =
*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw
.
** Values are for standby/alar
m; alarm
for keypads means armed with backlighting on and sounder on
†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Outp
ut
combined
must not exceed 600 mA
(500 mA ma
x from Aux. Output).
‡Values are for relays OFF/relays ON.
CALIFORNIA STATE FIRE MARSHALL
(CSFM
) AND UL RESIDENTIAL FIRE
24-HOUR BATTERY BACKUP REQUIREMENT
S
Th
e California State Fire Marshal
and UL have regulations which require that all residential fire alarm control panels must be provided with a
backup battery which has sufficient capacity to operate the panel and its attach
ed peripheral dev
ices
for 24 hours in the intended
st andby
co
ndition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requ
irements without
using a supplementary power supply,
provided tha
t th
e panel’s auxiliary power and
be
ll outpu
t
currents are limited as indicated below.
OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES
OUTPUT CURRENT LIMITATIONS
BATTERY INFORMATION
Output Current Total
Maximum Auxiliary Curre
nt
Battery Capaci
ty
To Use (Amp/Hrs)
Recommended B
at
tery
(Yu
a
sa Model No.)
600mA maximum total of
auxiliary power plus bell
output currents
45mA
160mA
200mA
425mA
500mA
4AH
7AH
8AH
14AH
18
AH
‡‡
NP4
-
12 (or ADEMCO 467)
NP7
-12
NP4
-12 (two) ‡
NP7
-12 (two)
‡
NPG18
-
12
‡
NOTE:
Use
two batteries, connected in p
ar
allel. O
b
tain
Battery Harness Kit
100
-
02111
. (Both batteries will fit inside the cabinet.)
‡‡
18AH must be mounted in a separate cabinet.
Mounting
and Wiring the C
ontrol
2-3
AC Power, Battery, and Ground Connections
1321 Transform
er
Connect
the
1321 Transformer (1321CN in
Canada) to terminals 1 and 2 on the control
board. See Wire Run Chart for wire size to
use.
•
Use caution when wiring the
transformer
to the control to guard
against blowing th
e transformer fuse
(the fuse i
s non-repl
aceable).
Wire Run Chart
Distance from control
Wire Size
Up to 50 feet
# 20
50–
100 feet
# 18
100-250 feet
# 16
•
Wiring to the AC transformer must not exceed 250 feet usi
ng 16 gauge wire. The voltage
reading b
etwe
en terminals 1 and 2 of the co
ntrol must
not fall below 16.5VAC or an “AC
LOSS” message will be displayed.
•
Do not plug the transformer into the AC outlet
until all wiring connections to the control
are complete.
As a safety precaution, always power down
the control when making such
c
on
nections
.
Battery Connections
1.
Place t
he 12
-
volt backup battery in the cabinet.
2. After all connections to the control are completed and AC power has been applied,
connect the red and black flying leads on the c
ontr
ol board to the battery. Do not
attach
these leads to the battery terminals un
til all connections are completed.
UL
For UL installations and Residential fire installations, refer to the chart on page 2-2
at left for the correct battery size required t
o meet the mandatory standby time.
Battery
Saver Feature
The battery will disco
nnect from the system after its voltage decreases below 9VDC. This
assists the control panel in recharging the battery when AC is restored.
IMPORTANT:
The panel will not pow
er u
p initially on battery power onl
y. You m
ust plug the
transformer in first, and
then connect the battery.
Earth Ground
•
This product has been designed and laboratory
-
tested to ensure its resistance to damage
from generally expected levels of lightn
ing
and electrical discharge, and does not n
ormally
require an earth ground.
•
If an earth ground is desired for additional protection in areas of severe electrical activity,
terminal 25 on the control board, or the cabinet, may be used as the ground connection
point
(use
minimum
14AWG
wire). The f
ollowing are examples of good earth gr
ounds
available at most installations.
Metal Cold Water Pipe:
Use a non-
corrosive metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is
elec
trically connected and secured
.
AC Powe
r Outlet Ground:
Available from 3-pron
g, 120VAC power outlets only. To test the
integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as
the UL Listed
Ideal Model 61
-
035, or equi
va
lent, av
a
ilable at most electrical supply stor
es.
Insta
llation and Setup Guide
2-4
Sounder (Bell) Connections
Basic Connections
1.
Make sounder connections
to
alarm output terminals 3 (+) and 4 (
–
).
2. If not using bell supervisi
on, connec
t the supplied 820 ohm resistor acros
s terminals 3 and
4. If using bell supervision, see Supervised Output paragraph below.
•
The 12VDC sounder output activates when an alarm occurs.
•
Total current drawn from th
is o
utput cannot exceed 2 amps (goin
g beyond
2 amps will
overload the power suppl
y, or may cause the electronic circuit protecting the sounder
output to trip).
•
You must install a battery, since the battery supplies this current.
Su
perv
ised Output
1. Connect the suppl
ied 820 o
hm Bell Supervision EOL resistor acr
oss the terminals of the last
sounder. See Figure 5.
Bell Supervision Note:
The value of the Bell Supervision EOL Resistor is 820 ohms.
High Impedance Device Note:
If a hig
h im
pedance sounding device is used
(ex. 745X3),
the bell supervision resistor (i
ncluded) must be installed at the device.
2. Set field
∗
91 Option Selection for Bell Supervision (option 1).
This control complies with NFPA requirements for temporal pulse s
ounding of fire notification
appli
ances. Tem
poral pulse s
ounding for a fire alarm consists of: 3 pulses
– pause
– 3 pulses
–
pause
– 3 pulses
–etc.
UL
•
Use only UL Listed sounding devices for
UL installations.
•
Bell supervision is
required for fire alarm
install
ations.
•
The total c
urrent drawn from the alarm
output and the
auxiliary power output,
combined, cannot exceed 600mA. In
addition, the sounding device must be a
UL Listed audible signal appliance rated
to operate in a 10.
5-13.8VDC voltage
range, and mus
t be mount
ed indoors.
Figure 5. Sounder Wiring (Supervised)
Connecting the Keypads and Other Addressable Devices
UL
For UL985 Residential Fire Installations
,
t
wo keypads must be installed, one near the control panel
an
d
the other can be
remotely moun
ted.
One
keypad, nearest the control panel, must use a direct connection
to the control panel
. The second
(possible remo
te) keypad must be connected to the control panel via an ECP
-
ISO (
ECP Isolator)
.
Connections
Conn
ect keypads and other addressa
bl
e device
s
(4204, 4219, 4229,
5881,
GSMV
4G
, etc.
)
to the control’s keypad terminals as shown on the
Summary of Connections diagram. The
system supports up to 8 keypads, which can be assigned to partitions in any combination
(see program fields *190-*196)
.
Use the
Table of Device Addresses to determine the appropriate address for each
device
.
Determine
wire size using the Wire Run Chart
on the following page. For single 4-wire runs,
determine the current drawn by all units, then refe
r to the
Wiring Run chart to determine the
maxim
um length that can be safely used for each wire siz
e.
Supplementary Power
(optional)
UL
Use a UL Listed,
battery
-backed supply for
UL installation
s. The
battery supplies power to
these k
eypads in case of
AC power loss.
The bat
tery
-backed power
supply
shoul
d have
enough power to supply
the keypads with the UL
required minimum standby
power time.
Use supplementary power if the
control’s aux. power load for al
l
devices
exceeds 600mA (suggested
power supply
: AD12612). Connect as
shown in F
igure 6. Be sure to
connect the negative (
–) terminal on
the power supply
unit to terminal 4
(AUX
–) on the control.
IMPORTANT:
Keypa
ds powered
from supplies that do not have a
backup
battery will not function if
AC power is lost. Mak
e sure to
power at least one keypad in each
partition from the control’s auxiliary
power output.
Figure 6. Using a Suppl
ementary Power
Supply
Mounting
and Wiring the C
ontrol
2-5
Keypad Notes
Set device
addresses
. Refer to the i
nstructions included with the devices and set each
address
according to the
Table of Device Addresses
.
See
data
fields *190
-*196 in
the
Progra
mming Guide
for details on enabling keyp
ad
addresses
, assigning ke
ypad partitions
, and selecting keypad sounding options.
IMPORTANT:
Each keypad must be assigned a unique, predefined addres
s,
from 16 to 23.
The first keyp
ad is ad
dress 16
(default = partition 1, all sounds enabled).
TOUCH SCREEN KEYPAD (AUI)
NOTES:
•
Use of AUI devices (e.g., 6280, Tuxedo) is independent from standard keypads and does
not affect the number of s
tandard keypads the system can
support.
•
AUI devices must be set for address 1,
2, 5**, or 6
** depending on which unit is enabled in
field *189.
** VISTA
-
20P series
Communication
Device
(Long Range Radio
)
Connections
Connect the data in/data out te
rminals and voltage input term
in
als of t
h
e
communication
device
to the control's keypad connection points.
Set the
device’s
address to “03” following
the instructions provided with the device
.
•
Use
a compatible
communic
ation device
(e.g.,
GSMV4G
, GS
MX
4G, IGSM
V4G
).
U
L
The us
er shall be notified
that all equipment neces
sary for
the transmission of alarm, trouble, supervisory and
other signals
located at the residence shall have a s
econdary power capacity of 24 hours.
Wire
Ru
n
Chart
F
or Devices* Drawing Aux Power From The Control (12V+ & 12V
–
)
Wire
TOTAL CURREN
T DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size
50 mA or less
100 mA
300 mA
500 mA
600 mA
#22
900 ft (274m)
450 ft (137m)
150 ft (46m)
90 ft (27m)
75 ft
(
2
3m)
#2
0
1400 ft (427m)
700 ft (213m)
240 ft (73m)
140 ft (43m)
120 ft (37m)
#18
1500
ft (457m)
1100 ft (335m)
350 ft (107m)
220 ft (67m)
170 ft (52m)
#16
1500 ft (457m)
1500 ft (457m)
550 ft (168m)
350 ft (107m)
270 ft (
82m)
* Includes Keypads, RF R
eceiver
s, Zone Expander/Relay Units, and
Communicat
ion Device.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based
on the
current draw of that dev
ice
alone
.
The length of all wire runs for both partitions combined m
ust not exceed 1500 feet (457m) when unshielded quad conductor cable is used
(750 feet if shielded cable is used). This restriction is due to the capacitiv
e effect on the data lines when
quad cabl
e is used.
Table of Device Addresses
This Device
Uses Addre
ss
Reports as
††
Enabled By...
