4208U Vs. 4208SN
The 4208U is a universal 8-Zone wired expansion module that can be used with any Honeywell Alarm Panel that supports V-Plex Polling Loop devices. The 4208SN is an 8-Zone wired expansion module as well, but it can only be used on panels that support the 'Serial Polling' input type.
|
|
|
Older versions of the Ademco (which became Honeywell) VISTA Series Alarm Panels that supported V-Plex technology did not support serial number devices. These panels were more simple, and the V-Plex devices that worked with them were also simple. The devices had dip switches. The dip switch settings determined the zone number(s) that would be used by the device.
Newer panel versions are able to support V-Plex devices that use a serial number to designate the device being used. The zone is programmed with an input type of ‘Serial Polling’ along with the serial number and loop number of the device. The newer panels can also still support the older style modules. This is helpful when replacing an older panel with a newer one, where the older modules installed in the field still work. For more information about this, check out this FAQ.
The chart below shows a comparison between the 4208U and the 4208SN:
Feature | 4208U | 4208SN |
---|---|---|
Current Draw (see below) |
|
|
Polling Loop Only | 28.6mA | 33.6mA |
Polling Loop + External Power | .6mA / 28mA | .6mA / 33mA |
Dimensions | 6-7/16” W X 4-¼” H X 1-¼” D | 6-7/16” W X 4-¼” H X 1-¼” D |
Resistor Value | 10K EOLR w/ 300 Ohm Tolerance. Resistor is required on each zone. | 10K EOLR w/ 300Ohm Tolerance. Resistor is required on each zone. |
Unique Serial Numbers | 128 | 256 |
Loop Response Time |
400 Millisecond 10 millisecond option set via dip switch for loops A and B only |
400 Millisecond 10 millisecond option set via dip switch for loops A and B only |
Input Types Supported | Left Loop Dip Switch / Serial Polling | Serial Polling |
Agency Listings |
UL 985 Household Fire UL 1023 Household Burglary UL 609 Commercial Burglary UL 864 Commercial Fire* CSFM FM CUL CE (Requires #N6361) |
UL 985 Household Fire UL 1023 Household Burglary UL 609 Commercial Burglary UL 864 Commercial Fire* CSFM FM (Pending) CUL CE (Requires #N6361) |
* For UL Listed Commercial Fire Usage: Use NO contacts, Style B, and supervise these loops using Model #EOL100 fire listed 10K EOLRs (purchased separately).
Did you find this answer useful?
We offer alarm monitoring as low as $10 / month
Click Here to Learn MoreRelated Products
Related Categories
- Wired Security System Zone Expanders
- Wired Zone Expanders
- Wired Security System Zone Expanders
- Wired Zone Expansion Modules
- Answered
- Answered By
- Julia Ross