System Sensor RRS-MOD with 4-Wire i3™ Smokes on a VISTA-20P
Related Products
Document Transcript
-
1
-
Step
-by-Step
Tech Support
Updated 7/12/13
Vista-20P / FA168C Family w/RRS-Mod & 4-
wire Smokes
Wiring:
Sample shows Zone 2 for 4
-Wire Smoke Detectors.
Fire Zone Reset:
Using a 4204 we can
program the panel to do a fire zone reset:
*79 Programming:
01 Relay Position?
1-4
01
01 Module Addr?
07-
15
12
Enter Output No.
00 = QUIT
00
01 Output Type?
Realy
1
Enter Output No.
00 = QUIT
01 -
2
-
Step
-by-Step
Tech Support
Updated 7/12/13
*8
0 Programming:
U
sing Additional Fire Zones:
If you have another fire zone, or are using Keypad Fire Panic, these also will trip the RRS
-MOD.
When using a EOL supervision Relay, t
he pulsing RRS
-MOD
( witho
ut a latched smoke
detector
) w
ill
cau
se rapid Trouble/Restore reporting to C.S. W
hen the RRS
-MOD starts to pulse the zone will report to
the panel a trouble on an open then a restore on close,
and will do this for the duration of the sounder. The
logic of
the panel tells the dialer to report every T
rouble and every R
estore. This means
every time it
pulses it sends a signal to the dialer queue
, caus
ing
multiple
Trouble reports to be sent to C
entral
Station.
To prevent these repeat Trouble
reports when oth
er Fire Zones are tripped, you
can
wire one of the triggers
to the positive side of fire zone (zone 2 in our case)
, and
program the
trigger to activate upon “Alarm” of
these other zones in a Zone List. When one of these zones trip, the trigger will hold a
short to ground on
Zone
2, putting it into Alarm and preventing it from responding to the pulsing of the RRS
-MOD.
*79 Programming:
Output Funct. #
(00 = Quit)
00
Output #?
Relay 01
01
01
Zo
ne Type
54
01 Activated by:
Zone
Type
2
01 A E P Trig
?00 0 0 -
ZL=1
Output Funct. #
(00 = Quit)
01
Enter Output No.
00 = QUIT
00
17 Out Normal Low?
0=No, 1=Yes
0
Enter Output No.
00 = QUIT
17
Trigger 1 = Output # 17
Trigger 2 = Output # 18
-
3
-
Step
-by-Step
Tech Support
Updated 7/12/13
*80 Programming:
*8
1 Programming:
If zone 2 is entered in this Zone List it will cause the LED of the Smokes on Zone 2 NOT
to
Latch on Alarm!
01 Enter Zn Num.
(00 = Quit)
00
01 Enter Zn Num.
(00 = Quit)
95
01 Enter Zn Num.
(00 = Quit)
02
Zone list No.
(00 = Quit)
01
Output Funct. #
(00 = Quit)
00
Output Funct. #
(00 = Quit)
00
Output #?
17
0
3
Output Action
Off
0
0
3
Enter Zone Type
Disarming
22
0
3
Activated by:
Zone Type
2
02 A E P Trig
?00 0 0 -
ZL=
1
Output Funct. #
(00 = Quit)
03
Output #?
17
0
2
Output Action
Stay Closed
02
Enter Event
Alarm
1
0
2
Zone List
01
0
2
Activated by:
Zone List
1
0
2
A
E P Trig
?00 0 0 -
ZL=1
Output Funct. #
(00 = Quit)
02
Heat Zone
P
anic Zone
- Uploaded