RF Receiver
00
100
*56 zone programming: input device type entry
AUI 1
(touchscreen)
01
automatic if AUI enable field *189 e
nabled for AUI 1
AUI 2
(touch
sc
r
een)
02
automatic if AUI enable field *189 enabled for AUI 2
AUI 3
(touchscreen) (V20P)
05
automatic if AUI enable field *189 enabled for AUI 3
AUI 4
(touchscreen) (V20P)
06
automatic if AUI enable field *189 enabled f
or A
s
UI 4
Communication Devic
e
(
L
RR
)
03
103
automatic if
communic
ation device
is enabled in
field *29
Zone Expanders (4219/4229):
module 1 (for zones 09 -
16)
module 2 (for zones 17 -
24)
module 3 (for zones 25 -
32)
module 4 zones 33 -
40
module 5 zones
41
-
48
07**
08
09
†
10
†
11
†
107
108
109
110
111
*56 zone programming: input device type, entry 2, then:
automatic if zone no. 9-
16 set as AW type or relay assigned
automatic if zone no. 17-
24 set as AW type or relay assigned
automatic if
zone no. 25-
32
set as AW type or relay assigned
automat
ic if zone no. 33-
40 set as AW type or relay assigned
automatic if zone no. 41
-
48 set as AW type or relay assigned
Relay Modules (4204):
module 1
module 2
module 3
module 4
12
13
14
†
15
†
112
113
114
115
*79 output
device programming: device ad
dr
es
s prom
p
t:
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
Keypads:
keypad 1
keypad 2
keypad 3
keypad 4
keypad 5
keypad 6
keypad 7
keypad
8
16
17
18
19
20
21
22
23
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
data field programming as listed below:
always enabled for partition 1, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data fi
eld *195
data fi
e
ld *196
RIS Communication
25
n
/a
autom
a
tic
** address 07 not available if zone
-doubling enabled
† 4219/4229
addresses 9-
11 and 4204
addresses 14-
15 apply to the VISTA
-20P.
†† Addressable devices are identified by “
1” plus the device address
when reporting. Enter report code for zone 91 to enable addressable
device reporting (default = reports enabled). See field *199 for addressable device 3
-digit/2-
digit identification keypad display options
.
Insta
llation and Setup Guide
2-6
Hardwire Zones and Zone Ex
pa
ns
ion
Ha
r
dwire Zones
Normally Open Zones/ N.O. EOLR Zones
1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the
EOLR
across the loop wires at the last device.
2. Enable norm
ally open/EOLR
zones
using
Zone Programming mode, “Hardwire Type”
prompt.
Normally Closed Zones/ N.C. EOLR Zones
1. Connect closed circuit devices in series in the high (+) side o
f the loop; for EOLR zones,
connect the EOLR
in series following the last device
.
2. Enabl
e normally closed/EOLR
zones using Zone Programming mode, “Hardwire Type”
prompt.
End of Line Resistor (EOLR) Notes
•
If the EOLR is not at
the end of the loop, the zone is not properly supervised and t
he
system may not respond to an
“open” on
the zone.
•
Zone 1 is intended for EOLR
only.
UL
For UL commercial burglar alarm installations, use EOLR zones.
Double
-
Balanced Zones
(V20P only)
Connect as shown below (res
i
stor provided for
one device)
.
IMPORTA
NT:
Double-balanced zones provide
zone tamper protection, and should be used as
burglary zones only.
Do not use double
-balanced zones as fire
zones.
13
12
14
T
AMPER
CON
T
ACTS
T
AMPER
CON
T
ACTS
Fig. 7. Typical Double Balanced Zones
Zone Doubling
(V20P only)
Thi
s
fe
ature
p
rovides two hardwired normally
closed zones for each standard hardwired zone
connected to the control’s terminals (but does
not increase the total numbe
r of zones
supported by the control). If enabled (Zone
Programm
ing mode, “Hardwire Type” prom
pt,
option
“3”), hardwire zones are automatically
paired as shown in the table. Connect as
shown (resistors
supplied
; use 3k and 6.2k 5%,
1/4W or bigger resis
tors
).
•
Do not use zone doubling for fire zones.
NOTE:
A short acr
oss the EOL (i.e., at
terminal
) on
either
zone of a zone-doubled pair
or on a double-
balanced zone causes a tamper
condition (displayed as CHECK plus zone
numbers).
10
11
Fig. 8. Typical Zone Doubling Wiring
Zone Doubling Table
Zone
Paired with zone
2
10
3
11
4
12
5
13
6
14
7
15
8
16
NOTE:
Zone numbers used for zone doubling
cannot be used for anything else (ex. cannot
be used for 4219 zones)
Smoke Detectors
1.
Connect up to 16 (
10, if “clean me” option used) 2
-
wire smoke detectors across zone 1
terminals 8 (+) and 9 (
-) as s
hown
in th
e Summary of Connections diagram at the back
this manual. Observe proper polarity when connecting the detectors.
2. Connect an EOL resistor across the loop wires at the last detector.
3.
Connect 4-wire smoke detecto
rs (
number of detectors
depends
on detec
tor current draw)
to any zone from 2-8 as shown in Figures
9a and 9b (on next page).
Power Reset:
This control does not automatically reset power t
o 4-wire smoke detector
zones, so you must use a relay (e.g., 4204, 4229)
, or on
-b oard trigger to reset power
(also required for fire verification). Do this by programming the designated relay/trigger
as zone type 54 (fire zone re
set); see
On
-Board Trigger
section for other information.
NOTE:
Max
imum current on trigger 17 is 10
0m
A.
Mounting
and Wiring the C
ontrol
2-7
Smoke Detector Notes
•
Fire Verification (zone type 16):
The
control panel will “verify” a fire alarm by resetting the
smoke detectors after the first alarm trigger, and then waiting up t
o 90 seconds for a
second alar
m
trigger.
If the smoke detector or thermostat does not trigger again, the control
will disregard the first trigger, and no alarm signal will occur. This feat
ure eliminates false
alarms due to electrical or physical transients
.
SIA Installations:
If usin
g fire ver
ification on zones other than zone 1, UL Fire Alarm Listed
relay accessories must be used to reset power as described in the Power Reset paragraph
above.
•
The zone 1 alarm current supports only one smoke detector in
the alarmed state.
•
Clean Me
Opt ion:
If enabled (field *174 = 1; *56 zone programming, response time prompt
= 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the
maximum number of detectors is redu
ced to 10 (not standard 16). R
efer to th
e ESL
documentation included with the smoke detector for information regarding compatibility with
the clean-me option.
•
Do not use 4
-
wire smoke det
ectors on zone 1.
Figure 9a. 4
-Wire Smoke Detector Using Relay for Power Reset
Figure 9b.
4-W
ire Sm
oke Detector Using Output 17 for Power Reset
4219/4229
Expansion
Zones
1.
Connect each module to the control’s keypad terminals a
nd set the device addresses.
See the Table of Device Addresses to s
elect an appropriate address f
or each mo
dule.
•
VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules.
•
VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules
.
2. Connect sensors to the module’s loops.
•
Use
appropriate
end-
of-line resistors (2k ohms)
at the end of
loops connected to the
4219/4229
modules.
•
Expansion zones have normal response time
(300–
500 msec), except zone connected
to each module’s loop “A,” which can be set
for fast response (10–
15 mse
c).
3. If using relays with the 4229, connect t
he desired field wiring to the unit's relay contact
terminals.
Insta
llation and Setup Guide
2-8
Installing the RF Receiver and Wireless Transmitter Zones
C
ompatible Receivers
Use
an
y
ADEMCO
5800 Series Wireless Receivers, such as:
RF Receiver
No. of Zones
5881EN
L/5882L
up to 8
5881EN
M/5882M
, up to 16
6150RF
5881EN
H,
VISTA-20P = up to 40 plus 16 buttons
5883
H
,
6160RF
VISTA
-
15
P
= up to 26 plus 8 buttons
Re
ce
iv
er Con
n
ections
WIRELESS ZONE
NUMBERS
VISTA-
20P:
transmitter zones 9-
48
button zones 49-
64
VISTA-
15P:
transmitter zones 9-
34
button zones 49-
56
1.
Set Device Address to “00” (set all switches to the right, “off”
p
osition).
2. Mount the receiv
er, noting
that the RF receiver can detect signals from transmitters
within a nominal range of 200 feet.
3. Connect the receiver's wire harness to the control's keypad terminals. Plug the
connector at the other end of the har
ness into the receiver. Refer t
o the inst
allation
instructions provided with the receiver for further installation procedures regarding
antenna mounting, etc.
Figure
10. 5881/
5882 RF Receiver
(cover removed)
RF Receiv
er
N
otes
† These fields must be
enabled for
Residential Fire,
UL Residential Burglar
Alarm, and UL Commercial
Burglar Alarm installations.
Set the following options:
*22
RF Jam Option†
*24
RF House ID Code
(if using wireless keypads) for ea
ch parti
tion
*67
Transmitter Low Battery Report Code†
*75
Transmitter Low battery restore report code†
•
The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if
communication between the panel
and
receiver is interrupted, or if
no vali
d RF signals from
at least one supervised transmitter are received within 12 hours.
If the receiver is mounted remotely:
•
Place the RF receiver in a high, centrally located area for best recepti
on.
•
Do not locate the receiver
or transmi
tters on or near metal objects. This will decrease
range and/or block transmissions.
•
Do not locate the RF receiver in an area of high RF interference (indicated by frequent or
prolonged lig
hti ng of the LED in the receiver;
ran
dom fli
cker is OK).
•
Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from
the microprocessors in those units.
Mounting
and Wiring the C
ontrol
2-9
Installing the
Transmitters
•
Refer to the table of c
o
mpatible devices at the back
of
t
his ma
n
ual.
•
Supervised transmitters† send check
-in signals to the receiver at 70-90 minute intervals. If
at least one check
-in message is not received
from each transmitter within a 12
-
hour period,
the “missing” transmit
ter number(s) and “CHECK
XX” i
s displaye
d. († Hand-held
transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send check
-in
signals.)
•
To
be sure rec
eption of the transmitter's signal at the proposed mounting location i
s
adequate, perform a Go/No Go
Test, des
cribed in the
Testing the System
section.
•
Install transmitters in accordance with the instructions provided with each.
•
Set
5827, 5827BD,
5804BD wireless keypads to the programmed
House ID (field *24),
using its DIP switches (5827) or follow the instructions provided with the device.
