System Sensor RRS-MOD with Multiple 4-wire Smoke Zones with EOLSR on VISTA-20P
Related Products
Document Transcript
Updated by Tech Support: 9/8/2011
-
1
-
Using RRS-MOD with Multiple 4-wire Smoke Zones and the
End of Line Supervision Relays on ‘Plus’ Series Panels
Notes:
Installing multiple 4
-wire smokes zones, tied to one RRS
-MOD, on the ‘P’ Series panels can cause your dialer to run
away sending multiple troubles
when
activated.
o
The theory behind this is that once the device is activated it will reverse polarity to all y
our smokes wired to the
RRS
-MOD.
o
The smokes that did not go into alarm will cause a trouble because the power has reversed and the End of Lin
e
S
upervision Relay will now
pulse open and close causing multiple trouble
s on the zone. This is why the panel
wil
l send multiple Troubles to your Central Station.
o
Bell Supervision MUST be disable
d to prevent activation of the RRS
-MOD when not in alarm condition. S
ee
wi
ri ng diagram for more information on Page 2.
Programming:
*79 Output Device
Mapping
*80 Output Function Programming
Output #1:
(Zone Open)
Output Function #1: (Remove wire on Zone not
in alarm)
Output Function #4: (Stop parameters
for Func
tion
#2)
Output
Type:
1 (Relay)
Activated
By:
Zone # or Zone List
Activated
By:
Zone Type
Module
Add:
12
Zone #:
Fire Zones Not in alarm
Zone Type:
22 (disarm)
Relay Pos.
2
Enter Event:
1 (Alarm)
Action:
0 (off)
Action:
2 (Close and Stay Closed)
Output #:
1
Output #2
:
(Zone Open)
Output #:
2
Output
Type:
1 (Relay)
O
utput Function #5 (Smoke Reset)
Module
Add:
12
Output Function #2: (Remove wire on Zone not
in alarm)
Activated by:
Zone Type
Relay Pos.
3
Activated
By:
Zone # or Zone List
Zone Type:
54 (Smoke Reset)
Zone #:
Fire Zones Not in alarm
Action:
N/A
Output #3
:
(Smoke Reset)
Enter Event:
1
(Alarm)
Output #:
3
Output
Type:
1 (Relay)
Action:
2 (Close and Stay Closed)
Module
Add:
12
Output #:
1
Relay Pos.
1
Output Functio
n #3: (Stop parameters for
Function
# 1)
Activated
By:
Zone type
Zone Type:
22 (disarm)
Action:
0 (off)
Output #
2
*** Y
ou must have 1 relay programmed for every fire zone that you have enabled and don’t forget
to
include your K
eypad Fire
Panics
in
the Zone Lists! *** Updated by Tech Support: 9/8/2011
-