Can I connect a wired smoke to my L5200 or L7000?

Despite the fact that the L5200 and L7000 offer zone 1 as an End of Line Resistor supervised zone, the panel will not allow you to program this zone as a Fire or as a Carbon Monoxide zone. One reason may be that there is no current available on this zone to operate a 2-wire smoke detector, and there is no auxiliary power output on the panel for powering 4-wire smoke detectors or carbon monoxide detectors. It would be possible to operate a heat detector on zone 1, but because Fire is considered a life safety zone type, and having the fire zone type available for heat detectors only might cause confusion, Honeywell has chosen to err on the side of caution and not provide this programming option at all.

Did you find this answer useful?

We offer alarm monitoring as low as $10 / month

Click Here to Learn More
You won't be able to interface a hardwired smoke with the L5200/L7000. If the device closes when it's activated, it is a normally open device. Typically they require a resistor if used on a fire loop on a compatible panel.
If I want to hardwire a mechanical heat detector to Zone 1 (not fire or smoke), how would it be programmed? I'm looking to use the System Sensor 5602 194°F Fixed Temp/Rate-of-Rise, Single-Circuit Mechanical Heat Detector, which has 2 wires, does not require power, and would close the circuit when triggered. Is that considered a 'Normally Open' or 'Normally Closed', and does it require a resistor?

Related Products

Honeywell LYNXTOUCH L5100 - LYNX Touch Wireless Alarm Control Panel
Honeywell L5100
LYNX Touch Wireless Alarm Control Panel
Honeywell L5200 - LYNX Touch Wireless Home Security System and Alarm Control Panel
Honeywell L5200
LYNX Touch Wireless Home Security System and Alarm Control Panel
Honeywell L5100-SIA - LYNX Touch Wireless Alarm Control Panel
Honeywell L5100-SIA
LYNX Touch Wireless Alarm Control Panel

Related Categories


Answered
Answered By