•
Use *56 or *58 Zone Programming Menu modes to progr
am zone information and enroll
transmitters (VISTA-20P: zones 9-48, bu
ttons 49
-64; VISTA
-15P: zones 9
-34
, butto
ns 49
-
56).
•
Wireless Keys:
Use Wireless Key Programming Templates section of the *58 Zone
Programming Menu mode to program zone information and
enroll each button of the
wireless keys used. Once a wireless key is en
rolled, it must be assigned t
o a user b
efore it
becomes active. See Adding/Deleting Security Codes section for procedure.
The RF supervision period for the VISTA
-20PCN and VISTA
-15PCN is three hours for Fire zones
(Zone Type 9 and 16) and 12 hours for al
l other zone types.
UL
The foll
ow
ing tr
ansmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804,
5804BD, 5814, 5816TE
MP, 5819, 5819WHS & BRS, and 5850.
The 5827BD
can be used in UL Listed Residential
Burglar installations.
Trans
mi
tt
er Bat
t
ery Life
•
See Wireless Transmitter paragraph in the
Limitations of This Alarm System
sta
tement
located at the end of this manual for information on transmitter battery life.
• Some transmitters (e.g., 58
02 and
5802CP) cont
ain long-life but non-replaceable
batteries, and no battery installation is required. At the end of their life, the complete unit
must be replaced (and a new serial number enrolled by the control).
• Button
-type transmitters
(such as
5801, 580
2, and 5802CP
) should be periodically tested
for battery life.
• The 5802MN and 5804 Button Transmitters have replaceable batteries.
Do
not install batteries in wireless transmit
ters until you are ready to enro
ll during
system
programming. After enrolling, batteries need not be removed.
Insta
llation and Setup Guide
2-10
Connecting Relay Modules
and Output Triggers
4204/4229 Relay Modules
UL
For UL installation
requirements, refer t
o the
Installation Instruction
s for
the
4204.
1.
Mount either remotely or in the control panel.
2. Connect each module to the control’s keypad terminals and set the device addresses as
previously described in the
Connecting
Keypads and Other A
ddressable Device
s
section. U
se the con
nector harness supplied with the module. Use standard 4-conductor
twisted cable for long wiring runs.
VISTA-20P: Up to 16 relays
VISTA-15P: Up to 8 rela
ys
3. Connect the desired field wiring to the unit's relay c
ontact terminals.
•
Supervisi
on:
4204
and 4229
modules are supervised against removal. The module’s
device address
is displayed as follows if a module is disconnected from the control’s
terminals, or if the
module cover is removed and t
he tamper
jumper is installed:
Alpha:
CHECK xx Wire Expansion
FAU
LT xx Wire Expansion
ALARM xx Wire Expansion
Fixed
-Glass: lxx (or 91 if field *199 set for 2-digit display)
where “xx is the module’s address.
•
If comm
unication/tamper failure occur
s on
a dev
ice with zones wired to it, all zones on the
device will be displayed in their respective partitions.
On
-
Board Triggers
Connect field wiring to the desired trigger pin on the 8
-
pin trigger connector centrally l
o
cated
above the terminal stri
p.
•
Use a
4-wire cable
(N4632-4,
not
supplied) as shown below.
Figure
13b. On
-Board Trigger
Connector
with 4
-Wire Cable for Trigger Use On
ly
•
Trigger outputs
are normally high, and go low upon prog
rammed condition.
•
The output
s can be
programmed for inverted operation (normally low, go high) using *79
Menu mode.
•
Program these triggers using *80/*81 Menu modes as you would for any other relay
output.
•
When using these outputs, note:
pin 1 =
out
put number 17 (trigger 1):
15
ohms to
ground when closed (output low), open when off (output high, normal
default); can be used to reset smoke detector power (must set “output normal low =
yes” in *79 Menu mode, and set for zone type 54, fire zone reset
, in *80 Menu
mode); or can supp
ort 12V
relay module (
e.g., Altronix AX
-RBS)
that draws less than
100mA
pin 5 =
output number 18 (trigg
er 2):
100 ohms to ground when closed (output low); open when off (output high, normal
default); or can support 12V re
lay module that draws less tha
n 20mA
UL
If on
-board triggers are used, the wiring between the control unit and the UL Listed device mus
t
be run in conduit, be no more than 3 feet apart
, and have no intervening barriers or walls.
Mounting
and Wiring the C
ontrol
2-11
Phone Line
and Audio
Alarm Verification (AAV) Conn
ecti
ons
Phone Line
Connect incoming
phone line and
handset wiring to the main terminal block (via an
RJ31X
jack) as shown in the Summary of Connections diagram at t
he back of this manual.
Wire
co
lo
rs rep
r
esent the colors of the cable to the RJ31X jack.
Audio Alarm Verification
Connections
(UVS System
)
Using the UVS System with UVCM Module
The UVS system provides audio alarm verification via the phone line.
•
Refer to the connection diagra
m below.
•
Connections use one of the on
-board triggers
.
•
Set field *91 for AAV and program the appropriate output (out
put 17 or 18) using *80 Menu
mode: select zone type 60 and output action 1 (clos
e for 2 seconds).
•
For voice
session m
onitoring, connect an EOLR zone to UVCM module terminals 6 & 7, and
program the zone as zone type 81 (*56 Menu mode).
E.g., Using outp
ut 18 for the trigger, program an output function in *80 Menu mode as:
ZT = 60
, P = 0, Action = 1, Device = 18
•
Sugge
sted AAV Module: ADEMCO UVS (shown) or Eagle 1250
UL
UL installations using the AAV feature must use the ADEMCO UVCM module (part of t
he
ADEMCO UVS system).
Figure
15. Connection of AAV Unit
Insta
llation and Setup Guide
2-12
Audio Alarm
Verification
Conn
ections
(AV
S Sy
stem)
Using the AVS System with AVS Module and AVST Remote Stations
The AVS system provides audio alarm verification via the phone line or via AlarmNet if
the
GSMV
4G
or
GSMX4G
module
is used as the communication device.
Refer to the inst
ructions inc
luded with
the AVS system for installation procedures. The
following is a summary.
Mounting
the AVS Base Unit
As shipped, the AVS Base unit board
comes pre-mounted on its mounting
bracket, which is designed to mount
inside the
control cabinet.
Refer to the
diagram at
right.
a. Position the mounting plate/PC
board assembly in the bottom of the
control’s cabinet.
b. Slide the mounting plate to the right
so that the plate’s left-hand tang
slides under the cabinet’s tie
-wrap
loop.
c. Secure the assembly to the ca
binet
using the two self
-tapping screws
provided.
BATTERY NOTE:
When using a 7AH battery, mount the battery vertically on the bottom left
-
hand side of the cabinet, with the terminals facing down and right (negative termi
nal closest
to the
PC board br
acket).
Wiring the AVS to the Control
The AVS Base unit board has several terminal blocks for making connections to remote
stations, telephone lines, and to the control panel. The AVS base unit connects to the
control
’s ECP t
erminals, with all
other ECP d
evices con
necting to the AVS base unit ECP
terminals.
See the diagram on
the next
page for specific wiring connections.
DIP Switch:
Set the AVS DIP switch to the appropriate address (V15P =
08; V20P = 11).
IMPORTANT:
The AVS
should be the onl
y ECP device
connected
to the control’s ECP
terminals. Connect all other ECP devices (keypads, expander modules, etc.) to the ECP
terminals on the AVS board.
Connecting an
Optional GSMV
4G
/GSMX4G
Module
a. If using a GSMV
4G
or GSMX4G
modu
le for 2-way voic
e operation,
install t
he module
according to its instructions.
NOTE:
The module must be mounted within three feet of the
control.
b. Connect the audio cable from the
module to the Audio connector on the AVS board. The
audio cable is suppl
ied with th
e GSMV
4G
/GSMX4G
mod
ule.
c. Co
mplete all other GSMV
4G
/GSMX4G
wiring following the instructions included with that
module.
The following
summarizes the programming steps for AVS operation
(refer to the Programming
Guide for details of the AVS Qui
ck Command options)
:
a. Instal
l the AVS
module according to its instructions.
b. Use one of the control’s AVS Quick Program commands as follows
:
•
installer code + [#] + 03:
enable AVS operation
without panel sounds on the AVST
•
installer code + [#] +
04:
enabl
e AVS operation and
enable pan
el sounds on the AVST
speaker
•
installer code + [#] + 05:
remove all programming options set by [#] + 03 quick
command
•
installer code + [#] + 06
: remove all programming options set by [#] + 04 quick
command
c
.
Use data
field
∗
55 Dynamic
Si
gn
aling
P
riority to select the desired reporting paths.
Mounting
and Wiring the C
ontrol
2-13
Figure 1
6. Connections for the AVS System
Insta
llation and Setup Guide
2-14
3-1
SECTION 3
System Communication and Operation
Panel Communication
with C
entral Station
This
system accommodates several formats for reporting alarms and other system conditions to the Central
Station. The process of a successful transmission consists of both the method of communication between the
control panel and the Central S
tation rec
eiver; and the actual way the information is sent and displayed at the
Central Station.
When the panel calls the Central Station receiver, it waits to hear a “handshake” frequency from the receiver to
confirm that t
he receiv
er is on-
line and ready
to recei
ve its message. Once the panel hears the handshake
it is
programmed to listen for, it sends its message. The panel then waits for a “
kissoff” frequency from the receiver
acknowledging
that the
message was received
and
under
stood.
If the handshake frequency is not given or is not understood by the panel, the panel will not send its message.
Once the handshake frequency is received and understood by the panel, the panel sends its message
. If the
re is
an error in the
transmiss
ion (the receiver does not receive a “valid” message), the kissoff frequency is not given by
the Central Station receiver.
The panel makes a total of eight attempts to the primary telephone number and eight attempts t
o the secondary
telephone num
ber
(if pr
ogrammed) to get a valid message through. If the panel is not successful after its
numerous attempts, the keypad displays COMM. FAILURE (on alpha keypads) or FC (on fixed-
word keypads).
Report Code
Forma
ts
The following chart indicates the types of (handshake/kissoff) frequencies that the panel supports and the different
formats that can be sent with each.
FORMAT
HANDSHAKE
TRANSMITS DATA
KISSOFF
TRANSMIT TIME
Low S
p
eed
1400
Hz
1900Hz (10PPS)
14
00
H
z
Under
15 secs
3+1, 4+1, 4+2
(Standard report)
Sescoa/Rad
2300 Hz
1800Hz (20PPS)
2300 Hz
Under 10 secs
3+1, 4+1, 4+2
(Standard report)
Express
1400
–
2300 Hz
DTMF (10 cps)
1400 Hz
Under 3 secs
4+2
Contact ID
1400
–
230
0 Hz
DTMF (10 cps)
14
00
H
z
Under
3 secs
The following table describes each format in greater detail.
FORMAT TYPE
DESCRIPTION
3+1 and 4+1
Standard Formats
Comprises a 3
-
(or 4
-
) digit subscriber number and a s
i
ngle
-
dig
it report
code (e.g.,
Al
a
rm, Tro
u
ble, Restore, Open, Close, etc).
3+1 and 4+1
Expanded Formats
Comprises a 3
-
(or 4
-
) digit subscriber number and a two
-
digit report code.
The first digit is displayed on the first line. On the second line, it is r
epeated
3 (or 4) times and is
followed b
y the second digit. This is the “expanded”
digit.
4+2 Format
Comprises a 4
-
digit subscriber number and 2
-
digit report code.
ADEMCO Contact ID
Reporting Format
Comprises a 4
-
or 10
-
digit subscriber number (dependi
n
g on for
mat
selected), 1
-digi
t event qua
lifier (“new” or “restore”), 3
-digit event code, and
3-digit zone number, user number, or system status number (see the
following page).
Installation and Setup Guide
3-2
The following table lists codes for reports sent in different formats:
Cod
e for
Cod
e for
Type of
3+1/4+1
3+
1/4+1
Co
de for
Report
Standard
Expanded
4+2
Alarm
SSS(S) A
SSS(S) A
SSSS AZ
AAA(A) Z
Trouble
SSS(S) T
SSS(S) T
SSSS Tt
TTT(T) t
Bypass
SSS(S) B
SSS(S) B
SSSS Bb
BBB(B) b
AC Loss
SSS(S) E
SSS(S) E
SSSS EA
C
EE
E(E) A
C
Low Batt
SSS(S) L
SSS
(S)
L
SSSS
LL
B
LLL(L) L
B
Open
SSS(S) O
SSS(S) O
SSSS OU
OOO(O) U
Close
SSS(S) C
SSS(S) C
SSSS CU
CCC(C) U
Test
SSS(S) G
SSS(S) G
SSSS Gg
GGG(G)g
Restore
SSS(S) R
SSS(S) R
SSSS RZ
Alarm
RRR(R) Z
AC Restore
SSS(
S) R
A
SSS
(S) R
A
SSSSR
A
A
c
R
A
R
A
R
A
(R
A
)A
c
LoBat Res.
SSS(S) R
L
SSS(S) R
L
SSSS R
L
L
B
R
L
R
L
R
L
(R
L
)L
B
Trouble Res.
SSS(S) R
T
SSS(S) R
T
SSSS R
T
t
R
T
R
T
R
T
(R
T
)t
Bypass Res.
SSS(S) R
B
SSS(S) R
B
SSSS R
B
b
R
B
R
B
R
B
(R
B
)b
Where:
SSS or SSSS =
Subscriber ID
C =
Close Code–
1st Digit
A =
Alar
m C
ode–
1st
digit
U =
User Number (in hex)
Z =
Typically Zone Number*
–2nd digit
Gg =
Test Code (1st & 2nd digits)
Tt =
Trouble Code (1st & 2nd digits)
R =
Restore Code (Alarm)
Bb =
Bypass Code (1st & 2nd digits)
R
T
t =
Restor
e Code (T
rbl) 1st & 2nd digits
EA
C =
AC
Loss Code (1st & 2nd digits)
R
B
b =
Restore Code (Byps) 1st & 2nd digits
LL
B =
Low Battery Code (1st & 2nd digits)
R
A
A
C
=
Restore Code (AC) 1st & 2nd digits
O =
Open Code–
1st Digit
R
L
L
B =
Restore Code (Bat) 1st &
2nd digit
s
*Zone numbers for:
& #, or B
= 99; 1 +
, or A = 95; 3 + #, or C = 96; Duress = 92
System Communication
3-3
Ademco Contact ID
®
The Ademco Contact ID
®
Reporting Format comprises the following:
4-digit or 10-
digit subscriber number (depending on format selected).
1-digit
event qua
lifier (“new” or “restore”).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see
below
).
Ademco Contact ID
®
Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where:
CCCC(CCCCCC)
=Custome
r (subscriber) ID
Q =
Event qualifier, where: E = new event , and R = restore
EEE =
Event code (3 hexadecimal digits)
Note:
For a complete list of event codes, refer to the central office receiver
manual.
GG =
Partition Nu
mber (system messages
show “
00”)
ZZZ =
Zone/contact ID number reporting the alarm, or user number for open/close
reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes
in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
(some event co
des may not apply to
certain
control panels)
Code
Definition
110
Fire Alarm
121
Duress
122
Alarm, 24
-
hour Silent
123
Alarm, 24
-
hour Audible
131
Alarm, Perimeter
132
Alarm, Interior
134
Alarm, Entry/Exit
135
Alarm, Day/Night
143
Alarm, Expansio
n Module
145
ECP
Mo
d
ule cov
e
r tamper
146
Silent Burglary
150
Alarm, 24
-
Hour Auxiliary/Monitor zone
162
Carbon Monoxide
301
AC Power
302
Low System Battery/Battery Test Fail
305
System Reset (Log only)
321
Bell/Siren Trouble
333
Trouble, Expa
ns
i
on Mod.
Supervision
341
Trouble, ECP Cover Tamper
344
RF Receiver
Jam
351
Telco Line
Fault
353
Long Range Radio
Trouble
354
Failure to Communicate
373
Fire
Loop Trouble
374
E
x
it Erro
r
Alarm
380
Global Trouble, Trouble Day/Night
Code
Definition
381
RF Sensor Supervision
382
Supervision Auxiliary Wire Zone
383
RF Sensor Tamper
384
RF Sensor Low
-
battery
393
Clean Me
401
Disar
med, Armed AWAY, A
rm
e
d
MAXIM
U
M
403
Schedule Arm/Disarm AWAY
406
Cancel by User
407
Remote Arm/Disarm (Downloading)
408
Quick Arm AWAY
409
Keyswitch
Arm/Disarm AWAY
441
Disarmed/Armed STAY/INSTANT,
Quick
-
Arm STAY/INSTANT
442
Keyswit
ch
Arm/Dis
a
rm STAY
455
Scheduled Arm Fail
459
Recent Closing
(SIA panels only)
570
Bypass
601
Manually Triggered Dialer Test
602
Periodic Test
606
AAV to Follow
607
Walk Test Entered/Exited
623
Event Log 80% Full
625
Real
-
Time C
lock was Changed (
lo
g
only)
627
Program Mode Entry (log only)
628
Program Mode Exit (log only)
642
Latch Key (log only)
750
-
789
Reserved for Configurable Zone Type
report codes (check with central station
when using these codes)
Installation and Setup Guide
3-4
Uploading/Downl
oading via the Int
ernet
UL
: Up/downloading via the Internet has not been evaluated by UL.
This control, when used with a compatible Internet/Intranet Communication
Device
, supports upload/download
programming capability via the Internet using the AlarmNet
network or, depen
ding on the
communication
module used, a Private local area network (Intranet). This allows site maintenance independent of central
station monitoring, and modification to sites globally via the Internet. Depending on the module used, Int
ernet
connection f
rom the pr
otected premises is either via high speed (broadband) cable or phone service, or via the
GSM/GPRS digital cellular network (GSM modules).
Refer to the instructions provided with the communication module for information regarding its installation,
programmi
ng, and registration. The System Requirements table below lists two sets of system requirements,
depending upon whether you intend to communicate over the Internet or whether you are communicating over a
Private LAN (Intranet).
Compatible Commu
ni cation M
odules:
The following modules support Internet uploading/downloading, but
future modules may also provide Internet upload/download support; refer to the module’s instructions for
compatibility.
Compatible Modules: GSMV4G, GSMX4G, etc.
System Req
ui rements
I
nternet Communication
At the Installation Site:
•
Appropriate Internet Communication Module
•
7720P Programmer
•
Broadband Internet Access (for wired modules)
•
Broadband (Cable/DSL) Modem (for wir
ed modules)
•
Broadband (Cable/DSL) Router (for
wired modu
les if
connecting more than one device to the Internet)
•
IP compatible Control Panel
At the Downloading Office:
•
Broadband Internet Access
•
Broadband (Cable/DSL) Modem
•
Broadband (Cable/DSL) R
outer (optional, if connecting
more than one de
vice to th
e Internet)
•
Computer running Compass Downloading Software
version that supports Internet upload/download for this
control.
Intranet (Private LAN) Communication
, if applicable*
At the Installation Site:
•
Internet/Intranet Communication Module
•
7720P Pr
ogrammer
•
Ethernet Network Connection
•
IP compatible Control Panel
At the Downloading Office:
•
7810iR
-ent IP Receiver
•
Internal Router
•
Computer(s) running the following software:
- Compass Do
wnloading Software version that supports
IP upl
oad/downloa
d for this control.
- Compass Connect Data Server Application
- Compass Connect Control Server Application
* see module’s instructions for applicability for LAN usage
(ex. 7845i
-ent supports LAN)
NOTE:
Compass, the Compass Connect Data Server,
and
the C
ompass Connect Control Server applications may all
be installed on the same computer if desired. If they are
installed on one computer, the computer must have a fixed
IP Address.
To set up the control panel, do the following:
1. Connect the modul
e to the
control panel’s ECP (keypad) terminals.
2. Internet Users: For wired modules, connect the module to the Internet via a cable/DSL modem and router.
Intranet Users: Connect the module to the Intranet
(LAN) via the appropriate Ethernet connection.
3. Enable
the module in the control panel (
using
∗
29 Menu mode) to enable alarm reporting and module
supervision.
4. Using the module’s programming menus (via
∗
29 Menu mode or 7720P programmer), program the
communication device module for address 3 and pr
ogr
am
the
module’s
other options
as required.
5. Register the module with AlarmNet. The module must be registered before downloading or alarm reporting can
take place.
To perform upload/download functions:
1. Connect the computer to the Internet and star
t the Compa
ss downloading software.
2. Open the control’s account, then select the Communications function and click the
Connect
button.
3. At the Connect screen, check that the control’s MAC address is enter
ed and the TCP/IP checkbox is checked.
4. Clic
k
Connect
.
The Internet connection to the control is made automatically via AlarmNet.
5. Once connected, use the Compass downloading software as normal to perform upload/download functions.
System Operation
3-5
System Security Co
des
The systems provides
one Instal
ler code, one System Master code, plus a set of other user codes intended for
other users of the system. These codes can each be assigned one of 5 authority levels, which determine the
functions eac
h code can perform as listed in the table below
.
VISTA-
20
P: Provides 48 security codes (plus Installer code), including one System Master code, two Partition
Master codes, and 45 general user codes.
VISTA-
15P: Provides 32 security codes (plus Installer code), including one System Master code and 31 gene
ral
user
codes.
Authority Levels
(can be assigned to users 03-
49 only; users 1 and 2 cannot be changed)
Level
User No.
Functions
Installer
01
(default=4112) perform all security fun
ctions except can disarm only if used to arm; c
an
enter
program mode; can change System Master code; cannot assign other user codes
NOTE: For security purposes, the factory default installer code should be changed.
System Master
02
(default 1234) onl
y one system master code per system; can perform al
l
s
ecurity
functions,
add/delete users in either partition, change system master code, view event log, set system
clock, program keypad macro, program scheduled events, activate output devices
(triggers/re
lays)
Partition
Master
(default)
P1 = 03
P2 = 33
V
IS
T
A
-
20P.
S
ame as Master, except add/delete users limited to assigned partition only,
(these users can be assigned different authority levels, if desired; any user can be
assigned the partition master authority level)
0
-
User
03
-
49 (V20P)
03
-
33 (V15P)
perf
or
m
securi
t
y functions (arm, disarm, etc.) only; cannot add/delete users, view event log,
set system clock or program scheduled events
1
-
Arm Only
see “user”
arm system only
2
-
Guest
see “user”
can disarm
the system only if it was used to arm the system
3
-
D
u
ress
se
e
“user”
performs security functions, but also silently sends a duress message to the central station;
reports as duress code user number.
4
-
Partition
Master
see “user”
VISTA
-
20P. See Partition
Master paragraph above; used to assign other user n
um
b
ers as
partition masters
Refer to the user guide for
procedures on adding/deleting security codes and changing user attributes.
The following is a brief description of how to add user codes
.
Changing the System Master code
:
Using Installer code: Inst
aller code
+ [8] + 02 + new code
Using current System Master code: System Master code + [8] + 02 + new code + new code again
Adding a User Code:
Master code + [8] + 2-
digit user no. + user’s code
Deleting a User Code:
Master code + [8] + 2-
digit user no. +
[#] [0]
Assigning Attributes:
Master code + [8] + 2-
digit user no. + [#] [attribute no.] + value
Attributes:
Values
1 =
Authority Level
0-4 (see Authority Level table above)
2 =
Access
Group
0-8 (0 = not assigned to a group)
3 =
Active Partition(s)
1, 2, 3 (
common)
for this user;
Enter partitions consecutively if used
and press [#] to end the entries.
4 =
RF Zone No.
Assigns user number to button type zone for arm/disarm (
keyfob must be
enrolled in system first
; see
Wireless Key Templates
sectio
n in the
Pr ogramming Guide
).
Deactivating a key fob:
You can deactivate the arming/disarming functions for a
key fob (ex. if lost or stolen) by deleting the associated key fob
user. See “Delete
a User” above. Other key fob functions such as panic or dev
ice activa
tion (if
programmed) remain active. To fully remove the programming for a key fob,
delete the zone(s) associated with the keyfob functions.
IMPORTANT SECURITY NOTICE
Please inform the User about the security importance of their key fob, and what to
do if i
t is lost.
Explain that the key fob is similar to their keys or access card. If lost or stolen, another person can
compromise their security system. They should immediately notify the Dealer/Installer of a lost or stolen key
fob. The Dealer/Insta
lle r will t
hen remove the key fob programming from the security system.
5 =
Open/Close Paging
1 for yes, 0 for no
Installation and Setup Guide
3-6
Keypad Functions
The following is a brief list of system commands. For detailed information concerning system functions, refer to
the User
's Manual.
For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI)
User’s Guide.
Voice Keypads
The 6150V/6160V Voice Keypads provide the following features:
•
Message Center, which lets the user record and playback one message.
•
Voice
Status, which can announce system status by using the STATUS key.
•
Voice Chime, which can alert users to the opening of doors/windows while the system is disarmed.
Re
fer to the User Guide for specific procedures for activating and using these feat
ures.
Keypad Commands
Function
Description
Silence
Burglary A
larms
Pressing any key will silence the keypad sounder for 10 seconds. Disarming
the system
(s
ecurity code + OFF)
silence
s
both keypad and external sounders.
Silence Fire o
r
C
arbon
Monoxide Alarms
Press the OFF [1] key to silence the keypad sounder and, for fire alarms, the external sounder.
The detector sounding
stops when the contaminated air is
cleared from the detector;
see the
detector’s instructions
for further informa
ti
o
n
.
Qui
c
k Arm
If enabled (field
∗
21), you can press [#] in place of the system's security code, plus the desired
arming key (Away, Stay, Instant, Maximum)
Single
-
Button armi
ng
If programmed (*57 Function Key menu mode), lettered keys A
-
D can be used fo
r
a
rming,
u
sing
options 3-AWAY, 4
-STAY, 5
-NIGHT
-STAY, or 6
-Step
-Arming
If used, no security code is required to arm the system.
Alarm Memory
When the system is disarmed, any zo
nes that were in an alarm condition during the armed
period will be displayed. To
clear t
his display, simply repeat the disarm sequence (enter the
security code and press the OFF key) again.
Arming Away
Enter
code + AWAY [2] or simply
press appropriate lettered key on the keypads (see “Single
-
Button Arming” abov
e). If the
“Auto
-Stay Arm” feature is enabled (field *84) and the entry/exit
door
is not
opened and closed within the programmed exit delay time, the system will
automatically arm in STAY mode if armed from a wired keypad (non-RF device). If the door
is
op
en
e
d and c
l
osed within the exit delay period, the system arms in AWAY mode.
Arming Stay
Enter
code + STAY [3] or simply press appropriate key on the keypad
s (see “Single
-
Button
Arming” above). See “Arming Away” above for Auto
-
Stay arm
in
g
featur
e
.
Arming Night
-
Stay
Enter
code + STAY [3] + STAY [3] or simply press appropriate key on the keypads (see “Single
-
Button Arming” above).
Arming
Instant
Enter
code + INSTANT [7].
Arming Maximum
Enter
code + MAXIMUM [4] or simply press appropriate lettered key on the keypads (see
“Single
-
Button Arming” above).
Disarming
Enter
code
+ O
FF [1]. If entry delay or an alarm is active, you do not need to press OFF.
By
pa
s
sing Zo
n
es
Enter
code + BYPASS [6] + zone number(s).
Forced (Quick) Bypass
To automatically bypass all faulted zones, use the “Quick Bypass” method.
Enter code +
BYPASS + [#], then wait for all open zones to be displayed. Arm w
hen
displa
y indicates “ZONE
BYPASSED” and “READY TO ARM”.
Chime Mode
Enter
code + CHIME [9]. To turn chime off, enter code + CHIME again.
Activate Output D
evices
If relay outputs (via a
4204, or
4229)
are u
se
d
, two k
e
ypad entries available to the user are
included. If programmed, these entries can be used to manually
activate or deactivate the
device(s) for starting or stopping some action, such as turning lights on or off, etc. These
keypad entries are:
[Security Co
de] + # + 7 + [2-digit Device #] activates (starts) that device.
[Security Code] + # + 8 + [2
-
digit De
vice #] deactivates (stops) that device.
System Operation
3-7
SUMMARY OF ARMING MODES
Arming Mode
Features for Each Arming Mode
Exit Dela
y
Entry Delay
Perimeter Armed
Interior Armed
AWAY
Yes
Yes
Yes
Yes
STAY
Yes
Yes
Yes
No
NIGHT
-
STAY
Yes
Yes
Yes
only those zones
listed in Night
-Stay
zone list
INSTANT
Yes
No
Yes
No
MAXIMUM
Yes
No
Yes
Yes
Panic Keys
There
are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send
a report to the central station.
Each key can be programmed for 24-
hour Silent, 24-
hour Audible, Fire,
or Persona
l Emergency responses.
The programmed Panic response is activated when the appropriate key is pressed
for at least 2 seconds.
The Panic keys are identified by the system as follows:
Keys
Displayed as Zone
[A]
(
∗
/1)
95
[B]
(
∗
/#)
99
[C]
(3/#)
9
6
IMPORTA
NT:
For a
Silent panic function (if programmed) to be of practical value, you must program a report
code for the zone and the system must be connected to a central station.
Setting the Real
-Time Clock
IMPORT
ANT:
The Real
-Time Clock must be set before the end of the installation.
NOTE:
All partitions must be
disarmed before time/date can be set.
Set the time and date by doing the following:
1.
+[#] + [6] [3]
(Maste
r Code)
Alpha Display:
DISARMED
READY TO ARM
2.
Press [
∗
] when the time/date is displayed.
A cursor appears under the first digit of the hour.
To move cursor ahead, press [
∗
]. To go back, press [#].
•
Enter the 2-
digit hour setting.
•
Enter the 2-
digit min
ute setting.
•
Press [1] for PM or [2] for AM.
•
Enter the last two digits of the current year.
•
Enter the 2-
digit month setting.
•
Enter the 2-
digit day setting.
3.
To exit, press [
∗
] when cursor is at the last digit, or wait
30
seconds.
TIME
/DATE
SAT
04:04PM 10/17/00
Current time display
TIME/DATE SAT
04:04P2000/10/17
Time/date editin
g display
Installation and Setup Guide
3-8
Various System Trouble Displays
Alpha Display
Fixed Disp.
Meaning
ALARM CANCELED
CA
Will
appear if an exit or interior zone contained a fault during closing at the time the
Exit Delay
ended (e.g., exit door left open), but the system was disarmed during
the Entry Delay
time. The alarm sounder
and keyp
ad sound continuously, but stop
when the system is disarmed. No message will be transmitted to the central
station.
EXIT ALARM
EA
Appears
when Exit Delay
ends if an exit or interior zone contained a fault during
closing. The a
larm sounde
r and keypad sound continuously until the system is
disarmed (or timeout occurs). An “Exit Alarm” mes
sage is sent to the central
station. Also results if an alarm from an exit or interior zone occurs within 2 minutes
after the end of an Exit Del
ay
.
CHECK
CHECK
Indicates
that a problem exists with the displayed zone(s) and requires attention.
ALARM 1xx
FAULT 1xx
CHECK 1xx
1xx
1xx
1xx
91
Indicates
that communication between control and a zone expander or wireless
receiver is interrupted, where “x
x” is the d
evice address
. Check the wiring and DIP
switch settings on the units.
If field
*199 is set to “1,” all ECP module problems are displayed as “91.”
If there are wireless sensors in the system, the Check condition may also be
caused by
some change in the environment that prevents the receiver from
receiving signals from a particular se
nsor.
SYSTEM LO BAT
BAT
With
no zone number indicates that the system's standby battery is weak.
LO BAT
BAT
With
a zone number and a once
-
per
-
mi
n
ute bee
p
ing at the keypad indicates that a
low
-battery condition exists in the wireless sensor displayed (zone “00” indicates a
wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display
may occur.
NOTE: Some wireless sensors conta
in a non-replaceable long-life battery which
requires replacement of the entire unit at the end of battery lif
e (e.g., Nos. 5802,
5802CP).
TELCO FAULT
94
Telephone Line Failure, indicates that a monitored telephone line (if
p
r
ogramme
d
in field *92) has been cut or disconnected. Depending on how the system was
programmed, the keypad m
ay also produce a trouble sound, and the external
sounder may be activated. Silence by entering installer code + OFF.
Busy
-
Standby
dl
If this r
em
a
ins dis
p
layed for more than 1 minute, the system is disabled.
NOTE for CANADIAN PANELS:
Power up time is 2 minutes, and CID code 305
System Reset is sent if the [#] + [0] command is not performed before the 2
minutes expires.
Mode
m
Comm
C
C
T
he syst
e
m is in communication with the central station for change of function or
status verification.
no dis
play
no display
Power Failure
If there is no keypad display at all and the LEDs are unlit,
operating power (AC and
batter
y) for the
system has stopped and the system is inoperative.
If the message “AC LOSS” (Alpha display keypads) or
“NO AC” (Fixed
-Word
display keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up duri
ng a prol
onged AC power outage, the
control's power will shut down to minimize deep discharge of the battery.
Comm. Failure
FC
A communication failure has occurred.
Open Circuit
0C
The keypad is not receiving signals from the control; sees an open circ
ui
t
.
Long
Rng Trbl
bF
Backup
communication device (
LRR
)
had
communication failure.
Bell Failure
70
Bell superv
ision failure.
RCVR Jam
90
RF jam detected.
KEYPAD LOW BAT
00 BAT
Wireless keypad low battery.
Phone Okay
Cd
The dialer test has been success
fu
l
(CID c
o
de 601).
Dialer Off
d0
The dialer is disabled.
Test in Progress
dd
Walk test mode is active
(CID co
de 607).
Upload Completed
dC
The upload or download session was completed.
Upload Failed
dF
The upload or download session failed before compl
et
i
on.
4-1
SECTION 4
Testing the System
About Test Procedures
After the installation is complete, you should perform the following tests:
System Test
:
Checks that all zones have been installed properly and the system
responds
to faults.
Dialer Test:
Checks that the phone connection to the central station is working properly.
Go/No Go Test:
Checks that transmissions can be received from transmitters. Should be performed
before permanently mounting transmitters.
RF Sniffe
r Mode
:
Checks that RF transmitter serial numbers have been properly enrolled.
Battery Tests:
Automatic battery tests are performed by the system.
System Test
NOTE:
Test mode can be entered from any keypad. Howe
ver, fau
lted zones appear only on those keypads
assigned to the partition to which the zone is assigned (i.e.,
partition 1 zones appear only on partition 1 keypads,
etc.). To see another partition’s faulted zones, view a keypad assigned to that partition
or use th
e GOTO
command (code +[
∗
] + partition number 0-
3, where 0 is the keypad’s home partition).
With the s
ystem in the disarmed state, check that all zones in the partition to be tested are intact (not faulted).
Doors and windows with contacts should
be closed,
PIRs should be covered (use a cloth to mask them
temporarily if necessary). If a “NOT READY” message
is displayed, press [
∗
] to display the faulted zone(s).
Restore faulted zone(s) if necessary, so that the “READY” message is displayed.
1. Ente
r Installe
r Code
+ 5 [
TEST
], then press “0” at the prompt to start Walk Test mode.
1=DIA
L, 0=WALK
(no special display on Fixed-
Word keypads)
The following will be displayed on the initiating keypad
and a Contact ID report will be sent (code 6
07):
TEST IN PROGRESS
(“dd” displayed on Fixed-
Word Display Keypads)
2. Upon entering the system test mode, the outside sounder should sound for 1 second.
If the backup battery is discharged or missing, the sounder may not turn on and a “LO
W B
ATTERY”
report
will be transmitted with a “TEST” report.
The keypad will beep about every 30
seconds as a r
eminder that the system is in the Test mode.
NOTE:
Wireless motion detectors (Passive Infrared units) will send signals out o
nly if t
hey have been
inactive for 3 minutes (conserves battery life).
3. Test all sensors using the procedure described in the User’s Guide “Testing the System” section.
4. After checking sensors, turn off the test mode by entering installer code + OF
F.
NOTE
: T
est mode automatically ends after 4 hours. During the final 5 minutes (after 3 hours 55 minutes of
Te
st mode), the keypad emits a double-
beep every 30 seconds to alert that the end of Test mode is nearing.
Checking Transmitter Enrollment (Sniff
er
Mode
)
Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are
disarmed before trying to enter this mode, since this is a system-
wide command.
1. From a keypad in partition 1, press
[Installer
code] + [#] + 3.
NOTE:
If the communicator is in the process of sending a report to the central stati
on, the system will not
go into the Sniffer mode. If so, wait a few minutes, and try again.
The keypads in both partitions will display all zone numbers of
wireless units (in both partitions)
programmed into the system. Fault each transmitter in turn, causing each one to send a signal.
As the
system receives a signal from each of the transmitters, the zone number of that transmitter disappears fr
om
the displ
ay.
2. After all transmitters have been checked, exit the sniffer mode by keying [Installer code] +
OFF.
IMPORTANT:
Sniffer mode does not automatically expire. You must manually exit Sniffer mode (by entering
[Installer code] + OFF) to return
to normal
operation.
Installation and Setup Guide
4-2
NOTES:
•
All BR type units must physically be activated to clear the display.
•
When
one
button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other
buttons on that transmitter are cleared from the display. Thi
s also a
pplies to 5816 and 5817
transmitters, which have multiple loops (zones).
•
Any transmitter that is n
ot “enrolled” will not turn off its zone number.
Go/No Go Test Mode
The
Go/No Go Test verifies adequate
RF signa
l strength from the proposed transmitter location, and allow you
to reorient or relocate transmitter
s if necessary, before mounting the transmitters permanently. This mode is
similar to the Transmitter Test mode, except that the wireless receiv
er
gain is
reduced. This will enable you to
make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system
is in the normal operating mode.
1. Enter
[Installer code] + [#] + 4 f
rom the partition being tested.
For mult
i-partition systems, repeat this test for
each partition.
2. After you have placed transmitters in their desired locations and the approximate length of wire to be run to
sensors is connected to the transmitter's screw terminals (if used), fault
each trans
mitter. Do not conduct this
test with your hand wrapped around the transmitter, as this will cause in
accurate results.
a. The keypad will beep three times to indicate signal reception and display the zone number.
b. If the keypad does not beep,
you
should
reorient or move the transmitter to another location. Usually a
few inches in either direction is all
that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then permanently
mount each of the transm
itters a
ccording to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: [any user c
ode (partition-
specific)] + OFF.
Dialer Communication Test
and Periodic Test Reports
1. En
ter Installer Code
+ 5 [
TEST
], then press “1” at the prompt to start the Dialer Test
(checks phone line
integrity only; does not confirm report transmissions)
.
1=DIAL, 0=WALK
(no special display on Fixed-
Word keypads)
Th
e following
will be displayed (accompanied by 2 beeps) if test is successful:
PHONE OKAY
(“Cd” displayed on Fixed
-Word Display Keypads)
A Contact ID report will also be sent (code 601)
If the dialer test is unsuccessful, “COMM FAILURE” (or FC) is displayed
.
2. En
ter Installer code + OFF to clear the display and exit.
Automatic Periodic Test Report
The system can be set to automatically send test reports (enabled in field *64; Contact ID code 602) at specified
intervals. Frequency of the reports is set
in Scheduli
ng mode (event 11) or by the following key commands:
installer code + [#] + 0 + 0
= test report sent
every 24 hours
installer code + [#] + 0 + 1
= test report sent once per week
installer code + [#] + 0 + 2
= test report sent every 28 days
Ea
ch mode s
ets schedule 32 (VISTA
-20P) or schedule 08 (VISTA
-15P) to the selected repeat option; the first test
report is sent 12 hours after command.
To ensure that test reports are sent at the times expected, set the Real
-Time Clock to the proper time
be
for e
enter
ing the test report schedule command.
Automatic Standby Battery Tests
1. An aut
omatic test is conducted every 3 minutes to ensure that a standby battery is present and properly
connected. If a battery is not present or is n
ot proper
ly connected, a “
LOW BATTERY” message is
displayed and, if so programmed,
will be reported to the central station.
2. A battery capacity test is automatically conducted for 2 minutes every 4 hours, beginning 4 hours a
fter exi
ting
the Programming mode or after powering up the system. In addition, entry into the Test mode will
also
cause a battery capacity test to be initiated. If the battery cannot sustain a load, a “
Low Battery” message
is
display
ed and, if so programmed, will be reported to the central station.
5-1
SECTION 5
Specifications & Accessories
Se
curity Control
1. Physical:
12-
1/2” W x 14-
1/2” H x 3” D (318mm x 368mm x 76mm)
2. Electrical:
VOLTAGE INPUT: 16.5VAC from plug-
in 25VA transfor
mer, ADEM
CO 1321 (in U.S.A.)
RECHARGEABLE BACKUP BATTERY: 12VDC, (sealed lead acid type)
; see Battery Table
in Mounting & Wiring section for proper battery sizes for various maximum current drains
.
Charging
Voltage: 13.8VDC.
ALAR
M
SOUNDE
R: 12V, 2.0 Amp output can drive 12V BELLS or can drive one or two
702
(series connected) self
-contained 20-
watt sirens. Do
not
connect
two 702s in parallel.
AUXILIARY POWER OUTPUT: 12VDC, 600mA max.
NOTE
: For UL installations, Alar
m
Sounder
plus Auxiliary Power currents should not
exceed 600mA total
(500mA Aux, 100mA Bell Output)
.
FUS
E (if installed
): Battery (3A) No. 90
–12
(PC
board may have a PTC device instead of a
fuse. The PTC serves as an automatically resetting fuse.
)
NOTE
: This eq
uipment shall be installed in accordance with the National Electrical Code,
ANS
I/NFPA 70 and the N
ational Fire
Alarm
Code, ANSI/NFPA 72.
3. Communication:
FORMAT SUPPORTED:
ADEMCO Express:
10 characters/sec, DTMF (TouchTon
e) Data
Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
ADEMCO Low Speed:
10 pulses/sec, 1900Hz Data Tone, 1400Hz ACK/KISSOFF.
Radionics/SESCOA:
20 pulses/sec, 1800Hz Data Tone, 2300Hz ACK/KISSOFF.
Can report 0-
9, B
-F
Ademco Contact ID
10 characters/sec., DTMF (TouchTone) Data Tones,
1400/2300Hz ACK, 1400Hz KISSOFF.
LINE SEIZE: D
ouble Pole
RINGER EQUIVALENCE: 0.1B
FCC REGISTRATION No.: 5GBUSA-
44003-
AL
-E
4.
Maximum Zone Resistance:
Zones
2–8 = 300 ohms excluding EOLR
sta
ndard zones
Zone 1 = 100 ohms excluding EOLR
SIA Minimum Hardware Configuration:
1 model VIST
A-20PSIA/15PSIA control panel
, and 1 6160V keypad,
and 1 UL Listed Bell.
Compatible Devices
Keypads:
6150 Fixed-
Word Keypad, 6160 Alpha Keypad, 6150V a
nd
6160
V Voice Keypads, 628
0 Touch Screen Keypad,
Tuxedo Touch
Advanced User Interface
(AUI)
Wireless Receivers:
5881
EN
L/5882L: accepts up to 8 transmitters
5881
EN
M/5882M: accepts up to 16 transmitters
5881
EN
H/5882H: accepts up to system maximum trans
mitters
5883
H Transceiver: accepts up to system maximum transmitters
6150RF Keypad/Transceiver: accepts up to
16
transmitters
6160RF Keypad/Transceiver: accepts up to system maximum trans.
Zone Expansion:
4219
WIRED EXPANSION MODULE
4229
WIRED
EXPANSION/RELAY MODULE
Relay Module:
4204
RELAY MODULE
Communication
GSMV
4G,
GSMX4G,
IGSMV4G, 7847i
Device:
Installation and Setup Guide
5-2
2-Wire Smoke Detector:
Detector Type
System Sensor
Model No.
Photoelectric w/heat
se
nsor
2
W
T
-
B
Photoelectric
2W
-
B
Photoelectric
2151 w/B110LP base
Transformers:
1321: 16.5VAC, 25VA Plug-In Transformer (No. 1321CN in Canada)
Sounders:
AB12M 10” Motorized Bell & Box
702 Outdoor Siren
719 2-Channel Siren
713 High P
ower Speaker
745VSD3 Voice Siren Driver
746 Indoor Speaker
747 Indoor Siren
747PD Two-Tone Piezo Dynamic Indoor Siren
747UL Indoor Siren
748 Dual Tone Siren
749 Speaker/Horn
713 Speaker
WAVE Speaker
WAVE2 Two
-Tone Siren
WAVE2PD Two
-Ton
e Piezo D
ynamic Siren
5800WAVE Wireless Siren
System Sensor MHW
(white
)/;
MHR
(red) Indoor Piezo Sounder
CONTACTING TECHNICAL SUPPORT
PLEASE, before you call Technical Support
, be sure yo
u:
• REA
D THE INSTRUCTIONS!
• Check all wiring connections.
• Determine that the power supply and/or backup battery are supplying proper voltages.
• Verify your programming information where applicable.
• Note the proper model number of this product, and t
he
versi
on level (if known) along with any documentation
that came with the product.
• Note your Resideo
customer number and/or company name.
Having this information handy will mak
e it easier for us to serve you quickly and effectively.
Technical Support:
........................................................................................
1-8 00-645
-7492 (8 a.m.
-10 p.m. E
T.)
MyWebTech
: ...............................................................................................................................
www.resideo.com
6-1
SECTION 6
Regulatory Agency Stat
ements
FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15
The user shall not make any changes or modifications to the equipment unl
ess autho
rized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's
authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has be
en found
acceptable for use. The FCC requires the following statement for your
information:
This equipment generates and uses
radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's
instructions, may ca
use interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B
computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to prov
ide reasonable p
rotection
against such
interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment
does cause interference to radio or television reception, whi
ch can be deter
mined by
turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the foll
owing measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until in
terferenc
e is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna
leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the ra
dio or tel
evision receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for hel
p.
This Class B digital apparatus complies with Canadian ICES
-003.
Cet appareil numérique de la classe B est conforme à la norme N
MB
-003 d
u Canada.
FCC/IC STATEMENT
This device complies with Part 15 of
the FCC rules and
RSS
-210 of Industry Canada. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) This device must accept
any int
erference received, including interference that may cause
undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS
-210 des Industries Canada. Son fonctionnement est soumis aux conditions
suivantes:
(1) Cet apparei
l ne doi
t pas causer d'
interférences
nuisibles. (2) Cet appareil doit accepter toute interférence
reçue y compris les
interférences
causant une réception
indésirable.
Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subs
idiary of
Resideo Technologies, Inc., 2 Corporate Center
Drive., Melville, NY 11747, Ph: 516-
577
-2000
TELEPHONE/MODEM INTERFACE
FCC Part 68
This equipment complies with Part
68 of the FCC rules. On the fro
nt cover of this equipment is a label that contai
ns the FC
C registration number and
Ringer Equivalence Number (REN). You must provide this information to the telephone company when requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-
company
-provided
coin ser
vice. Connection to party lines is subject to state tariffs. This equipment is
hearing-
aid compatible.
Industry Canada
NOTICE
: The Industry Canada Label identifi
es certified equipment. This cert
ification means that the equipment meets telecomm
unication
s network
protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The
Department does
not guarantee the equipment will
operate to the user’s satisfaction.
Before inst
alling thi
s equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications com
pany.
The equipment must also be instal
led using an acceptable method of
connection. The customer should be aware that com
pliance
with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs
or alterations made by the user to
this equipment
, or equ
ipment malfunctions, may give the telecommunications company to request the user to disconnect the equipment.
Users should ensure for their own protection that the
electrical ground connections of the power utility, telephone lines and internal m
etallic w
ater pipe
system, if present, are connected together, This precaution may be particularly important in rural areas.
Caution
: Users should not attempt to make such c
onnections themselves but should contact appropriate electric inspection authority
, or elec
trician, as
appropriate.
Ringer Equivalence Number Notice:
The
Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termi
nation on
an interface may consist of any combination of devices subject only to the requirement that the
sum of the Ringer Equivalence Numbers of all the devices does not ex
ceed 5.
Industrie Canada
AVIS:
l’étiquette d’Industrie Canada identifie le matéri
el homolo
gué. Cette étiquette certifie que le matériel est conforme aux normes de protection,
d’exploitation et de sécurité des réseaux de télécommunications, comme le prescr
ivent les documents concernant les exigences techniques relatives
au matériel term
inal. Le M
inistère n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il
est permis de le raccorder aux installations de l’enterprise locale de télécommuni
cation. Le
matériel doit également être installé en suivant une méthode acceptée da raccordement. L’abonné ne doit pas oublier qu’il est
possible que la
conformité aux condit
ions énoncées ci
-dessus n’empêche
pas la dégradation du service dans certaines sit
uations.
Les réparations de matériel nomologué doivent être coordonnées par un représentant désigné par le fournisseur. L’entreprise d
e télécommunications
peut demander à l’
utilisateur da débrancher un appareil à la suite de réparations ou de modifications
effectué
es par l’utilisateur ou à cause de mauvais
fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la terre de la sourc
e d’energie électrique, de lignes
téléphoniques et
des canalisations d’eau métalli
ques, s’i
l y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissement :
L’utilisateur ne doit pas tenter de faire ces raccordements lui
-même; i
l doit avoir racours à un service d’inspection de
s install
ations
électriques, ou à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie
(IES) assigné à chaque dispositif terminal indique le nombre max
imal de terminaux qui peuvent êtr
e
raccordés à une interface. La terminaison d’une
interfac
e téléphonique peut consister en une combinaison de quelques dispositifs, à la seule condition
que la somme d’indices d’équivalence de la sonnerie de tous les dispos
itifs n’excède pas 5.
Installation and Setup Guide
6-2
UL NOTI
CES
1.
Entry Delay No. 1 and No. 2 (f
ields
∗
35,
∗
36) cannot be greater than 30 seconds for UL Residential
Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL
Commercia
l Burglar Alarm installations, total entry delay may not exceed 45 seconds.
2.
For
UL Comme
rcial Burglar Alarm and UL Residential Burglar Alarm installations with line security, total
exit delay time must not exceed 60 seconds.
3.
The maximum number of reports per armed period (field
∗
93) must be set to “0” (unlimited) for UL
installat
ions.
4.
Periodic testing (see scheduling mode) must be at least every 24 hours.
5.
Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installat
ions (Aux
power 500mA max.).
6.
All partitions must be owned and managed by the sam
e person(s).
7.
All partitions must be part of one building at one street address.
8.
If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9.
For UL commercial
burglar alarm installations the control unit mus
t be prot
ected from unauthorized
access. The tamper switch
installed to protect the control unit enclosure door is suitable for this purpose.
10.
Remo
te downloading without an alarm c
ompany technician on-site (unattended downloading)
is not
permissible for UL installations.
11.
Auto
-disarming is not a UL Listed feature.
12.
As SIA limits for delay of alarm reporting and sounding can exceed UL limits for
commercial and
residential appli
cations, the following UL requirements per UL681 a
re provi
ded:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a
local alarm sounding device to p
ermit the
alarm system user to enter and disarm t
he system,
or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system w
ithout standard line security or
encrypted line security, or
c) 120 seconds for a
system t
hat does not transmit an alarm signal to a remote monitoring location.
13.
This control is not intended for bank safe and vault applications.
SIA Quick Reference Gu
ide
1. *31 Single Alarm Sounding per Zone: If “0” selected, “alarm sounding per zo
ne” will b
e the same as the
“number of reports in armed period” set in field *93 (1 if one report, 2 if 2 reports, unlimited for zones in
zone list 7).
2. *34 Exit Delay: Min
imum exit delay is 45 seconds.
3. *35/*36 Entry Delay 1 and 2: Minimum entry delay
is 30 sec
onds.
4. *37 Audible Exit Warning: Feature always enabled; field does not exist.
5. *39 Power Up in Previous State: Must be “1,” power up in previous state.
6. *40
PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting di
sable opt
ion in field
*91 must be set.
7. *50 Burglary Dial Delay: Delay must be a
minimum of 30 seconds.
8. *59 Exit Error Alarm Report Code: Always enabled.
9
*68 Cancel Re
port Code: Default is “code enabl
ed.”
10.
*69 Recent Closing Report Code: Always en
abled.
11. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable
must be set to “1” (enabled).
12.
*93 No. reports in Arme
d Period: Must be set for 1 or 2 report pairs.
13.
Cross zone timer programming is
set in f
ield
∗
85; cross zone pairs are assigned in zone list 4 using
∗
81
Zone List mode.
14.
Duress code is assigned by using the “add a user code” procedure found in the Us
er Guide. Enable
Duress code reporting by programming zone 92 using
∗
56 Zone Progr
amming mod
e.
15.
Fire alarm verification is a built
-in system feature when a zone is programmed for zone type 16.
6-3
– NOTES
– Installation and Setup Guide
6-4
– NOTES
–
7-5
SECTION 7
Limitations and Warranty
WARNING
THE LIMITATIONS OF THIS ALARM S
YSTEM
While this System is an advanced design sec
urity s
ys tem, it does not offer guaranteed protection against burglary, fire or other
emergency. Any alarm system, whether commercial or residential, is subject to compromis
e or failure to warn for a variet
y of
reasons. For example:
•
Intruders may gain a
ccess th
rough unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
•
Intrusion detectors (e.g., passive infrared detectors), smoke detect
ors, and many other sensing devices will not work
without
power. Battery
-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly.
Devices powered solely by AC will not work if their AC power supply
is cut off for any reason, h
owever
briefly.
•
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently
checked during a weekly test, bl
ockage can occur if a metal object is moved into t
he path.
•
A user may not be able to reach a panic or emergency button quickly enough.
•
While smoke detectors have played a key role in reducing residential fire deaths in
the United States, they may not a
ctivate or
provide early warning for a variety of
reasons
in as many as 35% of all fires, according to data published by the Federal
Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with
this System may not work
are as f
ollows. Smoke detectors may have been improperly
installed
and positioned. Smoke detectors may not sense fires that
start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side
of closed doors.
Smoke detectors
also may not sense a fire on another level of a r
esidenc
e or building. A second floor detector, for example,
may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense
every kind of fire ev
ery time. In general, detectors may not always war
n about
fires caused by carelessness and safety
hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson. Depending on the nature of the
fire and/
or location of the smoke detectors,
the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time
to
prevent injury or death.
•
Passi
ve Infrared Motion Detectors can only detect intr
usion wi
thin the designed ranges as diagrammed in their installation
manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection,
and intrusion c
an only be detected in unobstructed areas covered
by thos
e beams. They cannot detect motion or intrusion that
takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical t
ampering,
masking, painting or spraying of any material on the mirrors, windows or
any par
t of the optical system can reduce their
detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of the
protec
ted area approaches the temperature range of 90° to 105°F (32° to 40°C), the detec
tion per
formance can decrease.
•
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other
side of closed
or partly open doors. If warning
devices are located on a different level of the r
esidenc
e from the bedrooms,
then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning
if the alarm is muffl
ed by noise from a stereo, radio,
air conditioner or other appliance, or by passing
traffi
c. Finally, alarm
warning devices, however loud, may not warn hearing-
impaired people.
•
Telephone lines needed to transmit alarm signals from a premises to a central
monitoring station may be out of
service or
temporarily out of service. Telephone
lines are
also subject to compromise by sophisticated intruders.
•
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to
protect
themselves from the emer
gency situation. In the case of a monitored alarm
system,
authorities may not respond appropriately.
•
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed t
o last as
long as 10 years, the electronic components could fail at any time.
The
most com
mo
n cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security keypad (and
remote keypad
) shoul
d be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions.
Longevity of batteries
may be as much as 4 to 7 years, depending on the environment, usage, and the speci
fic wire
less device
being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce
the actual battery life in
a given installation. This wirel
ess system, however, can identify a true low
-batt
ery situ
ation, thus allowing
time to arrange a change of battery to maintain protection for that given point within the system.
Installing an alarm system may make the owner
eligible for a lower insurance rate, but an alarm system is not a substitute for
insurance.
Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to
insure their lives and property.
We continue to develop new and improved protection
devices. Users of alarm systems owe it to themsel
ves and
their loved ones
to learn about these developments.
Installation and Setup Guide
7-6
– INDEX
–
1321
................................
1-2, 2-
3, 2-
11
3+1 and 4+1 Standard Formats
.......
3-1
4204
....
1-2, 2-
2, 2-5, 2 -6, 2-
11, 3-
6, 5-
1
4219
.............1
-1, 1-
2, 2-
2, 2
-5, 2-
7, 5
-1
42291
-1, 1-
2, 2-
2, 2
-5, 2
-6, 2-7, 2
-11, 3
-6,
5-1
5801
................................................
2-9
5802
................................
.........
2-9, 3-
8
5802CP
.....................................
2-9, 3-
8
5827
................................
................
2-9
5827BD
............................................
2-9
5881
................................
.........
2-2, 2-
8
8-pin connector
..............................
2-10
AC Power Supply
.............................
1-2
AC T
ransformer
...............
2-3, 2-
12, 5-
2
Ademco Contact ID
..........................
3-3
Alarm Output
.............................
2-2, 2-
4
Arming Away
....................................
3-6
Arming Instant
................................
.. 3-6
Armi
ng Modes
................................
.. 3-7
Arming Stay
.....................................
3-6
Audio Alarm Verification
.................
2-13
Audio Alarm Verification (AAV)
......
2-13
AUI
..................................................
2-5
Authority Levels
...............................
3-5
Auxiliary Output
...............................
2-2
Backup Battery
................................
1-2
Battery Life
................................
.......
2-9
Battery Tests
.............................
4-1, 4
-2
Bypassing Zones
.............................
3-6
Cabinet
................................
............
2-1
California State F
ire Mars
hall
...........
2-2
Caller ID Unit
................................
. 2-13
Charging Voltage
.............................
5-1
Chime Mode
................................
....
3-6
Clean Me Option
..............................
2-7
Communication
.........................
3-1, 5-
1
Communication Device
....................
5-1
Communication Device (LRR)
......
2-5, 3
Contact ID Reporting
.......................
5
-1
CSFM
................................
..............
2-2
Current Draw Worksheet
..................
2-2
Device address
................
2-5, 2-11,
3-8
Dialer Communication Test
..............
4-2
DIP Switches.
..................................
2-9
Disarming
................................
........
3-6
Double-
Balanced
.............................
2-6
Entry Delay
...............................
3-7, 3-
8
EOLR
................................
.......
2-6, 5-
1
Exit Delay
................................
. 3-7, 3-
8
Exit Error Alarm
..................................
3
Exit
Error Alarm
...............................
3-8
Expansion Zones
.............................
2-7
Fast Busy Signal
............................
2-13
Fire Verification
................................
2-7
Go/No Go
Test Mode
.......................
4-2
Handshake
................................
......
3-1
Hardwired zones
..............................
1-1
HAYES Modem
...............................
1-1
House ID
.........................................
2-9
Ideal Model 61–
035
.........................
2-3
Installer Code
...........................
4-1, 4-
2
Keypad addr
esses
...........................
2-5
Kissoff
................................
.............
3-1
Lock
................................
.................
2-1
Low Battery Message
......................
4-2
Model 112 Tamper Switch
.............
2-10
Modem
................................
............
3-8
On
-board tri
ggers
..........................
2-14
Output relays
................................
... 1-2
Panic Keys
......................................
3-7
Periodic Test Reports
......................
4-2
Phone Line
....................................
2-13
Pow
er Failure
..................................
3-8
Power supply
.....................
2-2, 2-
4, 7-
3
Relay Modules
...............................
2-11
Report Code
................................
....
3-1
Repor
t Code Formats
......................
3-1
Response time
................................
2-7
RF House ID Code
..........................
2-8
RF Interference
...............................
2-8
RF j
am detec
tion .............................
1-1
RF Jam Option
................................
2-8
RF Receiver
...........
2-1, 2-
2, 2-
5, 2
-8, 3
RJ31X Jack
...................................
2-13
SA4120XM
-1 Cable
.........................
2-3
Security Codes
.........................
1-1, 3-
5
Silent Burglary
................................
....
3
Silent Panic
................................
.....
3-7
Sniffer
Mode
....................................
4-1
Sounder connections
.......................
2-4
Supplementary Power
.....................
2-4
System Communication
...................
3-1
System T
est ....................................
4-1
Tamper switch
........................
2-10, 6-
2
Telco Line..................................
2-13, 3
Telephone Line Monitoring
..............
1-1
Test Mode
................................
4-1, 4-
2
Transmitters
....................................
2-9
Trigger outputs
..............................
2-12
Trouble Displays
.......................
3-7, 3-
8
UL
.....................
2-2, 2-
4, 2-
11, 5-
1, 6-
2
Wire Run Chart
.........................
2-4, 2-
5
Zone Doubling
.................................
2-6
7-7
Figure 1
7. Summary of Connections
The product should not be disposed of with other household waste. Check for the nearest
authorized
collection centers or authorized recyclers. The correct disposal of end-
of-life equipment
will help prevent potential negative
consequences for the envi
ronment and human health.
Any attempt to reverse-
engineer this device by decoding proprietary protocols
, de-
compiling
firmware, or any similar actions is strictly prohibited.
For Support visit: w
ww.resideo.com.
For
Warranty information visit: www.
resideo.com.
www.resideo.com
2 Corporate Center Driv
e, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manu
factured
by Resideo Technologi
es, Inc. and its
affiliates.
ÊK5305
-
1V10C~Š
K5305
-
1V
10
C
3
/
1
5
Rev.
C
- Uploaded